3.10.2 Comply with local health department regulations.
<br />3.10.3 Flush with clean, potable water until water runs clear.
<br />3.10.4 Fill system with with chlorine solution containing at least 50 ppm of chlorine.
<br />Allow to stand for at least 24 hours.
<br />3.10.5 Purge system of chlorine solution before putting into service.
<br />3.11. Inspection
<br />3.11.1 Notify Inspector as required by local authority when all work is completely
<br />installed and tested leak -tight.
<br />3.11.2 Do not conceal piping or fixtures until approval has been obtained from
<br />inspector.
<br />3.12. Cleaning Equipment and Premises:
<br />3.12.1 Thoroughly clean all parts of fixtures and equipment. exposed parts which are
<br />to be painted shall be thoroughly cleaned of foreign matter with grease, oil,
<br />soldering flux, etc. removed
<br />3.12.2 Exposed metal work shall be carefully brushed down with steel brushes to
<br />remove rust and other spots and touched up with primer.
<br />End of Section 22 40 00
<br />Section 23 70 00
<br />Central HVAC Equipment
<br />1. General
<br />1.1. Summary
<br />1.1.1 Provide all materials and equipment and perform all labor required to install
<br />HVAC systems complete as indicated, as required by code, and as specified
<br />herein. All sizes, etc. are Publix minimum and if local code requirements are
<br />higher, the work shall be bid and installed accordingly.
<br />1.1.1.1 Obtain and pay for all permits, bonds, inspection.
<br />1.1.1.2 Provide roof top and split HVAC systems or install systems provided
<br />by Publix as described below.
<br />1.1.1.3 All A/C curbs set for drying -in by Roofer.
<br />1.1.1.4 All roof mounted fans will be furnished by Publix and installed by
<br />HVAC Contractor. Curbs will be furnished by Publix for installation
<br />by Roofer.
<br />1.1.1.5 Provide hurricane brackets and other supports required to secure units
<br />to structure for wind and seismic conditions.
<br />Seismic: Seismic hazard level as designated by Authority Having
<br />Jurisdiction.
<br />Hurricane: FM 1-90 or higher if designated by Authority Having
<br />Jurisdiction.
<br />1.1.1.6 Provide sheet metal duct systems as indicated on Drawings and
<br />described in Specifications.
<br />1.1.1.7 Provide exhaust ducts between the cooking hoods and the roof
<br />mounted exhaust fans.
<br />1.1.1.$ Provide double -wall metal gas vents.
<br />1.1.1.9 Provide all other materials and services required for installation
<br />described in Contract Documents.
<br />1.1.2 HVAC Equipment:
<br />1.1.2.1 Publix will provide equipment delivered to the site of Construction.
<br />Coordinate delivery schedule with construction progress. Provide all
<br />labor, equipment, materials, and services required for installation and
<br />satisfactory completion of HVAC work.
<br />1.1.2.2 In addition to above, provide equipment, delivery, required staging
<br />and storage, and all other services required to complete the Work.
<br />1.1.3 Coordinate work with work of others. Notify concerned parties before
<br />proceeding with work that will affect them.
<br />1.2. Definitions: Explanation and precedence of Documents:
<br />1.2.1 For purposes of clarity and legibility, HVAC drawings are essentially
<br />diagrammatic and, although size and location of equipment are drawn to scale
<br />wherever possible, Contractor shall make use of all Contract Documents.
<br />1.2.2 Although the locations of the equipment and ductwork may be shown on the
<br />Drawings in certain positions, the Contractor shall be guided by the
<br />architectural details and conditions existing at the job, correlating this work
<br />with that of others.
<br />1.2.3 The Drawings indicate size, connection points and routes of ducts and
<br />equipment. It is not intended, however, that all offsets, rises and drops are
<br />shown. Install all items as required to fit structure, avoid obstructions, and
<br />retain clearance, headroom, openings and passageways.
<br />1.2.4 Remodels: Carefully examine all existing conditions, existing work in place
<br />and premises and compare the Drawings with the existing conditions.
<br />Submittal of bid indicates that the Contractor has examined the Site and
<br />Drawings and has included all required work in his bid. No allowances will be
<br />made for error resulting from Contractor's failure to visit job sites and to
<br />review Drawings.
<br />1.2.5 Conflicts, discrepancies, interferences and omissions in Documents shall be
<br />brought to the attention of the Architect for clarification prior to
<br />commencement of work.
<br />1.3. Submittals:
<br />1.3.1 Submit LOIs in accordance with Section 01 33 00 Submittal Procedures.
<br />1.3.2 Within 30 days of Contract Commencement (Authorization to Proceed), submit
<br />the following shop drawings and cut sheets for Publix Engineer's approval:
<br />Cooling Equipment
<br />Air Handling Equipment
<br />Heating Equipment
<br />Air Distribution
<br />Valves, Gauges, Specialties, Thermometers, Misc.
<br />Insulation
<br />Round and Oval Duct - submittals and shop drawings
<br />All submittal data shall have rough -in dimensions, connection sizes,
<br />any special installation requirements, certified performance data and
<br />horsepower, voltage and phase for all equipment.
<br />Equipment, fixtures and trim with cuts including rough -in
<br />dimensions.
<br />Other items required to complete the work
<br />1.3.3 Submit four identical bound copies of all items. Arrange categories in order
<br />listed above.
<br />1.3.4 Literature for the above shall have rough -in dimensions, connection sizes, and
<br />special installation requirements.
<br />1.3.5 Project Record Drawings: Comply with Section 01 78 39.
<br />1.4. Quality:
<br />1.4.1 Subcontractor:
<br />1.4.1.1 The HVAC Subcontractor shall be a reputable firm regularly engaged
<br />in this type of work, employing skilled workmen, and with proper
<br />equipment.
<br />1.4.1.2 Upon request Subcontractor shall show evidence of at least two
<br />similar jobs, of comparable size and character, installed and operating
<br />within the previous two years prior to Bid Opening.
<br />1.4.1.3 Publix reserves the right to refuse any Subcontractor with or without
<br />cause.
<br />1.4.2 Personnel:
<br />1.4.2.1 Employ an experienced Superintendent to oversee all operation.
<br />1.4.2.2 Work shall not proceed without adequate supervision present at all
<br />times.
<br />1.4.2.3 Work shall be accomplished by workers certified in their trade as
<br />masters, journeymen, and apprentices in accordance with regulations
<br />of the governing authority or customary practice. Utilize workers with
<br />skills in proportion to complexity of tasks required.
<br />1.4.2.4 Publix reserves the right to reject personnel with or without cause.
<br />1.4.3 Quality standards: Work will be judged in comparison to work of similar types.
<br />Substandard construction as judged by Publix Representative will not be
<br />accepted.
<br />1.4.4 Regulations: Comply with applicable provisions of the following codes (latest
<br />version adopted by governing agencies):
<br />National Fire Protection Association (NFPA)
<br />Local Building Code
<br />ASME Code for Un-Fired Pressure Vessels
<br />ASHRAE Code for Refrigeration Apparatus
<br />Safety Code for Mechanical Refrigeration.
<br />National Electric Code/State Mechanical Code.
<br />OSHA - For construction
<br />Other applicable laws and regulations.
<br />1.4.5 Participate in the pre -construction conference.
<br />1.5. Sequencing:
<br />1.5.1 Notify General Contractor, or any others, of all chases, sleeves and openings
<br />required so that the work can be accomplished without delay. Provide
<br />necessary sleeves, etc., to be installed. Otherwise, HVAC Sub -Contractor
<br />shall pay for appropriate trades to perform cutting and patching.
<br />1.5.2 Joists, girders, beams, columns or reinforcing steel shall not be cut.
<br />1.5.3 Where construction necessitates the routing of ducts or piping through
<br />structural members, or framing, permission to make such installation shall first
<br />be obtained from the Publix Field Representative
<br />1.6. Temporary Operation: The Owner may require operation of part or all of the
<br />installation prior to Final Acceptance.
<br />1.7. After acceptance of the Work, the Owner reserves the right to make emergency
<br />repairs as required to keep equipment in operation without voiding the Contractor's
<br />guarantee nor relieving the Contractor of his responsibilities during the guarantee
<br />period.
<br />1.8. Operating Instructions and Service Manual:
<br />1.8.1 Provide two neatly bound copies of maintenance and instructions book, parts
<br />lists pertaining to all equipment furnished.
<br />1.9.2 Each section shall be indexed and include parts lists, instruction books,
<br />suppliers' phone numbers and addresses, and individual equipment guarantees
<br />all in separate sections.
<br />1.8.3 Representatives of the Owner shall be instructed by the Contractor as to
<br />complete care and operation of the HVAC system. Inform the Architect in
<br />writing as to the persons who received the instructions and the date that this
<br />was done.
<br />1.9. Warranty:
<br />1.9.1 Units shall have a manufacturer's standard one-year warranty against all
<br />defects.
<br />1.9.2 Provide industry standard five-year compressor replacement warranty.
<br />2. Products
<br />2. 1. General: All equipment and materials shall be furnished in strict accordance with the
<br />equipment schedule and specifications requirements.
<br />2.2. Nameplates
<br />2.2.1 Nameplates shall not be painted.
<br />2.2.2 All switches, starters, and major pieces of equipment shall be identified with
<br />black plastic nameplates with engraved white letters.
<br />2.3. Packaged Rooftop Air Conditioners: See Drawings.
<br />2.4. Controls:
<br />2.4.1 An Environmental Control Panel will be furnished and installed by Publix to
<br />control all AC units. Conduit, line voltage circuits, interlocks, etc., shall be
<br />furnished and installed by the Contractor, as shown on drawings.
<br />2.5. Filter Media: Full two inch thick dual density polyester material.
<br />2.6. Air Distribution
<br />2.6.1 General:
<br />2.6.1.1 All air distribution shall be supplied by manufacturers whose testing
<br />procedures are in accordance with ASHRAE Standard 70-1991.
<br />2.6.1.2 Furnish and install, unless otherwise noted, all grilles, registers, and
<br />outlets at the location and of the type and size shown on the Drawings.
<br />Install foam rubber gaskets behind flanges of all grilles and registers
<br />to prevent leakage and streaking. Adjust air volumes and set
<br />deflection in accordance with Drawings.
<br />2.6.2 Return Air Grilles and Registers:
<br />2.6.2.1 All grilles shall be suitable for smooth surface mounting.
<br />2.6.2.2 Coordinate installation of door grilles with door installation.
<br />2.6.2.3 Where indicated, provide opposed blade dampers
<br />2.6.2.4 Approved manufacturers:
<br />Airguide
<br />Aeemostat
<br />Bailey and Tuttle
<br />Lindab
<br />Metal Industries
<br />Nailor Industries
<br />Price
<br />Titus
<br />2.6.3 Outlets:
<br />2.6.3.1 All supply outlets shall be aluminum (or alurnini�ed steel where
<br />required when part of rated roof -ceiling assembly) and products of a
<br />single manufacturer. Return air grilles, outlets, registers and door
<br />grilles shall be of etched aluminum with acrylic finish and as
<br />indicated.
<br />2.6.3.2 Provide steel grills and fire dampers, radiation dampers as indicated
<br />on the Drawings and in accordance with U.L. roof -ceiling assembly
<br />design where indicated
<br />1.6.3.3 Provide UL listed lay -in ceiling outlets complete with radiation
<br />damper and thermal blanket. Approved Manufacturer:
<br />Nailor Industries
<br />Other manufacturer as approved by Publix Engineer.
<br />2.6.3.4 Variable volume type shall be factory insulated, complete with
<br />controls, damper, change over thermostat as indicated on the
<br />Drawings. Approved Manufacturer:
<br />Metal Industries
<br />Price
<br />2.6.4 Louvers: Aluminum, drainable with bird screen, AMCA certified.
<br />Greenheek ESD-403
<br />Ruskin #ELF-375D
<br />Louvers and Dampers Inc. IEL-4-104, ALL Series
<br />2.7. Sheet Metal Ductwork:
<br />2.7.1 Galvanized Ductwork: All duct and fittings shall be manufactured from
<br />galvanized steel of lock forming quality per ASTM A-527. The zinc coating
<br />shall be minimum G90 (1,25 oz. 1 sq. ft.) per ASTM A924. Seams on fittings
<br />shall be welded or tacked & sealed. Individual fittings are required,
<br />manifolding is not permitted. Comply with SMACNA requirements for duct
<br />construction for ventilation and air conditioning systems.
<br />2.7.2 Stainless steel ductwork: ASTM A480, Type 316 sheet -form with #4 finish for
<br />surfaces exposed to view; Type 304sheet-form, with #1 finish for concealed
<br />ducts.
<br />2.7.3 Rectangular Duct Work:
<br />2.7.3.1 Panels shall be cross broken. (Beaded duct not acceptable)
<br />2.7.3.2 Longitudinal standing seams may be used
<br />2.7.3.3 Comer closures are not required
<br />2.7.3.4 Hangers shall be band iron
<br />2.7.3.5 Elbows shall be as drawn.
<br />2.7.3.6 Where indicated vaned elbows shall be double vaned.
<br />2.7.3.7 Connections shall be either 90 degree straight with Titus Model AG-
<br />45 control grid or radius tap -in.
<br />2.7.3.8 Inspection plates and test holes are not required.
<br />2.7.3.9 Fresh air intake shall be square or rectangular standard
<br />2.7.3.10 Access doors shall be insulated and removable.
<br />2.7.3.11 Sealer on all joints: Sealants shall have a Flamespread Rating of 25 or
<br />less, Smoke Developed Rating of less than 50 to comply with NFPA
<br />90A. .
<br />Hardcast Iron Grip Water -Based Duct Sealant 601.
<br />United McGill, United Duct Sealer.
<br />Precision Adhesives PA-2084A Duct Sealant.
<br />Fosters 32-19
<br />2.7.4 Round and Flat Oval Duct:
<br />2.7.4.1 All exposed ductwork shall be spiral lockseam construction standard
<br />SMACNA gauges tested to + 1OWG. Longitudinal seam duct is
<br />prohibited. Comply fully with SMACNA recommendations.
<br />2.7.4.2 Where ductwork is exposed to view, provide G90 galvanized metal
<br />suitable for painting.
<br />2.7.4.3 Field Joints in Exposed Ductwork: Lindab Inc. SPIRO safe duct
<br />system, or Ductmate industries Spirahnate Round Duct Connector and
<br />"Ovalmate Flat Oval Duct Connector" or approved equals.
<br />2.7.4.4 Substitution of sizes by cross section area or equivalent round formula
<br />must have written prior approval.
<br />2.7.4.5 Ductwork assemblies shall a the type tested to 10" WG (min.) by UL
<br />181.
<br />2.7.4.6 Approved Duct Manufacturers:
<br />Eastern Sheet Metal
<br />Lindab, Inc/R. V. Money, Inc. - St. Petersburg, Florida
<br />United McGill Corp.
<br />2.7.4.7 Gauges (Single Wall Ductwork):
<br />Diameter Gauge Major Dim Gauge
<br />Round Duct Flat -Oval Duct
<br />3" - 14" 26 Ga. 3"-24" 24 Ga
<br />15" - 26" 24 Ga. 25" - 48" 22 Ga.
<br />28" - 36" 22 Ga. 49" - 70" 20 Ga.
<br />38" - Up 20 Ga. 71" - Up 18 Ga
<br />Round Fittings Flat -Oval Fittings
<br />3" - 14" 24 Ga. 3"-36" 20 Ga
<br />15" - 26" 22 Ga. 37' - 60" 18 Ga.
<br />28" - 50" 20 Ga. 61" - Up 16 Ga.
<br />2.7.4.8 Doublewall Ductwork
<br />2.7.4.8.1 Double wall duct and fittings shall consist of a perforated
<br />inner liner, a 1 inch, 1.501b./ft3 (unless otherwise specified)
<br />layer of fiber glass insulation and a solid outer pressure shell.
<br />A retaining fabric shall be wrapped between the perforated
<br />inner duct and the fiber glass insulation.
<br />2.7.4.8.2 All fitting ends from 5" to 24" O.D, shall have rolled edges
<br />for added strength and rigidity during installation and
<br />shipping..
<br />. 2.7.4.9.3 Double wall to single wall transitions shall be provided
<br />where insulated duct connects to non -insulated, single wall
<br />duct. Transitions also act as insulation ends reducing the
<br />double wall outer shell diameter to the inner shell diameter.
<br />2.7.4.8.4 Gauges (Double Wall Ductwork):
<br />Round Duct Flat -Oval
<br />Dia. Inner Outer Maj Ax. Inner Outer
<br />3 - 12" 26 26 Ga. 3 - 22" 24 24 Ga.
<br />13 - 24"26 24 Ga. 23 - 34" 24 22 Ga.
<br />25 - 34"26 22 Ga. 35 - 46" 24 22 Ga.
<br />35 - 50"24 20 Ga. 47 - 58" 22 20 Ga.
<br />59 - 68"22 20 Ga.
<br />69 - UP 20 18 Ga.
<br />Round Fittings Flat -Oval Fittings
<br />Dia. Inner Outer Ma. Ax. Inner Outer
<br />3 - 12" 24 24 Ga. 3 - 22" 24 20 Ga
<br />13 - 24"24 22 Ga 23 - 34" 24 20 Ga
<br />25 - 34"24 20 Ga. 35 - 46" 22 18 Ga.
<br />35 - 50"22 20 Ga. 47 - 58" 22 18 Ga.
<br />59 - 68"20 16 Ga.
<br />69 - UP 20 16 Ga.
<br />2.7.4.9 Duct Hangers - 8' 0" C/C max distance.
<br />2.8. Flexible Duct:
<br />2.8.1 Factory insulated on aluminum liner, UL listed Class 1 Air Duct, STD. 181 and
<br />NFPA Bulletin 90A, with F/S kraft metallized mylar vapor barrier jacket.
<br />2.8.2 Entire assembly shall be UL-181, class llisted, and meet NFPA 90A, with
<br />flamespread rating less than 25, and smoke developed 50 or less.
<br />2.8.3 Minimum working pressure 6" w.g.
<br />2.8.4 Maximum length-10 feet.
<br />2.8.5 Supports shall be spaced maximum 3 feet, support band min. 2 in. wide: Use
<br />Wiremold duct collars and galvanized strap clamps or equal as approved by
<br />Engineer.
<br />2.8.6 Spin in fittings shall be Metal Masters Model MS 1-6G or equal as approved by
<br />Engineer.
<br />2.8.7 Approved products:
<br />Flexinaster TL -M
<br />Insulated Metalflex V-250-LTL
<br />Thermo -Fin Type A-300
<br />2.9. Duct Leakage Loss:
<br />2.9.1 Each system shall meet SMACNA and ASHRAE leakage class 3. This leakage
<br />will be determined by the test and balance consultant.
<br />2.9.2 Loss exceeding leakage class 3 requirements shall be corrected by the HVAC
<br />Contractor prior to acceptance by Publix.
<br />2.10. Duct Hangers:
<br />2.10.1 Duct hangers shall be threaded rods or metal straps with metal bands or angles.
<br />See details in the mechanical drawings.
<br />2.10.2 Alternate system: Load -rated cable suspension system. The system shall have
<br />a specified manufacturer's safe working load (SWL) and supplementary safety
<br />factor of at least five times the SWL. The system shall be verified by
<br />SMACNA Testing & Research and shall be in compliance with SMACNA
<br />Duct Construction Standards guidelines, 1995 ed., ch. 4.
<br />2.10.2.1 Approved System: Gripple Hang -Fast.
<br />2.11. Grease Hoods:
<br />2.11.1 Install UL classified range hoods as indicated on the Drawings and in
<br />. accordance with NFPA 96. Hoods shall be 18 gage, 304 stainless steel, liquid
<br />tight welds, grease extractors, vapor proof lights with factory pre -piped fire
<br />suppressor. Manufactured by greenheck, furnished by Publix
<br />2.12. Suppression
<br />2.12.1 Provide fire protection system (specified Section 15355-Automatic Fire
<br />Suppression System) for all grease -laden air removal hoods (Designated GH-).
<br />Fire dampers shall be at the supply air inlets.
<br />2.13. Grease Hood Exhaust Duct
<br />2.13.1 Provide welded 16 ga. galvanized steel exhaust duct as indicated on Drawings.
<br />2.13.2 Access door shall be U.L. listed
<br />2.14. Oven Gas Flues
<br />2.14.1 Provide a complete insulated double wall gas venting system (U.L. Listed
<br />#103), 1400 degrees F. rating and draft hood for the gas fired equipment and
<br />bakery ovens where indicated.
<br />2.14.2 Thimbles, flashing, rain cap as required
<br />2.14.3 Air Intake: Single wall construction.
<br />2.15. Devices and other miscellaneous items:
<br />2.15.1 Dampers: Opposed blade, butterfly type, or splitter, all factory made as
<br />indicated. Each shall have a locking quadrant accessible for adjustment, with
<br />extension sleeve for duct wrap insulation.
<br />2.15.2 Air Turning Device for Registers: Titus model AG-45 or similar device as
<br />approved by Architect.
<br />2.15.3 Radiation Dampers: UL listed and installed where indicated
<br />2.15.4 Piping System for Condensate: Schedule 40 PVC.
<br />2.16. Insulation:
<br />2.16.1 Concealed HVAC Ductwork:
<br />2.16.1.1 Insulate externally with foil scrim kraft (FSK) fiberglass blanket type
<br />insulation, ASTM C 1136, thickness and R value as indicated on the
<br />Drawings.
<br />2.16.1.2 Comply with ASHRAE 90.1 and energy code requirements of the
<br />AHJ.
<br />2.16.1.3 Materials shall have flamespread less than 25, and smoke developed
<br />less than 50.
<br />2.16.1.4 Approved manufacturers:
<br />Johns Manville .
<br />CetainTeed
<br />Owens Corning
<br />Knauf
<br />2.16.1.5 Neatly cut and fit insulation to the duct surface with all- duct joints
<br />overlapped 2" minimum, secured with outward -clinch staples 4" on
<br />center each way.
<br />2.16.1.6 On ducts 24" or greater in width the insulation on the underside of the
<br />duct shall be secured to the sheet metal surface with Foster'S #85-20,
<br />or equal, adhesive, and secured mechanically with sheet metal screws
<br />- and caps, or mechanical fasteners adhered to the duct on not more
<br />than 18" centers each way.
<br />2.16.1.7 All transverse and longitudinal seams, and penetrations of the vapor
<br />barrier facing shall be covered with SMACNA rated foil backed tape
<br />applied in and sealed with Foster's #30-80 or #30-65, or equal, vapor
<br />barrier mastic.
<br />2.16.2 Where indicated, exposed double wall HVAC duct work shall be internally
<br />insulated with fiberglass.
<br />2.16.2.1 Insulate internally with fiberglass rigid board type insulation and
<br />retaining fabric, ASTM C1136, thickness and R value as indicated on
<br />the Drawings.
<br />2.16.2.2 Materials shall have flamespread less than 25, and smoke developed
<br />less than 50.
<br />2.16.2.3 Approved manufacturers:
<br />Johns Manville
<br />CetainTeed
<br />Owens Corning
<br />Knauf
<br />2.16.3 Fire-resistant Grease Duct Wrap
<br />2.16.3.1 Alternative to 1 and 2 hour fire resistant rated gypsum shaft
<br />enclosures. Product shall be a flexible, O" clearance, non -asbestos
<br />system, encapsulated with a scrim re -enforced foil. no flame, no
<br />smoke characteristics for the foil blanket. Install per manufacturer's
<br />guidelines.
<br />2.16.3.1.1 Approved manufacturers and products:
<br />Vesuvius - Pyroscat Ductwrap and Pyroscat Fast R Duct Wrap
<br />3M - Fire Barrier Ductwrap 15A
<br />Thermal Ceramics FireMaster-FastWrap+
<br />2.16.3.2 Follow the manufacturer's guidelines for securing ductwrap, welded
<br />stickpins only, banding and sealers.
<br />2.17. Ductwork accessories:
<br />2.17.1 Control Dampers Provide dampers with parallel blades for 2 position control,
<br />or opposed blades for modulating control.
<br />2.17.1. I All metal parts galvanized steel.
<br />2.17.1.2 Blades: 16ga.
<br />2.17.1.3 Bearings: Heavy duty molded nylon.
<br />2.17.1.4 Axles: 1/2" dia. steel, 9" OC.
<br />2.17.1.5 Steel Frames:
<br />2.17.1.5.1 Up to 25 sq. ft.: 2"Xl/2"Xl/8"
<br />2.17.1.5.2 Over 25 sq. ft.: 4"Xl 1/4"Xl6ga.
<br />2.17.1.6 Acceptable Manufacturers:
<br />Greenheck
<br />Ruskin
<br />2.17.2 Fire Dampers:
<br />2.17.2.1 Fire dampers shall be rated where indicated and shall be UL 555
<br />listed.
<br />2.17.2.2 All metal parts galvanized steel, dynamically tested.
<br />2.17.2.3 Casings: 20 ga.
<br />2.17.2.4 Blades: 24 ga.
<br />2.17.2.5 Fusible Link: 160 - 165 deg. F.
<br />2.17.2.6 Damper: Positive lock type with curtain type blade, positive lock in
<br />closed position, with curtain 100% out of airstream.
<br />2.17.2.7 Steel Frames:
<br />2.17.2.7.1 Up to 25 sq. ft.: 2"Xl/2"Xl/8"
<br />2.17.2.7.2 Over 25 sq. ft.: 4"Xl 1/4"Xi6ga.
<br />2.17.2.8 Acceptable Manufacturers:
<br />Greenheck
<br />Ruskin
<br />2.17.3 Duct access doors:
<br />2.17.3.1 Construct of same gauge or heavier as ductwork served. Provide
<br />insulated doors for insulated ductwork. Provide flush frames for un-
<br />insulated ductwork, extended frames for externally insulated
<br />ductwork. Provide one side hinged, other side with one handle type
<br />cam latch for all doors. If space is limited for a hinged door swing,
<br />then provide a two handle type cam latch door.
<br />2,17.3.2 Door sizes shall accommodate to allow fire dampers and other devices
<br />to be accessed for repair or reset to normal position after being
<br />activated.
<br />Largest Dimension of Duct Access Door Nom. Dimension
<br />Up to 10" 6"X6"
<br />10" to 16" 8"X8"
<br />17" to 24" 12"X12"
<br />25" to 36" 16"X16"
<br />37" and larger 24"X16"
<br />2.17.3.3 Acceptable manufacturers:
<br />Greenheck
<br />Ruskin
<br />2.17.4 Fabricate kitchen hood ducts from 16 ga. galvanized steel sheets, 18 ga.
<br />stainless stell where exposed Conform to NFPA 96. Ali joints and seams shall
<br />be welded liquid tight. Provide a flange for duct at top of exhaust fan curb.
<br />3. Execution:
<br />3.1. General
<br />3.1.1 Neatness counts. Make all joints, connections, unions, etc. with proper care to
<br />insure that tight connections are made without excess material, well secured to
<br />supports.
<br />3. L2 Install duct with runs straight, shop formed radiuses at bends, and adequate
<br />supports.
<br />3.1.3 Verify all field dimensions and locations of equipment and fixtures within the
<br />layout to ensure close, neat fit, with other trades work.
<br />3.2. Installation:
<br />3.2.1 Installation of rooftop A.C. units:
<br />3.2.1.1 Publix will furnish factory fabricated steel roof curbs complete with
<br />wood nailer strips. Curbs are shipped fully assembled and tapered to
<br />fit roof slope.
<br />3.2.1.2 Provide materials and coordination with other trades required to
<br />ensure that curbs are installed properly.
<br />3.2.1.3 Attach units to curbs as indicated on the Drawings.
<br />3.2.1.4 Lift all A/C units with spreader bars to prevent cable damage to
<br />cabinets and components.
<br />3.2.1.5 Publix will accept only those units which are in new condition without .
<br />dents or other damage. Scratches or paint damage are to be re -painted
<br />with manufacturer's paint.
<br />3.2.1.6 In the event that field repair involves the refrigeration circuit of any
<br />unit, such repair is to be made by the unit manufacturer or his
<br />representative.
<br />3.2.1.7 Provide each unit with a PVC condensate drain trap in accordance
<br />with Drawings and unit manufacturer's recommendation.
<br />3.2.1.8 Piping of unit mounted heat reclaim coils) will be by Publix.
<br />3.2.2 Installation of rooftop fans:
<br />3.2.2.1 Publix will furnish factory fabricated steel roof curbs complete with
<br />wood nailer strips. Curbs are shipped fully assembled. Slope
<br />accommodation is through steel frame provided under other sections.
<br />3.2.2.2 Provide materials and coordination with other trades required to
<br />ensure that curbs are installed properly.
<br />3.2.2.3 Attach fans to curbs as indicated on the Drawings.
<br />3.3. Equipment Start -Up:
<br />3.3.1 All rooftop A.C. units shall be started and adjusted for proper operation by the
<br />manufacturer or his representative. No equipment shall be run prior to this
<br />start-up. All units shall be made ready for start-up at the same time.
<br />3.3.2 Contractor shall have qualified personnel in attendance to coordinate ductwork
<br />and electrical aspects of the start-up.
<br />3.4. Substantial Completion Inspection
<br />3.4.1 All of the following items must be completed prior to Substantial Completion
<br />Inspections. No exceptions will be made and no payment will be made until all
<br />items are completed.
<br />3.4.2 Cleaning Equipment and Premises:
<br />3.4.2.1 Thoroughly clean all parts of the apparatus and equipment. Exposed
<br />parts which are to be painted shall be thoroughly cleaned of cement,
<br />plaster, and other material and all oil and grease spots shall be
<br />removed. Repaint or touch up as required to make look like new.
<br />Surfaces shall be carefully wiped and all cracks and comers scraped
<br />out.
<br />3.4.2.2 Exposed metal work shall be carefully brushed down with steel
<br />brushes to remove rust and other spots and touched up with primer.
<br />3.4.3 Testing and Balancing Systems
<br />3.4.3.1 Publix will provide a test and balance contractor. This service will be
<br />done in the presence of the HVAC Sub- Contractor, so that
<br />deficiencies can be noted.
<br />3.4.3.2 Comply with "Standards for Field Measurement and
<br />Instrumentations" Form No. 81266 Volume One. as published by the
<br />Associated Air Balance Council.
<br />3.4.3.3 Submit three (3) copies of the complete test reports to the Publix
<br />Refrigeration Department prior to Final Acceptance of the Project.
<br />3.4.3.4 Provide sufficient time before the completion date so that testing and
<br />balancing can be accomplished, and remediation made.
<br />3.4.3.5 Put all HVAC Equipment into full operation and continue operation
<br />during each working day of testing and balancing.
<br />3.4.3.6 All dampers shall be in wide open or neutral position prior to test and
<br />balance of the system.
<br />3.4.3.7 Implement changes recommended by the testing and balancing
<br />contractor, including pulley changes, balancing dampers and other
<br />items as required to obtain proper system balance as judged by the
<br />testing and balancing contractor and the Publix Architect.
<br />3.4.3.8 Maintain operation of the system for a minimum of 24 hours after
<br />balance has been obtained. Notify Publix Architect so that he may
<br />inspect the system under operating conditions.
<br />3.5. Prior to requesting a Final Inspection, submit a typed schedule or a marked up set of
<br />Drawings indicating the observed velocity of each grille, register or outlet. These test
<br />data shall be final readings after balancing the system.
<br />3.6. Dust streaking on exposed duct systems: After 6 months, examine all exposed
<br />ductwork for dust streaking. Where streaking has occurred, the causes ofthe streaking
<br />shall be determined and repaired. Streaked surfaces shall be cleaned and touched up
<br />to match the original finish.
<br />End of Section 23 70 00
<br />Section 26 00 00
<br />Electrical
<br />1. General
<br />l.l. Summary
<br />1.1.1 Comply with requirements of Sections O1 1100, O1 33 00, 0150 00, 0177 00,
<br />01 78 39.
<br />1.1.2 Provide all materials and equipment and perform all labor required to install
<br />electrical systems complete as indicated, as required by code, and as specified
<br />herein.
<br />1.1.3 Obtain and pay for all permits, bonds, inspection. Coordinate inspections with
<br />work as it progresses.
<br />1.1.3.1 Provide services necessary to coordinate work with work of others.
<br />Notify concerned parties before proceeding with work that will affect
<br />them.
<br />1.1.3.2 Provide electric service to connect with site utilities at a point outside
<br />the building as shown on the Drawings.
<br />1.1.3.3 Coordinate with Utilities all requirements for utility transformer and
<br />Metering.Furnish and install all utility requirements for electrical service (ie.
<br />transformer pad, CT compartment, meter base and pedestal)
<br />1.1.3-4 Install all panelboards, and contactors at the locations shown on the Drawings
<br />and specified herein.
<br />1.1.3.5 All spare, empty conduit and junction boxes to have pull string.
<br />1.1.3.6 Furnish and install all conduit and conductors between the load side of
<br />the feeder breakers to the branch panels.
<br />1.1.3.7 Furnish and install all branch circuits between the panelboards and the
<br />final terminal as shown on the Drawings and specified herein.
<br />1.1.3.8 Furnish and install all secondary service between the power company
<br />transformer to the main switch as indicated on the Drawings.
<br />L 13.9 Receive, store, install and make final electrical connections to all
<br />lighting fixtures as shown on the Drawings and specified herein.
<br />1.1.3.10 Furnish and install conduit and boxes only for the public address
<br />system and telephone outlets.
<br />1.1.3.11 Make electrical connections to the electric door operators as shown on
<br />the Drawings and specified herein.
<br />1.1.3.12 Make all electrical connections to equipment supplied by Publix.
<br />Electrical Contractor to verify all manufacturer equipment
<br />requirements prior to connection. Any conflicts or deviation in design
<br />to be brought to the attention of the Engineer.
<br />1.1.3.13 Make all electrical connections to refrigerated display cases and walk-
<br />in boxes as shown on the Drawings and specified herein.
<br />1.1.3.14 Make all electrical connections between the main switchboard and the
<br />refrigeration compressors and condensing equipment as shown on the
<br />Drawings and specified herein.
<br />1.1.3.15 Furnish and install all motor starters, disconnect devices, conduit and
<br />conductors for control and power wiring.
<br />1.1.3.16 Make all electrical connections between the main switchboard and the
<br />air conditioning compressors, air handling units, package units and
<br />strip heaters as shown on the Drawings and specified herein.
<br />1.1.3.17 Make all electrical connections between the machine rooms mounted
<br />refrigeration equipment and the refrigerated display cases, walk-in
<br />freezers and coolers as shown on the Drawings and specified herein.
<br />1.1.3.18 Furnish and install all conduit and conductors to totally electrically
<br />connect all controls as specified herein.
<br />1.1.3.19 Furnish and install all electrical work required for the dry chemical
<br />fire extinguisher system in the grease exhaust hoods. in compliance
<br />with NFPA Bulletins #17, 496, and with local codes.
<br />1.1.3.20 Furnish and install all electrical wiring devices as shown on the
<br />Drawings and specified herein.
<br />1.1.3.21 Furnish and install all conduit, conductors, disconnect devices and
<br />flexible metal conduit to completely wire all supply and exhaust fans
<br />as shown on the Drawings and specified herein.
<br />1.1.3.22 The Electrical Contractor is fully responsible and liable for damaged
<br />and lost materials furnished by Publix. It shall be required that he sign
<br />for the materials supplied by Publix.
<br />1.1.3.23 Panels for A/C and refrigeration mechanical systems, as furnished
<br />pre -wired internally by others, shall be mounted and connected by the
<br />Electrical Contractor. Refer to Drawings and Specifications for air
<br />conditioning.
<br />1.1.3.24 Furnish and install all electrical service and controls for fans installed
<br />by others.
<br />1.1.3.25 Furnish and install power wiring to each HVAC unit including the
<br />safety disconnect switch and other required electrical devices to make
<br />the unit operational as shown on the Drawings and specified herein.
<br />1.1.3.26 Install emergency generator and transfer switch complete, as furnished
<br />by Publix.
<br />1.1.3.27 Install conduit/boxes with pull string for fire alarm and burglar alarm
<br />system, as furnished by Publix per note on Electrical Drawings.
<br />1.1.3.28 Install and connect air conditioning control panel, energy management
<br />system, supplied by Publix.
<br />1.1.3.29 Install conduit, conductors and make connections to "Publix" sign,
<br />and all other facade signs and under -canopy signs (signs supplied and
<br />installed by Sign Contractor).
<br />1.1.3.30 Security and fire alarm systems or combined system: the Contractor
<br />shall supply and install conduit, boxes, and pull strings as shown on
<br />Drawings. Power supply, station controls and complete final hook-up
<br />by Fire Alarm Constrictor as noted on Drawings.
<br />1.1.4 Related Work by Other Contractors:
<br />1.1.4.1 Setting and roofing in of all curbs and pitch pockets by Roofing
<br />Contractor. (setting of A/C curb only shall be by A/C Contractor)
<br />1.1.4.2 Setting ofwater heaters, ovens, kitchen equipment, gondolas, cash
<br />registers, air conditioners, exhaust fans, refrigerated cases, meat room
<br />equipment, facade signs and other miscellaneous equipment by others.
<br />Final electrical connection by Electrical Contractor.
<br />1.1.4.3 Kitchen Hood Fire Protection System by Others.
<br />1.1.5 Publix reserves the right to furnish some items of electrical equipment to the
<br />Electrical Contractor. If this is done the Electrical Contractor shall install the
<br />equipment and deduct the cost of the equipment from his contract. Cost
<br />adjustment will be made by Change Order.
<br />1.1.6 All apparatus shall be installed at exact height and locations as shown on the
<br />Drawings, or if not shown, at heights and locations determined by applicable
<br />codes and laws.
<br />1.1.7 Perform all excavation and backfill required for services, and for all conduit
<br />and work inside and outside the building. Cutting of curbs, walks, concrete and
<br />paving required for excavation shall be done by appropriate trade.
<br />1.1.8 All store cases, coolers, and freezers will be furnished and set in place by
<br />Publix. Check Equipment Drawings against Drawings in order to verify exact
<br />locations.
<br />1.2. Definitions: Explanation and Precedence of Documents:
<br />1.2.1 For purposes of clarity and legibility, Electrical Drawings are essentially
<br />diagrammatic and, although size and location o€ equipment are drawn to scale
<br />wherever possible, Electrical Contractor shall make use of all Contract
<br />Documents.
<br />1.2.2 The Drawings indicate size, connection points and routes of conduit and
<br />equipment. It is not intended, however, that all offsets, rises and drops are
<br />shown. Install all items as required to fit structure, avoid obstructions, and
<br />retain clearance, headroom, openings and passageways.
<br />1.2.3 Remodels: Carefully examine all existing conditions, existing work in place
<br />and premises and compare the drawings with the existing conditions. Submittal
<br />of bid indicates that the Electrical Contractor has examined the Site and
<br />Drawings and has included all required work in his bid. No allowances will be
<br />made for any error resulting from Contractor's failure to visit Job Sites and to
<br />review Drawings/Documents. .
<br />1.2.4 Conflicts, discrepancies, interferences and omissions in Documents shall be
<br />brought to the attention of the Engineer for clarification prior to
<br />commencement of Work.
<br />1.3. Submittals:
<br />1.3.1 Submit LOI in accordance with Section 01 33 00 Submittal Procedures.
<br />1.3.2 Within 30 days of Contract Commencement (Authorization to Proceed), submit
<br />for Publix Engineer's approval:
<br />1.3.2.1 List of materials intended for use in the Project.
<br />1.3.2.2 Manufacturer's catalogue cuts of materials intended for use in the
<br />Project. LOI's not acceptable.
<br />1.3.2.3 Submittals to include: Switchgear, breakers, panel boards, starters,
<br />disconnects, relays, walkerduct, wire channel system, conduit, wire,
<br />boxes, wiring devices, receptacles, switches.
<br />1.3.2.4 Copies of licenses of key personnel if requested by Publix.
<br />1.3.2.5 Samples of materials if requested by Publix.
<br />1.3.2.6 Other items required to complete the Work
<br />1.3.3 Submit three identical bound copies of all items. Arrange categories in order
<br />listed above.
<br />1.3.4 All cuts for the above shall have rough -in dimensions, connection sizes, and
<br />any special installation requirements. In addition, furnish motor horsepower
<br />voltage and phase for all equipment.
<br />1.3.5 Close Out Documents:
<br />1.3.5.1 Comply with applicable provisions of Section 0178 39 Project
<br />Record Documents.
<br />1.3.5.2 Provide a complete set of manufacturer's warranties and warranty
<br />certificates.
<br />1.3.5.3 A copy of the final approval from the local building department.
<br />1.4. Quality:
<br />1.4.1 Subcontractor:
<br />1.4.1.1 The Electrical Subcontractor shall be a reputable firm regularly
<br />engaged in this type of work, employing skilled workmen, and with
<br />proper equipment.
<br />1.4.1.2 Upon request Subcontractor shall show evidence of at least two
<br />similar jobs, of comparable size and character, installed and operating
<br />within the previous two years prior to bid opening.
<br />1.4.1.3 Publix reserves the right to refuse any Subcontractor with or without
<br />cause.
<br />1.4.2 Personnel:
<br />1.4.2.1 Employ an experienced superintendent to oversee all operation.
<br />1.4.2-2 Work shall not proceed without adequate supervision present at all
<br />times.
<br />1.4.2.3 Work shall be accomplished by workers certified in their trade as
<br />masters, journeymen, and apprentices in accordance with regulations
<br />of the governing authority or customary practice. Utilize workers with
<br />skills in proportion to complexity of tasks required.
<br />1.4.2.4 Publix reserves the right to reject personnel with or without cause.
<br />1.4.3 Quality Standards
<br />1.4.3.1 Work shall be accomplished to ensure safety to all personnel during
<br />installation and after occupancy.
<br />1.4.3.2 Work will be judged by Publix in comparison to work of similar
<br />types. Substandard construction as judged by Publix Representative
<br />will not be accepted.
<br />1.4.3.3 Neatness counts. Make all joints, connections, unions, etc. with proper
<br />care to insure that tight connections are made without excess material,
<br />well secured to supports.
<br />1.4.3.4 Install conduit with runs straight, accurately formed radiuses at bends,
<br />and adequate supports.
<br />1.4.4 Regulations: Comply with applicable provisions of the following codes (latest
<br />version adopted by governing agencies):
<br />National Fire Protection Association (NFPA)
<br />National Electrical Code
<br />Local Utility Code
<br />Local Building Code
<br />Safety Code for Mechanical Refrigeration.
<br />Conform to governing codes, ordinances and regulations of city,
<br />county and state having jurisdiction. Where local codes are not
<br />applicable, conform to National Electric Code/State Electric Code
<br />where Project is located.
<br />OSHA - for construction
<br />1.4.5 Test the entire system. The solid neutral wire shall be tested for thorough
<br />grounding and all hot wiring shall be tested for shorts and grounding.
<br />1.4.6 Participate in the Pre -Construction Conference.
<br />1.4.7 Substitutions: Comply with Section 01 63 00 Product Options and
<br />Substitutions. In general, substitutions are not allowed
<br />1.5. Sequencing:
<br />1.5.1 Notify General Contractor, or any others, of all required chases, sleeves and
<br />openings required so that the work can be accomplished without delay. Provide
<br />necessary sleeves, etc., to be installed. Otherwise, Electrical Sub -Contractor
<br />shall pay for appropriate trades to perform cutting and patching.
<br />1.5.2 Joists, girders, beams, columns or reinforcing steel shall not be cut.
<br />1.5.3 Where construction necessitates the routing of conduit through structural
<br />members, fuming or under footings, permission to make such installation shall
<br />first be obtained from the Structural Engineer.
<br />1.6. Temporary Operation:
<br />1.6.1 The Owner may require operation of parts or all of the installation prior to
<br />Final Acceptance.
<br />1.6.2 Cost of utilities for such operation shall be paid by the Contractor. This
<br />operation does not constitute acceptance of the Contractor's Work.
<br />1.6.3 All electricity used for construction shall be paid for by the General Contractor.
<br />Furnish and install temporary electrical connection and meter for construction
<br />purposes. Remove temporary service when use is no longer required. Clean
<br />up and landscape as required.
<br />1.7. Emergency Repairs: The Owner reserves the right to make emergency repairs as
<br />required to keep equipment in operation without voiding the Contractor's guarantee
<br />nor relieving the Contractor of his responsibilities during the guarantee period.
<br />1.8. Operating Instructions and Service Manual:
<br />1.8.1 Provide two (2) neatly bound copies of maintenance and instructions book,
<br />parts lists pertaining to all equipment furnished.
<br />1.8.2 Each section shall be indexed and include parts lists, instruction books,
<br />suppliers' phone numbers and addresses, and individual equipment guarantees
<br />all in separate sections.
<br />1.8.3 Representatives of the Owner shall be instructed by the Contractor as to
<br />complete care and operation of the electrical system.. Inform the Engineer in
<br />writing as to the persons who received the instructions and the date that this
<br />was done.
<br />2. Products:
<br />2.1. Materials:
<br />2.1.1 All materials shall he new, of the best quality.
<br />2.1.2 All similar materials such as switches, panelboards, starters, contactors, fuses,
<br />circuit breakers, junction boxes, and other classes of equipment shall be of the
<br />same type and manufacturer.
<br />2.1.3 All equipment and materials shall be furnished in strict accordance with the
<br />equipment schedule and Specification requirements.
<br />2.2. Panelboards
<br />2.2.1 The panelboards shall be dead -front, totally enclosed, with locking doors, with
<br />quick -lab ambient corrected bolt -in type circuit breakers in one, two or three
<br />pole common trip units as noted on the Drawings, UL approved. The
<br />panelboards shall be 3 phase, 4 wire, solid neutral, ground buss, voltage and
<br />number of poles as noted on the Drawings. Panelboards shall have copper
<br />bussing. The circuits shall be connected to individual poles of the panel exactly
<br />as shown on the Drawings, and the panel shall be provided with a typewritten
<br />directory.
<br />2.2.2 All panels shall be factory assembled.
<br />2.2.3 Ground fault circuit in
<br />terrupters shall be provided on each circuit as required
<br />by the NEC or where specified on the Drawings.
<br />2.2.4 Provide all panels sized as noted on the Drawings or as required.
<br />2.2.5 Circuit breakers supplying High Intensity Discharge (HID) shall be equipped
<br />with HID compensated breakers.
<br />2.2.6 Equipment ground bus and neutral bus to be copper with screw type lugs.
<br />2.2.7 All panels noted on drawings with isolated ground circuits shall have a copper
<br />isolated ground bus in addition to equipment ground bus.
<br />2.2.8 Acceptable Manufacturers:
<br />G.E
<br />Square - D
<br />ITE. Div. of Siemens -Allis
<br />2.3. Service and Switchboard
<br />2.3.1 Secondary service entrance shall be as indicated on the Drawings. and shall be:
<br />2.3.1.1 Pad mounted transformer
<br />2.3.1.2 Coordinate Publix drawings with site electrical drawings. Conflicts
<br />are to be brought to the Engineer for clarification/resolution.
<br />2.3.2 Verify method of service with local utility company and obtain written
<br />approval from Publix Representative before commencement of work.
<br />2.3.3 Obtain all utility requirements for commercial service installation. Electrial
<br />Contractor must provide all requirements of the utility for a complete and
<br />operational system.
<br />2.3.4 System shall be grounded in conformance with NEC. and as shown on
<br />Drawings.
<br />2.3.5 All switchgear and panels shall be sized as noted on the Drawings or as
<br />required
<br />G.E.
<br />Square - D
<br />ITE Div. of Siemens -Allis,
<br />2.4. Main Switchboard
<br />2.4.1 General: Furnish and install the service entrance distribution switchboard as
<br />herein specified and shown on the Drawings.
<br />2.4.2 The switchboard shall meet Underwriters' Laboratories enclosure requirements
<br />and be furnished with an Underwriters' Laboratories label
<br />2.4.3 Construction: Square D Busstack construction or approved equal.
<br />2.4.4 Enclosure Construction
<br />2.4.4.1 The switchboard framework shall consist of steel channels welded or
<br />bolted to the frame to rigidly support the entire shipping section for
<br />moving on rollers and floor mounting. The framework is to be
<br />formed, code gauge steel, rigidly welded and bolted together to
<br />support all cover plates, bussing and component devices during
<br />shipment and installation.
<br />2.4.4.2 Each switchboard section shall have an open bottom and individual
<br />removable top plate for installation and termination of conduit. top
<br />and bottom Conduit areas are to be clearly shown and dimensioned on
<br />the Shop Drawings. Switchboards are to be front access only.The
<br />wireway front covers are to be hinged to permit access to the branch
<br />switch load side terminals without removing the covers. All enclosure
<br />plates shall be screw removable and small enough for easy handling
<br />by one man. The paint finish shall be gray enamel over a rust -
<br />inhibiting phosphate primer.
<br />2.4.5 Bussing:
<br />2.4.5.1 The switchboard bussing shall be plated and of sufficient cross -
<br />sectional area to continuously conduct amperage as indicated on
<br />Drawings with a maximum average temperature rise of 50 degrees c.
<br />above an ambient temperature of 25 degrees c.
<br />2.4.5.2 The buss shall be aluminum with 100% neutral with an integrated
<br />equipment rating of 100,000 amps (sym) A.I.C. at 240V, 65,000 amps
<br />(sym) A.I.C. at 48OV.
<br />2.4.5.3 The buss shall extend the full length of the available feeder area.
<br />2.4.6 Withstand Rating,
<br />2.4.6.1 The switchboard, as a complete unit, shall be given a single withstand
<br />short circuit current rating by the manufacturer. The withstand short
<br />circuit current rating shall certify that all equipment is cap_ able of
<br />withstanding the stress of a fault equal to the interrupting rating of the
<br />least overcurrent protective device contained therein. Such rating shall
<br />be established by actual tests by the manufacturer on equipment
<br />constructed similarly to the subject switchboard This test data shall be
<br />available and shall be furnished to the Engineer, if requested, with or
<br />before the submittal of Approval Drawings.
<br />2.4.6.2 The complete unit shall have interrupting rating of not less than
<br />100,000 amps Tins symmetrical at 240 volts,65000 amps RMS
<br />symmetrical at 48OV.
<br />2.4.6.3 All devices in the switchboard to be fully rated . Series rating is
<br />unacceptable.
<br />2.4.7 Main Switch (Two-step stored energy electronic trip molded case circuit
<br />breaker):
<br />2.4.7.1 Individually fixed mounted through contact type, equipped with an electric
<br />trip device for remote shunt trip operation.
<br />2.4.7.2 Circuit breakers shall have power terminals to accomodate either cable or
<br />bolted buss connections.
<br />2.4.7.3 Circuit protective devices shall be two-step stored energy type circuit breaker,
<br />UL listed for 100% continuous current when applied in QED switchboards.
<br />Sensor ampere ratings shall be as shown on the drawings or as otherwise
<br />indicated.
<br />2.4.7.4 Provide a fixed instantaneous (High Level Selective Override) circuit on
<br />breaker(s). The circuit shall have a defeatable instantaneous adjustment to
<br />allow the breaker to remain closed for up to 30 cycles during overcurrents
<br />below the rnis symmetrical short in withstand ratings. The circuit shall trip
<br />instantaneously when current levels exceed applicable withstand ratings.
<br />2.4.7.5 Circuit breakers shall be factory sealed and shall have a date code on its face.
<br />Poles shall be labeled with respective phase designs.
<br />2.4.7.6 Breaker faceplate shall indicate reated ampacity. Breaker faceplate shall
<br />indicate UL and EEC certification standards with applicable voltage systems
<br />and corresponding AIC ratings.
<br />2.4.7.7 Each circuit breaker shall be equipped with a push -to -trip button to operate
<br />the trip mechanism mechanically.
<br />2.4.7.8 Provide local control push buttons to OPEN and CLOSE circuit breaker.
<br />Color coded visual indication of contact position (OPEN or CLOSED) shall
<br />be provided on the front of the breaker. Provide for local manual charging
<br />following CLOSE operation, with color coded visual indicatin of charging
<br />status. Visual indicator shall indicate CHARGED only when closing springs
<br />are completely charged.
<br />2.4.8 The main switch shall be as manufactured by Square "D" or equal as approved
<br />by Publix Engineer 100% rated at specified amps - no substitutes.
<br />2.4.9 Bus Duct: (When Used)
<br />2.4.9.1 Service entrance bus duct shall be amps as shown on Drawings, 3
<br />phase, full neutral, suitable for 120/209 volts service, inside -outside
<br />location.
<br />2.4.9.2 The bus duct shall be complete with all necessary elbows, transformer
<br />taps, fire stops, wall flange for fittings and supports to provide a
<br />satisfactory installation as indicated on the Drawings.
<br />2.4.9.3 The bus duct shall be of the same manufacturer as the main
<br />switchboard.
<br />2.4.9.4 The bus duct shall have the same interrupting rating as the main
<br />switchboard
<br />2.4.9.5 Support for bus duct by General Contractor.
<br />2.4.10 Fusible Switches:
<br />2.4.10. I The fusible switches shall be quick -make, quick -break and suitable for
<br />use on the services described by the size shown on the associated
<br />Drawings. The units shall be listed and approved by Underwriters'
<br />Laboratories for heavy duty entrance use and where applicable, shall
<br />be dual horsepower rated for both standard one-time or dual -element
<br />fuses. The fusible switches shall be group mounted in panel -type
<br />construction. Each switch shall be equipped with Class 'R' rejection
<br />type fuse clips per Bussman or Littlefuse KTN-R, Class "R" type.
<br />2.4.10.2 Each switch is to be enclosed in a separate steel enclosure. The
<br />enclosure shall employ a hinged cover for access to the fuses which
<br />shall be interlocked with the operating handle to prevent opening the
<br />cover when the switch is in the on position. This interlock shall be
<br />constructed so that it can be released with a standard electrician's tool
<br />for testing fuses without interrupting service. The units shall have
<br />padlocking provisions in the offposition and the operating handle
<br />position shall give positive switch position indication, i.e. horizontal
<br />oft; diagonal on. Switches shall pass industry standard I2T
<br />withstandability tests and fuse race tests as described elsewhere in the
<br />Specifications.
<br />2.4.10.3 All fusing -as manufactured by Bussman or Littlefuse; dual -element
<br />and current limiting as shown on the Drawings.
<br />2.5. Contactors
<br />2.5.1 Contactors shall be manufactured by Square'D', Siemens, or General Electric;
<br />or others as approved by Publix in writing specifically for this project.
<br />P
<br />ub ix®
<br />S U P E R M A R K E T S
<br />CORPORATE OFFICES
<br />FACILITIES DESIGN
<br />BOX 407, LAKELAND, FL 33802
<br />(863) 680.5295
<br />PHYSICAL ADDRESS:
<br />3300 AIRPORT RD., LAKELAND, FL 33811
<br />PUBLIX FACILITIES
<br />DESIGN DEPARTMENT
<br />DAVID TAULBEE, AIA
<br />ARCHITECT-FL.REG.91318
<br />DAVID RUBIN, AIA
<br />ARCHITECT - FL. REG.92557
<br />GA. REG.1 1881
<br />SC. REG. 7477
<br />AL. REG.623A
<br />JOHN W. KITCHENS, PE
<br />CIVIL/STRUCTURAL- FL_ REG. A5277
<br />GA. REG. 020251
<br />SC. REG.16340
<br />AL. REG. 20382
<br />TN. REG. 101507
<br />PAUL C. HARMAN, PE
<br />STRUCTURAL - FL. REG. 5195P
<br />GA. REG. 27740
<br />SC. REG.21754
<br />AL. REG.24905
<br />TN.REG.107882
<br />JOHN J. CARAMALIS, PE
<br />MECHANICAL- FL. REG. A3889
<br />GA. REG. 021246
<br />SC. REG.16521
<br />AL. REG.20581
<br />TN.REG.108507
<br />ANTHONY CLEMENTI, PE
<br />MECHANICAL- FL. REG. 54781
<br />GA. REG.31882
<br />SC.REG.25591
<br />AL. REG.2SA69
<br />TN. REG. 111382
<br />RAYMOND J. SIRIANNI, PE
<br />ELECTRICAL- FL. REG. 5AO85
<br />GA. REG. 025636
<br />SC. REG. 19743
<br />AL. REG.23065
<br />TN.RE-G.108038
<br />NORMAN MEIER, PE
<br />ELECTRICAL - FL. REG. 59422
<br />GA. REG. 31492
<br />SC. REG.25290
<br />AL. REG. 28079
<br />© COPYRIGHT 2008
<br />PUBLIX SUPER MARKETS, INC.
<br />THESE CONSTRUCTION DOCUMENTS ARE THE
<br />PROPERTY OF PUBLIX SUPER MARKETS, INC. AND
<br />ARE NOT TO BE COPIED OR REUSED FOR ANY
<br />SPECIFIC BUILDING WITHOUT WRITTEN PERMISSION.
<br />THESE DRAWINGS SHALL NOT BE DUPLICATED
<br />WITHOUT PRIOR WRITTEN PERMISSION OF
<br />PUBLIX SUPER MARKETS, INC_
<br />THE DESIGN INDICATED IN THESE CONSTRUCTION
<br />DOCUMENTS DOES, TO THE BEST OF MY KNOWLEDGI
<br />INFORMATION, AND BELIEF, COMPLY WITH THE
<br />APPLICABLE MINIMUM BUILDING CODES
<br />PLOT DATE:
<br />10 JAN 08
<br />REVISION DATA:
<br />#1245 (REPL. #0390)
<br />ZEPHYR COMMONS
<br />PRETTY POND RD.
<br />& HWY. 301
<br />ZEPHYRHILLS, PASCO CO.,
<br />FLORIDA
<br />5,4•,4
<br />DRAWING TITLE:
<br />t Version 07.2
<br />
|