ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />PET <br />DUPLEX OUTLET ABOVE COUNTER <br />FFF <br />WEATHERPROOF DUPLEX OUTLET <br />W.P. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />G.F.I. <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />VIM DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 THREE-WAY SWITCH <br />24 FOUR-WAY SWITCH <br />$R RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />I_o WALL MOUNTED LIGHT FIXTURE <br />ORECESSED LIGHT FIXTURE <br />P.C. LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />Q EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />®D ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH CHIMES (OPTIONAL) <br />PB PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD SMOKE DETECTOR <br />CM SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB TELEPHONE/USB (OPTIONAL) <br />© TELEVISION (OPTIONAL) <br />® 2 (2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O THERMOSTAT <br />�]M ELECTRIC METER <br />.tip ELECTRIC PANEL <br />DISCONNECT SWITCH <br />ROUGH -IN FOR OPT. CEILING FAN <br />G J <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G J OPT. CEILING FAN <br />A9 (1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />I I <br />I I <br />I I <br />LAV <br />.J 1 <br />L TUB/ <br />W/C SHOWER <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />t <br />I OPT <br />LAV <br />ILAV <br />I Irl <br />I <br />L W/C <br />SHOWER <br />\`nd F FC <br />STUDOR <br />\ R. <br />VENTI 1 DBL SINK <br />Tt W/ DISP. <br />W/C <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />UNIT -A 1532 (1532) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1533 S.F. <br />4599 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10599 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />OTHER LOAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33659 <br />1st at 1 0 <br />10000 <br />BALANCE OF WATTS AT 40% <br />9464 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />5200 <br />TOTAL: 31768 <br />LOAD WATTS --- 240 VOLTS <br />AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Optional Overhead Service 200A <br />Same As Underground Indoor Panel <br />150 Or 200 Amp Service Center <br />NEMAt <br />2lxl AMP <br />1 0-200 A P Serial Cable <br />NEMA <br />3R <br />Power Co. Feed ---_ 11 i- <br />#4 Solid COPPER Ground <br />C.O. <br />II <br />Intersystem Bonding <br />Termination Per <br />NEC 17, 250.94 5/8" Galvanized Driven Ground <br />Rods at least 6' apart <br />Typical 150-200 Amp Electrical Riser Diagram <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 - 17, LOCAL CODES AND THE LOCAL POWER CO. <br />------------------------- <br />OUTDOOR LIVING <br />INSTALL LIGHT <br />ROUGH -IN <br />FOR OPT. <br />FAN/LIGHT GFI <br />.rn <br />a <br />GFI <br />I <br />DINING <br />I KITCHEN 1 <br />.1-1 FI I O <br />i <br />I <br />I <br />I <br />I <br />I <br />I <br />DISCONNECT <br />GFI � --- <br />- <br />SWITCH FOR <br />DISPOSAL IN CAB <br />UNDER SINK <br />C.M <br />\ II <br />\ I <br />GREAT <br />\ I <br />ROOM <br />\ <br />1 <br />/�>ROUGH-IN\ <br />FOR OPT. CH <br />FAN/LIGHT 1 <br />< <br />I <br />AYTCH <br />UPSTAIRS <br />`I <br />1 / <br />1 / <br />I <br />FOYER <br />G <br />-- \ <br />GFI <br />@ 44" <br />A.F.F. ' \ <br />O <br />ENtRY I WP <br />LIGHT AS 0 GFI <br />DB <br />I GARAG E <br />I I <br />PER SPECS <br />DB & GFI TO <br />---- _—_—_ <br />BE ALIGNED <br />GARAGE <br />VERTICALLY <br />LIGHT AS <br />PER SPECS <br />GARAGE <br />DOOR <br />I <br />GFI <br />--------------- <br />I <br />1 <br />I <br />I J <br />bz <br />I <br />I <br />j <br />HLU Z <br />ZOO <br />Oa <br />1- <br />NU <br />I <br />I <br />W <br />\ �C(aj� <br />W <br />\ j_m <br />DW <br />I <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />1ST ELECTRICAL - UNIT -A <br />1532 <br />SCALE: YV=1'-0" <br />DEDICATED RECEPTACLE <br />FOR MICROWAVE RANGE <br />HOOD PER SPECS <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />F_ _ — _ — — — — — — — �I <br />2ND ELECTRICAL - UNIT -A 1532 <br />SCALE: Y4"=1'-0" <br />c*a <br />0 <br />c� <br />o <br />Jz <br />N <br />0 <br />Y No PE78750 <br />}` <br />A++ S T ATE C'F cF A <br />.•�4+•+ '�` <br />� '.',`fit..,` <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida Building Code - <br />Residential 7th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />M <br />11- a <br />o �$ <br />80S. <br />N N 6 o <br />n <br />a <br />Q <br />NO ik 4J. <br />C <br />J 4 w <br />c��t+ a <br />Z <br />3 <br />Lu <br />tmV a <br />W <br />L <br />ij N (O <br />Z <br />ILZ <br />Ci <br />Ln N Z <br />N <br />O V 6 W <br />W <br />El El <br />CD <br />z N 8 <br />0 <br />z � S <br />z <br />J — <br />N-MQ <br />V tg <br />jt` <br />fa <br />W <br />0 <br />v) <br />W o <br />c <br />�NCD <br />c <br />L Ll J <br />1— r 8 <br />z <br />Of N d co <br />¢ N <br />416— <br />CD <br />� <br />W <br />M <br />ch <br />w ¢ <br />10 <br />Z <br />wo <br />U, K <br />Z <br />n. p <br />-1 <br />zo <br />oa <br />O <br />U <br />OS <br />WX <br />= OU <br />OW <br />Z <br />O <br />N <br /><z <br />aZ <br />I <br />W <br />mo <br />o <br />N � <br />N <br />-W <br />zz <br />Z <br />J <br />O <br />Q W <br />3 <br />Fm <br />0 <br />ZZ <br />5° <br />Z <br />9F <br />� <br />Zla�. <br />�d <br />OU <br />o Q <br />>L <br />M <br />m <br />NCC <br />T <br />O <br />O <br />CV <br />LM <br />N <br />`� <br />�./ <br />' A <br />o <br />U <br />v, O <br />U <br />OO <br />m <br />O <br />Ln <br />N <br />C14O <br />Lei <br />C <br />04 <br />Q r <br />d <br />L0 <br />C) <br />T- <br />T <br />o <br />z <br />E 0 <br />0 <br />WE c <br />a <br />U � <br />¢ o <br />JOB <br />NO : 22-11668-11666 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />13 <br />