ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES. - <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI LIL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />FqT <br />WEATHERPROOF DUPLEX OUTLET <br />W.P. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />G.F.I. <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 THREE-WAY SWITCH <br />?4 FOUR-WAY SWITCH <br />$R RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />❑0 HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />I--O WALL MOUNTED LIGHT FIXTURE <br />ORECESSED LIGHT FIXTURE <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />P.C. <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />rD ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH CHIMES (OPTIONAL) <br />PB PUSH BUTTON SWITCH (OPTIONAL) <br />06 PUSH BUTTON SWITCH - DOOR BELL <br />SD SMOKE DETECTOR <br />CM SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />a TELEPHONE (OPTIONAL) <br />e USB TELEPHONE/USB (OPTIONAL) <br />TV TELEVISION (OPTIONAL) <br />TV 2 (2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O THERMOSTAT <br />�]M ELECTRIC METER <br />_a ELECTRIC PANEL <br />DISCONNECT SWITCH <br />ROUGH -IN FOR OPT. CEILING FAN <br />C� J <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />r J OPT. CEILING FAN <br />(1) PHONE LINE, (1) DATA PORT <br />150A/200A INDOOR <br />NEMA I <br />150 AMP/ <br />200 AMP <br />4 to lights & outlets <br />2 to appliances and GFI <br />Dto WH <br />to Range <br />to HVAC <br />MO--t <br />150=2/0 <br />200=4/0 in 2" Conduit <br />200 amp <br />150 amp <br />UNDERGROUND Disconnect <br />SERVICE BY POWER CO. <br />INTERSYSTEM 4 Bare Cu Ground <br />BONDING #4 GROUNDING WIRE <br />TERMINATION PER WITH CODE APPROVED <br />NEC 17, 250.94 CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram REV.03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />1.5" VTR <br />1 <br />II\ <br />I <br />I <br />-lil 3" VTR <br />I � � <br /><\\ <br />PLUMBING RISER_ <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC TO <br />BE VERIFIED WITH PLUMBER <br />W <br />SWITCH FOR <br />DISPOSAL <br />/ GFII Lj X <br />DW <br />GFI <br />KITCHE <br />DEDICATED <br />RECEPTACLE FOR <br />ICROWAVE RANGE <br />HOOD PER SPECS <br />SPEC 3 & 4 KITCHEN <br />SCALE: %4'=1'-0" <br />- — — — — — — — — — — — — — — — — — — — — — — � r <br />12G F <br />6/J <br />' ROUGH -IN FOR <br />IOPT. CLG. FAN/ <br />LIGHT PRE -WIRE <br />/ SWITCH FOR <br />DISP05AL <br />FAMILY <br />I PENDANT <br />I ROUGH -IN FOR AS PER <br />OPT. CLG. FAN/ SPECS <br />' LIGHT PRE -WIRE ih <br />G � <br />IN <br />GP DISC. A/C PAD <br />NOOK <br />\ GFI <br />/KITCHE <br />REF <br />FOYER <br />7s CH <br />DINING <br />' PENDANT AS <br />PER SPECS <br />I <br />C.M.. <br />PWDR <br />,-- —4 <br />I:I:I:I:I: 1: 1: 1: 1: I: I: 1: 1-171:1.1: I ' I <br />UF=+=— — <br />I <br />•TO LIGHTS _ <br />AND <br />SWITCH <br />ABOVE <br />_AU IGFI <br />W. <br />GFI D. <br />42"A <br />%GFI @ 44"- — GFI @ 44" <br />A.F.F. A.F.F. <br />W.H. <br />\ J <br />/ Z 1 Z O <br />L) a <br />I U J <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE RANGE <br />HOOD PER SPECS <br />w w <br />W Z J <br />205 <br />m <br />�U� <br />> 0j <br />LL <br />L <br />ENTRY ` GARAGE-__ _ —> W <br />DB & GFI TO / WP I BE ALIGNED�-- <br />---- GFI GARAGE —------J <br />I <br />VERTICALLI'r o LIGHT AS <br />PER SPECS <br />I \ <br />I GARAGE <br />r--------------- Doop--------------- <br />I GFI <br />\ I IRRIGATION <br />GFI @ 44" <br />\ I A.F.F. <br />I I <br />I I <br />I I <br />I I <br />� I I <br />\ ------------------------------ <br />\ ------------------------------ <br />COACH LIGHTS COACH LIGHTS <br />OR PREWIRE AS OR PREWIRE AS <br />PER SPECS / PER SPECS <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />I I <br />I I I <br />I I I <br />I I I <br />I I I <br />L----------I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />L- — — — — — — — — — - <br />— — — — — — — — — — — — — — — — — — — — — — — — — — — — <br />SECOND FLOOR ELECTRICAL PLAN <br />FIRST FLOOR ELECTRICAL PLAN - ELEV-B_ ELEV-B <br />M <br />N <br />- <br />to <br />N <br />r <br />J <br />d <br />9 W <br />o s <br />f N <br />- <br />w = Z <br />o o i. <br /><n N L <br />N ® f9 <br />sL r.e N <br />ea <br />d a� rs <br />CE <br />ea <br />0 <br />C'M <br />N <br />0 <br />N <br />M <br />u7 <br />0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural <br />plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code <br />- <br />Residential <br />7th Edition. Engineer's signature and seal <br />is only for <br />the structural <br />engineering portions of the drawing pages bearing <br />Engineer's <br />signature and seal. <br />I �a"? <br />sagU <br />Pk <br />Q <br />ON <br />O M t8 N v <br />N <br />N tm <br />O C <br />tk <br />' <br />0 <br />'Lo 00 <br />M N LJL <br />yt <br />W <br />to <br />U)r-t� u, w <br />M 0v a a <br />W <br />IL °' <br />Cn z <br />z o <br />Z <br />—ern <br />r m "r CD <br />p <br />y: o o <br />N cZi O m <br />pa <br />W <br />r J m <br />r° 2 a, rn d - z <br />z <br />LL <br />o � o w <br />Z U U) F <br />N M <br />< <br />' <br />Z <br />O U ❑❑❑ <br />X^ ?,i W <br />N C� <br />� O <br />z N <br />� � <br />� <br />Q <br />z <br />�Q) <br />Q) <br />ch o <br />L„ y <br />U <br />OLi, <br />N <br />g <br />w. <br />c/1 <br />� <br />C <br />o 0. 6fi! <br />♦— J <br />8 <br />I <br />' <br />- <br />w N <br />U o N <br />c <br />• <br />Q 0 <br />r <br />0 <br />Z- <br />Z <br />M <br />� �z <br />i <br />o <br />=o <br />>m <br />Z p <br />U <br />o� <br />z <br />zm <br />oa <br />4— <br />o 0 <br />C1 <br />Q E <br />0 <br />as <br />0 <br />oQ <br />�z <br />wo <br />Ww <br />�W <br />vo to <br />C <br />4 0 <br />z z <br />=Y <br />W <br />'0 <br />Z, <br />6 -' <br /><� <br />�Z <br />co <br />a <br />z <br />g o <br />a <br />W <br />w a <br />z <br />m <br />40 <br />oLL <br />z <br />r-3 <br />�h <br />o <br />wQ <br />ao <br />v <br />ola <br />° 3 <br />0 Q <br />L <br />0 <br />m <br />to <br />(7 <br />(Q Cfl <br />O <br />r <br />CD <br />U <br />O <br />0 <br />N <br />m <br />_ <br />L0 <br />N <br />0) <br />U') O <br />Ln <br />N <br />M N <br />r <br />Iv <br />m <br />M CM <br />o <br />Z <br />Z <br />:3 <br />E O <br />ii LO <br />M <br />a <br />0 <br />a o <br />JOB <br />NO: <br />23-06103 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />3 <br />III _F--- _ — S t iT— - -iC-11 - -I. _.. 1 V <br />