+A.
<br />TERMITE SPECIFICATIONS:
<br />1. A PERMANENT SIGN WHICH IDENTIFIES THE TERMITE TREATMENT PROVIDER
<br />AND NEED FOR RE -INSPECTION AND TREATMENT CONTRACT RENEWAL SHALL
<br />BE PROVIDED. THE SIGN SHALL BE POSTED NEAR THE WATER HEATER OR
<br />ELECTRIC PANEL.(FBC 104.2.6)
<br />2. CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1'-0"
<br />AWAY FROM BUILDING SIDE WALKS.(FBC 1503.4.4)
<br />3. IRRIGATION/SPRINKLER SYSTEMS INCLUDING ALL RISERS AND SPRAY HEADS
<br />SHALL NOT BE INSTALLED WITHIN 1'-0" OF THE BUILDING SIDE WALLS.(FBC 1503.4.4)
<br />4. TO PROVIDE FOR INSPECTION FOR TERMITE INFESTATION, BETWEEN WALL
<br />COVERING AND FINAL EARTH GRADE SHALL NOT BE LESS THAT 6 INCHES.
<br />EXCEPTION: PAINT OR DECORATIVE CEMENTATIOUS FINISH LESS THAN 5/8"
<br />THICK ADHERED DIRECTLY TO THE FOUNDATION WALL.(FBC 1403.1.6)
<br />5. INITIAL TREATMENT SHALL BE DONE AFTER ALL EXCAVATION AND BACKFILL
<br />IS COMPLETE.(FBC 1816.1.1)
<br />6. SOIL DISTURBED AFTER THE INITIAL TREATMENT SHALL BE RETREATED
<br />INCLUDING SPACES BOXED AND FORMED.(FBC 1816.1.2)
<br />7. BOXED AREAS IN CONCRETE FLOORS FOR SUBSEQUENT INSTALLATION OF TRAPS,
<br />ETC., SHALL BE MADE WITH PERMANENT METAL OR PLASTIC FORMS. PERMANENT
<br />FORMS MUST BE OF A SIZE AND DEPTH THAT WILL ELIMINATE THE DISTURBANCE OF
<br />SOIL AFTER THE INITIAL TREATMENT.(FBC 1816.1.3)
<br />8. MINIMUM 6 MIL VAPOR RETARDER MUST BE INSTALLED TO PROTECT AGAINST RAINFALL
<br />DILUTION. IF RAINFALL OCCURS BEFORE VAPOR RETARDER PLACEMENT, RETREATMENT IS
<br />REQUIRED.(FBC 1816.1.4)
<br />9. CONCRETE OVERPOUR AND MORTAR ALONG THE FOUNDATION PERIMETER MUST BE
<br />REMOVED BEFORE EXTERIOR SOIL TREATMENT.(FBC 1816.1.5)
<br />10. SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE
<br />WITHIN 1'-0" OF THE STRUCTURE SIDEWALLS.(FBC 1816.1.6)
<br />11. AN EXTERIOR VERTICAL CHEMICAL BARRIER MUST BE INSTALLED AFTER CONSTRUCTION
<br />IS COMPLETE INCLUDING LANDSCAPING AND IRRIGATION. ANY SOIL DISTURBED AFTER
<br />THE VERTICAL BARRIER IS APPLIED, SHALL BE RETREATED.(FBC 1816.1.6)
<br />12. ALL BUILDINGS ARE REQUIRED TO HAVE PRE -CONSTRUCTION TREATMENT.(FBC 1816.1.7)
<br />13. A CERTIFICATE OF COMPLIANCE MUST BE ISSUED TO THE BUILDING DEPARTMENT
<br />BY A LICENSED PEST CONTROL COMPANY BEFORE A CERTIFICATE OF OCCUPANCY
<br />WILL BE ISSUED. THE CERTIFICATE OF COMPLIANCE SHALL STATE: "THE BUILDING
<br />HAS RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN
<br />TERMITES. THE TREATMENT IS IN ACCORDANCE WITH THE RULES AND LAWS OF THE
<br />FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES."(FBC 1816.1.7)
<br />14. AFTER ALL WORK IS COMPLETED, LOOSE WOOD AND FILL MUST BE REMOVED FROM
<br />BELOW AND WITHIN 1'-0" OF THE BUILDING. THIS INCLUDES ALL GRADE STAKES,
<br />TUB TRAY BOXES, FORMS, SHORING OR OTHER CELLULOSE CONTAINING MATERIAL.
<br />(FBC 2303.1.3)
<br />15. NO WOOD, VEGETATION, STUMPS, CARDBOARD, TRASH, ETC., SHALL BE BURIED
<br />WITHIN 15'-0": OF ANY BUILDING OR PROPOSED BUILDING.(FBC 2303.1.4)
<br />ABBREVIATIONS
<br />A.B.
<br />Anchor Bolt
<br />F.B.C.
<br />Florida Bldg. Code
<br />Opn'g.
<br />Opening
<br />Abv.
<br />Above
<br />Fin. Flr.
<br />Finished Floor
<br />Opt.
<br />Optional
<br />A/C
<br />Air -Conditioner
<br />F.G.
<br />Fixed Glass
<br />Pc.
<br />Piece
<br />Adj.
<br />Adjustable
<br />Flr.
<br />Floor
<br />Ped.
<br />Pedestal
<br />A.F.F.
<br />Above Finished Floor
<br />Fdn.
<br />Foundation
<br />P.L.
<br />Parallam
<br />A.H.U.
<br />Air Handler Unit
<br />Flr. Sys.
<br />Floor System
<br />PLF
<br />Pounds per linear foot
<br />ALT.
<br />Alternate
<br />F.PI.
<br />Fireplace
<br />Plt. Ht.
<br />Plate Height
<br />B.C.
<br />Base Cabinet
<br />Ft.
<br />Foot / Feet
<br />Plt Sh.
<br />Plant Shelf
<br />B.F.
<br />Bifold Door
<br />Ftg.
<br />Footing
<br />PSF
<br />Pounds per square foot
<br />Bk Sh
<br />Book Shelf
<br />FX
<br />Fixed
<br />P.T.
<br />Pressure Treated
<br />Bm.
<br />Beam
<br />Galy.
<br />Galvanized
<br />Pwd.
<br />Powder Room
<br />BOT.
<br />Bottom
<br />G.C.
<br />General Contractor
<br />Rad.
<br />Radius
<br />B.P.
<br />Bypass door
<br />G.F.I.
<br />Ground Fault Interrupter
<br />Ref.
<br />Refrigerator
<br />Brg.
<br />Bearing
<br />G.T.
<br />Girder Truss
<br />Req'd.
<br />Required
<br />Cir.
<br />Circle
<br />Hdr.
<br />Header
<br />Rm.
<br />Room
<br />Clg.
<br />Ceiling
<br />Hgt.
<br />Height
<br />Rnd.
<br />Round
<br />Col.
<br />Column
<br />HB
<br />Hose Bibb
<br />R/SH
<br />Rod and Shelf
<br />Comp.
<br />A/C Compressor
<br />Int.
<br />Interior
<br />SD.
<br />Smoke Detector
<br />C.T.
<br />Ceramic Tile
<br />K/Wall
<br />Kneewall
<br />S.F.
<br />Square Ft.
<br />D
<br />Dryer
<br />K.S.
<br />Knee Space
<br />Sh.
<br />Shelves
<br />Dec.
<br />Decorative
<br />Laun.
<br />Laundry
<br />SHT
<br />Sheet
<br />Ded.
<br />Dedicated Outlet
<br />Lay.
<br />Lavatory
<br />S.L.
<br />Side Lights
<br />Dbl.
<br />Double
<br />L.F.
<br />Linear Ft.
<br />S.P.F.
<br />Spruce Pine Fir
<br />Dia.
<br />Diameter
<br />L.T.
<br />Laundry Tub
<br />Sq.
<br />Square
<br />Disp.
<br />Disposal
<br />Mas.
<br />Masonry
<br />S.Y.P.
<br />Southern Yellow Pine
<br />Dist.
<br />Distance
<br />Max
<br />Maximum
<br />Temp.
<br />Tempered
<br />D.S.
<br />Drawer Stack
<br />M.C.
<br />Medicine Cabinet
<br />Thik'n.
<br />Thicken
<br />D.V.
<br />Dryer Vent
<br />Mfgr.
<br />Manufacturer
<br />T.O.B.
<br />Top of Block
<br />D.W.
<br />Dishwasher
<br />Micro.
<br />Microwave
<br />T.O.M.
<br />Top of Masonry
<br />Ea.
<br />Each
<br />Min
<br />Minimum
<br />T.O.P.
<br />Top of Plate
<br />E.W.
<br />Each Way
<br />M.L.
<br />Microlam
<br />Trans.
<br />Transom Window
<br />Elec.
<br />Electrical
<br />Mir.
<br />Mirror
<br />Typ.
<br />Typical
<br />Elev.
<br />Elevation
<br />Mono
<br />Monolithic
<br />UCL
<br />Under Cabinet Lighting
<br />Ext.
<br />Exterior
<br />N.T.S.
<br />Not to Scale
<br />U.N.O.
<br />Unless Noted Otherwise
<br />Exp.
<br />Expansion
<br />VB
<br />Vanity Base
<br />Vert.
<br />Vertical
<br />V.L.
<br />Versalam
<br />VTR
<br />Vent through Roof
<br />W
<br />Washer
<br />W/
<br />With
<br />W/C
<br />Water Closet
<br />W.A.
<br />Wedge Anchor
<br />Wd
<br />Wood
<br />WP
<br />Water Proof
<br />MASTER REVISIONS
<br />DATE I DESCRIPTION
<br />STRUCTURAL NOTES:
<br />FOUNDATIONS
<br />SOIL TO BE COMPACTED TO AT LEAST 95%
<br />OF MAX. DRY DENSITY AS DETERMINED BY
<br />ASTM - 1557 ( MODIFIED PROCTOR)
<br />FOUNDATION INSPECTIONS
<br />A FOUNDATION SURVEY SHALL BE PERFORMED AND A
<br />COPY OF THE SURVEY SHALL BE ON SITE FOR THE BUILDING
<br />INSPECTORS USE, OR ALL PROPERTY MARKERS SHALL BE
<br />EXPOSED AND A STRING STRETCHED FROM MARKER TO
<br />MARKER TO VERIFY REQUIRED SETBACKS.
<br />CAST IN PLACE CONCRETE
<br />1. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE
<br />STRENGTH AT 28 DAYS OF 3000 PSI, A SLUMP OF 6"
<br />PLUS OR MINUS 1", AND HAVE 2 TO 5% AIR ENTRAINMENT,
<br />AND A MAXIMUM WATER/CEMENT RATIO OF 0.63
<br />2. ALL REINFORCING STEEL SHALL BE NEW DOMESTIC
<br />DEFORMED BILLET STEEL CONFORMING TO ASTM A-615
<br />GRADE 40.
<br />3. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185.
<br />WWF SHALL BE LAPPED AT LEAST 6" AND CONTAIN AT
<br />LEAST ONE CROSS WIRE WITHIN THE 6".
<br />4. HOOKS SHALL BE PROVIDED AT DISCONTINUOUS ENDS OF
<br />ALL TOP BARS OF BEAMS.
<br />5. HORIZONTAL FOOTING BARS SHALL BE BENT 1'-0"
<br />AROUND CORNERS OR CORNER BARS WITH A 2'-0"
<br />LAP PROVIDED
<br />6. MINIMUM LAP SPLICES ON ALL REINFORCING BAR
<br />SPLICES SHALL BE 40 BAR DIAMETERS TYP.
<br />7. CONCRETE COVER MIN. 3" WHEN EXPOSED TO EARTH OR
<br />1 1/2" TO FORM
<br />REINFORCING STEEL
<br />ALL REINFORCING STEEL SHALL BE NEW DEFORMED BARS
<br />FREE FROM RUST, SCALE & OIL & SHALL MEET ASTM A-615
<br />REINFORCING FOR FOOTING SHALL BE SUPPORTED ON PRE-
<br />CAST CONCRETE PADS, TOP REINFORCING SHALL BE
<br />POSITIVELY SUPPORTED BY TEMPORARY STRINGERS.
<br />DOWELS FOR COLUMNS & FILLED CELLS SHALL BE SECURED
<br />IN PLACE BY USING ADDITIONAL CROSS- REINFORCING TIED
<br />TO FOOTING REINFORCING. SPLICES IN REINFORCING WHERE
<br />PERMITTED SHALL BE THE FOLLOWING MINIMUM, UNLESS
<br />OTHERWISE INDICATED ON THE DRAWINGS:
<br />FIGS, WALLS, COLUMNS, BEAMS, SLABS: 36 DIA. OR 2'-0" MIN., WHICHEVER IS MORE.
<br />FILLED CELL REINFORCING: 40 DIA. OR 2'-0" MIN., WHICHEVER IS MORE.
<br />TEMPERATURE REINFORCING: 20 DIA. OR 1'-0" MIN., WHICHEVER IS MORE.
<br />WELDED WIRE MESH: 8" LAP
<br />MASONRY WALL CONST.
<br />1. HOLLOW LOAD BEARING UNITS SHALL BE NORMAL
<br />WEIGHT, GRADE N, TYPE 2, CONFORMING TO ASTM C90,
<br />WITH A MINIMUM NET COMPRESSIVE STRENGTH OF
<br />1900 PSI (f'm = 1500 PSI )
<br />2. MORTAR SHALL BE TYPE "S", CONFORMING TO
<br />ASTM C270.
<br />3. COARSE GROUT SHALL CONFORM TO ASTM C476 WITH A
<br />MAXIMUM AGGREGATE SIZE OF 3/8" AND A MINIMUM
<br />COMPRESSIVE STRENGTH OF 3000 PSI SLUMP 8" TO 11".
<br />4. VERTICAL REINFORCEMENT SHALL BE AS NOTED ON THE
<br />DRAWINGS WITH THE CELLS FILLED WITH COARSE GROUT.
<br />5. VERTICAL REINFORCEMENT SHALL BE HELD IN POSITION
<br />AT THE TOP AND BOTTOM AND AT A MAXIMUM SPACING
<br />OF 192 BAR DIAMETERS. REINFORCEMENT SHALL BE PLACED
<br />IN THE CENTER OF THE MASONRY CELL TYPICAL UNLESS
<br />OTHERWISE NOTED.
<br />6. REINFORCING STEEL SHALL BE LAPPED A MINIMUM OF 40 BAR
<br />DIAMETERS, UNLESS OTHERWISE NOTED ON THE DRAWINGS
<br />7. GROUT STOPS SHALL BE PROVIDED BELOW BOND BEAM. PLASTIC
<br />SCREEN, METAL LATH STRIP OR CAVITY CAPS MAY BE USED TO
<br />PREVENT THE FLOW GROUT INTO CELLS BELOW. THE USE OF FELT
<br />PAPER AS A STOP IS PROHIBITED.
<br />WOOD CONSTRUCTION
<br />1. WOOD CONSTRUCTION SHALL CONFORM TO THE NFPA
<br />"NATIONAL DESIGN SPECIFICATION FOR WOOD
<br />CONSTRUCTION", LATEST EDITION.
<br />2. ALL EXTERIOR WOOD STUD WALLS, BEARING WALLS, SHEAR
<br />WALLS AND MISC. STRUCTURAL WOOD FRAMING MEMBERS,
<br />( I.E. BLOCKING OR GABLE END BRACING ) SHALL BE EITHER
<br />SOUTHERN PINE, OR S.P.F. NUMBER 2 GRADE SHALL BE
<br />USED REGARDLESS OF SPECIES.
<br />ALL WORK SHALL COMPLY WITH ALL
<br />PREVAILING CODES, FLORIDA BUILDR,''
<br />CODE, NATIONAL ELECTRIC CODE AND
<br />C;'1Y OF, ZEPHYRHILLS ORDINANCES
<br />(REVIEWED
<br />MAY 0 9 2005
<br />3. ANY WOOD FRAME INTERIOR BEARING WALL STUDS THAT
<br />HAVE HOLES IN THE CENTER OF THE STUD UP TO 1" DIA.
<br />SHALL HAVE STUD PROTECTION
<br />SHIELDS FOR ALL HOLES OVER 1" IN DIA.
<br />FOR PLUMBING LINES, ETC. SHALL BE REPAIRED WITH
<br />SIMPSON HSS2 STUD SHOES,TYP., U.N.O.
<br />WOOD FRAMING INSPECTION
<br />ALL PLUMBING, ELECTRICAL, AND MECHANICAL
<br />ROUGH -INS MUST BE COMPLETE, INSPECTED
<br />AND APPROVED BEFORE REQUESTING FRAMING
<br />INSPECTION.
<br />PREFABRICATED WOOD TRUSSES
<br />1. ALL PREFABRICATED WOOD TRUSSES SHALL BE SECURELY
<br />FASTENED TO THEIR SUPPORTING WALLS OR BEAMS WITH
<br />HURRICANE CLIPS OR ANCHORS.
<br />2. PREFABRICATE WOOD TRUSSES SHALL BE DESIGNED IN
<br />ACCORDANCE WITH THE LATEST EDITION OF THE "NATIONAL
<br />DESIGN SPECIFICATION FOR STRESS -GRADE LUMBER AND
<br />ITS FASTENERS" AS RECOMMENDED BY THE NATIONAL
<br />FOREST PRODUCTS ASSOCIATION.
<br />3. TRUSS MEMBERS AND CONNECTIONS SHALL BE PROPOR-
<br />TIONED ( WITH A MAXIMUM ALLOWABLE STRESS INCREASE
<br />FOR LOAD DURATION OF 25%) TO WITHSTAND THE LIVE
<br />LOADS GIVEN IN THE NOTES AND TOTAL DEAD LOAD.
<br />4. BRIDGING FOR PRE-ENGINEERED TRUSSES SHALL BE AS
<br />REQUIRED BY THE TRUSS MANUFACTURER UNLESS
<br />NOTED ON THE PLANS.
<br />5. TRUSS ELEVATIONS AND SECTIONS ARE FOR GENERAL
<br />CONFIGURATION OF TRUSSES ONLY. WEB MEMBERS ARE
<br />NOT SHOWN, BUT SHALL BE DESIGNED BY THE TRUSS
<br />MANUFACTURER IN ACCORDANCE WITH THE FOLLOWING
<br />DESIGN LOADS:
<br />6. DESIGN SPECIFICATIONS FOR LIGHT WEIGHT METAL
<br />PLATE CONNECTED WOOD TRUSSES PER THE TRUSS
<br />PLATE INSTITUTE TPI LATEST EDITION.
<br />7. PRE-ENGINEERED WOOD TRUSSES SHALL BE DESIGNED BY
<br />THE MANUFACTURER IN ACCORDANCE WITH SPECIFIED LOADS
<br />AND GOVERNING CODES . SUBMITTALS SHALL INCLUDE TRUSS
<br />FRAMING PLANS AND DETAILS SHOWING MEMBER SIZES,
<br />BRACING, ANCHORAGE, CONNECTIONS, TRUSS LOCATIONS, AND
<br />AND PERMANENT BRACING AND/OR BRIDGING AS REQUIRED
<br />FOR ERECTION AND FOR THE PERMANENT STRUCTURE. EACH
<br />SUBMITTAL SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />REGISTERED STRUCTURAL ENGINEER. SUBMIT 3 COPIES FOR
<br />REVIEW AND APPROVAL PRIOR TO FABRICATION.
<br />8. THE TRUSS MANUFACTURER SHALL DETERMINE ALL SPANS
<br />WORKING POINTS, BEARING POINTS, AND SIMILAR CONDITIONS.
<br />TRUSS SHOP DRAWINGS SHALL SHOW ALL TRUSSES, ALL
<br />BRACING MEMBERS, AND ALL TRUSS TO TRUSS HANGERS.
<br />UPLIFT CONNECTORS
<br />1. UPLIFT CONNECTORS SUCH AS HURRICANE CLIPS, TRUSS
<br />ANCHORS AND ANCHOR BOLTS ARE ONLY REQUIRED ON
<br />MEMBERS IN WALLS THAT ARE EXPOSED TO UPLIFT FORCES.
<br />INTERIOR LOAD BEARING WALLS ARE NOT ALWAYS EXPOSED
<br />TO UPLIFT FORCES. THE MEMBERS OF THESE WALLS WOULD
<br />NOT NEED TO HAVE CONNECTORS APPLIED. PLEASE CONSULT
<br />THE TRUSS ENGINEERING FOR THE LOCATION OF THESE WALLS.
<br />STRUCTURAL DESIGN CRITERIA
<br />CODES:
<br />FLORIDA BUILDING CODE, 2001 EDITION WITH 2003 REVISIONS
<br />BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE (ACI 318-02)
<br />SPECIFICATIONS FOR STRUCTURAL CONCRETE BUILDINGS (ACI 301-02)
<br />BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI 530-02)
<br />NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION, 2001 EDITION
<br />APA PLYWOOD DESIGN SPECIFICATION
<br />LIVE LOADS:
<br />ROOF 20 PSF (REDUCIBLE)
<br />RESIDENTIAL FLOOR, UNLESS OTHERWISE INDICATED 40 PSF
<br />BALCONIES 40 PSF
<br />STAIRS 40 PSF
<br />LIGHT PARTITIONS (DEAD LOAD), U.N.O. 20 PSF
<br />10 PSF ATTIC L.L.
<br />WIND LOADS:
<br />WIND LOADS BASED ON FBC, SECTION 1606.2.
<br />(F.B.C.)
<br />WIND VELOCITY: 123 M.P.H., USE FACTOR: 1.0
<br />CONCRETE
<br />ALL CONCRETE UNLESS OTHERWISE INDICATED 3000 PSI
<br />STRENGTH
<br />PEA GRAVEL CONCRETE FOR MASONRY CELLS ONLY 3000 PSI
<br />0 28 DAYS
<br />(DO NOT USE FOR CONCRETE COLUMNS OR TIE BEAMS)
<br />REINFORCING:
<br />WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185
<br />ALL REINFORCING BARS ASTM A615-40 40,000 PSI
<br />ALL STIRRUPS AND TIES ASTM A615-40 40,000 PSI
<br />CONCRETE
<br />ASTM C90-99b, STANDARD WEIGHT UNITS, fm=1500 PSI
<br />MASONRY
<br />MORTAR TYPE "S" 1800 PSI
<br />UNITS:
<br />CONCRETE GROUT 3000 PSI
<br />CONTINUOUS MASONRY INSPECTION IS REQUIRED DURING CONSTRUCTION
<br />STRUCTURAL
<br />ALL STRUCTURAL AND MISCELLANEOUS STEEL A36 36,000 PSI, U.N.O
<br />STEEL:
<br />SHOP AND FIELD WELDS: E70XX ELECTRODES
<br />ALL BOLTS CAST IN CONCRETE: ASTM A36 OR ASTM A-307
<br />WOOD FRAMING:
<br />BEAMS, RAFTERS, JOIST, PLATES, ETC. U.N.O.
<br />NO. 2 SOUTHERN YELLOW PINE (19% M.C.)
<br />ROOF DECK: PLYWOOD C-C/C-D, EXTERIOR, or OSB
<br />FLOOR SHEATHING: T&G A-C GROUP 1 APA RATED (48/24)
<br />WALL SHEATHING: PLYWOOD C-C/C-D, EXTERIOR OR OSB
<br />VERSA LAM BEAM Fb = 2900 PSI (2.OE)
<br />WOOD COLS. PARALLAM 2.0E U.N.O.
<br />WOOD ROOF
<br />DESIGN LOADS:
<br />TRUSSES:
<br />TOP CHORD LIVE LOAD: 20 PSF
<br />TOP CHORD DEAD LOAD: 10 PSF
<br />BOTTOM CHORD DEAD LOAD: 10 PSF
<br />40 PSF
<br />BOTTOM CHORD ATTIC LIVE LOAD: 10 PSF
<br />SEE DRAWINGS FOR SPECIAL CONCENTRATED LOADS. DESIGN
<br />FOR NEW WIND UPLIFT AS PER SPECIFIED CODES, DEDUCTING
<br />A MAXIMUM OF 5 P.S.F. DEAD LOAD, BUT NOT EXCEEDING ACTUAL
<br />DEAD LOAD.
<br />WOOD FLOOR
<br />DESIGN LOADS:
<br />TRUSSES:
<br />DEAD LOAD: 15 PSF
<br />LIVE LOAD: 50 PSF
<br />TOTAL: 65 PSF
<br />SOIL BEARING
<br />ASSUMED ALLOWABLE SOIL BEARING PRESSURE AFTER COMPACTION: 2000 PSF
<br />VALUE:
<br />SEE SOILS REPORT AND SPECIFICATIONS FOR COMPACTION REQUIREMENTS
<br />IF SOIL CONDITIONS IN THE PROJECT DO NOT MEET OR EXCEED THE CAPACITY
<br />THE GENERAL CONTRACTOR SHALL CONTACT THE ENGINEER PRIOR TO
<br />FOUNDATION POUR FOR VERIFICATION OF FOUNDATION DESIGN.
<br />BUILDING DATA
<br />CONSTRUCTION TYPE - TYPE VI UNPROTECTED WIND SPEED 123 MPH (3 SEC. GUST)
<br />(SECTION 608 - FBC 2001) WIND IMPORTANCE FACTOR - (Iw) = 1.0
<br />MEAN ROOF 15 FT. HIGH WIND EXPOSURE - "B" (FBC 1606.1.8)
<br />TYPICAL FOR SINGLE HOMES INTERNAL PRESSURE COEFFICIENT = +/ 0.55 (PARTIALLY
<br />ENCLOSED BLDG)
<br />DESIGN WIND PRESSURE:
<br />(COMPONENT AND CLADDING) WORST CASE (10 SF - END ZONE)
<br />WINDOWS AND DOORS
<br />123 MPH + 38 PSF / - 40 PSF
<br />GARAGE DOORS (V = 123 MPH)
<br />SINGLE 9x7 +37.0 PSF / -40.0 PSF
<br />DOUBLE 16x7 +37.0 PSF / -41.0 PSF
<br />SEE FLOOR PLAN FOR ACTUAL PRESSURES
<br />ENGINEERED PLANS
<br />ON FILE
<br />COLONIAL ANDE 2003
<br />GENERAL NOTES:
<br />Qo
<br />y °
<br />�o
<br />oQ���
<br />wa
<br />ma
<br />w0LL
<br />0ZZ
<br />� m
<br />THE FOLLOWING TECHINCAL CODES
<br />wo
<br />U Xo Z) LL L)
<br />y
<br />o p
<br />SHALL APPLY:
<br />frp z U
<br />(- CL 2 UJ ¢
<br />a c7
<br />2001 FLORIDA BUILDING CODE,
<br />w C) d 0
<br />4)
<br />o
<br />WITH 2003 REVISIONS
<br />PLUMBING , MECHANICAL, FUEL GAS,
<br />W " w
<br />w w¢ o
<br />(Aw
<br />-'
<br />m
<br />ENERGY EFFICIENCY, ACCESSIBILITY,
<br />AND NFPA 70-02
<br />0
<br />C� ow Y o 0
<br />Q � Z
<br />0
<br />v Cr
<br />NATIONAL ELECTRICAL CODES
<br />II-- p 0
<br />o
<br />Dw-w
<br />O a<Z2
<br />+ W
<br />w
<br />O wu,w¢z
<br />0
<br />w < 0
<br />0
<br />mo o
<br />1. TANK TYPE WATER CLOSET VOLUME
<br />1.6 GALLONS
<br />IX z o- -
<br />Q LL
<br />��" m
<br />t <_J
<br />2. WALL MOUNT WATER CLOSET VOLUME
<br />g w o a
<br />Er o � -' ¢
<br />a ¢ Z m
<br />N m
<br />p 0
<br />3.5 GALLONS
<br />3. WATER FLOW RATE.
<br />(n a ¢ ui o ¢
<br />W fr_
<br />06
<br />uO p r-ti
<br />PUBLIC FACILITIES 0.5 G.P.M.
<br />; > ¢ z
<br />+
<br />+ rn
<br />PRIVATE FACILITIES 2.2 G.P.M.
<br />a 0 3 ¢ 0
<br />SHOWER HEADS 2.5 G.P.M.
<br />4. ALL WATER LINE PLUMBING
<br />r z ao CS
<br />Z
<br />TO BE PVPC
<br />~ W 3 m
<br />rn
<br />VTR LOCATIONS ARE APPROXIMATE
<br />0 Z ''' < N `4 y
<br />o Z 0 0
<br />m
<br />AND MAY CHANGE DUE TO JOBSITE
<br />LU 0 ¢ L) -� O
<br />o Z
<br />CONDITIONS
<br />z Q 9 0 ��* .
<br />�c�Z ,yea
<br />OP Q
<br />N
<br />THE FOLLOWING SHALL COMPLY
<br />z w aw_ o 0 W Z O
<br />0
<br />E o
<br />WITH THE 2001FBC.
<br />LU
<br />WZoMZ00aC Z
<br />m N
<br />❑ PORCHES AND BALCONIES
<br />~ 0 Z i T J O 3
<br />M M C
<br />SECTION1014
<br />❑ HANDRAILS - SECTION 1007.5
<br />0LL <a WU)a-Wm W
<br />(n a ¢ ~ 0 ¢ m 0
<br />0NNw
<br />co `m
<br />❑ GUARDRAILS - SECTION 1015, 1019.9
<br />M n 0 < ==) �p
<br />0 U- ao � v (o
<br />N
<br />❑ STAIRS SECTION 1007
<br />� 3 � n = Z
<br />OJ
<br />'CV:> W
<br />i a
<br />❑ CHIMNEY & FIREPLACE
<br />SECTION 2804-2806 (MFGR)
<br />oz�o~axurt
<br />� � W 0 � Fn n❑❑ �
<br />:Xmci
<br />m < a- � 0 2 0
<br />SECTION 2113-2114 (MAS)
<br />❑ EGRESS WINDOWS
<br />E3
<br />SECTION 1005.4
<br />5. ALL OPENINGS SHALL COMPLY WITH
<br />to
<br />2001; FBC WIND LOADS AS STATED
<br />W
<br />BELOW. ATTACHMENTS OF WINDOWS,
<br />DOORS, SLIDING GLASS DOORS
<br />AND O.H. GARAGE DOORS ARE TO DELEGATED
<br />It
<br />THE MANUFACTURER OF THESE ITEMS. THE
<br />N LIN
<br />MANUFACTURER OF THESE ITEMS
<br />SHALL SUBMIT ATTACHMENTS FOR
<br />Z 0 r N
<br />SITE INSTALLATION.
<br />0 J M N
<br />SEE ATTACHED SPECIFICATION SHEETS FOR
<br />.
<br />N In
<br />MANUFACTURERS DESIGN CRITERIA AND
<br />W M �
<br />INSTALLATION METHODS FOR WINDOWS,
<br />;
<br />lz
<br />DOORS, SLIDING GLASS DOORS, OVERHEAD
<br />_
<br />M
<br />O 0
<br />GARAGE DOORS, AND ROOFING.
<br />.a
<br />aNL�
<br />IL
<br />6. ALL DOORS INTERIOR & EXTERIOR ARE
<br />m
<br />6'-8" UNLESS OTHERWISE NOTED
<br />Q in IL
<br />ALL SHOWER ENCLOSURES TO BE
<br />.w F W
<br />'-
<br />TEMPERED GLASS
<br />a
<br />7. ALL WINDOWS WITHIN 24" OF DOORS
<br />(INTERIOR & EXTERIOR) AND WITHIN
<br />-.. Z
<br />18" OF FLR TO BE TEMPERED GLASS.
<br />(SECTION 2405.2)
<br />INDEX OF DRAWINGS
<br />Zo
<br />z w
<br />z
<br />�
<br />UJ I—
<br />SHT NO TITLE
<br />ozN�¢
<br />° � - _'
<br />z�'=3(n
<br />¢Nww
<br />z QoO
<br />Cr
<br />1 COVER SHEET
<br />inw w LU Q
<br />3 0 U
<br />2 FLOOR PLAN
<br />�oz
<br />O�w
<br />3 FOUNDATION PLAN
<br />�>wo�
<br />N a <
<br />4 ELECTRICAL PLAN
<br />5 ELEVATIONS
<br />Z
<br />6 TRUSS LAYOUT
<br />Ln
<br />S-1 MASONRY DETAILS
<br />c-4
<br />c)
<br />=
<br />Lo
<br />0
<br />LINTEL PLAN AND DETAILS
<br />o
<br />QMS-2
<br />DETAILS
<br />LooS-3
<br />S-4 DETAILS
<br />w
<br />�
<br />0
<br />S-5 DETAILS
<br />S-6 DETAILS N
<br />S-7 STRUC. NOTES &
<br />O Cn
<br />Lu
<br />HANGER INFORMATION
<br />J
<br />0
<br />S-8 DETAILS
<br />O _..I
<br />z
<br />w
<br />o
<br />S-9 DOOR DETAILS
<br />N '-
<br />Q
<br />U
<br />-
<br />Z E Z
<br />ao
<br />Z
<br />S-10 ROOFING DETAILS
<br />Z
<br />Z W >
<br />S-10A ROOFING DETAILS
<br />(�
<br />C
<br />O
<br />o 0
<br />0Q
<br />S-11 GARAGE DETAILS
<br />J
<br />Q
<br />z
<br />o w 0
<br />S-12 DETAILS
<br />PRODUCT APPROVAL
<br />W
<br />Q
<br />N
<br />a
<br />S-13
<br />-
<br />_
<br />cr -
<br />S-14 WINDOW DETAILS
<br />-
<br />Z
<br />0
<br />m= Z
<br />S-15 SGD DETAILS
<br />w 0
<br />-
<br />Cr
<br />0
<br />S-16 D ETA I LS
<br />LO F-
<br />2 --�
<br />a
<br />S-17 DETAILS
<br />Q p
<br />��o
<br />Ld
<br />S-18 DETAILS
<br />z V
<br />O
<br />a Z o
<br />J
<br />U
<br />=¢
<br />NOTICE TO BUILDER
<br />�_ 2
<br />Cr
<br />IT IS THE INTENT OF THIS DESIGNER THAT
<br />THESE PLANS ARE ACCURATE AND ARE
<br />0
<br />O
<br />SHEET NO.
<br />a
<br />CLEAR ENOUGH FOR THE LICENSED PROFESS-
<br />ONAL TO CONSTRUCT THIS PROJECT.
<br />Ld
<br />IN THE EVENT THAT SOMETHING IS UNCLEAR
<br />OR NEEDS CLARIFICATION..STOP..AND CALL
<br />z N
<br />OF
<br />THE DESIGNER LISTED IN THIS TITLE PAGE. IT
<br />w
<br />25
<br />co
<br />0
<br />IS THE RESPONSIBILITY OF THE LICENSED
<br />PROFESSIONAL THAT IS CONSTRUCTING THIS
<br />\
<br />LAST PLOT DATE
<br />0
<br />March 11,
<br />2005
<br />0
<br />O
<br />PROJECT TO FULLY REVIEW THESE DOCUMENTS
<br />�/�
<br />BEFORE CONSTRUCTION BEGINS AND ANY AND 0
<br />ALL CORRECTIONS, IF NEEDED, TO BE MADE
<br />COVER SHEET
<br />BEFORE ANY WORK IS DONE.
<br />
|