Laserfiche WebLink
l L__ I i111 <br />1 1111,119, _�L <br />ELECTRICAL SPECIFICATIONS <br />1.1 SCOPE <br />A. WORK INCLUDED: Include the following Wo►k in addition to iteme needy part of this Ssctime <br />01 Wiring for lighting and power. <br />02 Installation of 11"V fixtures with lamps. <br />03 Lighting panelboards and distribution ponsiboords. <br />04 Connection of equipment shown. <br />05 Control wiring. <br />08 Disconnection and removal of existing fixtures and wkkg not to be mead. <br />1.2 MINIMUM COMPLIANCE STANDARDS <br />A. AN work shall be done In accordance with the requksmerrb of the foNowkW <br />01 Florida Building Cade Sixth Edition (2017). <br />02 Florida Building Code — Electrical Conservation Sixth Edition (2017). Section C405. <br />03 2014 lows of the National Electrical Code (NFPA 70). <br />04 AN Receptacle Control to conform to ASHRAE Standard 90.1. 8.4.2. 2010. <br />05 Miring In Patient Cam Areas sholl comply with NEC 517. <br />08 Other applicable NFPA Codes. <br />07 Regulation of local outhoritles having JurledloUom <br />B. Furnish and Install all labor, natotal and equlprne►t and services necessary for compleb and <br />soh installation of the electrical system Indicated on the drowkhgs and noted In the <br />specMtoatlone hereinafter. Electrical systsrrhe and equipment shall In general include the following: <br />01 Gensrd prodNom for electrical work. <br />02 Mliring, distribution equipment and devices. <br />03 Ughthq fixtures and lamps. <br />04 Grounding systern. <br />1.3 GENERAL PROVISIONS FOR ELECTRICAL WORK <br />A. DRAWN=- Elea4ted drawings considered diagrammatic and Indicate general arrangement of work <br />and systerm. Refer to ather drawings to verify Wootton of equipment, etc. Check drawings of <br />other trodee to verify exact space condition or underground Ones. Drawing Scales prohibit the <br />Indication of all offeeb, flttbgr and occesaarles required. however these Rena will be <br />provided by this subcontractor at no extra cast to the owner. <br />B. QUALITY OF MATERIALS: New, best of their respective Wnd, free from defeats, and listed by <br />Underwriter's Laboratories. Inc. or bearing their label. <br />C. SHOP DRAWINGS. Submit four (4) copies of shop d owkngs for lighting fixtures and ponelboards. <br />Obtain approval before equipment is ordered. built or Installed <br />D. EXCAVATION AND BACKFNIJNG: Excavate, backfill and restore surfaces for all electrical work. <br />E. Visit alb and inspect existing fociNtles before bid in order to ensus proper evaluation of <br />wai kh conditions and location of existing equipmenM <br />1.4 WOW. DISTRIBUTION EQUIPMENT AND DEVICES <br />A. CONDUCTORS: Copper. In accordance with ASTM Standards. size references AWL. Conductors No. 10 and <br />smaller she solid. No. 8 and larger stranded. Insulation of conductor thermoplastic. type THHN <br />(min. she: No. 12) any wire installed outside, underground, in skhbs. or exposed to moisture <br />shall have THWN insulation. <br />B. RACEWAYS: RICID STEEL CONDUIT. full weight pipe golvahhed. Wedded. and minimum 1/2 Inch except <br />as noted or required for wiring. ELECTRICAL METALLIC TUBING (BM. thin wait pips. gdvandted. threadless, <br />commselorh fittings. and minimum 1/2" except as noted or required for wiring. FLEXIBLE STEEL CONDUIT, <br />continuous ekgWob* galvanised, and minimum 1/2- Wn except as noted or required for wking. PVC <br />CONDUIT, heavy duly tyiw she as Indicated. Separate raceways shall be used for each voltage system. <br />Type AC or MC Cable where permitted. <br />C. DISCONNECT SMOTCHE& General Duty, horsepower rated for motor Wade 800 or 250 volt rating, fused <br />or non—fussd as notsd: number of poles as indicated, cover Interlocked with ew114 Enclowre <br />NEMA 1 for Wear use and NEMA 3R for weatherproof applications. Switch to be Square 'D" or equal. <br />D. CIRCUIT BREAKERS: Moiled care. thermal —magnetic quick—makt, qutok—break. bolt —on We with <br />manually operated inwiated trip —Tres handle. Multi —pole types with Internal common trip bar. <br />Terminate suitable for copper or aluminum conductors. Interrupting capacity minimum 10.000 RMS <br />symmetrical amperes circult breaksm to be Square V or equal, type as required. <br />E. PANELBOARDS: Voltage. phasing and ampere ratings as indicated. circuit breaker type as Indicated, <br />busbam of hand drawn capper. minimum 96% conductivitygalvanized steel back box. door and trim. <br />AN comers topped and welded, hardware chrome plated with flush Wok and catch. Hinges *emt— <br />conceded. 5 knuckle steel with nonferrous pins. 180 degree opening@. Mkrtmun gutter space 5- <br />31e rides, top and bottem. Increase she where required by code. Directory holder complete <br />with dear pketic transparent cover Mdioa&g typewritten NA of feeder cables, conduit sins, <br />circuit numbers. outlets of equipment supplied. and their location. Circuit breaker typs <br />pan boards to be Square "D- type NQOD or 1-0e, or equal. A plastic label shall be lactated on exte for of <br />panelboard Identifykg the "stern voltage. phase. and current rating. <br />F. MIRING DEVICES: AN devices the product of the same maewhehmr. Wall switches single pole, 20 <br />ampere, 120 volt. Wait switches thm*—way. 20ampen, 120 volt. Receptacles duplex, 2 wire: 3 <br />pole grounded, 20 ampere. 120 volt. <br />0. DEVICE PLATES: Provide for all outlets whore devices are Installed. Provide engraved markkg for <br />*pedal outlets. Provide blank plates for empty or future outlet boxes. DEVICE AND DEVICE PLATES <br />COLORS TO BE VERIFIED WITH INTERIOR DESIGNER AND OWNER. <br />1.5 L.WTNIG FIXTURES AND LAMPS <br />A. Furnish and Install complete system of lighting fixtures, lamps, accessories and supports as <br />specified and Indicated. SubmWAW of equal quality are allowed. <br />1.6 GROUNDING SYSTEM <br />A. EQUIPMENT: pound non—durrent carrying metal parts of pandboord. raceways and oil fighting <br />- fixtures. AN aondul is shall have equipment grounding conductors. <br />1.7 INSTALLATION <br />A. Secure all supports to building structure. Support horizontal num <br />of metallic conduit not more than 10 rest apart. Run exposed raceways paaild with or at right <br />angles to walls. <br />8. Pace raceways over water, steam or other piping when pull boxes are not required. No raceway <br />within 3 Inches of steam or hot water pipw or appliances, except crosdngs where r*assay @hall <br />be at least 2 Inches from pipe cover. <br />C. Cut conduit ends square, ream smooth. Point male threads of field threaded condult with graphite <br />base pipe compound. Draw up tight with conduit ooup&W <br />D. Leave wire sufficiently long to permit mcMig final connections. in raceways over 50 Test In <br />which wiring Is not Installed. furnish pull wire. <br />E Verify kootlone of outlet and awltd► w <br />F. Support pans. junction and pull boxes Indspendently to building structure with no weight bearing <br />on oondulte. <br />G. Connect condult to motor conduit brminal boxes with flexible conduit: minimum 18 Inches In <br />length and 50% dock. Do not terminate in or fasten raceways to motor foundation. <br />H. Contractor to remove and salvage all abandoned elecblcal sguiment. <br />1. This contractor shall *wmnt all labor and materials for one year from dote of fled written <br />acceptance. <br />J. Owner assumes responsibility to do periodic maintenance on all Aluminum Wire Connections and wig <br />provide a signed letter to attest to this agreement. <br />K. Contractor will provide to the Building Owner. within 30 days after the dab of the system acceptance. record <br />drewk.gs of the actual installation Documents and Manuals per C405.8.4 <br />L Contractor loll provide construction documents that certify lighting contrals mest performance alto of <br />Section C405 of the Florida BuNft Cods Sixth Edition (=7) Energy Conservation, and provided to the <br />Building Owners within 90 days of mosipt of the Cortifieate of Occupancy per C408.3.2 of the same code. <br />1.8 LOW VOLTAGE <br />A. Low Voltage wiring drawings to be provided by allmm <br />ELECTRICAL SYMBOLS <br />SM — MANUAL. MOTOR STARTER SIZED AS REQUIRED <br />S3D— 3—WAY SINGLE POLE DIMMER SWITCH (O-1OV OR LINE VOLT. AS REQUIRED) <br />SD — SIIOLE POLE DIMMER SNITCH (0-10V OR LINE VOLTAGE AS REQUIRED) <br />Sap— 3—WAY SINGLE POLE TOGGLE SWIM W/PILOT LIGHT <br />S — SINGLE POLE TOGGLE SWITCH <br />S3 — 3—WAY SMKNLE POLE TOGGLE SWITCH <br />So — -a/b- INDICATES LIMS TO BE SWITXM <br />G.,b — OCCUPANCY SENSOR W/iWO LEVELS OF LIGHTING LINE VOLTAGE <br />— TIME CLACK MENDE SWITCH (MAX. 2 HR) <br />m — LINE VOLTAGE WALL MOUNTED OCCUPANCY SENSOR <br />® — LINE VOLTAGE COLING MOUNTED OCCUPANCY SENSOR <br />0 — LINE VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR (LARGE RESTROOMS) <br />® — LINE VOLTAGE WALL MOUNTED OCCUPANCY SENSOR (SMALL RESTROOMs) <br />® — LE MOI.E_YILALL.MOUNiED OCCUPANCY SENSOR W/2 LIGHT CONTROL. <br />® — (WALL MOUNTED OCCUPANCY SENSOR (CLOSETS) <br />m — WALL MOUNTED DIMMABLE OCCUP44M SENSOR <br />VERIFY LINE VOLTAGE OR 0-10V <br />® — MANUAL "ON" OCCUPANCY SENSOR <br />MANUAL 'ON- DIMMABLE OCCUPANCY SENSOR <br />® — VERIFY LINE VOLTAGE OR 0-10V <br />® — LINE VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR FOR REiCEPTACLES <br />®— gDAAYYL1.41�TpS84SOR ��y gp��p� <br />— RECEPTACLES f BE F TOE IN TOE THATpCCU CONTROLLED. <br />PTr <br />M. <br />—Wiff IeIUST TO MIDICATE TWIT THEY ARE CONTROLLED. <br />— SIMPLEX RECEPTACLE <br />— DUPLEX RECEPTACLE <br />QUADRAPLEX RECEPTACLE <br />— FLOOR BOX W/DUPLDl RECEPTACLE LOCATIONS TO BE VERIFIED W/OWNERS <br />FLOOR BOX W/OUADRAPLDL RECEPTACLE. VERIFY LOCATIONS W/OWNERS <br />MONITOR CABLE/VERIFY TERMINATION W/OWNERS <br />GFl — GROUND FAULT INTERRUPTER <br />WP — WATER PROOF 3R — NEMA 3R <br />NF — NON —FUSED NL — NIGHT LIGHT <br />— DISCONNECT SWITCH <br />— ELECTRICAL PANELBOARD <br />EMERGENCY LX*1TING/EX1T SIGN W/BATTERY BACKUP <br />EMERGENCY LIC1fTNi—W/BATTERY BACKUP 3 <br />TC — TIME COCK <br />® — PHOTO ELECTRIC SENSOR <br />® — 208V 30 RECEPTACLE <br />— CONDUIT IN FLOOR <br />RC — RECEPTACLE CONTACTOR <br />® — 208V RECEPTACLE — VERIFY <br />_ 2 VOICE (CAT 5)/2 DATA (CAT 8) OUTLET <br />DATA Al COMMUNICA71 NS TO BE VERIFIED W/OWNERS <br />Q— RESTROOM EXHAUST FAN <br />NOTE: <br />Occupancy Sensors are to be bccupancy/Vaoancy Sensors unless khdioated <br />otherwise. W: 'Manual On" In a Vacancy sensor w/auto off. <br />MARK <br />MFG CATALOG NUMBER <br />LAMPS <br />REMARKS <br />QUANITY <br />A <br />METALUX 24rP4735C <br />40,4W/LED <br />LAY IN <br />5 PER UNIT <br />B <br />METALUX 4BCLED—LD4-32SL—F—UNV—GL—L835—CD1—U <br />32,5W/LED <br />WALL <br />PER UNIT <br />C <br />METALUX 8ST2L804OR <br />78,2W/LED <br />STRIP <br />10 PER UNIT <br />D <br />EAT❑N WP1135LPC (W/DUSK TO DAWN CONTROL) <br />13W/LED <br />WALL <br />14 <br />E <br />LUMARK WPSLED-30—GL—UNV <br />27W/LED <br />WALL PACK <br />2 <br />X-1 <br />SURE—LITES LPXC50SD <br />LED <br />EXIT/EMERG. LIGHT <br />X-2 <br />SURE—LITES APELH2 <br />LED <br />EMERG, LIGHT <br />NOTES: <br />1, ALL LIGHTING AND SWITCHING TO MEET FLORIDA ENERGY <br />CODE REQUIREMENTS <br />2, ALL LIGHTING TO BE VERIFIED WITH OWNERS BEFORE PURCHASE <br />3, LAMP COLOR INDEX IS TO BE VERIFIED W/❑WNERS BEFORE <br />4, ALL EMERGENCY LIGHTING TO BE WIRED AHEAD OF ANY <br />5, OTI—ER LIGHT FIXTURES BEING EQUAL AND APPROVED BY <br />PURCHASE <br />SWITCHING OR TIME CLOCK/LIGHTING <br />OWNER ARE PERMITTED <br />CONTRACTORS <br />6. CONTRACTOR TO VERIFY STEM MOUNTS <br />7. VERIFY W/CONTRACT❑R IF STEM OPTI❑NS REQUIRED <br />I "FM I n n <br />SUITE A SUITE B <br />LIGHTING PLAN <br />I hereby certif y that I have reviewed this plan and found it to bE <br />compliance with ASCE 7-10 and the Florida Building Code 2017 6th Edi <br />David W. Smith, P.E. # <br />in <br />ion <br />3608 <br />ENGINEER LICENCE #536 <br />CHANCEY PARTNERS <br />3761 CORREIA DR <br />ZEPHYRHILLS, FLORIDA <br />D.W.SMITH9M.S.,P.E.#53608 <br />FLORIDA PROFESSIONAL ENGINEER LICENSE NUMBER 53608 <br />PROJECTS ENGINEERING CONSULTANT <br />9909 WALLASTON DRIVE—DADE CITY FLORIDA 33525 <br />PHONE1813-469-2289 E-MAIL 6sflpe@earthlink.net <br />RICK GOLLHARDT - DRAFTSMAN <br />813- 781- 3651 <br />rgollhardt@tampabay.rr.com <br />LIGHT N G PLAN SHEET OF <br />3 OF 7 <br />SCALE DATE JOB NO. <br />DO NOT SCALE 9 OCT 2020 <br />DES I GN/BRAWN �C�ECKED 2020-1003 <br />R. GOLLHARDT D.S.,p.e. <br />W4 <br />