Laserfiche WebLink
ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2"AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />& Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11.In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14, Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />comer counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />'DUPLEX <br />ff <br />OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />FiiiF <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />$ <br />WALL SWITCH <br />j3 <br />THREE-WAY SWITCH <br />P4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />I-..O <br />WALL MOUNTED LIGHT FIXTURE <br />RECESSED LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />EXHAUST FAN <br />,Q, <br />EXHAUST FAN/LIGHT COMBINATION <br />®D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />F0 <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />© <br />TELEVISION (OPTIONAL) <br />© 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />I] <br />ELECTRIC METER <br />_>Q <br />ELECTRIC PANEL <br />_L-I <br />DISCONNECT SWITCH <br />Q��12 <br />61 J <br />ROUGH -IN FOR OPT, CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W( ROUGH -IN FOR <br />G J <br />OPT. CEILING FAN <br />+� <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />AIL <br />I <br />I <br />I <br />f <br />I <br />I <br />I i <br />I { <br />LAV <br />� I <br />L TUB/ <br />W/C SHOWER <br />LAV <br />3" VTR <br />AIL <br />i <br />I <br />I <br />I <br />I <br />I OPT. <br />LAV <br />I LAV <br />I <br />I <br />tl WIC <br />SHOWER <br />` `end F FC <br />STUDOR <br />1 ,t DBL SINK <br />VEI <br />L TW/ DISP. <br />W/C <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />Unit -A- (1532) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1533 S.F. <br />4599 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10599 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33659 <br />1st 10 KW at 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9464 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />5200 <br />TOTAL: 31768 <br />LOAD WATTS --- 240 VOLTS <br />AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Optional Overhead Service 200A <br />Same As Underground Indoor Panel <br />150 Or 200 Amp Service Center <br />NEMR 1 <br />MI - P <br />200 AM P <br />TE�RMA N <br />1 �0-200 AMP i i T l—Serial Cable <br />3R <br />Power Co. Feed ---, IJ #4 Solid COPPER Ground <br />II <br />Intersystem Bonding <br />Termination Per <br />NEC 08, 250,94 5/8" Galvanized Driven Ground <br />Rods at least 6' apart <br />Typical 150-200 Amp Electrical Riset biogram <br />TOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />'HE NFPA 70 - 17, LOCAL CODES AND THE LOCAL POWER dO. <br />C.O. <br />O <br />------------------------- <br />OUTDOOR LIVING <br />INSTALL LIGHT <br />ROUGH -IN / <br />FOR OPT. <br /><�/j�� <br />FAN/LIGHT <br />WP <br />GFI <br />t <br />.M <br />(J} QDGFI <br />DINING <br />KITCHEN l <br />110, <br />FI I 0 <br />GFI <br />SWITCH FOR <br />DISPOSAL IN CAB <br />UNDER SINK <br />GREAT ROOM \ <br />/,>ROUGH -IN` <br />FOR OPT. <br />FAN/LIGHT <br />y � I� <br />/ I <br />C.M <br />1 UPSTAIRS t <br />DISCONNECT <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE <br />RANGE HOOD PER <br />SPECS <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />OWNER'S <br />BEDROOM <br />>ROUGH -IN <br />FOR OPT. <br />FAN/LIGHT <br />� V <br />S.D <br />O. BATH <br />\ \VV/t'I-D v//� <br />-y- _j I C <br />I <br />�I <br />�rrwN. <br />° LOFT Lj \ <br />FOYER I GQ <br />- --- c.M <br />` <br />GFI <br />BATH 2 <br />@ 44" W.H. <br />\ <br />..-- A.F.F. ' \ O <br />S.D i <br />GFI <br />I WIC „- ` <br />EN I WPDB I GARAG E <br />I <br />LIGHT AS b GFI <br />I <br />PER SPECS <br />, <br />I �� ����ROUGH-IN <br />DB & GFI TO / <br />----------- <br />L---------- 1 FOR OPT. <br />BE ALIGNED GARAGE <br />VERTICALLY \ LIGHT AS <br />\` �fi FAN/LIGHT <br />\PER SPECS <br />\BEDROOM 2 <br />GARAGE <br />U <br />DOOR <br />_ <br />' - GFI.-- <br />- i--- - - - - - - - - - - - i <br />- <br />t I I <br />I j z I0 Q <br />�0� '-'� <br />\ >- W ►>- I <br />>_jm I>w <br />COACH LIGHTS <br />POEWIRE AS <br />PER SPECS <br />1ST ELECTRICAL - UNIT -A 1532 <br />SCALE: Y4"-l'•0" <br />2ND ELECTRICAL - UNIT -A 1532 <br />SCALE: &=V-0" <br />GW <br />® <br />a O <br />ti X <br />m <br />tE O a <br />N-. [V <br />N R <br />sa <br />eo � m <br />'— r, <br />N ¢^ <br />.g <br />N <br />N <br />0 <br />N <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida Building Code - <br />Residential 7th Edition. Engineer's signature and seal is only for <br />the structural engineering portions <br />of the drawing pages bearing <br />Engineer's signature and seal. <br />N <br />a <br />E <br />6 <br />V <br />CR <br />{ Co <br />m <br />N r0 <br />�mv <br />LL <br />o U_ <br />a <br />INn <br />V <br />Z <br />W <br />t o co <br />W <br />o maw o <br />w <br />W <br />Z <br />C5�O'O' m <br />N Z Q J <br />OU <br />Z <br />W <br />M r <br />Z N C <br />z Co <br />Z o <br />¢ s. <br />J — <br />d � <br />�z <br />— N <br />M <br />v�o <br />LU <br />0 <br />L /^� <br />l <br />I—y N <br />F— (n <br />RigLU <br />!— J E <br />I <br />0 VS <br />c `� <br />¢ o <br />N Of <br />o <br />w <br />Cl) <br />Cl) <br />¢2 <br />zos <br />z <br />No <br />>� <br />CL o <br />E <br />Z0 <br />tN <br />X O <br />OQ <br />00 <br />�K <br />co E <br />as <br />aZ <br />N <br /><zmo <br />m <br />CY <br />OE <br />Z <br />- � <br />wo <br />>z <br />N <br />o <br />Z <br />Q <br />OLL� <br />wLL <br />Z <br />�W <br />W <br />o <br />�- <br />O <br />�� <br />w¢ <br />=3 <br />S20 <br />yo <br />O <br />w <br />aF <br />0 <br />> d- <br />2 <br />E <br />ca <br />T <br />I:d7 <br />N <br />r <br />ciiS <br />E <br />cc <br />� <br />� <br />� <br />CD <br />CD <br />O <br />M <br />C <br />6oLo <br />N <br />N <br />U-5 <br />0�0 O <br />Q CV <br />T <br />LO <br />c9 <br />cy)oo <br />r <br />r <br />iU <br />w <br />C <br />M r <br />o <br />Z <br />z <br />E <br />a <br />is <br />U <br />c <br />D <br />a <br />° <br />Q p <br />JOB NO: 22-11681-11674 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />13 <br />