<br />Re: Wood Construction Connector Compliance for 2015 International Codes & 2017 Florida Codes
<br />To Whom It May Concern:
<br />Section 2303.5 of the 2015 International Building Code (IBC) and 2017 Florida Building Code (FBC) specifies that
<br />joist hangers shall be tested per ASTM D7147 Testing and Establishing Loads of Joist Hangers Previous versions of
<br />the IBC and FBI required testing to oomply with ASTM D1761 Test Method for Mechanical Fasteners in Wood. Both
<br />methods determine a connector's allowable load as the lowest of thefollowing;
<br />1. Lowest ultimate of three tests (or average of 6) with a safety factor of 3
<br />2. Average load at 1/8-inch deflection
<br />3. Calculations per American Wood Council National Design Specification for Wood Construction (NDS)
<br />The primary changes in ASTM D7147 are requirements to measure properties of the tested materials, such as steel
<br />strength, fastener strength, and wood specific gravity. The tested ultimate loads must be adjusted when tested
<br />material properties exceed the specified properties.
<br />ICC, Evaluation Services (ICC-ES) revised AC13 Acceptance Criteria for Joist Hangers and Sirrlar Devices in
<br />October 2016 to incorporate a methodology to evaluate products to the 2015 I -Codes, Simpson Strong -Tie is working
<br />on re-evaluating wood construction connector loads to the new standard to update our product evaluation reports to
<br />the 2015 I -Codes. As soon as the updated evaluation reports are completed, we will apply for Florida Product
<br />Approvals,
<br />However, reevaluating a large number of products will take time. While manufacturers work with product certification
<br />agencies to update their wood connector evaluation reports, we recommend that budding departments under the
<br />2015 1-Codes and 2017 Florida Codes continue to accept code reports shoving compliance to the 2012 and 2014
<br />editions; respectively, until July 2018.
<br />The information in this letter is valid until 613=018 when it will be re-evaluated by Simpson Strong -Tie. Please visit
<br />www,stronotie.com for additional pertinent information. If you have questions or need further assistance regarding
<br />this matter, please contact the Simpson Strong -Tie Engineering Department at 800.999 5099.
<br />Sincerely,
<br />SIMPSON STRONG -TIE COMPANY INC.
<br />Keith Cullum, P.E„ LEED AP dwfBDW
<br />Engineer, Southeast U.S: Branch
<br />Page 1 of I
<br />Simpson Strong -Tie Company Inc. 2221 Country Lane McKinney, TX 75069 Phone: 972 542.0326 Fax 972.542.4139 wirsro stronatie.com
<br />CU
<br />C a) U
<br />Q O O
<br />C6 -
<br />'� U C� E
<br />� 0 U
<br />0 O
<br />O � = O
<br />= 0 U_
<br />CU O C- 4- >
<br />Q
<br />'- E 0
<br />L
<br />1� (� O�-
<br />z
<br />O
<br />O
<br />r�
<br />V
<br />0
<br />U
<br />0
<br />O
<br />V/
<br />co
<br />La
<br />ca
<br />Z W
<br />Z
<br />Z
<br />Q
<br />J
<br />a.
<br />SHEET NO.
<br />PA 1,0
<br />A3
<br />FL17244.1
<br />z
<br />ESR-3455
<br />A23
<br />FL1044fi.2
<br />ESR-2808
<br />HD210-2
<br />FL17232.3
<br />ESR-3445
<br />HU210-2
<br />FL10856.4
<br />ESR-2549
<br />HD212-2
<br />FL17232.3
<br />ESR-3445
<br />HU212-2
<br />FL10858.4
<br />ESR-2549
<br />HD216
<br />FL17232.3
<br />ESR-3445
<br />HU218
<br />FL10856.5
<br />ESR-2549
<br />HD216-3
<br />FL17232.3
<br />ESR-3445
<br />HU216-3
<br />FL10858.1
<br />ESR-2549
<br />HD26
<br />FL17232.2
<br />ESR-3445
<br />HU28
<br />FL10856.3
<br />ESR-2543
<br />HD28-2
<br />FL17232.3
<br />ESR-3445
<br />HU28-2
<br />FL10856.4
<br />ESR-2549
<br />HD410
<br />fL17232.4
<br />ESR-3445
<br />HU410
<br />FL10856.9
<br />ESR-2549
<br />HD412
<br />FL17232.4
<br />ESR-3445
<br />HU412
<br />FL10858.9
<br />ESR-2549
<br />HD610
<br />FL17232.4
<br />ESR-3445
<br />HU610
<br />FL10858.10
<br />ESR-2549
<br />HD0410
<br />FL17241.7
<br />ESR-3444
<br />HUC0410
<br />FL11468.11
<br />SIM200804
<br />HGA10
<br />FL17699.1
<br />Evacuation Report
<br />HGA10KT
<br />FL11470.4
<br />SIM200803
<br />HGAM10
<br />FL17699.1
<br />Evaluation Report
<br />HGAM10KT
<br />FL11470.4
<br />SIM200803
<br />HHCP2
<br />FL17238.7
<br />ESR-3448
<br />HCP2
<br />FL10447.2
<br />ESR-2551
<br />HTA18
<br />FL17680.4
<br />Evaluation Report
<br />HETA16
<br />FL11473.5
<br />SIM200802
<br />HTA20-18
<br />FL17660.4
<br />Evaluation Report
<br />HETA20
<br />FL11473.5
<br />SIM200802
<br />HTT18
<br />FL17324.2
<br />Evaluation Report
<br />HTT16
<br />FL11496.1
<br />ES-0130
<br />HTT45
<br />FL17324.2
<br />Evaluation Report
<br />HTT22
<br />FL11498.1
<br />ES-0130
<br />HTW18
<br />FL17244.8
<br />ESR-3455
<br />HTS18
<br />FLt0456.22
<br />ESR-2613
<br />HTW20
<br />FL17244.8
<br />ESR-3455
<br />HTS20
<br />FL10456.23
<br />ESR-2613
<br />HTW24
<br />FL17244.8
<br />ESR•3455
<br />HTS24
<br />FL10456.24
<br />ESR-2613
<br />HTW30
<br />FL17244.8
<br />ESR-3455
<br />HTS30
<br />FL10456.26
<br />ESR-2613
<br />HTWM16
<br />FL6223.2
<br />Evaluation Report
<br />HTSM16
<br />FL11473.11
<br />SIM200802
<br />HTWM20
<br />FL8223.2
<br />Evaluation Report
<br />HTSM20
<br />FL11473.11
<br />SIM200802
<br />HUGT2
<br />FL8223.3
<br />Evaluation Report
<br />HGT2
<br />FL10456.18
<br />ESR-2613
<br />HUGT3
<br />FL6223.3
<br />Evaluation Repo
<br />PRODUCT APPROVAL SPECIFICATION SHEET (2018) January 9, 2019
<br />the information and approval numbers on the building components listed below Kf the will be utilized on the
<br />As required by Florida Statute 553.842 and Florida Administrative Code 9B•72, please provide g y
<br />construction project for which you are applying for a building permit. We recommend you contact your local product supplier should you not know the product approval number for any of the applicable listed
<br />products.
<br />Category/Subcategory
<br />Manufacturer
<br />Product Description
<br />Approval Number(s)
<br />Test Pressures
<br />1. EXTERIOR DOORS
<br />A. SWINGING
<br />ThermaTru
<br />Firber-Classic and Smooth -Star {NON -IMPACT)
<br />pL204g1,1
<br />+67.0l-67.0 psi
<br />ThermaTru
<br />Firber-Classic and Smooth -Star (NON -IMPACT)
<br />pL204g1.g
<br />+87.0/-67.0 psf
<br />ThermaTru
<br />Firber-Classic and Smooth -Star (NON -IMPACT)
<br />FL204g1.g
<br />+87.0l-67.0 psf
<br />ThermaTru
<br />Firber-Classic and Smooth -Star (NON -IMPACT)
<br />FL20481.14
<br />+67.0/-67.0 psf
<br />ThermaTru
<br />Classic -Craft and Benchmark
<br />FL15225.1
<br />+67.0/-67.0 psf
<br />ThermaTru
<br />Smooth -Star and Benchmark
<br />FL15225.5
<br />+67.0/-67,0 psf
<br />ThermaTru
<br />FiberClassic, Smoothstar, ClassicCraft, Rustic
<br />FL7640.1
<br />+87.0/-87.0 psf
<br />B. SLIDING
<br />MI Wintlows and Doors
<br />Series 420
<br />FL15332.1 - FL15332.5
<br />+40.0/-00.0 psf
<br />PGT
<br />Series 5570
<br />FT.251.10
<br />C. SECTIONAL
<br />Clopay Building Products
<br />Residential WindCode Doors W5 (8X7J
<br />FL15279.37
<br />+30.0l-32.0 psf
<br />Clopay Building Products
<br />Residential WindCode Doors WS {18X7)
<br />FL15279.53
<br />+30.0/-30.0 psf
<br />Clopay Building Products
<br />Residential WindCode Doors 11v6 (8X7)
<br />FL15278.85
<br />+38.0/-42.0 psf
<br />Clopay Building Products
<br />Residential WindCode pours W6 (16X7)
<br />FL15279.102
<br />+37.0/-41.0 psf
<br />D. METAL LOUVERED DRS
<br />Curries Division of AADG, Inc
<br />607,707,727,747,and 847 Single &Pairs of Doors
<br />FL11537.1
<br />NIA (see inst sht)
<br />2. WINDOWS
<br />A. SINGLE HUNG
<br />MI Windows and Doors
<br />Series 185
<br />FL17499.2
<br />+50.0l-55.0 psf
<br />PGT
<br />Series 5500
<br />FL239.7
<br />B. HORIZONTAL SLIDER
<br />MI Windows and Doors
<br />Series 188
<br />FL15351.1
<br />+40.0l-50.0 psf
<br />C. FIXED
<br />MI Windows and Doors
<br />Series 185
<br />FL15349.1
<br />+40.0/-40.0 psf
<br />PGT
<br />Sedes 5520
<br />FL243.9
<br />D. MULLION
<br />MI Windows and Doors
<br />Series 5764
<br />FL15353.2
<br />N/A
<br />PGT
<br />Series 5500
<br />FL261.1
<br />N/A
<br />E. OTHER
<br />3. PANEL WALL
<br />A. SIDING
<br />James Hardie Building Prod.
<br />Cemplank lap Siding and HardiePlank Lap Siding
<br />FL13192.1 - FL13192.2
<br />N/A
<br />B. SOFFITS
<br />Alside
<br />Solid arid Vented Soffit
<br />FL15272.1 - FL15272.2
<br />+70.0/-70.0 psf
<br />C. OTHER
<br />4. ROOFING PRODUCTS
<br />A. ASPHALT SHINGLES
<br />GAF
<br />3 Tab, Dimensional
<br />FL10124.1
<br />N/A
<br />B. UNDERLAYMENTS
<br />Tamko
<br />15IbfeltUnderlayment
<br />FL12328.6
<br />N/A
<br />C. ROOFING FASTENERS
<br />NOT USED
<br />D. ROOF VENTILATORS
<br />Thompson Arch Metal Comp.
<br />Off Ridge Vents
<br />FL16918.1 - FL16918.4
<br />N/A
<br />Florida Metal Products, Inc
<br />Vent RV10
<br />FL21580.3
<br />N/A
<br />Lomanco, Inc
<br />DA-4 Exahust Vent
<br />FL17202.1
<br />N/A
<br />E. ROOFING TILES
<br />Boral Tile
<br />Villa 900
<br />FL7849.27 - FL7849.28
<br />N/A
<br />Boral Tile -
<br />Saxony 900
<br />FL7849.18 - FL7849.20
<br />N/A
<br />F. METAL ROOF
<br />Gulf Coast Supply &Manufacturing, LLC
<br />0.032" Aluminum GulfLok 18" wide roof panel
<br />FL11651.2 R3
<br />N/A
<br />5. SHUTTERS
<br />A. STORM PANELS
<br />Global Protection Products
<br />Galvanized Steel Storm Panels
<br />FL15076.1 - FL15076.2
<br />N/A
<br />All American Shutters &Glass
<br />Galvanized Steel Storm Panels
<br />FL17869.1
<br />NIA
<br />8. STRUCTURAL
<br />COMPONENTS
<br />A. WOOD CONNECTORS/
<br />USP Structural Conn.
<br />see chart
<br />ANCHORS
<br />Simpson Strong -Tie
<br />see chart
<br />B. TRUSS PLATES
<br />ITW Building Components
<br />Alpine Truss Plates
<br />FL1999.1 - FL1999.4
<br />N/A
<br />MiTek Industries, Inc.
<br />Truss Plates
<br />FL2197.1 - FL2197.5
<br />N/A
<br />C. ENGINEERED LUMBER
<br />Weyerhaeuser
<br />Rim Board, LVL, PSL, LSL
<br />FL6527.1 - FL6527.5
<br />N/A
<br />D. MATERIAL
<br />Cast -Crete Corp,
<br />High Strength Concrete Lintels
<br />FL158.1
<br />N/A
<br />Commercial Concrete Products, Inc.
<br />High Strength Concrete Lintels
<br />FL1774
<br />N/A
<br />e time ofinspection of these products, the followin information must be available to the inspector on the
<br />The products listed below did not demonstrate product approval at plan review. I understand that at th tim p g r p
<br />jobsite; 1) copy of the product approval, 2) the performance characteristics which the product was tested and certified to comply with, 3) copy of the applicable manufacturers installation requirements. Further, I
<br />understand these products may have to be removed if approval cannot be demonstrated during inspection.
<br />APPLICANT SIGNATURE
<br />DATE
<br />I �
<br />9�,ii- i i.udioiu-�t liliwirrtwiwiil1i nt�mi:, r�irr,111 1 I, 1�T �I Ji Kill '� lltss
<br />
|