Laserfiche WebLink
ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16"AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is Intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance With FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided With a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14, Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The Width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />comer counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />Lznk <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />?4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />0 <br />EXHAUST FAN <br />tQ <br />EXHAUST FAN/LIGHT COMBINATION <br />® <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PUSH BUTTON SWITCH (OPTIONAL) <br />F0 <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />® <br />TELEVISION (OPTIONAL) <br />®2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />f <br />ELECTRIC METER <br />owl <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />L J <br />ROUGH -IN FOR OPT. CEILING FAN <br />12 <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G J <br />OPT. CEILING FAN <br />(9D <br />(1) PHONE LINE, (1) DATA PORT <br />150Ar200A INDOOR <br />PANEL CENTER <br />MAIN <br />0 <br />200 amp <br />150 amp <br />UNDERGROUND IDIs <br />SERVICE BY POWER CO.-� <br />INTERSYSTEM <br />BONDING <br />TERMINATION PER <br />to lights & outlets <br />to appliances and GFI <br />to WH <br />o Range <br />D HVAC <br />200=410 in 2" Conduit <br />v v <br />V <br />4 Bare Cu Ground <br />NEC 17, 250.94 CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram REV. 03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />15'-0" <br />VERIFY METER <br />LOCATION WITH <br />BUILDER <br />r� WP � TH.B. <br />gPIRRIGATION <br />I VERIFY LOCATION GFI @ 44" A.F.F. <br />/ ELECTRICAL PANEL <br />ROUGH -IN FOR <br />OPT. CLG. FAN/ r <br />LIGHT PRE -WIRE � I <br />I / I <br />I I / GFI @ 44" � <br />A.F.F. <br />— f I <br />BEDROOM 6 ' 2 CAR GARAGE 1 <br />DEDICATED RECEPTACLE GFI FOR I <br />FOR MICROWAVE RANGE GAR. DOOR <br />C.M S.D HOOD PER SPECS �- —' ` PREWIRE <br />7 <br />4 GFI 7GjFI <br />WP <br />\ I <br />PATIO F KIM u_CAFE ' !W <br />I <br />'PENDANT AS U. . S IT H <br />PER SPECS ; iF R D SP SA j O I <br />I <br />6'-6 SIN WI D SP I I <br />----I C#I O L------------ <br />I D.W. I `c o <br />— — v- • I @ " <br />/ GFI FL---F,-- — ---- ,� I . GF.F. <br />I UC� I I <br />V GFI v <br />473 ICHI hqP <br />FOYER <br />I <br />� I <br />N Y <br />----------- �B ----- <br />_WP <br />--- — GFI <br />FAMILYRM <br />G <br />ROUGH-IN FOR � ` FLEA( <br />OPT. CLG. FAN/ / / I I \ <br />WP LIGHT PRE -WIRE 43 <br />GFI <br />DISC.ROUGH-IN FOR <br />OPT CLG. FAN/ <br />LIGHT PRE -WIRE <br />TO LIGHTS <br />AC PAD AC PAD AND SWITCH <br />ch <br />Hil I 1 111 1111111111 17=1 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I f I 1 11 1 1 11 1 1 1 1 11 1 11 1 1 1177 11 1 11 1 11 1 11 1 11 1 11 <br />ABOVEdb <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC TO <br />BE VERIFIED WITH PLUMBER <br />FIRST FLOOR ELECTRICAL PLAN - ELEV-B1 <br />SCALE: Y4'=V-0" <br />N <br />N <br />o� <br />o <br />m "b <br />CD W <br />2 <br />u Q: o <br />� � k <br />� too <br />i <br />N <br />c <br />E <br />v � Q <br />� m % <br />C <br />� 4.1 <br />0 <br />N <br />N <br />O <br />N <br />M <br />0 <br />To the best of the Engineers knowledge, information and belief, <br />the structural plans and specifications contained <br />within these <br />drawings comply with the 2020 Rorida Building Code - <br />Residential <br />7th Edition. <br />Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />t» <br />F E <br />(0 <br />V$ <br />m m <br />Q :te N <br />h <br />r <br />fnN� <br />N <br />lit <br />ILL <br />M LL <br />WLLU. <br />Wa <br />0 <br />to <br />� @ C44 <br />m <br />ILW <br />W fR2pjO' <br />Z to Cl) Z <br />W <br />J <br />Z O 0 <br />J <br />W <br />❑❑ <br />0^ <br />z N <br />z � <br />zU) o <br />Y <br />J — <br />d � <br />z <br />4J (_a F <br />�4- <br />N <br />LU <br />O W g <br />N <br />C5 <br />CCS r to <br />W <br />L 8 <br />zr I <br />C oo <br />Q N � <br />O <br />w <br />Z <br />E E <br />o <br />-g <br />> <br />Z® <br />0 <br />ui z <br />❑ a <br />�_ � <br />° <br />U <br />&S <br />_° <br />S <br />Z <br />O <br />o <br />N � <br />d p <br /><� <br />o <br />as <br />Z <br />WZ <br />¢� <br />.�.. i <br />m� <br />0 <br />zz <br />Z <br />J <br />a� <br />�Z <br />ID <br />om <br />aZ <br />a. <br />Nw <br />W <br />U <br />o <br />o <br />mi <br />CID <br />° 3 <br />> (� <br />LID <br />Lid <br />ai <br />Of <br />B <br />c� <br />(D <br />H <br />L <br />M <br />C� <br />v J <br />m <br />m <br />LN <br />N <br />0 <br />C:) <br />00 <br />N <br />M <br />C` <br />T <br />coLo <br />z <br />E <br />y <br />m <br />C <br />:3 <br />JOB <br />NO: <br />22-06471 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />4.0 <br />