ELECTRICAL OUTLET BOXES SMALL BE INSTALLED ON ONE <br />SIDE ONLY IN EACH FRAMING SPACE, PROVIDED THE <br />OPENING DOES NOT EXCEED 16 SQ. IN. ALL CLEARANCES <br />BETWEEN THE OUTLET BOXES AND THE GYPSUM BOARD MUST <br />BE COMPLETELY FILLED WITM JOINT COMPOUND OR OTHER <br />APPROVED MATERIAL. <br />4" SQUARE BOX ,_ 31 <br />1 <br />RIGID OR EMT CONDUIT CONNECT <br />GROUNDING LUGS OF RECEPTACLES <br />-is W!M= <br />BACK TO BACK ELECTRICAL <br />OUTLETS DETAIL <br />TYPICAL ROUGH -IN <br />REQUIREMENTS DETAIL <br />METAL STUD <br />^ROVIDE CONDUIT SUPPORTS <br />4 ACCORDANCE WITH NEC. <br />PACING REQUIREMENTS FOR <br />YPE OF RACEWAY REQ'D. <br />YPICAL OUTLET BOX <br />TEEL CITY NO. 1501 <br />SOX SUPPORT <br />I ACCORDANCE WITH <br />3C 4304 OUTLET ON <br />PPOSITE SIDES OF WALLS <br />I THE SAME STUD SPACE <br />UST BE SEPARATED BY <br />MINIMUM OF 24" HORIZ, <br />]DISTANCE <br />NO OUTLETS BACK TO <br />BACK ( OFFSET 12" ) <br />STRUCTURAL UNIT <br />BEAM CLAMP OR HANGER <br />CLAMP AS REQUIRED BY <br />WEIGHT SUPPORTED <br />ALL THREAD — SIZE AS <br />REQUIRED <br />RACEWAY — 1/2" THROUC-A4T 6" <br />CONDUIT HANGER <br />STRUCTURAL UNIT <br />BEAM CLAMP OR MANGER <br />CLAMP AS REQUIRED BY <br />WEIGHT SUPPORTED <br />RACEWAY - I/2" THROUGwT 6" <br />NOTE: <br />TIE WIRE SHALL NOT BE USED AS A COMPONENT <br />OF ANY RACEWAY HANGER SYSTEM. <br />TYPICAL RACEWAY SUPPORT METHODS DETAIL <br />CONDUIT TO OTHER <br />FIXTURES —� <br />LIGHT FIXTURE <br />1/2" d1a FLEXIBLE CONDUIT TO <br />EACH LIGHT ( 6' LONG ) <br />LIGHT FIXTURE —4 11/16" sq. x 1 1/2" DEEP <br />JUNCTION BOX MAX. 4 TAP <br />CONDUIT TO PANEL50ARD OR <br />OTHER FIXTURES <br />RECESSED LIGHT FIXTURE WIRING TAP DETAIL <br />SUPPORT FROM FIXTURE BODY <br />( NOT Y BAR SYSTEM ) TO <br />STRUCTURE, FOUR TIE WIRES <br />PER FIXTURE ( NOT TO EXCEED <br />45° IN OPPOSING DIRECTION <br />'T' BAR SUPPORTED HANGS FIXTURES WITH <br />INDEPENDENTLY OF FOUR TIE WIRES TO <br />FIXTURE ROOF PURLIN <br />RECESSED LAY -IN FIXTURE <br />X T <br />SURFACE MOUNTED FIXTURE <br />ON LAY - IN CEILING <br />HANG FIXTURE W <br />WIRES TO BAR J <br />BOLTS IN CONC. <br />BOX <br />JUNCTION BOX <br />( 2 PER BOX) <br />FOUR TIE <br />T OR EYE <br />DOR ABOVE <br />NOTE: <br />12 GA. WIRE TIES <br />JUNCTION BOX SUPPORTS TIED <br />UNISTRUT FRAMING t ANCHORED <br />INDEPENDENTYL TO CEILING " T " <br />BARS <br />ELECTRICAL CONSTRUCTION NOTES <br />1 ALL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC. ) LATEST ADDITION, <br />AND APPLICABLE STATE AND LOCAL ORDINANCES, EACH PIECE OF ELECTRICAL EQUIPMENT INSTALLED <br />SHALL BEAR A U.L. LABEL. ALL WORK SHALL BE PERFORMED IN COMPLIANCE WITH THE OCCUPATIONAL <br />SAFETY AND HEALTH ACT ( OSHA ) LATEST EDITION. <br />2 THE ELECTRICAL CONTRACTOR SHALL ARRANGE AND PAY FOR ALL PERMITS, FEES, INSPECTIONS, ETC., <br />AND CARRY ALL INSURANCE AS REQUIRED BY LAW PRIOR TO STARTING CONSTRUCTION. <br />3 THE ELECTRICAL CONTRACTOR SMALL PROVIDE ALL NECESSARY LABOR, MATERIALS, TRANSPORTATION, <br />RIGGING, TOOLS, STORAGE, ETC., FOR ALL WORK INDICATED AND REQUIRED FOR A COMPLETE INSTALLATION. <br />4 THE ELECTRICAL WORK SHALL INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING. WORKMANSHIP <br />SMALL BE OF THE HIGHEST QUALITY AS ESTABLISHED BY TRADE STANDARDS. <br />5 ELECTRICAL CONTRACTOR SMALL KEEP A MASTER SET OF PLANS THAT ARE TO BE MARKED UP <br />TO REFLECT "AS BUILT" CONDITIONS ON A DAILY BASIS. THESE "AS BUILT" MARK UPS MAY BE REVIEWED <br />BY THE ARCHITECT, ENGINEER OR OWNER'S REPRESENTATIVE, AT THEIR REQUEST WITHOUT PRIOR NOTIFICATION, <br />THESE "AS BUILT" MARK UPS WILL BE REVIEWED BY THE ENGINEER AND TURNED OVER TO THE OWNER AT <br />THE CONCLUSION OF THE PROJECT, <br />6 THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COMMUNICATION WITH THE LOCAL BUILDING <br />DEPARTMENT AND INSPECTION PERSONNEL TO REVIEW CONTRACT DOCUMENTS PRIOR TO INSTALLATION. <br />1 THE OWNER WILL NOT BE HELD LIABLE FOR FIELD CHANGES THAT ARISE FROM CONTRACTOR ERROR OR <br />OMISSIONS OF MATERIALS OR WORKMANSHIP IN WORK PERFORMANCE. <br />8 THE ELECTRICAL CONTRACTOR SMALL MAKE ALL NECESSARY ARRANGEMENTS WITH THE LOCAL POWER <br />COMPANY FOR SERVICES AND SMALL BE RESPONSIBLE FOR VERIFICATION OF ALL UTILITIES AND THE <br />PLACEMENT LOCATIONS OF THE ELECTRICAL SERVICE AND EQUIPMENT. THE ELECTRICAL CONTRACTOR <br />SMALL PAY AL NECESSAY CHARGES TO THE POWER COMPANY PRIOR TO CONSTRUCTION. <br />9 AL ELECTRICAL EQUIPMENT, MATERIAL, AND WORKMANSHIP SHALL BE GUARANTEED FOR A PERIOD OF <br />ONE ( 1 ) YEAR FROM DATE OF ACCEPTANCE. <br />10 IN GENERAL, PLANS AND DIAGRAMS ARE SCHEMATIC ONLY, AND SHOULD NOT BE SCALED. COORDINATE <br />ALL ELECTRICAL WORK WITH OTHER TRADES, ( PLUMBING , HVAC, ETC. ) SO AS NOT TO CONFLICT IN <br />LOCATION OF PERFORMANCE OF OTHER SYSTEMS. <br />11 NECESSARY, OBVIOUSLY REQUIRED ELECTRICAL ITEMS THAT ARE NOT SHOWN ON THE DRAWINGS, DOES NOT <br />RELIEVE THE CONTRACTOR OF HIS RESPONSIBILITY TO INSTALL A COMPLETE AND SAFE ELECTRICAL SYSTEM <br />12 THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH OTHER TRADES SO THAT INTERFERENCES BETWEEN <br />CONDUITS, RACEWAYS, DUCTS, PIPING: AND STRUCTURAL MEMBERS WILL BE AVOIDED. <br />13 THE ELECTRICAL CONTRACTOR SHALL FURNISH, INSTALL AND CONNECT ALL WIRINGS IN ACCORDANCE WITH <br />THE WIRING DIAGRAMS FOR POWER AND CONTROL OF ALL AIR CONDITIONINGS, HEATING AND VENTILATING <br />EQUIPMENT AS PROVIDED BY THE HVAC CONTRACTOR. <br />14 WIRE AND CABLE SHALL BE 600 VOLT MINIMUM AWG 012. ALL WIRING SHALL BE TYPE TW, THW OR THHN AS <br />NECESSARY TO MEET ALL APPLICABLE CODES. <br />15 AL WIRE AND CABLE SHALL BE IN CONDUIT, MINIMUM SIZE 1/2" WITH LARGER SIZES AS INDICATED OR <br />REQUIRED BY NEC. ALL SERVICE AND PANELBOARD FEEDER CONDUITS, CONDUITS IN OR BELOW FLOOR, <br />IN DAMP AND WET LOCATIONS, IN CONCRETE AND LARGER THAN TWO INCHES SHALL BE RIGID <br />GALVENIZED STEEL. <br />AL CONDUCTORS, UNLESS OTHERWISE NOTED, SMALL BE COPPER RUN IN APPROVED METAL RACEWAY. <br />METAL RACEWAY PENETRATING FLOORS AND FIRE RATED PARTITIONS SHALL BE SEALED AIR TIGHT WITH <br />MATERIAL RATED EQUAL TO THE PENETRATED MATERIAL, <br />FURNISH AND INSTALL ALL BRANCH CIRCUITS. CIRCUITS SMALL BE •12 WIRE IN 1/2" CONDUIT UNLESS <br />OTHERWISE NOTED, THESE ARE MINIMUM WIRE AND CONDUIT SIZES, ALL WIRE SHALL BE COPPER, NO <br />ALUMINUM CONDUCTORS WILL BE PERMITTED. <br />16 ALL NEW RACEWAYS/CONDUITS SHALL BE METALLIC MINIMUM SIZE 1/2", SUPPORTED AT INTERVALS NOT TO <br />EXCEED EIGHT l 8 ) FEET: ALL FITTINGS SHALL BE COMPRESSION TYPE, NO SETSCREW TYPE FITTINGS WILL <br />BE PERMITTED, <br />11 IN NO CASE MAY EMT OR FLEXIBLE CONDUIT BE RUN FROM FIXTURE TO FIXTURE WITHOUT THE USE OF OUTLET <br />BOXES. <br />IS FLEXIBLE CONDUIT CAN ONLY BE USED FOR SHORT ( MAXIMUM SIX FEET ) FINAL CONNECTIONS TO INTERIOR <br />LIGHTING FIXTURES AND EQUIPMENT. <br />19 THE ELECTRICAL CONTRACTOR SHALL FOLLOW THE SAME COLOR CODE IDENTIFICATION FOR EACH PHASE <br />THROUGHOUT THE SYSTEM FROM SERVICE SWITCH OR TRANSFORMER THROUGH ALL BRANCH CIRCUITS, <br />20 AL SLAB OR ROOF PENETRATIONS SHALL BE WITH APPROVED FIRE RATED AND SMOKE BARRIER FITTINGS. <br />PROVIDE ACCESSORIES ( PITCH POCKET, CONCRETE, ETC. ) AS REQUIRED. <br />21 ALL CONDUITS SHALL BE RUN CONCEALED WHERE POSSIBLE. EXPOSED CONDUITS SHALL BE RUN PARALLEL <br />AND /OR PERPENDICULAR TO BUILDING CONSTRUCTION. <br />22 CONDUIT MAY NOT BE RUN IN DUCTWORK. <br />23 THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTAL A 3/4" EMPTY CONDUIT FROM EACH TELEPHONE <br />OUTLET TO THE OWNER'S TELEPHONE BOARD, WITH PULL WIRE. PROVIDE ALL REQUIRED CONDUIT FROM <br />OWNER'S TELEPHONE BOARD TO BUILDINGS TELEPHONE ROOM, PROVIDE PULL BOXES AND PULL WIRE AS <br />REQUIRED, VERIFY EXACT LOCATIONS OF EXISTING TELEPHONE SERVICE AND CONDUITS. COORDINATE ALL <br />WORK WITH OTHERS TRADES AND TELEPHONE COMPANY. <br />24 THE ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTAL ALL CONDUIT, BOXES, FITTINGS, PULL WIRE, ETC. <br />REQUIRED FOR AL MISCELLANEOUS SYSTEMS PER OWNER'S REQUIREMENTS. COORDINATE EXACT LOCATIONS <br />AND REQUIREMENTS WITM OWNER. <br />25 ALL COMMUNICATION AND CONTROL WIRING SHALL BE IN CONDUIT, <br />26 FURNISH AND INSTALL PANEL BOARDS OF AMPACITIES SHOWN ON PLANS. PANELS SHALL BE CIRCUIT BREAKER <br />TYPE, WITM MAIN LUGS AND BRANCH CIRCUIT BREAKERS AS SCHEDULED. AL ELECTRICAL PANELS AND <br />EQUIPMENT SHALL BE U,L. LISTED AND APPROVED FOR SUCH USE, PANELS SHALL BE BOLT —ON TYPE AS <br />MANUFACTURED BY SQUARE 'D' OR APPROVED EQUAL. <br />21 ALL EQUIPMENT SMALL BE PROPERLY GROUNDED IN ALL RACEWAYS, BRANCH CIRCUITS t FEEDERS, <br />PER LOCAL ELECTRICAL CODES AND THE NEC. <br />28 THE ELECTRCIAL CONTRACTOR SHALL COORDINATE ALL RECEPTACLE AND OUTLET LOCATIONS WITH <br />ARCHITECTURAL DRAWINGS AND GENERAL CONTRACTOR BEFORE ROUGH IN. <br />29 ALL LIGHTING FIXTURES SHALL BE SELECTED BY THE OWNER AND INSTALLED BY THE ELECTRICAL <br />CONTRACTOR. ( LIGHTING FIXTURES INDICATED ON DRAWINGS AND SCHEDULES ARE FOR REFERENCE <br />ONLY. FIXTURES OF EQUAL QUALITY MAY BE USED AS DIRECTED. <br />30 ALL TEMPORARY ELECTRICAL SERVICE REQUIRED FOR CONSTRUCTION SHALL BE FURNISHED BY THE <br />ELECTRICAL CONTRACTOR. FOLLOWING CONSTRUCTION AL TEMPORARY WIRINGS AND EQUIPMENT SHALL <br />BE REMOVED WHEN DIRECTED BY THE GENERAL CONTRACTOR. ELECTRIC OUTLETS, CORDS, LIGHTS, <br />LIGHTING LEVELS, ETC., SMALL CONFORM TO O.S.H.A. AND LOCAL ORDINANCES. <br />31 ALL ELECTRICAL EQUIPMENT EXPOSED TO WEATHER SMALL BE WEATHERPROOF AND ALL CONDUIT <br />EXPOSED TO WEATHER SMALL BE HEAVY WALL GALVANIZED STEEL. <br />32 SUBMIT SIX COMPLETE COPIES OF SHOP DRAWINGS AND PRODUCT DATA FOR LIGHTING FIXTURES, <br />ELECTRICAL PANELS, SERVICE EQUIPMENT, WIRING DEVICES AND DISCONNECT SWITCHES, <br />U <br />Z <br />Lu <br />N <br />0- <br />Lu <br />— O <br />cri <br />� o <br />U <br />U d� <br />N cq <br />LLkw�) <br />(p .4 <br />0� <br />Q <br />l--1 <br />ENGINEERING <br />Lu <br />O <br />Lu <br />� cr ,i 0 <br />Z:3 <br />0 <br />Lu <br />�Jr <br />L <br />f LL � N <br />ENGINEERS SEAL <br />101 <br />SHEET <br />ROOM ADDITION <br />DRAWING SETS <br />SHEET NUMBER <br />r= 2 <br />Da.iger: <br />CRC <br />Prom Hy: <br />