ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. WEATHERPROOF DUPLEX OUTLET <br />G.F.I. GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />I -a SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />j WALL SWITCH <br />$3 THREE-WAY SWITCH <br />?4 FOUR-WAY SWITCH <br />jR RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />FO HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED LIGHT FIXTURE <br />4-P.C. LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />EXHAUST FAN <br />,) EXHAUST FAN/LIGHT COMBINATION <br />�D ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH CHIMES (OPTIONAL) <br />PB PUSH BUTTON SWITCH (OPTIONAL) <br />�BD PUSH BUTTON SWITCH - DOOR BELL <br />SD SMOKE DETECTOR <br />CM SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />e USB TELEPHONE/USB (OPTIONAL) <br />TV TELEVISION (OPTIONAL) <br />TV 2 (2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O THERMOSTAT <br />0 ELECTRIC METER <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />ROUGH -IN FOR OPT. CEILING FAN <br />C� J <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />L r J OPT. CEILING FAN <br />E7) (1) PHONE LINE, (1) DATA PORT <br />150A/200A INDOOR <br />PANEL CENTER <br />3 1 <br />\ <br />10 #14 to lights &outlets <br />NEMA 1 <br />10 #12 to appliances and GFI <br />---- <br />150 AMP/ <br />_- <br />200AMP <br />10 #10toWH <br />(� <br />#8 to Range <br />' <br />#6 to HVAC <br />.7R <br />-- --- <br />MAIN <br />0 <br />200 amp <br />150 amp <br />UNDERGROUND IDis <br />SERVICE BY POWER CO.---` <br />INTERSYSTEM <br />BONDING <br />TERMINATION PER <br />150=2/0 <br />200=410 in 2" Conduit <br />Bare Cu Ground <br />NEC 17, 250.94 CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram REV. 03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />CODES AND THE LOCAL POWERWTILITY COMPANY. <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE RANGE <br />HOOD PER SPECS- <br />I— <br />WZ <br />Z <br />>-OQ <br />> LU OJ m <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE RANGE <br />HOOD PER SPECS - <br />AC PAD <br />WP DISC. <br />GFI <br />A o, <br />• <br />I <br />DINING <br />\ 5'-0" <br />LIGHT AS PER <br />SPECS <br />{ PENDANT <br />- - Gf LIGHT PER <br />/ SPECS <br />GREAT RM <br />I r GFI <br />GFII <br />- — <br />r I -- ROUGH -IN <br />U.C. OUTLET <br />3 a FOR OPT. <br />o <br />— 0 1 I GF , FAN/LIGHT <br />1 SWITCH FOR OPT. CLG. FAN/ <br />I DISPOSAL ' `LIGHT PRE -WIRE <br />- GFII <br />Uj <br />GF <br />-"-10" <br />I I <br />-- <br />/ ' GFI @ 44" <br />- <br />W.H. A.F.F. <br />J 1 <br />Z LLI <br />� <br />p Z \ <br />' <br />E= a <br />U Q <br />OJ \ <br />� GARAGE <br />\ <br />LLLL. U LIGHT AS <br />PER SPECS <br />w LU <br />_ <br />>W <br />\GARAG E <br />GARAGE / <br />DOOR <br />GFI ' <br />--------------------------- ----� <br />I F I <br />- <br />I I I <br />I IRRIGATION GFI I I <br />@ 44" A.F.F. <br />1 <br />I I <br />I \ I <br />------------------- <br />a''s-----------------------------� <br />COACH LIGHTS <br />OR PREWIRE AS <br />` PER SPECS <br />U.C. OUTLET <br />SWITCH FOR <br />DISPOSAL <br />SPEC 3 & 4 KITCHEN <br />SCALE: Y4"=1'-0" <br />`H/ VJ I <br />\ <br />0WP OB <br />GFII I <br />I I <br />I I <br />I I <br />� I I <br />I I <br />I I <br />ENTRY <br />I I <br />I I <br />I I <br />r^ _�i <br />I� �I <br />II ALT II <br />j I AC PAD I I <br />Il 11 <br />OPT. <br />RECEPT. FOR <br />ALARM SYSTEM <br />PROVIDE PHONE / CABLE <br />AND OUTLET AT TECH <br />CENTER <br />— — — — — — — — — — — — — — — — — — <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />L------------------------------------ J <br />1.5" VTR 3" VTR ICI, <br />III, I <br />�I I <br />I I <br />I I <br />I I <br />I r� <br />3" VTR III I I <br />,I- <br />I I <br />� I <br />I I I I I <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC TO <br />BE VERIFIED WITH PLUMBER <br />3" <br />ELECTRICAL PLAN_ <br />R <br />co <br />:r <br />W <br />tomC-4 <br />r C u. Q <br />CO O xx <br />e � d <br />O <br />.�. <br />v ji <br />W ati as m <br />v <br />Ld �� <br />c <br />a� <br />cc <br />cco <br />�v <br />M <br />CV <br />0 <br />CV <br />M <br />0 <br />To the best of the Engineers knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code <br />- <br />Residential 7th Edition. Engineer's signature and seal <br />is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />tX �A�i�ajFe �✓ 4t�i'�1 N <br />ep" F. <br />r <br />O E o a <br />7 <br />0 <br />up <br />7 1co ID <br />0 N �k lL It <br />t" H <br />N <br />rnNo� a w <br />a <br />F <br />a <br />C .j w <br />mLLIL a U) Z <br />Z <br />13 <br />O <br />s <br />-05,F0 M 0 <br />y= o 0 <br />of 3:CN <br />�2 M <br />' <br />Ld <br />W <br />U5 op ¢ z <br />Z <br />IL <br />w <br />to N Z Q �U 2 <br />M <br />Cq Q U cn H <br />Z <br />O U ❑❑❑ <br />N M <br />o <br />CDN <br />21 iz:' Q <br />c/I <br />M <br />z w2 <br />`o <br />CD <br />2 <br />w <br />U <br />OLLJ <br />g <br />C <br />U" <br />C� <br />`— — g <br />I <br />v o <br />m <br />CO o, <br />_® <br />N <br />o <br />w <br />M <br />ZO <br />z <br />a <br />ca E <br />o <br />c <br />oo <br />zo <br />aN <br />Z0 <br />{— r0 <br />X� <br />�O <br />co <br />� 4 <br />H <br />< <br />0a <br />ro <br />�I— <br /><1 <br />o <br />K <br />aZ <br />w <br />� J <br />= <br />Ca <br /><o <br />m� <br />o° <br />m J <br />O U <br />m <br />Z' <br />aw <br />� <br />< <br />o � <br />�z <br />Z <br />a o <br />V�] <br />OLL <br />� <br />W <br />m <br />¢ <br />w <br />=0 <br />t7 <br />J <br />M <br />� <br />°Ia <br />O <br />d F <br />° <br />3 <br />> L6 <br />O <br />iD <br />cc <br />m <br />0 <br />\SJ <br />Co <br />LO <br />1 <br />O <br />CO <br />-� <br />M <br />CN <br />N <br />Ln <br />T- <br />T <br />r <br />m <br />> <br />T <br />(h M <br />o <br />LO <br />Z <br />Z <br />E <br />W <br />2 <br />`m <br />a <br />E <br />U <br />Q O <br />c <br />JOB <br />NO: <br />23-06119 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />3 <br />11 1 E I Ili I I I q —I i. . 111� I I I I it I 1 11, Al � I I J! I I 1TI1 ; I — 1 11 i - I I I ---F— I I <br />