2.5.2 Contactors shall be designed to carry the full rated current on a continuous
<br />basis.
<br />2.5.3 Contactors shall be electrically operated, mechanically held, and suitable for
<br />remote operation. The mechanically held contactors shall be supplied with coil
<br />clearing contacts which disconnect the magnet coil when operated to eliminate
<br />any AC magnetic hum.
<br />2.5.4 Contactors shall be as sized as shown on the Drawings and be installed in a
<br />NEMA I enclosure.
<br />2.6. Wire and Cable
<br />2.6.1 All wires shall be THHN copper unless otherwise noted. No wire shall be
<br />smaller than #12 AWG. except control wire. No aluminum wire will be
<br />permitted.
<br />2.6.2 Except as noted, no conductors smaller than #12 AWG shall be used. #10
<br />AWG shall be used on runs of over 100 ft.
<br />2.6.3 In no case shall the number of conductors installed in conduits exceed the
<br />maximum fill allowed by the NEC. Should this occur on the Drawings, the
<br />Electrical Contractor shall inform the Engineer before installation. Conductors
<br />shall not be installed beneath the heating equipment foundations.
<br />2.6.4 Control wire for the air conditioning and refrigeration equipment shall be type
<br />THHN stranded and no smaller than # 14 or where indicated on Drawings.
<br />2.6.5 Pull boxes are allowed only when required by code. Wire must be in one
<br />unspliced run to all secondary panel feeders, and in one unspliced run to all air
<br />conditioning and refrigeration units.
<br />2.6.6 Install all phase conductors, neutral conductor, and ground conductor from
<br />panel board to the equipment connection junction box. If the neutral conductor
<br />is not needed it shall be taped and identified in the J.B. for future use.
<br />2.7. Conduits and Raceways
<br />2.7.1 PVC: Schedule 40 conduit may be used under floor slab. Riser shall be heavy
<br />wall hot dipped galvanized steel.
<br />2.7.2 No PVC shall be installed above floor slab.
<br />2.7.3 GRC 90's shall be used on all runs over 50'.
<br />2.7.4 Underfloor Duct:
<br />2.7.4.1 Shall be "Waikerduet" (no substitutes) as manufactured by Walker/
<br />Textron Company, Parkersburg, West Virginia. Install complete
<br />service fittings, blanking plates, junction boxes, covers, etc., with
<br />threaded fittings. Use standard No. 2 and No. 4 duct with #2-24 x 2 x
<br />2 or 92-12 x 2 x 2 inserts as shown on Drawings; adaptors #1126a-3/
<br />4", for cable. Install Walker Duct junction boxes with brass tops
<br />recessed to receive terrazzo/methyl methacrylate. Verify locations of
<br />duct with Drawings.
<br />2.7.4.2 Top of cut insert shall be 3/4" below finish floor line.
<br />2.7.5 Raceways concealed in wall or ceiling spaces shall be standard weight hot
<br />dipped galvanized EMT with compression couplings or as specified below.
<br />2.7.6 All "L'S" used to turn up through concrete slabs shall be thick wall galvanized
<br />conduit & couplings.
<br />2.8. Time Switches
<br />2.8.1 Provide time switches as manufactured by Intermatic (no substitutes)
<br />2.8.2 Time switches shall be DPST, 40 amperes, 120 volt, AC motor and astronomic
<br />dial, spring -wound carry-over.
<br />2.8.3 Time clocks shall be labeled.
<br />2.9. Outlet Boxes, Fittings, and Connectors
<br />2.9.1 Unless hereinafter specifically noted or shown on the Drawings, the minimum
<br />size of branch circuit outlet boxes for concealed work shall be 4"x4"xl 1/2" for
<br />square boxes and 4"xl 1/2" for octagon boxes.
<br />2.9.2 Boxes shall be provided with plaster covers of sufficient depth to bring the face
<br />of the outlet substantially flush with the finished wall or ceiling. The box shall
<br />not project beyond the finished wall or ceiling line.
<br />2.9.3 Outlets in concrete block, or other hollow masonry walls:
<br />2.9.3.1 Openings in concrete block walls for outlets shall be cut to exact size
<br />with a masonry saw.
<br />2.9.3.2 Switch and receptacle mounting heights, as specified or noted may be
<br />adjusted so that the bottom of the outlet box may rest on the top of the
<br />wall block at the nearest mortar joint
<br />2.9.3.3 All unused outlets shall be provided with blank covers.
<br />2.9.4 Where conduits 1" or larger enter outlet boxes, the boxes shall be 4 11/16"x4 -
<br />11/16"x2 1/4" minimum. Boxes shall be of ample size to provide conductor
<br />spaces as required by the National Electric Code.
<br />2.9.5 "Handy", utility or sectional boxes will not be permitted in masonry v-
<br />2.9.6 When more than one switch or device is shown ganged at any location a one-
<br />piece box of suitable size shall be installed.
<br />2.9.7 Outlet boxes intended for the installation of lighting fixtures shall be equipped
<br />with 3/8" "No -Bolt" or equal fixture studs.
<br />2.9.8 Unless otherwise noted, all switches, receptacles and devices shown on the
<br />exterior of building walls shall be installed in flush mounted boxes provided
<br />with weatherproof gaskets.
<br />2.9.9 All conduit fittings (condulets) shall be of the cast metal threaded hub type,
<br />Crouse -Hinds, or Appleton.
<br />2.9.10 All rigid conduits entering panels, cabinets, outlet boxes, etc., shall be provided
<br />with loeknuts on both sides of such devices driven tight so as to maintain
<br />positive electrical and mechanical continuity throughout the conduit system.
<br />Insulated bushings shall be installed on the inside of the termination
<br />2.9.11 Threadless couplings shall not be used for rigid conduit.
<br />2.9.12 All EMT couplings and box connectors shall be of the set screw or
<br />compression type. Compression type shall be used in all coolers/freezers, or in
<br />outdoor applications. Cast connectors or couplings will be allowed.
<br />2.9.13 All flex conduit shall be steel w/steel fittings, and shall extend a maximum of
<br />10 ft. unless approved by Publix.
<br />2.9.14 All receptacles labeled GFI on drawings to be supplied as GFI receptacles.
<br />GFI circuit breaker or feed through series GFI circuit is unacceptable.
<br />2.9.15 All receptacles labeled IG (isolated ground) shell be IG listedand shall get a
<br />separate (from other equipmmnt ground) green with yellow stripe isolated
<br />ground conductor. All isolated ground circuits to include equipment ground
<br />conductor.
<br />2.9.16 All conduits to have an equipment ground conductor in addition to conductors
<br />shown on drawings.
<br />2.10. Junction Boxes: Wiring shall be neatly arranged, bundled and laced in proper groups.
<br />2.11. Pull Boxes
<br />2.11.1 Pull boxes shall be installed in conduit system where needed whether or not
<br />they are shown on the Drawings.
<br />2.11.2 Boxes shall be constructed of code gauge galvanized steel with screw covers.
<br />2.12. Safety Switches
<br />2.12.1 The basis of design and quality standards is Square - D.
<br />2.12.2 All units shall be of the same manufacturer.
<br />2.12.3 Safety switches shall be fusible, solid neutral, 277 volt, quick -make and quick -
<br />break with visible blades, single throw, general duty, of size and fusing as
<br />shown on the Drawings, or required for application. switches mounted out of
<br />doors shall be weatherproof heavy duty type with protective barrier over hot
<br />lugs.
<br />2,12.4 Exterior units shall be in rain tight enclosure. (NEMA 3R)
<br />2.13. Wall Switches
<br />2.13.1 Switches shall be flush mounted, quiet tumbler type, 250 volts, 20 amp. rated
<br />2.13.2 Wall plates shall be smooth, 302 stainless steel, one piece as indicated on the
<br />Drawings.
<br />2.13.3 Switches shall be installed on the "strike" side of the door swing.
<br />2.13.4 Switches shown near doors shall be not less than two inches and not more than
<br />twelve (12) inches from the trim.
<br />2.14. Receptacles
<br />2.14.1 All units shall be totally enclosed composition with side and rear connections.
<br />All units shall be equipped with ears and have a rating as listed below. All
<br />devices shall be Hubbel or Leviton. See symbol schedule on DWGS.
<br />2.14.2 Duplex convenience outlets with ground shall be 20 amp, 125 volt parallel slot,
<br />"U"-shaped ground, heavy duty 'IT" rated.
<br />2.14.3 120/208 volt, 3 wire receptacles with ground shall be single 3 wire polarized
<br />receptacles with grounding terminal.
<br />2.14A Weatherproof receptacles shall be duplex, 20 amp, 125 volt parallel slot
<br />receptacle with "U" shaped grounding slot in flush, weatherproof box with
<br />gasketed cover and self closing, spring door.
<br />2.14.5 Floor outlets shall be 20 amp, 125 volts single or duplex parallel slot
<br />receptacles with "U" shaped grounding slot as called for, located as shown on
<br />the Drawings. Provide slotted brass flush cap for sealing when not in use.
<br />2.14.6 All device cover plates shall be smooth 302 stainless steel, one piece.
<br />2.15. Lighting Fixtures
<br />2.15.1 All lighting fixtures shall be finished by Publix and installed by appropriate
<br />trade. In -line fuses are included with all fluorescent and metal halide fixtures.
<br />2.15.2 In areas of suspended ceilings two safety wires per fixture will be supplied and
<br />hung by the suspended ceiling Subcontractor; the Electrical Subcontractor shall
<br />tie fixtures in areas of suspended ceilings with two (2) #10 wire up to the roof
<br />joists per fixture.
<br />2.16. Electric Door Openers: Electric door openers shall be furnished and installed by
<br />others but wired with two (2) 115 volt, 20 amp, 3 wire circuits to control box at the
<br />top of the door.
<br />2.17. Intercom/Music/Paging System
<br />2.17.1 The Contractor shall supply and install sound outlets, conduit and junction
<br />boxes with equipment as shown on the Drawings (including architectural
<br />ceiling grid plan).
<br />2.17.2 The outlet boxes shall be standard boxes provided with blank covers.
<br />2.17.3 The conduit shall be not less than 1/2".
<br />2.18. Telephone Outlets:
<br />2.18.1 Provide outlets as located on Drawings,
<br />2.18.2 See Drawings for location and size of conduit runs,
<br />2.18.3 Provide stainless steel. outlet boxes and cover plates.
<br />2.19.4 Locate telephone control box inside telephone equipment room.
<br />2.18.5 Provide outlets for wall phones at indicated locations.
<br />2.19. Standby Electric -Emergency Generator and Transfer Switch
<br />2.19.1 Emergency generator and automatic load transfer switch will be furnished by
<br />Publix and shall be set in place and connected by the contractor.
<br />2.20. Grounding
<br />2.20.1 All wiring system shall be grounded in accordance with article 250 of the NEC.
<br />All items of electrical equipment not connected directly and mechanically to
<br />the conduit system shall be connected thereto with a jumper of suitable size.
<br />All breaks in the continuity of the conduit system shall be bridged with a
<br />jumper of the proper size between the next adjacent outlet or junction boxes
<br />regardless of the information on the drawings.
<br />2.20.2 All conduit runs shall include an equipment ground cnductor appropriately
<br />sized for the associated circuits.
<br />2.20.3 Due care must be taken as not to interchange circuit neutrals, as over heating of
<br />the panel board may occur.
<br />2.20.4 A green THHN insulated stranded 12 AWG conductor shall run unbroken from
<br />the system ground through the conduit system to the ground connections at all
<br />receptacles, switches and lights. Appliance outlets shall be in accordance with
<br />NEC. Table 250-95.
<br />2.20.5 Isolated ground, as required in the drawings, shall be a green THHN insulated
<br />stranded 12 AWG (min.) with yellow tracer line along the entier length.
<br />2.21. Tests
<br />2.21.1 The Electrical Contractor shall test all wiring and equipment for grounds,
<br />continuity and proper operation.
<br />2.21.2 When directed he shall demonstrate by use of a 500 volt megger, the insulation
<br />resistance of any circuit or group of circuits.
<br />2.21.3 Where such tests indicate the possibility of faulty insulation, the Electrical
<br />Contractor shall locate the point or points of such faulty insulation and shall
<br />pull out the faulty conductor or conductors, replace same with new and
<br />demonstrate the elimination of faults.
<br />3. Execution
<br />3.1. General:
<br />3.1.1 Temporary Electric Service: Install and maintain 120/240 volt, I phase, 3 wire,
<br />200 amp temporary service. power Consumption cost only paid by Contractor.
<br />Installation shall comply with OSHA; NEC; and all local requirements.
<br />3.1.2 The locations of the outlets, switches and convenience outlets shall be
<br />approximately as shown on the drawings and as specified, but exact locations
<br />shall be as directed by Publix Field Representative. The running of all circuits,
<br />switch legs and conduits is purely diagrammatic. Do not scale from Drawings.
<br />3.1.3 Rigging and hoisting that is incidental to the electrical portion of the Work
<br />shall be performed by the Electrical Contractor. This shall include the hoisting
<br />of equipment supplied by both the Electrical Contractor and Pubhx that are
<br />installed by the Electrical Contractor.
<br />3.1.4 Coordinate this work with other trades so that interference between the trades
<br />can be avoided.
<br />3.1.5 All channels, angles and other members for the installation and support of the
<br />electrical equipment shall be furnished and installed by the Electrical
<br />Contractor.
<br />3.1.6 The attachment of boxes, conduit, hangers, etc. shall be by machine screws or
<br />through bolts on steel, expansion bolts in concrete and masonry, and wood
<br />screws in wood. Wood composition plugs shall not be used.
<br />3.2. Excavation and Backfilling:
<br />3.2.1 Do all excavating required to install any underground conduit and after the
<br />same are in place and tested and approved, Thoroughly tamp earth around
<br />conduits and remove earth from premises as directed.
<br />3.2.2 Underground conduit must be covered by a minimum of three (3) inches of
<br />underslab fill.
<br />3.3. Conduit, Raceways, Etc.
<br />3.3.1 All metallic non -current carrying components and enclosures of the electrical
<br />wiring system are to be bonded and grounded.
<br />3.3.2 Furnish all necessary fittings and supports to make the raceways or busways fit
<br />the building structure and equipment. Raceway size shown or called for are
<br />minimum. The Electrical Contractor shall verify all raceway sizes with the
<br />dimensions of the particular cable to be installed
<br />3.3.3 All exposed raceways and conduit shall be neatly installed perpendicular or
<br />parallel to walls and floors. No exposed conduit is allowed in sales area or
<br />work rooms (except where required in exposed structure areas of stores without
<br />ceilings.)
<br />3.3.4 All raceways shall be supported by approved types of galvanized wall brackets,
<br />ceiling trapeze hangers, pipe hangers or pipe straps. Perforated metal strap or
<br />tie wire shall not be used for any conduit or raceway.
<br />3.3.5 All conduit located above ceilings shall be EMT or ERC, and must be installed
<br />within the area provided for on Drawings.
<br />3.3.6 Areas for work of various trades: Conform to locations as defined in Section 01
<br />1100 Summary of Work.
<br />3.3.7 All conduit located underground may be PVC Schedule 40, except service
<br />entrance which may be concrete encased PVC schedule 40 or heavy wall rigid
<br />conduit, or weather proof buss duct as shown. Underground conduit lengths
<br />greater than 50' shall include GRC 90.
<br />3.3.8 All job cut threads shall be given a coat of rust -inhibitive paint.
<br />3.3.9 Caulk where conduit passes through walls, providing approved fire -stopping
<br />system where required. Caulk where conduit passes through walk-in freezers
<br />and coolers. All cutting in block work must be done with carborundum saw; no
<br />chisel or hammer work will be accepted.
<br />3 A Circuit Identification: Label all panels by approved means to identify circuits. Install
<br />equipment in cans, as per Drawings. Mark all panels, time clocks, starters, contactors,
<br />disconnect devices and main panels on the outside with riveted or approved attached
<br />plastic laminated labels 1" minimum high w/ 3/4" minimum letters of contrasting
<br />colors. All circuits shall be identified by typed lettering of contrasting color to tags &
<br />covered w/approved plastic cover.
<br />3.5. All panelboards shall include a typed directory of all associated loads. Refrigeration
<br />circuits shall be albeled with associated rfrigeration system number.
<br />3.6. Installation of Items Supplied by Others:
<br />3.6.1 All store fixtures and equipment, including shelf gondolas and check out
<br />stands, will be furnished and set in place by Publix, or others, and this
<br />Contractor shall make all required electrical connections. Verify items and
<br />their locations with Publix's Representative.
<br />3.6.2 Meat and Deli Department equipment will all be with plug-in connectors. Do
<br />not wire direct. (unless directed by Publix's Representative).
<br />3.6.3 All wiring and mounting shall be in cooperation with and under the direction of
<br />the Publix's Representative.
<br />3.6.4 Make connection to electric water heaters as furnished by Publix.
<br />3.7. Control of Outlets:
<br />3.7.1 Branch lighting circuits controlled at panels by a switch shall be located at the
<br />Manager's Office, unless indicated otherwise.
<br />3.7.2 Convenience outlets shall have no intermediate control between panels and
<br />outlets unless noted on the drawings.
<br />3.8. Connection of Conductors: All joints between conductors shall be connected with
<br />approved pressure type, connectors and insulated with scotch 33 tape and friction
<br />tape, if insulation is not provided in pressure type connector used.
<br />3.9. Sleeves at Fire Retardant Lumber: If fire treated lumber is required by local codes and
<br />ordinances, the Electrical Contractor shall provide PVC fitting boxes and piping that
<br />penetrate the fire resistant lumber. If the PVC components are not approved by local
<br />code, other approved methods must be used to protect against the salt in the fire
<br />resistant lumber.
<br />3.10. Final Inspection: All of the following items must be completed prior to final
<br />inspection. No exceptions will be made and no final payment will be made until all
<br />items are completed.
<br />3.10.1 Thoroughly clean all parts of the apparatus and equipment. Exposed parts
<br />which are to be painted shall be thoroughly cleaned of cement, plaster, and
<br />other material and all oil and grease spots shall be removed repaint or touch up
<br />as required to make look like new. Such surfaces shall be carefully wiped and
<br />all cracks and corners scraped out.
<br />3.10.2 Exposed metal work shall be carefully brushed down with steel brushes to
<br />remove rust and other spots and touched up with primer.
<br />End of Section 26 00 00
<br />Section 3120 00
<br />Earth Moving
<br />1. General
<br />1.1. Prepared Pad (Not In Contract)
<br />1.1.1 Pad preparation and Field Density Testing of the Pad are not part of the Work
<br />of this Contract.
<br />1.1.2 On projects for which Publix Super Markets, Inc. is the sole Owner, part or all
<br />of the Site Work may be part of this Contract; see Bid Forms and Contract for
<br />definitive list.
<br />1.1.3 Where use of sub -grade fill or on -site material for under -slab porous fill is not
<br />approved by Publix (see below) the pad will have been brought to an elevation
<br />of eight (8) inches below Finished Floor by the work of another contract.
<br />1.1.4 Where use of sub -grade fill or on -site material for under -slab porous fill is
<br />approved by Publix (as evidenced by acceptance of Deductive Altemate-see
<br />Article 3.2 below) the pad will have been brought to an elevation of four (4)
<br />inches below Finished Floor by the work of another contract.
<br />1.2. Field Density Tests and Samples
<br />1.2.1 The Contractor shall employ a testing laboratory acceptable to the Owner for
<br />testing of footing and foundation excavations, for testing of other areas where
<br />the prepared pad is disturbed by the Work of this Contract, and for testing of
<br />the underslab porous fill where said porous fill is part of the Work of this
<br />Contract.
<br />1.2.2 Sample specimens shall be recovered by the "Shelby Tube" or the "Sand
<br />Cone" method, or as otherwise directed by Engineer.
<br />1.2.3 Density Tests shall be secured at 50 ft. intervals in linear footing excavations,
<br />and at every spread footing.
<br />1.2.4 Density Tests shall be secured in areas of backfill and recompaction at vertical
<br />intervals not exceeding 12 in. and at a horizontal frequency of one per 4000 sq.
<br />ft. Areas requiring compacted fill that support small independent slabs shall
<br />have density tests at vertical intervals of 18" in the event this is a separate
<br />compaction procedure.
<br />1.2.5 Density Tests shall be secured in underslab porous fill (where such fill is part
<br />ofthe Work of this Contract) at a horizontal frequency of one per 4000 sq. ft.
<br />1.2.6 Densities shall conform to those specified in the Pad Preparation Contract,
<br />based on a Geotechnical Report and Publix' design criteria of 2000 psf
<br />minimum soil bearing capacity,
<br />1.3. Testing and Remediation:
<br />1.3.1 Any test result which does not conform to the requirements of the Contract
<br />shall be furnished verbally to both Engineer and Contractor within 24 hours
<br />after sampling. Written test results shall be distributed as specified in Section
<br />01340 - Submittals, and shall include horizontal and vertical location, test
<br />number, dry density, moisture content, percent compaction and Proctor
<br />Compaction Curve to which each test is referenced The Testing Laboratory
<br />shall also call attention, by a separate symbol, to those tests which do not
<br />conform with these Specifications.
<br />1.3.2 Field Density Tests and Samples: In the event of Test Results not in
<br />conformance with the Contract Requirements, Publix will obtain a Soils
<br />Engineer's recommendation for remedial measures. Remedial measures will be
<br />part of the Work of this Contract if they are required by activities of the
<br />Contractor after his receipt of a properly prepared pad. Remedial measures
<br />required by pre-existing conditions will be part of the Work of this Contract
<br />only by Change Order.
<br />1.4. Termite Treatment
<br />1.4.1 This Section contains information normally found in Section 3131 16 Termite
<br />Control.
<br />1.4.2 Submit LOI in accordance with Section 01 33 00 Submittal Procedures.
<br />1.4.3 Guarantee of Treatment: Upon completion of the Soil Treatment and as a
<br />condition for its Final Acceptance, the Contractor shall furnish to the Owner a
<br />written Guarantee stating that the Applicator guarantees the effectiveness of the
<br />soil treatment against termite infestation for a period of not less than five years
<br />from date of treatment. Any evidence of re -infestation within the Guarantee
<br />Period will require treatment without cost to the Owner.
<br />2. Products
<br />2.1. Termite Treatment: Provide pesticides approved for use by Federal and local
<br />authorities:
<br />ProBuild TC
<br />Premise
<br />Dragnet.
<br />Dursban TIC
<br />3. Execution
<br />3.1. Excavation
<br />3.1.1 Perform all excavation and cutting necessary to accommodate the work shown
<br />on the plan. Forms may be omitted if soil is suitable to provide accurate and
<br />stable trenches for concrete pours.
<br />3.1.2 Bottom of excavations shall be true and level to provide level bearing.
<br />3.1.3 Notify Publix' Representative should debris or deleterious materials be
<br />encountered during excavations. Publix will obtain a Soils Engineer's
<br />recommendation for remedial measures which will be part of the work of this
<br />Contract by appropriate Change Order if desired by Publix.
<br />3.1.4 Backfill under concrete floor slabs, walks, ramps, etc., where required by
<br />disturbance of the prepared pad shall be deposited in lifts not exceeding twelve
<br />(12) inches with each layer thoroughly compacted. Tamping and puddling shall
<br />be done at least 24 hours before concrete is laid Recompaction shall reach the
<br />compaction specified in the separate Contract which covers Pad Preparation, or
<br />the compaction actually achieved for the prepared pad, whichever is greater.
<br />3.1.5 Additional requirements for excavation and backfilling for underground
<br />utilities may be found in other sections.
<br />3.2. Underslab Porous Fill
<br />3.2.1 Provide 4 in. of porous fill unless Publix has determined that subgrade fill or
<br />on -site material meet the requirements for underslab porous fill, and has
<br />accepted a deductive alternate to delete porous fill from this Contract.
<br />3.2.2 Porous fill shall be clean sand, gravel, or crushed rock. Porous fill under
<br />interior slabs shall be graded between 1 1/2 in. and no. 4 sieve. Porous fill
<br />under exterior slabs, ramps, walks, pads, etc. shall be graded between 1 1/2 in.
<br />and no. 200 sieve.
<br />3.3. Termite Treatment:
<br />3.3.1 Mixing and application: Adhere strictly to manufacturer's written instructions
<br />for concentrations and application rates, and for methods of application.
<br />3.3.2 Treat on top of pad under the slabs over the entire area of Publix store
<br />including loading docks, and along both sides of foundation walls, along
<br />interior foundations, and around plumbing and electrical penetrations, and
<br />under sidewalks and all other paved areas within five feet of the building.
<br />End of Section 3120 00
<br />End of Project Manual
<br />Reflecting Changes Through
<br />27 March 2007
<br />Pubi I I X9
<br />S U PE R MARKETS
<br />CORPORATE OFFICES
<br />FACILITIES DESIGN
<br />BOX 407, LAKELAND, FL 33802
<br />(863)680-5295
<br />PHYSICAL ADDRESS:
<br />3300 AIRPORT RD., LAKELAND, FL 33811
<br />PUBLIX FACILITIES
<br />DESIGN DEPARTMENT
<br />DAVID TAULBEE, AIA
<br />ARCHITECT - FL. REG, 91318
<br />DAVID RUBIN, AIA
<br />ARCHITECT - FL. REG.92557
<br />GA, REG.1 1881
<br />SC. REG.7477
<br />AL. REG.623A
<br />JOHN W. KITCHENS, PE
<br />CIVIL/STRUCTURAL-FL REG. A5277
<br />GA. REG. 020251
<br />SC. REG.16340
<br />AL. REG.20382
<br />TN. REG. 101507
<br />PAUL C. HARMAN, PE
<br />STRUCTURAL- FL. REG. 51959
<br />GA. REG. 27740
<br />SC. REG.2175A
<br />AL. REG.24905
<br />TN. REG.107882
<br />JOHN J. CARAMALIS, PE
<br />MECHANICAL- FL. REG. 43889
<br />GA. REG. 021246
<br />SC.REG.16521
<br />AL.REG.20581
<br />TN.REG.108507
<br />ANTHONY CLEMENTI, PE
<br />MECHANICAL- FL. REG- 54781
<br />GA. REG.31882
<br />SC.REG.25591
<br />AL. REG.2BA69
<br />TN- REG- 111382
<br />RAYMOND J. SIRIANNI, PE
<br />ELECTRICAL- FL. REG. 54085
<br />GA. REG. 025636
<br />SC. REG. 19743
<br />AL. REG.23065
<br />TN.REG.108038
<br />NORMAN METER, PE
<br />ELECTRICAL- FL, REG.59422
<br />GA. REG. 31492
<br />SC. REG. 25290
<br />AL. REG.28079
<br />COPYRIGHT 2008
<br />PUBLIX SUPER MARKETS, INC.
<br />THESE CONSTRUCTION DOCUMENTS ARE THE
<br />PROPERTY OF PUBLIX SUPER MARKETS, INC. AND
<br />ARE NOT TO BE COPIED OR REUSED FOR ANY
<br />SPECIFIC BUILDING WITHOUT WRITTEN PERMISSION
<br />THESE DRAWINGS SHALL NOT BE DUPLICATED
<br />WITHOUT PRIOR WRITTEN PERMISSION OF
<br />PUBLIX SUPER MARKETS, INC.
<br />THE DESIGN INDICATED IN THESE CONSTRUCTION
<br />DOCUMENTS DOES, TO THE BEST OF MY KNOWLEDGE,
<br />INFORMATION, AND BELIEF, COMPLY WITH THE
<br />APPLICABLE MINIMUM BUILDING CODES
<br />PLOT DATE:
<br />10 JAN 08
<br />REVISION DATA:
<br />#12A5 (REPL. #0390)
<br />ZEPHYR COMMONS
<br />PRETTY POND RD.
<br />& HWY. 301
<br />ZEPHYRHILLS, PASCO CO.,
<br />FLORIDA
<br />5,4,4
<br />DRAWING TITLE:
<br />Version 07.2
<br />loop, ME -1,161
<br />
|