Laserfiche WebLink
ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />comer counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />FTF <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />® <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />6. <br />24 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />Q <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />®D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CHI <br />CHIMES (OPTIONAL) <br />P9 <br />PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />® <br />TELEVISION (OPTIONAL) <br />® 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />owl <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />G J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G J <br />OPT. CEILING FAN <br />A9 <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />)IL <br />I <br />I <br />I <br />I <br />I I <br />I I <br />I I <br />� I I <br />LAV <br />� I <br />L TUB/ <br />W/C SHOWER <br />LAV <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />I <br />OPT. <br />LAV <br />LAV <br />I <br />I <br />ti W/C <br />SHOWER <br />STUDOR <br />VENTQ � DBL SINK <br />L W/ DISP. <br />W/C <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />UNIT -A 1532 (1532) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1533 S.F. <br />4599 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10599 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33659 <br />1st 1OKWat 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9464 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />5200 <br />TOTAL: 31768 <br />LOAD WATTS --- 240 VOLTS <br />AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Optional Overhead Service 200A <br />Same As Underground Indoor Panel <br />150 Or 200 Amp Service Center <br />P I NEMA 1 <br />200 AMP <br />TER MA N <br />1 �0-200 AMP I I T /—Serial Cable <br />3R <br />Power Co. Feed _--� I_I I _ ir— #4 Solid COPPER Ground <br />C.O. <br />II <br />Intersystem Bonding <br />Termination Per <br />NEC 17, 250.94 5/8" Galvanized Driven Ground <br />Rods at least 6' apart <br />Typical 150-200 Amp Electrical Riser Diagram <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 - 17, LOCAL CODES AND THE LOCAL POWER CO. <br />------------------------- <br />OUTDOOR LIVING <br />INSTALL LIGHT <br />ROUGH -IN <br />FOR OPT. <br />> <br />FAN/LIGHT <br />� GFI <br />I <br />'M <br />\ <br />O <br />-----Tr--- <br />DINING <br />KITCHEN 1 <br />'000p� <br />FI � O <br />GFI ( <br />SWITCH FOR <br />DISPOSAL IN CAB <br />UNDER SINK <br />GREAT ROOM <br />^� /^TROUGH -IN\ <br />FOR OPT <br />i>fi� . <br />,FAN/LIGHT 1 <br />r� � <br />I <br />I I <br />1 / <br />I <br />1 <br />I <br />I <br />rGF1-j <br />j UPSTAIRS t <br />DISCONNECT <br />DEDICATED RECEPTACLE <br />FOR MICROWAVE RANGE <br />HOOD PER SPECS <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />F__ — — — — — — — — — — --I <br />FOYER <br />O <br />G <br />i <br />\ GFI <br />BATH 2 <br />@ 44" w.H. <br />- A.F.F. ' \ O <br />a� <br />GFI <br />1dh <br />I <br />/ I <br />WIC -- N <br />I DB <br />I <br />EN I WP GARAGE <br />I <br />I <br />GFI&::_-: I <br />LIGHT AS b7k1 <br />I I <br />PER SPECS <br />I <br />` <br />DB&GFI TO <br />�� /.^TROUGH -IN <br />- L----- .yf <br />_ FOR OPT. <br />____ _____ <br />BE ALIGNED \ GARAGE <br />, <br />VERTICALLY LIGHT AS <br />��j�fi��FAN/LIGHT <br />I3 <br />PER SPECS <br />\B E D ROO M 2 <br />GARAGE <br />DOOR <br />I GFI <br />I i---------------i <br />I I I <br />I J I <br />Z <br />; <br />l <br />W <br />�occ <br />I <br />�F.W <br />\ <br />WUj � <br />\ >_jm >w I <br />\ <br />L <br />COACH LIGHTS <br />— — — — — — <br />OR PREAS <br />PER SPECS <br />1ST ELECTRICAL - UNIT -A 1532 <br />SCALE: X"=V-0" <br />2ND ELECTRICAL —UNIT—A 1532 <br />SCALE: &=V-0" <br />tD <br />o <br />W <br />C3 <br />Q e o <br />Z <br />�; <br />C cc fj N <br />_ an x <br />u. cl. <br />N .fl N Z <br />Q CV Y <br />a <br />as « c <br />Es <br />°C 3 cc <br />iv y d o <br />o ca as <br />1✓ y c o <br />> d' •� T <br />N Qn <br />E <br />� o <br />a 5 <br />0 <br />c'M <br />O <br />N <br />N <br />0 <br />t <br />``,`��1lttltrf�fj <br />p . LE <br />lyh C)0. <br />.� <br />u46' i <br />C), <br />7 •No <br />= PE78750 <br />'- SIAIE OF •�� " <br />j"':Trt!tfi1%% <br />To the best of the Engineers knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida Building Code - <br />Residential 7th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />W <br />c EEo <br />O N U m <br />0) U <br />Y_� <br />0 <br />in <br />��� N " u;- a. <br />rnN0� LL <br />Q <br />a W <br />M LL LL; C7 <br />Z <br />_v o o <br />@ M °' 0 t <br />o Co L <br />W <br />Z <br />IL LL <br />rZ <br />D Ci J Lu <br />N M Z 0 <br />Z <br />1=- <br />O V ❑❑❑ <br />W <br />(D ; L <br />Z Cl) <br />z <br />Z C <br />J — <br />N <br />d. � <br />— N <br />z 9 <br />v�o <br />J� <br />4_j <br />(� <br />w � <br />M <br />U <br />Ow <br />Lv N <br />' <br />U <br />w <br />8 <br />! <br />x� <br />C2,(n <br />0 <br />& <br />S� <br />o <br />M <br />M <br />f <br />m <br />o <br />w <br />Z <br />Z <br />U_ <br />�o <br />Zo <br />oo0® <br />» <br />a <br />I m <br />2� <br />o0 <br />�� <br />0 <br />0 <br />o� <br />�Z <br />Z <br />Fes- <br />wo <br />�; <br />ro <br />cn ca <br /><o <br />m0 <br />0 <br />Z <br />Z <br />mJ <br />�xaw <br />Fb <br />�z <br />W <br />N <br />T <br />o <br />w <br />ao <br />.� <br />hZ <br />o <br />�w <br />aQ <br />;o <br />O�Z <br />o T <br />> 00 <br />CN <br />F-- <br />0 <br />L <br />Co 00 <br />OTO <br />M <br />T <br />r <br />r <br />� Y <br />T <br />EEO <br />U) m <br />00 <br />F_ <br />O <br />LA") <br />C <br />04 <br />O� <br />Q <br />Cfl <br />d <br />T.- <br />6 <br />m <br />� <br />T <br />N <br />O <br />o <br />Z <br />Z <br />E T <br />m r <br />M <br />� <br />M <br />a <br />E <br />ci <br />a o <br />JOB <br />NO: 23-13115-13120 <br />SCALE: <br />AS NOTED <br />SHEET NO. <br />11.1 <br />