K gin ring, c. <br />Profession.! Engineers <br />December 14, 2015 <br />Mr. Lyndon T. Pollock, AIA <br />Burt Hill/Pollock Krieg Architects <br />8250 College Parkway, #203 <br />Fort Myers, Florida 33919 <br />RE: Florida Hospital (Zephyrhills) — Revision 3 <br />Dear Lyn: <br />Office: (813) 241-6488 <br />Fax: (813) 241-6498 <br />Please review the revisions to the Electrical drawings for this project with the following changes: <br />ELECTRICAL <br />Drawing E5.0 <br />1. Replace existing undersized Aluminum conductors with 350kcmil THWN copper <br />conductors and 4/0 Cu neutral. <br />2. Change AIC calculations to new copper conductors in existing metal conduit. <br />3. Change to new conductors in service feeder voltage drop caktgatLns <br />If you have any questions, please call. <br />Respectfully, <br />KPI Engineering, Inc. <br />Shawn M. Jeffrey, Sr. — LEED AP <br />Design Group Manager / Partner <br />�4 <br />0193' <br />t �00 STATE OF *I, .4�` <br />IFS'=c4 ORIOP-''�'��N� <br />'ONAL ENG�\ <br />111111� <br />3203 Queen Palm Drive • Tampa, FL 33619 <br />