Laserfiche WebLink
3.10.2 Comply with local health department regulations. <br />3.10.3 Flush with clean, potable water until water runs clear. <br />3.10.4 Fill system with with chlorine solution containing at least 50 ppm of chlorine. <br />Allow to stand for at least 24 hours. <br />3.10.5 Purge system of chlorine solution before putting into service. <br />3.11. Inspection <br />3.11.1 Notify Inspector as required by local authority when all work is completely <br />installed and tested leak -tight. <br />3.11.2 Do not conceal piping or fixtures until approval has been obtained from <br />inspector. <br />3.12. Cleaning Equipment and Premises: <br />3.12.1 Thoroughly clean all parts of fixtures and equipment. exposed parts which are <br />to be painted shall be thoroughly cleaned of foreign matter with grease, oil, <br />soldering flux, etc. removed <br />3.12.2 Exposed metal work shall be carefully brushed down with steel brushes to <br />remove rust and other spots and touched up with primer. <br />End of Section 22 40 00 <br />Section 23 70 00 <br />Central HVAC Equipment <br />1. General <br />1.1. Summary <br />1.1.1 Provide all materials and equipment and perform all labor required to install <br />HVAC systems complete as indicated, as required by code, and as specified <br />herein. All sizes, etc. are Publix minimum and if local code requirements are <br />higher, the work shall be bid and installed accordingly. <br />1.1.1.1 Obtain and pay for all permits, bonds, inspection. <br />1.1.1.2 Provide roof top and split HVAC systems or install systems provided <br />by Publix as described below. <br />1.1.1.3 All A/C curbs set for drying -in by Roofer. <br />1.1.1.4 All roof mounted fans will be furnished by Publix and installed by <br />HVAC Contractor. Curbs will be furnished by Publix for installation <br />by Roofer. <br />1.1.1.5 Provide hurricane brackets and other supports required to secure units <br />to structure for wind and seismic conditions. <br />Seismic: Seismic hazard level as designated by Authority Having <br />Jurisdiction. <br />Hurricane: FM 1-90 or higher if designated by Authority Having <br />Jurisdiction. <br />1.1.1.6 Provide sheet metal duct systems as indicated on Drawings and <br />described in Specifications. <br />1.1.1.7 Provide exhaust ducts between the cooking hoods and the roof <br />mounted exhaust fans. <br />1.1.1.$ Provide double -wall metal gas vents. <br />1.1.1.9 Provide all other materials and services required for installation <br />described in Contract Documents. <br />1.1.2 HVAC Equipment: <br />1.1.2.1 Publix will provide equipment delivered to the site of Construction. <br />Coordinate delivery schedule with construction progress. Provide all <br />labor, equipment, materials, and services required for installation and <br />satisfactory completion of HVAC work. <br />1.1.2.2 In addition to above, provide equipment, delivery, required staging <br />and storage, and all other services required to complete the Work. <br />1.1.3 Coordinate work with work of others. Notify concerned parties before <br />proceeding with work that will affect them. <br />1.2. Definitions: Explanation and precedence of Documents: <br />1.2.1 For purposes of clarity and legibility, HVAC drawings are essentially <br />diagrammatic and, although size and location of equipment are drawn to scale <br />wherever possible, Contractor shall make use of all Contract Documents. <br />1.2.2 Although the locations of the equipment and ductwork may be shown on the <br />Drawings in certain positions, the Contractor shall be guided by the <br />architectural details and conditions existing at the job, correlating this work <br />with that of others. <br />1.2.3 The Drawings indicate size, connection points and routes of ducts and <br />equipment. It is not intended, however, that all offsets, rises and drops are <br />shown. Install all items as required to fit structure, avoid obstructions, and <br />retain clearance, headroom, openings and passageways. <br />1.2.4 Remodels: Carefully examine all existing conditions, existing work in place <br />and premises and compare the Drawings with the existing conditions. <br />Submittal of bid indicates that the Contractor has examined the Site and <br />Drawings and has included all required work in his bid. No allowances will be <br />made for error resulting from Contractor's failure to visit job sites and to <br />review Drawings. <br />1.2.5 Conflicts, discrepancies, interferences and omissions in Documents shall be <br />brought to the attention of the Architect for clarification prior to <br />commencement of work. <br />1.3. Submittals: <br />1.3.1 Submit LOIs in accordance with Section 01 33 00 Submittal Procedures. <br />1.3.2 Within 30 days of Contract Commencement (Authorization to Proceed), submit <br />the following shop drawings and cut sheets for Publix Engineer's approval: <br />Cooling Equipment <br />Air Handling Equipment <br />Heating Equipment <br />Air Distribution <br />Valves, Gauges, Specialties, Thermometers, Misc. <br />Insulation <br />Round and Oval Duct - submittals and shop drawings <br />All submittal data shall have rough -in dimensions, connection sizes, <br />any special installation requirements, certified performance data and <br />horsepower, voltage and phase for all equipment. <br />Equipment, fixtures and trim with cuts including rough -in <br />dimensions. <br />Other items required to complete the work <br />1.3.3 Submit four identical bound copies of all items. Arrange categories in order <br />listed above. <br />1.3.4 Literature for the above shall have rough -in dimensions, connection sizes, and <br />special installation requirements. <br />1.3.5 Project Record Drawings: Comply with Section 01 78 39. <br />1.4. Quality: <br />1.4.1 Subcontractor: <br />1.4.1.1 The HVAC Subcontractor shall be a reputable firm regularly engaged <br />in this type of work, employing skilled workmen, and with proper <br />equipment. <br />1.4.1.2 Upon request Subcontractor shall show evidence of at least two <br />similar jobs, of comparable size and character, installed and operating <br />within the previous two years prior to Bid Opening. <br />1.4.1.3 Publix reserves the right to refuse any Subcontractor with or without <br />cause. <br />1.4.2 Personnel: <br />1.4.2.1 Employ an experienced Superintendent to oversee all operation. <br />1.4.2.2 Work shall not proceed without adequate supervision present at all <br />times. <br />1.4.2.3 Work shall be accomplished by workers certified in their trade as <br />masters, journeymen, and apprentices in accordance with regulations <br />of the governing authority or customary practice. Utilize workers with <br />skills in proportion to complexity of tasks required. <br />1.4.2.4 Publix reserves the right to reject personnel with or without cause. <br />1.4.3 Quality standards: Work will be judged in comparison to work of similar types. <br />Substandard construction as judged by Publix Representative will not be <br />accepted. <br />1.4.4 Regulations: Comply with applicable provisions of the following codes (latest <br />version adopted by governing agencies): <br />National Fire Protection Association (NFPA) <br />Local Building Code <br />ASME Code for Un-Fired Pressure Vessels <br />ASHRAE Code for Refrigeration Apparatus <br />Safety Code for Mechanical Refrigeration. <br />National Electric Code/State Mechanical Code. <br />OSHA - For construction <br />Other applicable laws and regulations. <br />1.4.5 Participate in the pre -construction conference. <br />1.5. Sequencing: <br />1.5.1 Notify General Contractor, or any others, of all chases, sleeves and openings <br />required so that the work can be accomplished without delay. Provide <br />necessary sleeves, etc., to be installed. Otherwise, HVAC Sub -Contractor <br />shall pay for appropriate trades to perform cutting and patching. <br />1.5.2 Joists, girders, beams, columns or reinforcing steel shall not be cut. <br />1.5.3 Where construction necessitates the routing of ducts or piping through <br />structural members, or framing, permission to make such installation shall first <br />be obtained from the Publix Field Representative <br />1.6. Temporary Operation: The Owner may require operation of part or all of the <br />installation prior to Final Acceptance. <br />1.7. After acceptance of the Work, the Owner reserves the right to make emergency <br />repairs as required to keep equipment in operation without voiding the Contractor's <br />guarantee nor relieving the Contractor of his responsibilities during the guarantee <br />period. <br />1.8. Operating Instructions and Service Manual: <br />1.8.1 Provide two neatly bound copies of maintenance and instructions book, parts <br />lists pertaining to all equipment furnished. <br />1.9.2 Each section shall be indexed and include parts lists, instruction books, <br />suppliers' phone numbers and addresses, and individual equipment guarantees <br />all in separate sections. <br />1.8.3 Representatives of the Owner shall be instructed by the Contractor as to <br />complete care and operation of the HVAC system. Inform the Architect in <br />writing as to the persons who received the instructions and the date that this <br />was done. <br />1.9. Warranty: <br />1.9.1 Units shall have a manufacturer's standard one-year warranty against all <br />defects. <br />1.9.2 Provide industry standard five-year compressor replacement warranty. <br />2. Products <br />2. 1. General: All equipment and materials shall be furnished in strict accordance with the <br />equipment schedule and specifications requirements. <br />2.2. Nameplates <br />2.2.1 Nameplates shall not be painted. <br />2.2.2 All switches, starters, and major pieces of equipment shall be identified with <br />black plastic nameplates with engraved white letters. <br />2.3. Packaged Rooftop Air Conditioners: See Drawings. <br />2.4. Controls: <br />2.4.1 An Environmental Control Panel will be furnished and installed by Publix to <br />control all AC units. Conduit, line voltage circuits, interlocks, etc., shall be <br />furnished and installed by the Contractor, as shown on drawings. <br />2.5. Filter Media: Full two inch thick dual density polyester material. <br />2.6. Air Distribution <br />2.6.1 General: <br />2.6.1.1 All air distribution shall be supplied by manufacturers whose testing <br />procedures are in accordance with ASHRAE Standard 70-1991. <br />2.6.1.2 Furnish and install, unless otherwise noted, all grilles, registers, and <br />outlets at the location and of the type and size shown on the Drawings. <br />Install foam rubber gaskets behind flanges of all grilles and registers <br />to prevent leakage and streaking. Adjust air volumes and set <br />deflection in accordance with Drawings. <br />2.6.2 Return Air Grilles and Registers: <br />2.6.2.1 All grilles shall be suitable for smooth surface mounting. <br />2.6.2.2 Coordinate installation of door grilles with door installation. <br />2.6.2.3 Where indicated, provide opposed blade dampers <br />2.6.2.4 Approved manufacturers: <br />Airguide <br />Aeemostat <br />Bailey and Tuttle <br />Lindab <br />Metal Industries <br />Nailor Industries <br />Price <br />Titus <br />2.6.3 Outlets: <br />2.6.3.1 All supply outlets shall be aluminum (or alurnini�ed steel where <br />required when part of rated roof -ceiling assembly) and products of a <br />single manufacturer. Return air grilles, outlets, registers and door <br />grilles shall be of etched aluminum with acrylic finish and as <br />indicated. <br />2.6.3.2 Provide steel grills and fire dampers, radiation dampers as indicated <br />on the Drawings and in accordance with U.L. roof -ceiling assembly <br />design where indicated <br />1.6.3.3 Provide UL listed lay -in ceiling outlets complete with radiation <br />damper and thermal blanket. Approved Manufacturer: <br />Nailor Industries <br />Other manufacturer as approved by Publix Engineer. <br />2.6.3.4 Variable volume type shall be factory insulated, complete with <br />controls, damper, change over thermostat as indicated on the <br />Drawings. Approved Manufacturer: <br />Metal Industries <br />Price <br />2.6.4 Louvers: Aluminum, drainable with bird screen, AMCA certified. <br />Greenheek ESD-403 <br />Ruskin #ELF-375D <br />Louvers and Dampers Inc. IEL-4-104, ALL Series <br />2.7. Sheet Metal Ductwork: <br />2.7.1 Galvanized Ductwork: All duct and fittings shall be manufactured from <br />galvanized steel of lock forming quality per ASTM A-527. The zinc coating <br />shall be minimum G90 (1,25 oz. 1 sq. ft.) per ASTM A924. Seams on fittings <br />shall be welded or tacked & sealed. Individual fittings are required, <br />manifolding is not permitted. Comply with SMACNA requirements for duct <br />construction for ventilation and air conditioning systems. <br />2.7.2 Stainless steel ductwork: ASTM A480, Type 316 sheet -form with #4 finish for <br />surfaces exposed to view; Type 304sheet-form, with #1 finish for concealed <br />ducts. <br />2.7.3 Rectangular Duct Work: <br />2.7.3.1 Panels shall be cross broken. (Beaded duct not acceptable) <br />2.7.3.2 Longitudinal standing seams may be used <br />2.7.3.3 Comer closures are not required <br />2.7.3.4 Hangers shall be band iron <br />2.7.3.5 Elbows shall be as drawn. <br />2.7.3.6 Where indicated vaned elbows shall be double vaned. <br />2.7.3.7 Connections shall be either 90 degree straight with Titus Model AG- <br />45 control grid or radius tap -in. <br />2.7.3.8 Inspection plates and test holes are not required. <br />2.7.3.9 Fresh air intake shall be square or rectangular standard <br />2.7.3.10 Access doors shall be insulated and removable. <br />2.7.3.11 Sealer on all joints: Sealants shall have a Flamespread Rating of 25 or <br />less, Smoke Developed Rating of less than 50 to comply with NFPA <br />90A. . <br />Hardcast Iron Grip Water -Based Duct Sealant 601. <br />United McGill, United Duct Sealer. <br />Precision Adhesives PA-2084A Duct Sealant. <br />Fosters 32-19 <br />2.7.4 Round and Flat Oval Duct: <br />2.7.4.1 All exposed ductwork shall be spiral lockseam construction standard <br />SMACNA gauges tested to + 1OWG. Longitudinal seam duct is <br />prohibited. Comply fully with SMACNA recommendations. <br />2.7.4.2 Where ductwork is exposed to view, provide G90 galvanized metal <br />suitable for painting. <br />2.7.4.3 Field Joints in Exposed Ductwork: Lindab Inc. SPIRO safe duct <br />system, or Ductmate industries Spirahnate Round Duct Connector and <br />"Ovalmate Flat Oval Duct Connector" or approved equals. <br />2.7.4.4 Substitution of sizes by cross section area or equivalent round formula <br />must have written prior approval. <br />2.7.4.5 Ductwork assemblies shall a the type tested to 10" WG (min.) by UL <br />181. <br />2.7.4.6 Approved Duct Manufacturers: <br />Eastern Sheet Metal <br />Lindab, Inc/R. V. Money, Inc. - St. Petersburg, Florida <br />United McGill Corp. <br />2.7.4.7 Gauges (Single Wall Ductwork): <br />Diameter Gauge Major Dim Gauge <br />Round Duct Flat -Oval Duct <br />3" - 14" 26 Ga. 3"-24" 24 Ga <br />15" - 26" 24 Ga. 25" - 48" 22 Ga. <br />28" - 36" 22 Ga. 49" - 70" 20 Ga. <br />38" - Up 20 Ga. 71" - Up 18 Ga <br />Round Fittings Flat -Oval Fittings <br />3" - 14" 24 Ga. 3"-36" 20 Ga <br />15" - 26" 22 Ga. 37' - 60" 18 Ga. <br />28" - 50" 20 Ga. 61" - Up 16 Ga. <br />2.7.4.8 Doublewall Ductwork <br />2.7.4.8.1 Double wall duct and fittings shall consist of a perforated <br />inner liner, a 1 inch, 1.501b./ft3 (unless otherwise specified) <br />layer of fiber glass insulation and a solid outer pressure shell. <br />A retaining fabric shall be wrapped between the perforated <br />inner duct and the fiber glass insulation. <br />2.7.4.8.2 All fitting ends from 5" to 24" O.D, shall have rolled edges <br />for added strength and rigidity during installation and <br />shipping.. <br />. 2.7.4.9.3 Double wall to single wall transitions shall be provided <br />where insulated duct connects to non -insulated, single wall <br />duct. Transitions also act as insulation ends reducing the <br />double wall outer shell diameter to the inner shell diameter. <br />2.7.4.8.4 Gauges (Double Wall Ductwork): <br />Round Duct Flat -Oval <br />Dia. Inner Outer Maj Ax. Inner Outer <br />3 - 12" 26 26 Ga. 3 - 22" 24 24 Ga. <br />13 - 24"26 24 Ga. 23 - 34" 24 22 Ga. <br />25 - 34"26 22 Ga. 35 - 46" 24 22 Ga. <br />35 - 50"24 20 Ga. 47 - 58" 22 20 Ga. <br />59 - 68"22 20 Ga. <br />69 - UP 20 18 Ga. <br />Round Fittings Flat -Oval Fittings <br />Dia. Inner Outer Ma. Ax. Inner Outer <br />3 - 12" 24 24 Ga. 3 - 22" 24 20 Ga <br />13 - 24"24 22 Ga 23 - 34" 24 20 Ga <br />25 - 34"24 20 Ga. 35 - 46" 22 18 Ga. <br />35 - 50"22 20 Ga. 47 - 58" 22 18 Ga. <br />59 - 68"20 16 Ga. <br />69 - UP 20 16 Ga. <br />2.7.4.9 Duct Hangers - 8' 0" C/C max distance. <br />2.8. Flexible Duct: <br />2.8.1 Factory insulated on aluminum liner, UL listed Class 1 Air Duct, STD. 181 and <br />NFPA Bulletin 90A, with F/S kraft metallized mylar vapor barrier jacket. <br />2.8.2 Entire assembly shall be UL-181, class llisted, and meet NFPA 90A, with <br />flamespread rating less than 25, and smoke developed 50 or less. <br />2.8.3 Minimum working pressure 6" w.g. <br />2.8.4 Maximum length-10 feet. <br />2.8.5 Supports shall be spaced maximum 3 feet, support band min. 2 in. wide: Use <br />Wiremold duct collars and galvanized strap clamps or equal as approved by <br />Engineer. <br />2.8.6 Spin in fittings shall be Metal Masters Model MS 1-6G or equal as approved by <br />Engineer. <br />2.8.7 Approved products: <br />Flexinaster TL -M <br />Insulated Metalflex V-250-LTL <br />Thermo -Fin Type A-300 <br />2.9. Duct Leakage Loss: <br />2.9.1 Each system shall meet SMACNA and ASHRAE leakage class 3. This leakage <br />will be determined by the test and balance consultant. <br />2.9.2 Loss exceeding leakage class 3 requirements shall be corrected by the HVAC <br />Contractor prior to acceptance by Publix. <br />2.10. Duct Hangers: <br />2.10.1 Duct hangers shall be threaded rods or metal straps with metal bands or angles. <br />See details in the mechanical drawings. <br />2.10.2 Alternate system: Load -rated cable suspension system. The system shall have <br />a specified manufacturer's safe working load (SWL) and supplementary safety <br />factor of at least five times the SWL. The system shall be verified by <br />SMACNA Testing & Research and shall be in compliance with SMACNA <br />Duct Construction Standards guidelines, 1995 ed., ch. 4. <br />2.10.2.1 Approved System: Gripple Hang -Fast. <br />2.11. Grease Hoods: <br />2.11.1 Install UL classified range hoods as indicated on the Drawings and in <br />. accordance with NFPA 96. Hoods shall be 18 gage, 304 stainless steel, liquid <br />tight welds, grease extractors, vapor proof lights with factory pre -piped fire <br />suppressor. Manufactured by greenheck, furnished by Publix <br />2.12. Suppression <br />2.12.1 Provide fire protection system (specified Section 15355-Automatic Fire <br />Suppression System) for all grease -laden air removal hoods (Designated GH-). <br />Fire dampers shall be at the supply air inlets. <br />2.13. Grease Hood Exhaust Duct <br />2.13.1 Provide welded 16 ga. galvanized steel exhaust duct as indicated on Drawings. <br />2.13.2 Access door shall be U.L. listed <br />2.14. Oven Gas Flues <br />2.14.1 Provide a complete insulated double wall gas venting system (U.L. Listed <br />#103), 1400 degrees F. rating and draft hood for the gas fired equipment and <br />bakery ovens where indicated. <br />2.14.2 Thimbles, flashing, rain cap as required <br />2.14.3 Air Intake: Single wall construction. <br />2.15. Devices and other miscellaneous items: <br />2.15.1 Dampers: Opposed blade, butterfly type, or splitter, all factory made as <br />indicated. Each shall have a locking quadrant accessible for adjustment, with <br />extension sleeve for duct wrap insulation. <br />2.15.2 Air Turning Device for Registers: Titus model AG-45 or similar device as <br />approved by Architect. <br />2.15.3 Radiation Dampers: UL listed and installed where indicated <br />2.15.4 Piping System for Condensate: Schedule 40 PVC. <br />2.16. Insulation: <br />2.16.1 Concealed HVAC Ductwork: <br />2.16.1.1 Insulate externally with foil scrim kraft (FSK) fiberglass blanket type <br />insulation, ASTM C 1136, thickness and R value as indicated on the <br />Drawings. <br />2.16.1.2 Comply with ASHRAE 90.1 and energy code requirements of the <br />AHJ. <br />2.16.1.3 Materials shall have flamespread less than 25, and smoke developed <br />less than 50. <br />2.16.1.4 Approved manufacturers: <br />Johns Manville . <br />CetainTeed <br />Owens Corning <br />Knauf <br />2.16.1.5 Neatly cut and fit insulation to the duct surface with all- duct joints <br />overlapped 2" minimum, secured with outward -clinch staples 4" on <br />center each way. <br />2.16.1.6 On ducts 24" or greater in width the insulation on the underside of the <br />duct shall be secured to the sheet metal surface with Foster'S #85-20, <br />or equal, adhesive, and secured mechanically with sheet metal screws <br />- and caps, or mechanical fasteners adhered to the duct on not more <br />than 18" centers each way. <br />2.16.1.7 All transverse and longitudinal seams, and penetrations of the vapor <br />barrier facing shall be covered with SMACNA rated foil backed tape <br />applied in and sealed with Foster's #30-80 or #30-65, or equal, vapor <br />barrier mastic. <br />2.16.2 Where indicated, exposed double wall HVAC duct work shall be internally <br />insulated with fiberglass. <br />2.16.2.1 Insulate internally with fiberglass rigid board type insulation and <br />retaining fabric, ASTM C1136, thickness and R value as indicated on <br />the Drawings. <br />2.16.2.2 Materials shall have flamespread less than 25, and smoke developed <br />less than 50. <br />2.16.2.3 Approved manufacturers: <br />Johns Manville <br />CetainTeed <br />Owens Corning <br />Knauf <br />2.16.3 Fire-resistant Grease Duct Wrap <br />2.16.3.1 Alternative to 1 and 2 hour fire resistant rated gypsum shaft <br />enclosures. Product shall be a flexible, O" clearance, non -asbestos <br />system, encapsulated with a scrim re -enforced foil. no flame, no <br />smoke characteristics for the foil blanket. Install per manufacturer's <br />guidelines. <br />2.16.3.1.1 Approved manufacturers and products: <br />Vesuvius - Pyroscat Ductwrap and Pyroscat Fast R Duct Wrap <br />3M - Fire Barrier Ductwrap 15A <br />Thermal Ceramics FireMaster-FastWrap+ <br />2.16.3.2 Follow the manufacturer's guidelines for securing ductwrap, welded <br />stickpins only, banding and sealers. <br />2.17. Ductwork accessories: <br />2.17.1 Control Dampers Provide dampers with parallel blades for 2 position control, <br />or opposed blades for modulating control. <br />2.17.1. I All metal parts galvanized steel. <br />2.17.1.2 Blades: 16ga. <br />2.17.1.3 Bearings: Heavy duty molded nylon. <br />2.17.1.4 Axles: 1/2" dia. steel, 9" OC. <br />2.17.1.5 Steel Frames: <br />2.17.1.5.1 Up to 25 sq. ft.: 2"Xl/2"Xl/8" <br />2.17.1.5.2 Over 25 sq. ft.: 4"Xl 1/4"Xl6ga. <br />2.17.1.6 Acceptable Manufacturers: <br />Greenheck <br />Ruskin <br />2.17.2 Fire Dampers: <br />2.17.2.1 Fire dampers shall be rated where indicated and shall be UL 555 <br />listed. <br />2.17.2.2 All metal parts galvanized steel, dynamically tested. <br />2.17.2.3 Casings: 20 ga. <br />2.17.2.4 Blades: 24 ga. <br />2.17.2.5 Fusible Link: 160 - 165 deg. F. <br />2.17.2.6 Damper: Positive lock type with curtain type blade, positive lock in <br />closed position, with curtain 100% out of airstream. <br />2.17.2.7 Steel Frames: <br />2.17.2.7.1 Up to 25 sq. ft.: 2"Xl/2"Xl/8" <br />2.17.2.7.2 Over 25 sq. ft.: 4"Xl 1/4"Xi6ga. <br />2.17.2.8 Acceptable Manufacturers: <br />Greenheck <br />Ruskin <br />2.17.3 Duct access doors: <br />2.17.3.1 Construct of same gauge or heavier as ductwork served. Provide <br />insulated doors for insulated ductwork. Provide flush frames for un- <br />insulated ductwork, extended frames for externally insulated <br />ductwork. Provide one side hinged, other side with one handle type <br />cam latch for all doors. If space is limited for a hinged door swing, <br />then provide a two handle type cam latch door. <br />2,17.3.2 Door sizes shall accommodate to allow fire dampers and other devices <br />to be accessed for repair or reset to normal position after being <br />activated. <br />Largest Dimension of Duct Access Door Nom. Dimension <br />Up to 10" 6"X6" <br />10" to 16" 8"X8" <br />17" to 24" 12"X12" <br />25" to 36" 16"X16" <br />37" and larger 24"X16" <br />2.17.3.3 Acceptable manufacturers: <br />Greenheck <br />Ruskin <br />2.17.4 Fabricate kitchen hood ducts from 16 ga. galvanized steel sheets, 18 ga. <br />stainless stell where exposed Conform to NFPA 96. Ali joints and seams shall <br />be welded liquid tight. Provide a flange for duct at top of exhaust fan curb. <br />3. Execution: <br />3.1. General <br />3.1.1 Neatness counts. Make all joints, connections, unions, etc. with proper care to <br />insure that tight connections are made without excess material, well secured to <br />supports. <br />3. L2 Install duct with runs straight, shop formed radiuses at bends, and adequate <br />supports. <br />3.1.3 Verify all field dimensions and locations of equipment and fixtures within the <br />layout to ensure close, neat fit, with other trades work. <br />3.2. Installation: <br />3.2.1 Installation of rooftop A.C. units: <br />3.2.1.1 Publix will furnish factory fabricated steel roof curbs complete with <br />wood nailer strips. Curbs are shipped fully assembled and tapered to <br />fit roof slope. <br />3.2.1.2 Provide materials and coordination with other trades required to <br />ensure that curbs are installed properly. <br />3.2.1.3 Attach units to curbs as indicated on the Drawings. <br />3.2.1.4 Lift all A/C units with spreader bars to prevent cable damage to <br />cabinets and components. <br />3.2.1.5 Publix will accept only those units which are in new condition without . <br />dents or other damage. Scratches or paint damage are to be re -painted <br />with manufacturer's paint. <br />3.2.1.6 In the event that field repair involves the refrigeration circuit of any <br />unit, such repair is to be made by the unit manufacturer or his <br />representative. <br />3.2.1.7 Provide each unit with a PVC condensate drain trap in accordance <br />with Drawings and unit manufacturer's recommendation. <br />3.2.1.8 Piping of unit mounted heat reclaim coils) will be by Publix. <br />3.2.2 Installation of rooftop fans: <br />3.2.2.1 Publix will furnish factory fabricated steel roof curbs complete with <br />wood nailer strips. Curbs are shipped fully assembled. Slope <br />accommodation is through steel frame provided under other sections. <br />3.2.2.2 Provide materials and coordination with other trades required to <br />ensure that curbs are installed properly. <br />3.2.2.3 Attach fans to curbs as indicated on the Drawings. <br />3.3. Equipment Start -Up: <br />3.3.1 All rooftop A.C. units shall be started and adjusted for proper operation by the <br />manufacturer or his representative. No equipment shall be run prior to this <br />start-up. All units shall be made ready for start-up at the same time. <br />3.3.2 Contractor shall have qualified personnel in attendance to coordinate ductwork <br />and electrical aspects of the start-up. <br />3.4. Substantial Completion Inspection <br />3.4.1 All of the following items must be completed prior to Substantial Completion <br />Inspections. No exceptions will be made and no payment will be made until all <br />items are completed. <br />3.4.2 Cleaning Equipment and Premises: <br />3.4.2.1 Thoroughly clean all parts of the apparatus and equipment. Exposed <br />parts which are to be painted shall be thoroughly cleaned of cement, <br />plaster, and other material and all oil and grease spots shall be <br />removed. Repaint or touch up as required to make look like new. <br />Surfaces shall be carefully wiped and all cracks and comers scraped <br />out. <br />3.4.2.2 Exposed metal work shall be carefully brushed down with steel <br />brushes to remove rust and other spots and touched up with primer. <br />3.4.3 Testing and Balancing Systems <br />3.4.3.1 Publix will provide a test and balance contractor. This service will be <br />done in the presence of the HVAC Sub- Contractor, so that <br />deficiencies can be noted. <br />3.4.3.2 Comply with "Standards for Field Measurement and <br />Instrumentations" Form No. 81266 Volume One. as published by the <br />Associated Air Balance Council. <br />3.4.3.3 Submit three (3) copies of the complete test reports to the Publix <br />Refrigeration Department prior to Final Acceptance of the Project. <br />3.4.3.4 Provide sufficient time before the completion date so that testing and <br />balancing can be accomplished, and remediation made. <br />3.4.3.5 Put all HVAC Equipment into full operation and continue operation <br />during each working day of testing and balancing. <br />3.4.3.6 All dampers shall be in wide open or neutral position prior to test and <br />balance of the system. <br />3.4.3.7 Implement changes recommended by the testing and balancing <br />contractor, including pulley changes, balancing dampers and other <br />items as required to obtain proper system balance as judged by the <br />testing and balancing contractor and the Publix Architect. <br />3.4.3.8 Maintain operation of the system for a minimum of 24 hours after <br />balance has been obtained. Notify Publix Architect so that he may <br />inspect the system under operating conditions. <br />3.5. Prior to requesting a Final Inspection, submit a typed schedule or a marked up set of <br />Drawings indicating the observed velocity of each grille, register or outlet. These test <br />data shall be final readings after balancing the system. <br />3.6. Dust streaking on exposed duct systems: After 6 months, examine all exposed <br />ductwork for dust streaking. Where streaking has occurred, the causes ofthe streaking <br />shall be determined and repaired. Streaked surfaces shall be cleaned and touched up <br />to match the original finish. <br />End of Section 23 70 00 <br />Section 26 00 00 <br />Electrical <br />1. General <br />l.l. Summary <br />1.1.1 Comply with requirements of Sections O1 1100, O1 33 00, 0150 00, 0177 00, <br />01 78 39. <br />1.1.2 Provide all materials and equipment and perform all labor required to install <br />electrical systems complete as indicated, as required by code, and as specified <br />herein. <br />1.1.3 Obtain and pay for all permits, bonds, inspection. Coordinate inspections with <br />work as it progresses. <br />1.1.3.1 Provide services necessary to coordinate work with work of others. <br />Notify concerned parties before proceeding with work that will affect <br />them. <br />1.1.3.2 Provide electric service to connect with site utilities at a point outside <br />the building as shown on the Drawings. <br />1.1.3.3 Coordinate with Utilities all requirements for utility transformer and <br />Metering.Furnish and install all utility requirements for electrical service (ie. <br />transformer pad, CT compartment, meter base and pedestal) <br />1.1.3-4 Install all panelboards, and contactors at the locations shown on the Drawings <br />and specified herein. <br />1.1.3.5 All spare, empty conduit and junction boxes to have pull string. <br />1.1.3.6 Furnish and install all conduit and conductors between the load side of <br />the feeder breakers to the branch panels. <br />1.1.3.7 Furnish and install all branch circuits between the panelboards and the <br />final terminal as shown on the Drawings and specified herein. <br />1.1.3.8 Furnish and install all secondary service between the power company <br />transformer to the main switch as indicated on the Drawings. <br />L 13.9 Receive, store, install and make final electrical connections to all <br />lighting fixtures as shown on the Drawings and specified herein. <br />1.1.3.10 Furnish and install conduit and boxes only for the public address <br />system and telephone outlets. <br />1.1.3.11 Make electrical connections to the electric door operators as shown on <br />the Drawings and specified herein. <br />1.1.3.12 Make all electrical connections to equipment supplied by Publix. <br />Electrical Contractor to verify all manufacturer equipment <br />requirements prior to connection. Any conflicts or deviation in design <br />to be brought to the attention of the Engineer. <br />1.1.3.13 Make all electrical connections to refrigerated display cases and walk- <br />in boxes as shown on the Drawings and specified herein. <br />1.1.3.14 Make all electrical connections between the main switchboard and the <br />refrigeration compressors and condensing equipment as shown on the <br />Drawings and specified herein. <br />1.1.3.15 Furnish and install all motor starters, disconnect devices, conduit and <br />conductors for control and power wiring. <br />1.1.3.16 Make all electrical connections between the main switchboard and the <br />air conditioning compressors, air handling units, package units and <br />strip heaters as shown on the Drawings and specified herein. <br />1.1.3.17 Make all electrical connections between the machine rooms mounted <br />refrigeration equipment and the refrigerated display cases, walk-in <br />freezers and coolers as shown on the Drawings and specified herein. <br />1.1.3.18 Furnish and install all conduit and conductors to totally electrically <br />connect all controls as specified herein. <br />1.1.3.19 Furnish and install all electrical work required for the dry chemical <br />fire extinguisher system in the grease exhaust hoods. in compliance <br />with NFPA Bulletins #17, 496, and with local codes. <br />1.1.3.20 Furnish and install all electrical wiring devices as shown on the <br />Drawings and specified herein. <br />1.1.3.21 Furnish and install all conduit, conductors, disconnect devices and <br />flexible metal conduit to completely wire all supply and exhaust fans <br />as shown on the Drawings and specified herein. <br />1.1.3.22 The Electrical Contractor is fully responsible and liable for damaged <br />and lost materials furnished by Publix. It shall be required that he sign <br />for the materials supplied by Publix. <br />1.1.3.23 Panels for A/C and refrigeration mechanical systems, as furnished <br />pre -wired internally by others, shall be mounted and connected by the <br />Electrical Contractor. Refer to Drawings and Specifications for air <br />conditioning. <br />1.1.3.24 Furnish and install all electrical service and controls for fans installed <br />by others. <br />1.1.3.25 Furnish and install power wiring to each HVAC unit including the <br />safety disconnect switch and other required electrical devices to make <br />the unit operational as shown on the Drawings and specified herein. <br />1.1.3.26 Install emergency generator and transfer switch complete, as furnished <br />by Publix. <br />1.1.3.27 Install conduit/boxes with pull string for fire alarm and burglar alarm <br />system, as furnished by Publix per note on Electrical Drawings. <br />1.1.3.28 Install and connect air conditioning control panel, energy management <br />system, supplied by Publix. <br />1.1.3.29 Install conduit, conductors and make connections to "Publix" sign, <br />and all other facade signs and under -canopy signs (signs supplied and <br />installed by Sign Contractor). <br />1.1.3.30 Security and fire alarm systems or combined system: the Contractor <br />shall supply and install conduit, boxes, and pull strings as shown on <br />Drawings. Power supply, station controls and complete final hook-up <br />by Fire Alarm Constrictor as noted on Drawings. <br />1.1.4 Related Work by Other Contractors: <br />1.1.4.1 Setting and roofing in of all curbs and pitch pockets by Roofing <br />Contractor. (setting of A/C curb only shall be by A/C Contractor) <br />1.1.4.2 Setting ofwater heaters, ovens, kitchen equipment, gondolas, cash <br />registers, air conditioners, exhaust fans, refrigerated cases, meat room <br />equipment, facade signs and other miscellaneous equipment by others. <br />Final electrical connection by Electrical Contractor. <br />1.1.4.3 Kitchen Hood Fire Protection System by Others. <br />1.1.5 Publix reserves the right to furnish some items of electrical equipment to the <br />Electrical Contractor. If this is done the Electrical Contractor shall install the <br />equipment and deduct the cost of the equipment from his contract. Cost <br />adjustment will be made by Change Order. <br />1.1.6 All apparatus shall be installed at exact height and locations as shown on the <br />Drawings, or if not shown, at heights and locations determined by applicable <br />codes and laws. <br />1.1.7 Perform all excavation and backfill required for services, and for all conduit <br />and work inside and outside the building. Cutting of curbs, walks, concrete and <br />paving required for excavation shall be done by appropriate trade. <br />1.1.8 All store cases, coolers, and freezers will be furnished and set in place by <br />Publix. Check Equipment Drawings against Drawings in order to verify exact <br />locations. <br />1.2. Definitions: Explanation and Precedence of Documents: <br />1.2.1 For purposes of clarity and legibility, Electrical Drawings are essentially <br />diagrammatic and, although size and location o€ equipment are drawn to scale <br />wherever possible, Electrical Contractor shall make use of all Contract <br />Documents. <br />1.2.2 The Drawings indicate size, connection points and routes of conduit and <br />equipment. It is not intended, however, that all offsets, rises and drops are <br />shown. Install all items as required to fit structure, avoid obstructions, and <br />retain clearance, headroom, openings and passageways. <br />1.2.3 Remodels: Carefully examine all existing conditions, existing work in place <br />and premises and compare the drawings with the existing conditions. Submittal <br />of bid indicates that the Electrical Contractor has examined the Site and <br />Drawings and has included all required work in his bid. No allowances will be <br />made for any error resulting from Contractor's failure to visit Job Sites and to <br />review Drawings/Documents. . <br />1.2.4 Conflicts, discrepancies, interferences and omissions in Documents shall be <br />brought to the attention of the Engineer for clarification prior to <br />commencement of Work. <br />1.3. Submittals: <br />1.3.1 Submit LOI in accordance with Section 01 33 00 Submittal Procedures. <br />1.3.2 Within 30 days of Contract Commencement (Authorization to Proceed), submit <br />for Publix Engineer's approval: <br />1.3.2.1 List of materials intended for use in the Project. <br />1.3.2.2 Manufacturer's catalogue cuts of materials intended for use in the <br />Project. LOI's not acceptable. <br />1.3.2.3 Submittals to include: Switchgear, breakers, panel boards, starters, <br />disconnects, relays, walkerduct, wire channel system, conduit, wire, <br />boxes, wiring devices, receptacles, switches. <br />1.3.2.4 Copies of licenses of key personnel if requested by Publix. <br />1.3.2.5 Samples of materials if requested by Publix. <br />1.3.2.6 Other items required to complete the Work <br />1.3.3 Submit three identical bound copies of all items. Arrange categories in order <br />listed above. <br />1.3.4 All cuts for the above shall have rough -in dimensions, connection sizes, and <br />any special installation requirements. In addition, furnish motor horsepower <br />voltage and phase for all equipment. <br />1.3.5 Close Out Documents: <br />1.3.5.1 Comply with applicable provisions of Section 0178 39 Project <br />Record Documents. <br />1.3.5.2 Provide a complete set of manufacturer's warranties and warranty <br />certificates. <br />1.3.5.3 A copy of the final approval from the local building department. <br />1.4. Quality: <br />1.4.1 Subcontractor: <br />1.4.1.1 The Electrical Subcontractor shall be a reputable firm regularly <br />engaged in this type of work, employing skilled workmen, and with <br />proper equipment. <br />1.4.1.2 Upon request Subcontractor shall show evidence of at least two <br />similar jobs, of comparable size and character, installed and operating <br />within the previous two years prior to bid opening. <br />1.4.1.3 Publix reserves the right to refuse any Subcontractor with or without <br />cause. <br />1.4.2 Personnel: <br />1.4.2.1 Employ an experienced superintendent to oversee all operation. <br />1.4.2-2 Work shall not proceed without adequate supervision present at all <br />times. <br />1.4.2.3 Work shall be accomplished by workers certified in their trade as <br />masters, journeymen, and apprentices in accordance with regulations <br />of the governing authority or customary practice. Utilize workers with <br />skills in proportion to complexity of tasks required. <br />1.4.2.4 Publix reserves the right to reject personnel with or without cause. <br />1.4.3 Quality Standards <br />1.4.3.1 Work shall be accomplished to ensure safety to all personnel during <br />installation and after occupancy. <br />1.4.3.2 Work will be judged by Publix in comparison to work of similar <br />types. Substandard construction as judged by Publix Representative <br />will not be accepted. <br />1.4.3.3 Neatness counts. Make all joints, connections, unions, etc. with proper <br />care to insure that tight connections are made without excess material, <br />well secured to supports. <br />1.4.3.4 Install conduit with runs straight, accurately formed radiuses at bends, <br />and adequate supports. <br />1.4.4 Regulations: Comply with applicable provisions of the following codes (latest <br />version adopted by governing agencies): <br />National Fire Protection Association (NFPA) <br />National Electrical Code <br />Local Utility Code <br />Local Building Code <br />Safety Code for Mechanical Refrigeration. <br />Conform to governing codes, ordinances and regulations of city, <br />county and state having jurisdiction. Where local codes are not <br />applicable, conform to National Electric Code/State Electric Code <br />where Project is located. <br />OSHA - for construction <br />1.4.5 Test the entire system. The solid neutral wire shall be tested for thorough <br />grounding and all hot wiring shall be tested for shorts and grounding. <br />1.4.6 Participate in the Pre -Construction Conference. <br />1.4.7 Substitutions: Comply with Section 01 63 00 Product Options and <br />Substitutions. In general, substitutions are not allowed <br />1.5. Sequencing: <br />1.5.1 Notify General Contractor, or any others, of all required chases, sleeves and <br />openings required so that the work can be accomplished without delay. Provide <br />necessary sleeves, etc., to be installed. Otherwise, Electrical Sub -Contractor <br />shall pay for appropriate trades to perform cutting and patching. <br />1.5.2 Joists, girders, beams, columns or reinforcing steel shall not be cut. <br />1.5.3 Where construction necessitates the routing of conduit through structural <br />members, fuming or under footings, permission to make such installation shall <br />first be obtained from the Structural Engineer. <br />1.6. Temporary Operation: <br />1.6.1 The Owner may require operation of parts or all of the installation prior to <br />Final Acceptance. <br />1.6.2 Cost of utilities for such operation shall be paid by the Contractor. This <br />operation does not constitute acceptance of the Contractor's Work. <br />1.6.3 All electricity used for construction shall be paid for by the General Contractor. <br />Furnish and install temporary electrical connection and meter for construction <br />purposes. Remove temporary service when use is no longer required. Clean <br />up and landscape as required. <br />1.7. Emergency Repairs: The Owner reserves the right to make emergency repairs as <br />required to keep equipment in operation without voiding the Contractor's guarantee <br />nor relieving the Contractor of his responsibilities during the guarantee period. <br />1.8. Operating Instructions and Service Manual: <br />1.8.1 Provide two (2) neatly bound copies of maintenance and instructions book, <br />parts lists pertaining to all equipment furnished. <br />1.8.2 Each section shall be indexed and include parts lists, instruction books, <br />suppliers' phone numbers and addresses, and individual equipment guarantees <br />all in separate sections. <br />1.8.3 Representatives of the Owner shall be instructed by the Contractor as to <br />complete care and operation of the electrical system.. Inform the Engineer in <br />writing as to the persons who received the instructions and the date that this <br />was done. <br />2. Products: <br />2.1. Materials: <br />2.1.1 All materials shall he new, of the best quality. <br />2.1.2 All similar materials such as switches, panelboards, starters, contactors, fuses, <br />circuit breakers, junction boxes, and other classes of equipment shall be of the <br />same type and manufacturer. <br />2.1.3 All equipment and materials shall be furnished in strict accordance with the <br />equipment schedule and Specification requirements. <br />2.2. Panelboards <br />2.2.1 The panelboards shall be dead -front, totally enclosed, with locking doors, with <br />quick -lab ambient corrected bolt -in type circuit breakers in one, two or three <br />pole common trip units as noted on the Drawings, UL approved. The <br />panelboards shall be 3 phase, 4 wire, solid neutral, ground buss, voltage and <br />number of poles as noted on the Drawings. Panelboards shall have copper <br />bussing. The circuits shall be connected to individual poles of the panel exactly <br />as shown on the Drawings, and the panel shall be provided with a typewritten <br />directory. <br />2.2.2 All panels shall be factory assembled. <br />2.2.3 Ground fault circuit in <br />terrupters shall be provided on each circuit as required <br />by the NEC or where specified on the Drawings. <br />2.2.4 Provide all panels sized as noted on the Drawings or as required. <br />2.2.5 Circuit breakers supplying High Intensity Discharge (HID) shall be equipped <br />with HID compensated breakers. <br />2.2.6 Equipment ground bus and neutral bus to be copper with screw type lugs. <br />2.2.7 All panels noted on drawings with isolated ground circuits shall have a copper <br />isolated ground bus in addition to equipment ground bus. <br />2.2.8 Acceptable Manufacturers: <br />G.E <br />Square - D <br />ITE. Div. of Siemens -Allis <br />2.3. Service and Switchboard <br />2.3.1 Secondary service entrance shall be as indicated on the Drawings. and shall be: <br />2.3.1.1 Pad mounted transformer <br />2.3.1.2 Coordinate Publix drawings with site electrical drawings. Conflicts <br />are to be brought to the Engineer for clarification/resolution. <br />2.3.2 Verify method of service with local utility company and obtain written <br />approval from Publix Representative before commencement of work. <br />2.3.3 Obtain all utility requirements for commercial service installation. Electrial <br />Contractor must provide all requirements of the utility for a complete and <br />operational system. <br />2.3.4 System shall be grounded in conformance with NEC. and as shown on <br />Drawings. <br />2.3.5 All switchgear and panels shall be sized as noted on the Drawings or as <br />required <br />G.E. <br />Square - D <br />ITE Div. of Siemens -Allis, <br />2.4. Main Switchboard <br />2.4.1 General: Furnish and install the service entrance distribution switchboard as <br />herein specified and shown on the Drawings. <br />2.4.2 The switchboard shall meet Underwriters' Laboratories enclosure requirements <br />and be furnished with an Underwriters' Laboratories label <br />2.4.3 Construction: Square D Busstack construction or approved equal. <br />2.4.4 Enclosure Construction <br />2.4.4.1 The switchboard framework shall consist of steel channels welded or <br />bolted to the frame to rigidly support the entire shipping section for <br />moving on rollers and floor mounting. The framework is to be <br />formed, code gauge steel, rigidly welded and bolted together to <br />support all cover plates, bussing and component devices during <br />shipment and installation. <br />2.4.4.2 Each switchboard section shall have an open bottom and individual <br />removable top plate for installation and termination of conduit. top <br />and bottom Conduit areas are to be clearly shown and dimensioned on <br />the Shop Drawings. Switchboards are to be front access only.The <br />wireway front covers are to be hinged to permit access to the branch <br />switch load side terminals without removing the covers. All enclosure <br />plates shall be screw removable and small enough for easy handling <br />by one man. The paint finish shall be gray enamel over a rust - <br />inhibiting phosphate primer. <br />2.4.5 Bussing: <br />2.4.5.1 The switchboard bussing shall be plated and of sufficient cross - <br />sectional area to continuously conduct amperage as indicated on <br />Drawings with a maximum average temperature rise of 50 degrees c. <br />above an ambient temperature of 25 degrees c. <br />2.4.5.2 The buss shall be aluminum with 100% neutral with an integrated <br />equipment rating of 100,000 amps (sym) A.I.C. at 240V, 65,000 amps <br />(sym) A.I.C. at 48OV. <br />2.4.5.3 The buss shall extend the full length of the available feeder area. <br />2.4.6 Withstand Rating, <br />2.4.6.1 The switchboard, as a complete unit, shall be given a single withstand <br />short circuit current rating by the manufacturer. The withstand short <br />circuit current rating shall certify that all equipment is cap_ able of <br />withstanding the stress of a fault equal to the interrupting rating of the <br />least overcurrent protective device contained therein. Such rating shall <br />be established by actual tests by the manufacturer on equipment <br />constructed similarly to the subject switchboard This test data shall be <br />available and shall be furnished to the Engineer, if requested, with or <br />before the submittal of Approval Drawings. <br />2.4.6.2 The complete unit shall have interrupting rating of not less than <br />100,000 amps Tins symmetrical at 240 volts,65000 amps RMS <br />symmetrical at 48OV. <br />2.4.6.3 All devices in the switchboard to be fully rated . Series rating is <br />unacceptable. <br />2.4.7 Main Switch (Two-step stored energy electronic trip molded case circuit <br />breaker): <br />2.4.7.1 Individually fixed mounted through contact type, equipped with an electric <br />trip device for remote shunt trip operation. <br />2.4.7.2 Circuit breakers shall have power terminals to accomodate either cable or <br />bolted buss connections. <br />2.4.7.3 Circuit protective devices shall be two-step stored energy type circuit breaker, <br />UL listed for 100% continuous current when applied in QED switchboards. <br />Sensor ampere ratings shall be as shown on the drawings or as otherwise <br />indicated. <br />2.4.7.4 Provide a fixed instantaneous (High Level Selective Override) circuit on <br />breaker(s). The circuit shall have a defeatable instantaneous adjustment to <br />allow the breaker to remain closed for up to 30 cycles during overcurrents <br />below the rnis symmetrical short in withstand ratings. The circuit shall trip <br />instantaneously when current levels exceed applicable withstand ratings. <br />2.4.7.5 Circuit breakers shall be factory sealed and shall have a date code on its face. <br />Poles shall be labeled with respective phase designs. <br />2.4.7.6 Breaker faceplate shall indicate reated ampacity. Breaker faceplate shall <br />indicate UL and EEC certification standards with applicable voltage systems <br />and corresponding AIC ratings. <br />2.4.7.7 Each circuit breaker shall be equipped with a push -to -trip button to operate <br />the trip mechanism mechanically. <br />2.4.7.8 Provide local control push buttons to OPEN and CLOSE circuit breaker. <br />Color coded visual indication of contact position (OPEN or CLOSED) shall <br />be provided on the front of the breaker. Provide for local manual charging <br />following CLOSE operation, with color coded visual indicatin of charging <br />status. Visual indicator shall indicate CHARGED only when closing springs <br />are completely charged. <br />2.4.8 The main switch shall be as manufactured by Square "D" or equal as approved <br />by Publix Engineer 100% rated at specified amps - no substitutes. <br />2.4.9 Bus Duct: (When Used) <br />2.4.9.1 Service entrance bus duct shall be amps as shown on Drawings, 3 <br />phase, full neutral, suitable for 120/209 volts service, inside -outside <br />location. <br />2.4.9.2 The bus duct shall be complete with all necessary elbows, transformer <br />taps, fire stops, wall flange for fittings and supports to provide a <br />satisfactory installation as indicated on the Drawings. <br />2.4.9.3 The bus duct shall be of the same manufacturer as the main <br />switchboard. <br />2.4.9.4 The bus duct shall have the same interrupting rating as the main <br />switchboard <br />2.4.9.5 Support for bus duct by General Contractor. <br />2.4.10 Fusible Switches: <br />2.4.10. I The fusible switches shall be quick -make, quick -break and suitable for <br />use on the services described by the size shown on the associated <br />Drawings. The units shall be listed and approved by Underwriters' <br />Laboratories for heavy duty entrance use and where applicable, shall <br />be dual horsepower rated for both standard one-time or dual -element <br />fuses. The fusible switches shall be group mounted in panel -type <br />construction. Each switch shall be equipped with Class 'R' rejection <br />type fuse clips per Bussman or Littlefuse KTN-R, Class "R" type. <br />2.4.10.2 Each switch is to be enclosed in a separate steel enclosure. The <br />enclosure shall employ a hinged cover for access to the fuses which <br />shall be interlocked with the operating handle to prevent opening the <br />cover when the switch is in the on position. This interlock shall be <br />constructed so that it can be released with a standard electrician's tool <br />for testing fuses without interrupting service. The units shall have <br />padlocking provisions in the offposition and the operating handle <br />position shall give positive switch position indication, i.e. horizontal <br />oft; diagonal on. Switches shall pass industry standard I2T <br />withstandability tests and fuse race tests as described elsewhere in the <br />Specifications. <br />2.4.10.3 All fusing -as manufactured by Bussman or Littlefuse; dual -element <br />and current limiting as shown on the Drawings. <br />2.5. Contactors <br />2.5.1 Contactors shall be manufactured by Square'D', Siemens, or General Electric; <br />or others as approved by Publix in writing specifically for this project. <br />P <br />ub ix® <br />S U P E R M A R K E T S <br />CORPORATE OFFICES <br />FACILITIES DESIGN <br />BOX 407, LAKELAND, FL 33802 <br />(863) 680.5295 <br />PHYSICAL ADDRESS: <br />3300 AIRPORT RD., LAKELAND, FL 33811 <br />PUBLIX FACILITIES <br />DESIGN DEPARTMENT <br />DAVID TAULBEE, AIA <br />ARCHITECT-FL.REG.91318 <br />DAVID RUBIN, AIA <br />ARCHITECT - FL. REG.92557 <br />GA. REG.1 1881 <br />SC. REG. 7477 <br />AL. REG.623A <br />JOHN W. KITCHENS, PE <br />CIVIL/STRUCTURAL- FL_ REG. A5277 <br />GA. REG. 020251 <br />SC. REG.16340 <br />AL. REG. 20382 <br />TN. REG. 101507 <br />PAUL C. HARMAN, PE <br />STRUCTURAL - FL. REG. 5195P <br />GA. REG. 27740 <br />SC. REG.21754 <br />AL. REG.24905 <br />TN.REG.107882 <br />JOHN J. CARAMALIS, PE <br />MECHANICAL- FL. REG. A3889 <br />GA. REG. 021246 <br />SC. REG.16521 <br />AL. REG.20581 <br />TN.REG.108507 <br />ANTHONY CLEMENTI, PE <br />MECHANICAL- FL. REG. 54781 <br />GA. REG.31882 <br />SC.REG.25591 <br />AL. REG.2SA69 <br />TN. REG. 111382 <br />RAYMOND J. SIRIANNI, PE <br />ELECTRICAL- FL. REG. 5AO85 <br />GA. REG. 025636 <br />SC. REG. 19743 <br />AL. REG.23065 <br />TN.RE-G.108038 <br />NORMAN MEIER, PE <br />ELECTRICAL - FL. REG. 59422 <br />GA. REG. 31492 <br />SC. REG.25290 <br />AL. REG. 28079 <br />© COPYRIGHT 2008 <br />PUBLIX SUPER MARKETS, INC. <br />THESE CONSTRUCTION DOCUMENTS ARE THE <br />PROPERTY OF PUBLIX SUPER MARKETS, INC. AND <br />ARE NOT TO BE COPIED OR REUSED FOR ANY <br />SPECIFIC BUILDING WITHOUT WRITTEN PERMISSION. <br />THESE DRAWINGS SHALL NOT BE DUPLICATED <br />WITHOUT PRIOR WRITTEN PERMISSION OF <br />PUBLIX SUPER MARKETS, INC_ <br />THE DESIGN INDICATED IN THESE CONSTRUCTION <br />DOCUMENTS DOES, TO THE BEST OF MY KNOWLEDGI <br />INFORMATION, AND BELIEF, COMPLY WITH THE <br />APPLICABLE MINIMUM BUILDING CODES <br />PLOT DATE: <br />10 JAN 08 <br />REVISION DATA: <br />#1245 (REPL. #0390) <br />ZEPHYR COMMONS <br />PRETTY POND RD. <br />& HWY. 301 <br />ZEPHYRHILLS, PASCO CO., <br />FLORIDA <br />5,4•,4 <br />DRAWING TITLE: <br />t Version 07.2 <br />