<br />ELECTRICAL SPECIFICATIONS
<br />1.1 SCOPE
<br />A. WORK INCLUDED: Include the following Wo►k in addition to iteme needy part of this Ssctime
<br />01 Wiring for lighting and power.
<br />02 Installation of 11"V fixtures with lamps.
<br />03 Lighting panelboards and distribution ponsiboords.
<br />04 Connection of equipment shown.
<br />05 Control wiring.
<br />08 Disconnection and removal of existing fixtures and wkkg not to be mead.
<br />1.2 MINIMUM COMPLIANCE STANDARDS
<br />A. AN work shall be done In accordance with the requksmerrb of the foNowkW
<br />01 Florida Building Cade Sixth Edition (2017).
<br />02 Florida Building Code — Electrical Conservation Sixth Edition (2017). Section C405.
<br />03 2014 lows of the National Electrical Code (NFPA 70).
<br />04 AN Receptacle Control to conform to ASHRAE Standard 90.1. 8.4.2. 2010.
<br />05 Miring In Patient Cam Areas sholl comply with NEC 517.
<br />08 Other applicable NFPA Codes.
<br />07 Regulation of local outhoritles having JurledloUom
<br />B. Furnish and Install all labor, natotal and equlprne►t and services necessary for compleb and
<br />soh installation of the electrical system Indicated on the drowkhgs and noted In the
<br />specMtoatlone hereinafter. Electrical systsrrhe and equipment shall In general include the following:
<br />01 Gensrd prodNom for electrical work.
<br />02 Mliring, distribution equipment and devices.
<br />03 Ughthq fixtures and lamps.
<br />04 Grounding systern.
<br />1.3 GENERAL PROVISIONS FOR ELECTRICAL WORK
<br />A. DRAWN=- Elea4ted drawings considered diagrammatic and Indicate general arrangement of work
<br />and systerm. Refer to ather drawings to verify Wootton of equipment, etc. Check drawings of
<br />other trodee to verify exact space condition or underground Ones. Drawing Scales prohibit the
<br />Indication of all offeeb, flttbgr and occesaarles required. however these Rena will be
<br />provided by this subcontractor at no extra cast to the owner.
<br />B. QUALITY OF MATERIALS: New, best of their respective Wnd, free from defeats, and listed by
<br />Underwriter's Laboratories. Inc. or bearing their label.
<br />C. SHOP DRAWINGS. Submit four (4) copies of shop d owkngs for lighting fixtures and ponelboards.
<br />Obtain approval before equipment is ordered. built or Installed
<br />D. EXCAVATION AND BACKFNIJNG: Excavate, backfill and restore surfaces for all electrical work.
<br />E. Visit alb and inspect existing fociNtles before bid in order to ensus proper evaluation of
<br />wai kh conditions and location of existing equipmenM
<br />1.4 WOW. DISTRIBUTION EQUIPMENT AND DEVICES
<br />A. CONDUCTORS: Copper. In accordance with ASTM Standards. size references AWL. Conductors No. 10 and
<br />smaller she solid. No. 8 and larger stranded. Insulation of conductor thermoplastic. type THHN
<br />(min. she: No. 12) any wire installed outside, underground, in skhbs. or exposed to moisture
<br />shall have THWN insulation.
<br />B. RACEWAYS: RICID STEEL CONDUIT. full weight pipe golvahhed. Wedded. and minimum 1/2 Inch except
<br />as noted or required for wiring. ELECTRICAL METALLIC TUBING (BM. thin wait pips. gdvandted. threadless,
<br />commselorh fittings. and minimum 1/2" except as noted or required for wiring. FLEXIBLE STEEL CONDUIT,
<br />continuous ekgWob* galvanised, and minimum 1/2- Wn except as noted or required for wking. PVC
<br />CONDUIT, heavy duly tyiw she as Indicated. Separate raceways shall be used for each voltage system.
<br />Type AC or MC Cable where permitted.
<br />C. DISCONNECT SMOTCHE& General Duty, horsepower rated for motor Wade 800 or 250 volt rating, fused
<br />or non—fussd as notsd: number of poles as indicated, cover Interlocked with ew114 Enclowre
<br />NEMA 1 for Wear use and NEMA 3R for weatherproof applications. Switch to be Square 'D" or equal.
<br />D. CIRCUIT BREAKERS: Moiled care. thermal —magnetic quick—makt, qutok—break. bolt —on We with
<br />manually operated inwiated trip —Tres handle. Multi —pole types with Internal common trip bar.
<br />Terminate suitable for copper or aluminum conductors. Interrupting capacity minimum 10.000 RMS
<br />symmetrical amperes circult breaksm to be Square V or equal, type as required.
<br />E. PANELBOARDS: Voltage. phasing and ampere ratings as indicated. circuit breaker type as Indicated,
<br />busbam of hand drawn capper. minimum 96% conductivitygalvanized steel back box. door and trim.
<br />AN comers topped and welded, hardware chrome plated with flush Wok and catch. Hinges *emt—
<br />conceded. 5 knuckle steel with nonferrous pins. 180 degree opening@. Mkrtmun gutter space 5-
<br />31e rides, top and bottem. Increase she where required by code. Directory holder complete
<br />with dear pketic transparent cover Mdioa&g typewritten NA of feeder cables, conduit sins,
<br />circuit numbers. outlets of equipment supplied. and their location. Circuit breaker typs
<br />pan boards to be Square "D- type NQOD or 1-0e, or equal. A plastic label shall be lactated on exte for of
<br />panelboard Identifykg the "stern voltage. phase. and current rating.
<br />F. MIRING DEVICES: AN devices the product of the same maewhehmr. Wall switches single pole, 20
<br />ampere, 120 volt. Wait switches thm*—way. 20ampen, 120 volt. Receptacles duplex, 2 wire: 3
<br />pole grounded, 20 ampere. 120 volt.
<br />0. DEVICE PLATES: Provide for all outlets whore devices are Installed. Provide engraved markkg for
<br />*pedal outlets. Provide blank plates for empty or future outlet boxes. DEVICE AND DEVICE PLATES
<br />COLORS TO BE VERIFIED WITH INTERIOR DESIGNER AND OWNER.
<br />1.5 L.WTNIG FIXTURES AND LAMPS
<br />A. Furnish and Install complete system of lighting fixtures, lamps, accessories and supports as
<br />specified and Indicated. SubmWAW of equal quality are allowed.
<br />1.6 GROUNDING SYSTEM
<br />A. EQUIPMENT: pound non—durrent carrying metal parts of pandboord. raceways and oil fighting
<br />- fixtures. AN aondul is shall have equipment grounding conductors.
<br />1.7 INSTALLATION
<br />A. Secure all supports to building structure. Support horizontal num
<br />of metallic conduit not more than 10 rest apart. Run exposed raceways paaild with or at right
<br />angles to walls.
<br />8. Pace raceways over water, steam or other piping when pull boxes are not required. No raceway
<br />within 3 Inches of steam or hot water pipw or appliances, except crosdngs where r*assay @hall
<br />be at least 2 Inches from pipe cover.
<br />C. Cut conduit ends square, ream smooth. Point male threads of field threaded condult with graphite
<br />base pipe compound. Draw up tight with conduit ooup&W
<br />D. Leave wire sufficiently long to permit mcMig final connections. in raceways over 50 Test In
<br />which wiring Is not Installed. furnish pull wire.
<br />E Verify kootlone of outlet and awltd► w
<br />F. Support pans. junction and pull boxes Indspendently to building structure with no weight bearing
<br />on oondulte.
<br />G. Connect condult to motor conduit brminal boxes with flexible conduit: minimum 18 Inches In
<br />length and 50% dock. Do not terminate in or fasten raceways to motor foundation.
<br />H. Contractor to remove and salvage all abandoned elecblcal sguiment.
<br />1. This contractor shall *wmnt all labor and materials for one year from dote of fled written
<br />acceptance.
<br />J. Owner assumes responsibility to do periodic maintenance on all Aluminum Wire Connections and wig
<br />provide a signed letter to attest to this agreement.
<br />K. Contractor will provide to the Building Owner. within 30 days after the dab of the system acceptance. record
<br />drewk.gs of the actual installation Documents and Manuals per C405.8.4
<br />L Contractor loll provide construction documents that certify lighting contrals mest performance alto of
<br />Section C405 of the Florida BuNft Cods Sixth Edition (=7) Energy Conservation, and provided to the
<br />Building Owners within 90 days of mosipt of the Cortifieate of Occupancy per C408.3.2 of the same code.
<br />1.8 LOW VOLTAGE
<br />A. Low Voltage wiring drawings to be provided by allmm
<br />ELECTRICAL SYMBOLS
<br />SM — MANUAL. MOTOR STARTER SIZED AS REQUIRED
<br />S3D— 3—WAY SINGLE POLE DIMMER SWITCH (O-1OV OR LINE VOLT. AS REQUIRED)
<br />SD — SIIOLE POLE DIMMER SNITCH (0-10V OR LINE VOLTAGE AS REQUIRED)
<br />Sap— 3—WAY SINGLE POLE TOGGLE SWIM W/PILOT LIGHT
<br />S — SINGLE POLE TOGGLE SWITCH
<br />S3 — 3—WAY SMKNLE POLE TOGGLE SWITCH
<br />So — -a/b- INDICATES LIMS TO BE SWITXM
<br />G.,b — OCCUPANCY SENSOR W/iWO LEVELS OF LIGHTING LINE VOLTAGE
<br />— TIME CLACK MENDE SWITCH (MAX. 2 HR)
<br />m — LINE VOLTAGE WALL MOUNTED OCCUPANCY SENSOR
<br />® — LINE VOLTAGE COLING MOUNTED OCCUPANCY SENSOR
<br />0 — LINE VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR (LARGE RESTROOMS)
<br />® — LINE VOLTAGE WALL MOUNTED OCCUPANCY SENSOR (SMALL RESTROOMs)
<br />® — LE MOI.E_YILALL.MOUNiED OCCUPANCY SENSOR W/2 LIGHT CONTROL.
<br />® — (WALL MOUNTED OCCUPANCY SENSOR (CLOSETS)
<br />m — WALL MOUNTED DIMMABLE OCCUP44M SENSOR
<br />VERIFY LINE VOLTAGE OR 0-10V
<br />® — MANUAL "ON" OCCUPANCY SENSOR
<br />MANUAL 'ON- DIMMABLE OCCUPANCY SENSOR
<br />® — VERIFY LINE VOLTAGE OR 0-10V
<br />® — LINE VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR FOR REiCEPTACLES
<br />®— gDAAYYL1.41�TpS84SOR ��y gp��p�
<br />— RECEPTACLES f BE F TOE IN TOE THATpCCU CONTROLLED.
<br />PTr
<br />M.
<br />—Wiff IeIUST TO MIDICATE TWIT THEY ARE CONTROLLED.
<br />— SIMPLEX RECEPTACLE
<br />— DUPLEX RECEPTACLE
<br />QUADRAPLEX RECEPTACLE
<br />— FLOOR BOX W/DUPLDl RECEPTACLE LOCATIONS TO BE VERIFIED W/OWNERS
<br />FLOOR BOX W/OUADRAPLDL RECEPTACLE. VERIFY LOCATIONS W/OWNERS
<br />MONITOR CABLE/VERIFY TERMINATION W/OWNERS
<br />GFl — GROUND FAULT INTERRUPTER
<br />WP — WATER PROOF 3R — NEMA 3R
<br />NF — NON —FUSED NL — NIGHT LIGHT
<br />— DISCONNECT SWITCH
<br />— ELECTRICAL PANELBOARD
<br />EMERGENCY LX*1TING/EX1T SIGN W/BATTERY BACKUP
<br />EMERGENCY LIC1fTNi—W/BATTERY BACKUP 3
<br />TC — TIME COCK
<br />® — PHOTO ELECTRIC SENSOR
<br />® — 208V 30 RECEPTACLE
<br />— CONDUIT IN FLOOR
<br />RC — RECEPTACLE CONTACTOR
<br />® — 208V RECEPTACLE — VERIFY
<br />_ 2 VOICE (CAT 5)/2 DATA (CAT 8) OUTLET
<br />DATA Al COMMUNICA71 NS TO BE VERIFIED W/OWNERS
<br />Q— RESTROOM EXHAUST FAN
<br />NOTE:
<br />Occupancy Sensors are to be bccupancy/Vaoancy Sensors unless khdioated
<br />otherwise. W: 'Manual On" In a Vacancy sensor w/auto off.
<br />MARK
<br />MFG CATALOG NUMBER
<br />LAMPS
<br />REMARKS
<br />QUANITY
<br />A
<br />METALUX 24rP4735C
<br />40,4W/LED
<br />LAY IN
<br />5 PER UNIT
<br />B
<br />METALUX 4BCLED—LD4-32SL—F—UNV—GL—L835—CD1—U
<br />32,5W/LED
<br />WALL
<br />PER UNIT
<br />C
<br />METALUX 8ST2L804OR
<br />78,2W/LED
<br />STRIP
<br />10 PER UNIT
<br />D
<br />EAT❑N WP1135LPC (W/DUSK TO DAWN CONTROL)
<br />13W/LED
<br />WALL
<br />14
<br />E
<br />LUMARK WPSLED-30—GL—UNV
<br />27W/LED
<br />WALL PACK
<br />2
<br />X-1
<br />SURE—LITES LPXC50SD
<br />LED
<br />EXIT/EMERG. LIGHT
<br />X-2
<br />SURE—LITES APELH2
<br />LED
<br />EMERG, LIGHT
<br />NOTES:
<br />1, ALL LIGHTING AND SWITCHING TO MEET FLORIDA ENERGY
<br />CODE REQUIREMENTS
<br />2, ALL LIGHTING TO BE VERIFIED WITH OWNERS BEFORE PURCHASE
<br />3, LAMP COLOR INDEX IS TO BE VERIFIED W/❑WNERS BEFORE
<br />4, ALL EMERGENCY LIGHTING TO BE WIRED AHEAD OF ANY
<br />5, OTI—ER LIGHT FIXTURES BEING EQUAL AND APPROVED BY
<br />PURCHASE
<br />SWITCHING OR TIME CLOCK/LIGHTING
<br />OWNER ARE PERMITTED
<br />CONTRACTORS
<br />6. CONTRACTOR TO VERIFY STEM MOUNTS
<br />7. VERIFY W/CONTRACT❑R IF STEM OPTI❑NS REQUIRED
<br />I "FM I n n
<br />SUITE A SUITE B
<br />LIGHTING PLAN
<br />I hereby certif y that I have reviewed this plan and found it to bE
<br />compliance with ASCE 7-10 and the Florida Building Code 2017 6th Edi
<br />David W. Smith, P.E. #
<br />in
<br />ion
<br />3608
<br />ENGINEER LICENCE #536
<br />CHANCEY PARTNERS
<br />3761 CORREIA DR
<br />ZEPHYRHILLS, FLORIDA
<br />D.W.SMITH9M.S.,P.E.#53608
<br />FLORIDA PROFESSIONAL ENGINEER LICENSE NUMBER 53608
<br />PROJECTS ENGINEERING CONSULTANT
<br />9909 WALLASTON DRIVE—DADE CITY FLORIDA 33525
<br />PHONE1813-469-2289 E-MAIL 6sflpe@earthlink.net
<br />RICK GOLLHARDT - DRAFTSMAN
<br />813- 781- 3651
<br />rgollhardt@tampabay.rr.com
<br />LIGHT N G PLAN SHEET OF
<br />3 OF 7
<br />SCALE DATE JOB NO.
<br />DO NOT SCALE 9 OCT 2020
<br />DES I GN/BRAWN �C�ECKED 2020-1003
<br />R. GOLLHARDT D.S.,p.e.
<br />W4
<br />
|