Laserfiche WebLink
End of Section 14 92 00 <br />Section 2100 00 <br />Fire Suppression <br />1. General <br />1.1. Submit LOIs in accordance with Section O1 33 00 Submittal Procedures, <br />1.2. System Description: <br />1.2.1 Construction Documents indicate the Design of a Fire Sprinkler System that <br />complies with the intent of Publix. Information contained in these Documents <br />shall be the only basis for Bid. <br />1.2.2 Publix is the approver of all systems that are acceptable to Factory Mutual. <br />However, Factory Mutual approval is a minimum requirement. Publix's <br />requirements exceed those of Factory Mutual in many particulars. <br />1.2.3 Design Changes: <br />1.2.3.1 It is recognized that there are several ways to obtain the protection <br />intended by Publb , and approvable by Factory Mutual Engineering. If <br />changes can be made to the Design to achieve cost or time savings, <br />these shall be submitted to Publix before requesting approval by <br />Factory Mutual or the Authority Having Jurisdiction. <br />1.2.3.2 Work shall not begin on the assumption of approvability of changes to <br />the Design. <br />1.2.3.3 If Publix approves design changes, submit Change Order request for <br />inclusion in Contract. <br />1.3. Scope of Work: <br />1.3.1 Provide complete overhead sprinkler system as shown on the Drawings and <br />described herein. <br />1.3.2 Make connection to the underground supply at the "Point of Service" as shown <br />on the Drawings. <br />1.3.3 Provide back flow preventer and OS&Y Valve assembly at location shown in <br />the Site Documents. <br />1.3.4 Locate Fire Department Connection as directed by the Authority Having <br />Jurisdiction. <br />1.3.5 Provide Dry Pipe System for exterior heads at locations north of Florida State <br />Highway 60, with under -canopy heads as indicated, and concealed heads as <br />required. <br />1.3.6 Provide interconnections to systems provided under separate contract or by <br />Owner. <br />1.3.7 Provide other systems and apparatus as needed for security of components, <br />ease of access by Fire Fighters and Officials, and as required for a complete, <br />integrated system. <br />1.4. Related Work by Others: <br />1.4.1 Connection to mains: <br />1.4.1.1 Underground fire water supply system shall be as approved by <br />Factory Mutual Engineering Div. Atlanta, GA or Charlotte NC, <br />including an acceptable outlet at a "Point of Connection" within 5 ft. <br />of the building, lateral from the fire main or backflow preventer, <br />funished and installed by outside utility Subcontractor. <br />1.4.1.2 All such Fire Sprinkler work shall be accomplished by a Fire <br />Sprinkler Contractor duly registered in the state of the work, and <br />qualified by experience in work of similar scope to that indicated in <br />the Contract Documents. Such work shall include, but not be limited <br />to, connections to mains, underground supplies, backflow preventers, <br />valves, fittings and other appurtenances required to connect the water <br />supply to the fire sprinkler system. <br />1.4.2 Central station alarm system, complete as shown on Drawings, furnished and <br />installed under separate contract. <br />1.5. Design Requirements <br />1.5.1 Minimum requirements for the design, manufacture, testing and methods of <br />installing all materials, apparatus, and equipment shall conform to the <br />requirements of the Factory Mutual Engineering Div., Atlanta, Ga., or <br />Charlotte, NC and to NFPA Standards 24 and 13. <br />1.5.2 Conform to the requirements of the local building code and the Authority <br />Having Jurisdiction. If conflicts occur between the requirements of the above <br />mentioned codes and authorities, the most stringent shall govern. <br />1.5.3 Obtain a Factory Mutual Engineering Assoc. flow test, performed within the <br />previous 6 month time period, and ensure its acceptability by all Authorities <br />Having Jurisdiction prior to basing calculations and proposal on the results of <br />the test. <br />1.5.4 Provide inspector's test connection at most remote point from riser. Provide <br />minimum 1 per riser. <br />1.5.5 Spacing of sprinklers shall not exceed 130 sq. ft. per sprinkler, without written <br />permission from Publix. <br />1.5.6 Sprinkler location: All sprinklers shall be located as shown on Engineer's <br />Drawings, and as required by codes, including vestibules and canopy attic <br />areas. <br />1.5.7 Storage Areas; Ordinary Hazard Group II: Provide a hydraulically designed <br />wet system to provide 0.25 gpm/sgft including the most remote 3000 sqft. <br />Spacing of sprinklers shall not exceed 100 sq. ft. per sprinkler. <br />1.5.8 Sales Areas, Work Areas; Ordinary Hazard Group II: Provide a hydraulically <br />designed wet system to provide 0.18 gpm/sgft for all areas including the most <br />remote 2500 sq. ft. <br />1.5.9 Hydraulic calculations shall include a total allowance of 250 gpm for outside <br />and inside hose streams. <br />1.6. Shop Drawings, Calculations and Approvals <br />1.6.1 Do not begin work until the shop drawings and calculations have been <br />approved by Publix Super Markets, Factory Mutual, and by the Authority <br />Having Jurisdiction. <br />1.6.2 Submit shop drawings and calculations simultaneously to the Publix Super <br />Markets Engineer, Factory Mutual Engineering Assoc., Atlanta, Ga. or <br />Charlotte, NC and the Authority Having Jurisdiction for approval. <br />1.6.3 Forward one copy of Factory Mutual's approved submittal to the Publix Super <br />Markets Engineer for records purposes. <br />1.7. Quality: <br />1.7.1 Subcontractor: <br />1.7.1.1 The Fire Sprinkler Subcontractor shall be a reputable firm regularly <br />engaged in this type of work, employing skilled workmen, and with <br />proper equipment. Work shall be performed by a firm licensed as a <br />Class I or II Fire Sprinkler Contractor. <br />1.7.1.2 Upon request, Subcontractor shall show evidence of at least two <br />similar jobs, of comparable size and character, installed and operating <br />within the two years prior to bid opening. <br />1.7.1.3 Publix reserves the right to refuse any Subcontractor with or without <br />disclosing cause. <br />1.7.2 Personnel: <br />1.7.2.1 Employ an experienced Superintendent to oversee all operation. <br />1.7.2.2 Work shall not proceed without adequate supervision present at all <br />times. Foreman shall be a Journeyman Sprinkler Fitter. <br />1.7.2.3 Work shall be performed by workers certified in their trade as <br />journeymen, and apprentices in accordance with regulations of the <br />governing authority or customary practice. Utilize workers with skills <br />in proportion to complexity of tasks required. <br />1.7.2.4 Publix reserves the right to refuse assignment of workers to Publix <br />work with or without disclosing cause. <br />1.7.3 Quality Standards . <br />1.7.3.1 Work shall be accomplished to ensure leak -proof installation. <br />1.7.3.2 Work will be judged by Publix in comparison to work of similar <br />types. Substandard construction as judged by Publix Representative <br />will not be accepted <br />1.7.3.3 Neatness counts. Make all joints, connections, unions, etc. with proper <br />care to insure that tight connections are made without excess material, <br />well secured to supports. <br />1.7.3.4 Install piping with runs straight, accurately formed radii at bends, and <br />adequate supports. <br />1.8. Pressure Test: <br />1.8.1 Perform testing as required by Factory Mutual and Authorities Having <br />Jurisdiction. Test results shall be certified by these agencies. <br />1.8.2 Asa minimum, test all piping and equipment under hydrostatic pressure of 200 <br />pounds per square inch for a 2 hour continuous period. <br />1.8.3 Correct all defects revealed by test. <br />1.8.4 Retest as required until system is leak free under test conditions. <br />2. Products <br />2.1. Heads <br />2.1-1 All sprinkler heads shall be UL listed, Factory Mutual approved, and the <br />product of one manufacturer. <br />2.1.2 Approved manufacturer's: <br />Viking <br />Victualic <br />Tyco <br />Reliable <br />Globe <br />2.1.3 Sprinkler heads shall be standard response thermosensitive glass bulb style, <br />standard pressure rated to 175 PSI. <br />2.1.4 Sprinklers with 1/2" orifices shall have 1/2" NPT connections, 17/32" orifices <br />shall have 3/4" NPT connections, dry pendant heads shall have 1" NPT <br />connections. <br />2.1.5 Areas with suspended ceilings: Use chrome recessed or semi -recessed type <br />sprinklers rated at 155 degrees F. unless otherwise noted on the plan. <br />2,1.6 In areas with exposed structure: <br />2.1.6.1 Sales/Customer Areas: Use brass upright type sprinklers rated at 155 <br />degrees F. Where suspended ceiling occurs use chrome pendant type <br />sprinklers rated at 155 degrees F. Provide chrome two-piece <br />escutcheons. <br />2.1.6.2 Storage, and other areas not used by customers: Use brass upright <br />type, rated at 286 degrees F. <br />2.1.7 Cooler/Freezer Areas: Provide 155 degree F dry pendant sprinklers. Seal pipe <br />penetration and insulate pipe to V-0" above top of cooler/freezer insulation <br />panel. Minimum barrel length shall be 18". <br />2.1.7.1 Approved Manufacturer: Viking <br />2.2. Provide spare sprinkler heads and wrenches. Provide number of cabinets, spare <br />sprinkler heads in locations required by NFPA 13 and Factory Mutual. Minimum <br />cabinet size shall be for 12 heads. <br />2.3. Dry Systems: Where required by local authorities, the system shall be controlled by a <br />separate wall or post indicator valve and dry pipe valve. Valves are to be equipped <br />with an air compressor, low air trouble alarm, and supervisory switches. Control <br />valves for either shall be located 4'-6" above finished floor. <br />2.3.1 Air compressors for dry systems will be direct drive, 208 volt, 3 phase, electric <br />motor driven, air cooled, with thermal overload protection. Units shall be fully <br />automatic, with a UL listed pressure switch, check valve and safety valve, oil - <br />less piston compressor, and permanently lubricated bearings. Include air filters <br />and riser mounting kits. <br />2.3.1.1 Approved manufacturer: General Air Products. <br />2.4. Back Flow Devices: Provide a Factory Mutual approved back flow device where <br />required by local codes. At stores located north of Florida Route 60, set assembly in <br />insulated below -ground concrete vault. <br />2.5. Inspector's test connection shall be piped to floor level on the inside of the building, <br />then stubbed through the wall and piped to grade. Conform to requirements of NFPA <br />13 and Factory Mutual. <br />2.6. Riser assembly shall include alarm valve with DPDT water flow switch, water motor <br />alarm, electrically supervised gate valve, main drain and pressure gauges. Water flow <br />switch and tamper switch. Riser assembly shall be located in rear of store. All risers <br />shall be interior risers. System control valve shall be a wall or post indicator type. <br />2.7. Provide pipe sleeves for all pipes passing through concrete floors and for all pipes <br />passing through concrete and masonry walls. <br />2.8. Provide escutcheons for all exposed pipes passing through floors and walls. <br />Escutcheons shall be chrome plated steel or stainless steel, two-piece hinged, fastened <br />with set screw, size to suit. Where subject to corrosion (outside) use stainless steel <br />only. <br />2.9. Tamper Switches: Provide Systems Sensor Supervisory switch OSY2 for outside <br />screw and yoke gate valves, or PIBV2 for post indicator gate valves, to be wired by <br />others. <br />2.10. All fittings shall be Factory Mutual approved and stamped and shall conform to the <br />requirements of NFPA. # 13 and the Factory Mutual Approval Guide, except that no <br />"slip" type fittings are to be used. <br />2.11. Piping: <br />2.11.1 Piping shall conform to the requirements of NFPA. #13 and the Factory Mutual <br />Approval Guide. Piping may be grooved, threaded and/or welded if all <br />components and methods are Factory Mutual approved. <br />2.11.2 Underground Service Piping: <br />2.11.2.1 Pipe: AWWA C900, PVC, AWWA C151, Ductile Iron Pipe <br />2.11.2.2 Fittings and Joints: AWWA C110 & C115, Ductile Iron Pipe ANSI <br />B 16.1 Cast Iron Pipe, for sizes 3"-48". <br />2.11.3 Above ground Service Piping: <br />2.11.3.1 Sprinkler Piping: ASTM-A795 and ASTM A35 for black and hot <br />dipped, zinc coated (galvanized) welded and seamless steel pipe. <br />ASTM A135 for electric resistance welded steel pipe. <br />2.11.3.1.1 Exterior Wet/Dry Sprinkler Piping: Gavlanized steel. <br />2.11.3.1.2 Interior Wet Sprinkler Piping: Black steel. <br />2.11.3.1.3 Interior Dry Sprinkler Piping: Galvanized steel. <br />2.11.3.2 Pipe sizes 1%2" shall be Schedule 40. <br />2.11.3.3 Pipe sizes 2 1/2" - 6" shall be Schedule 10. <br />2.11.4 Fire Department Connection Piping: <br />2.11.4.1 Interior: Same as Interior Sprinkler Piping above. <br />2.11.4.2 Exterior: Same as Exterior Service Piping above. Where stubbed -up <br />for connections above grade, use standard weight galvanized steel <br />pipe with galvanized malleable iron screw fittings. <br />2.11.5 Drain Piping: Schedule 40 galvanized steel screwed pipe with cast iron <br />drainage pattern screw fittings. <br />2.12. Valves: <br />2.12.1 Drain valves, test valves, and control valves shall be fitted with FM approved <br />enamelled signs indicating their use. <br />2.12.2 Gate Valves <br />2.12.2.1 Non Rising Stem: 4" - 12", iron body, 1751b. service rating, flanged <br />connections. UL listed, Factory Mutual approved. Bolted bonnet <br />indicator, bolt patter, solid bronze or resilient wedge. <br />Nibco F609 <br />2.12.2.2 Outside Screw and Yoke: 4" - 12" iron body 2001b. service rating, <br />flanged connections. UL listed, Factory Mutual approved. Epoxy <br />coated interior/exterior. Pregrooved stem for supervisory switch, <br />resilient wedge. <br />. Nibco F607RW <br />2.12.2.3 Other approved manufacturer's: <br />Mueller <br />Kennedy <br />Stockham <br />2.12.3 Alarm Check Valves: 3" - 8" iron body, 1751b. service rating, flanged or <br />grooved connection. UL listed, Factory Mutual approved. Vertical mounted <br />with complete trim for variable pressure. Bolted hand hole cover. EPDM <br />rubber clapper seal. <br />2.12.3.1 Wet Alarm Check Valves: <br />Central Model F or G <br />Viking Model J-1 <br />Reliable Model E <br />2.12.3.2 Retard Chambers: <br />Central Model F <br />Viking C-1 <br />Reliable Model E-1 <br />2.12.3.3 Dry Alarm Check Valves: <br />Central Model C <br />Viking F-1 <br />Victualic Series 756 Firelock <br />2.12.3.4 Accelerators and Exhausters: <br />Central Model A <br />Viking Model E-1 <br />Victualic Series 746 <br />2.12.4 Double Check Detector Assembly: Iron body, 175 lb. service rating. UL listed <br />Factory Mutual approved. Epoxy coated interior/exterior. Ductile iron or <br />stainless steel clapper, EPDM rubber seal. Resilient wedge outside screw and <br />yoke gate valves. <br />FEBCO 856, Watts 77ODCDA - OSY - RW, or equal as approved by <br />Publix Engineer. <br />2.12.5 Indicator Posts: Iron body. UL listed, factory Mutual approved for use with <br />non -rising stem gate valves: <br />NIBCO NIPIAJ upright post or NIP2AJ wall post <br />Grinnell <br />Kennedy <br />Mueller <br />Stockham <br />2.12.6 Drain Valves: Angle or globe type as required. <br />Jenkins 108-A angle or 106A globe or equal as approved by Publix <br />Engineer. <br />2.12.7 Check Valves: Factory Mutual approved swing check valves installed <br />horizontally, iron body, bronze mounted, 175 pound service rating. <br />2.13. Riser and Fire Department Connection <br />2.13.1 Riser: Provide riser where indicated on the drawings. Riser shall have alarm <br />valve, complete with valve trimmings, gauges, and all required accessory <br />equipment. Provide approved electric flow switch where indicated on the <br />drawings. <br />2.13.2 Inspector's Test Connection: 1" inspectors test valve, drain valve and pipe <br />extending to drain indicated on drawings. System shall also be connected into <br />the central fire alarm system. <br />2.13.3 Fire Department Connections: Factory Mutual approved flush type Fire <br />Department connections 4" F.I.P.T. outlet and two 2-1/2" NSHT inlets with <br />lettered nameplate. All exposed parts shall be rough brass and polished trim; <br />plate shall be lettered "Automatic Sprinkler", "Fire Department Connections". <br />2.14. Gauges <br />2.14.1 Pressure gauges shall be installed as required by code, Factory Mutual <br />approved 4 1/2" dial type, and shall have a maximum limit of not less than <br />twice the normal working pressure at the point where installed. <br />2.14.2 Control valves, drain valves, check valves, identification tags and drain piping <br />shall be approved for fire service and shall conform to the requirements set <br />forth in NFPA. # 13. <br />3. Execution <br />3.1. General <br />3.1.1 Architectural and Structural Drawings shall be used for building construction, <br />dimensions and specific locations. <br />3.1.2 Perform all cutting and fitting required for work of this Section in rough <br />construction of the building, and in areas of existing buildings and structures as <br />required by alterations and connections to existing. <br />3.1.3 All patching of finished construction ofnew and existing buildings shall be by <br />the General Contractor under the Sections of Specifications covering those <br />materials. <br />3.1 A Subcontractor shall perform all excavation and backfiU required for services, <br />inside and outside the building. Cutting of curbs, walks, concrete and paving <br />required by the excavation shall be done by Subcontractor. Any rock shall be <br />excavated 3 inches below the laying depth, and the trench shall be backfilled <br />with sand 3 inches deep. Over excavation shall be added in 12 inch layers and <br />mechanically compacted. Flooding or puddling not permitted. All piping which <br />will be under walks, planters, arcades, parking lots, concrete or asphalt shall be <br />mechanically compacted in 12 inch layers. Pipe under driveways shall have a <br />minimum cover of 3 ft. <br />3.1.5 Verify all field dimensions and locations of equipment and fixtures within the <br />layout as established by the General Contractor to insure close, neat fit, with <br />other trades work. - <br />3.1.6 No underground piping shall be covered until inspected by Publix' <br />Representative and Authority Having Jurisdiction. <br />3.1.7 Where the work is dependent upon work of other trades or work already in <br />place for its proper installation, examine such other work and see that is in the <br />proper condition and state of completion before continuing the installation. <br />3.1.8 Include the services of an experienced Superintendent, who shall be constantly <br />in charge of the work, together with qualified journeymen required to properly <br />unload, install, connect, adjust, start and operate and test the work involved, <br />including equipment and materials furnished by others and by Owner. All work <br />shall be executed in a first class workmanlike manner. Workmanship that, in <br />the opinion of Publix, is substandard or shoddy, shall be removed and replaced <br />with acceptable work at no cost to Publix. <br />3.1.9 Follow Drawings in laying out work and check Drawings of other trades to <br />verify spaces in which work will be installed. Coordinate work with other <br />trades. Maintain maximum headroom and space conditions at all points. Where <br />headroom or space conditions appear inadequate, notify Architect before <br />proceeding with installation. <br />3.2. Area of horizontal runs by trades: See Section O1 1100 Summary of Work. <br />3.3. Conceal all piping above suspended ceiling where practical. <br />3.4. If directed by Architect, the Subcontractor shall, without extra charge, make <br />reasonable modifications in the layout as needed to prevent conflict with work of <br />other trades or for proper execution of the work. <br />3.5. Provide qualified installers. Install materials, apparatus and equipment in neat, <br />workmanlike manner. <br />3.6. Cooperate with the work of other trades to prevent conflict or interference and to aid <br />rapid completion of the overall project. <br />3.7. Protect materials, apparatus and equipment from damage, moisture, dirt, debris and <br />work of other trades. Do not install damaged materials and equipment; remove them <br />from the site. <br />3.8. Install drops for sprinkler heads in areas with finished ceiling. Sprinkler heads in tile <br />ceilings shall be located within 1 1 /2" of the center of tile. Coordinate the exact <br />location of the ceiling grid with the ceiling contractor. <br />3.9. Examine all work of others. If any conditions exist which will prevent satisfactory <br />installation of materials or equipment the Architect shall be notified in writing. <br />Starting of work without notification indicates acceptance, and any or all changes <br />required will be at Contractor's expense. <br />3.10. Keep the job site free from accumulations ofwaste materials and rubbish. Leave the <br />job site and work in clean, orderly and acceptable condition. Clean all materials and <br />equipment of dirt, dust, paint, spots and stains, soil marks and other foreign matter. <br />3.11. The inside sprinkler piping shall be installed in such a manner that there will be no <br />leakage. <br />3.12. There shall be no on site welding of sprinkler piping. <br />3.13. Install, test and flush the fire protection underground from the "Point of Service" to <br />the building in accordance with NFPA. 24. <br />3.14. Requirements for Final Acceptance and Payment: <br />3.14.1 The entire system shall be tested under hydrostatic pressure. This pressure shall <br />be 50 psi greater than pressure in the main, but in no case less than 200 psi. <br />The test pressure shall be maintained for two (2) hours. Properly executed test <br />certificate shall be sent to Factory Mutual Engineering Association and Publix' <br />Representative upon Completion. <br />3.14.2 Furnish Publix' Representative with a complete set of all manufacturer's <br />warranties and instructions, and with two sets of as -built drawings. <br />3.14.3 Obtain Final Inspection and test required by the authorities having jurisdiction <br />for their acceptance of the system; provide adequate advance notice to Publix' <br />representative of such inspection and test; furnish Publix' Representative with <br />evidence of acceptance of the system by the local authority having jurisdiction. <br />3.14.4 Contractor's Material and Test Certificates for Underground Piping/ <br />Aboveground Piping shall be completed on the appropriate NFPA 13 form and <br />submitted to the Owner, Factory Mutual, and the authority having jurisdiction. <br />3.14.5 The system, upon completion and testing, shall be inspected and accepted by <br />Factory Mutual Engineering Association, <br />3.15. Guarantee <br />3.15.1 All equipment shall be tested, adjusted and placed in proper operating <br />condition by the subcontractor. Both the Contractor and the Engineer shall <br />advise the Architect in writing that the systems are installed according to the <br />Specifications and Drawings and are operating satisfactorily. The Owner shall <br />receive written warranty covering all defects in workmanship and material for <br />a period of one (1) year from the date of Final Acceptance. <br />3.15.2 All defects within this period shall be repaired without cost to the Owner. This <br />shall include adjustments, and all regular and preventative maintenance. <br />3.15.3 The Owner reserves the right to make emergency repairs as required to keep <br />equipment in operation without voiding the Contractor's warranty. <br />3.16. Final Inspection . <br />3.16.1 All of the following items shall be completed prior to final inspections. No <br />exceptions will be made and no final payment will be made until all items are <br />completed. - <br />3.17. Cleaning Equipment and Premises: <br />3.17.1 Thoroughly clean all exposed parts of the apparatus and equipment. Exposed <br />parts which are to be painted shall be thoroughly cleaned of cement, plaster, <br />and other material and all oil and grease spots shall be removed. Repaint or <br />touch up as required to make look like new. Such surfaces shall be carefully <br />wiped and all cracks and comers scraped out. <br />3.17.2 Exposed metal work shall be carefully brushed down with steel brushes to <br />remove rust and other spots and touched up with primer. <br />3.18. Identification, Operating Instructions and Service Manual: <br />3.18.1 Provide a permanent non -corrosive metallic placard indicating hydraulic design <br />and demand information, securely affixed to riser, one required each riser. <br />3.18.2 Manual: <br />3.18.2.1 Provide two (2) neatly bound copies of maintenance and instructions <br />book, parts lists pertaining to all equipment furnished. Submit to the <br />Architect for approval. <br />3.18.2.2 Each section shall be indexed and include parts lists, instruction <br />books, suppliers' phone numbers and addresses, and individual <br />equipment guarantees all in separate sections. <br />End of Section 21 00 00 <br />Section 22 40 00 <br />Plumbing <br />1. General <br />1.1. Summary <br />1.1.1 Provide all materials and equipment and perform all labor required to install <br />plumbing complete as indicated, as required by code, and as specified herein. <br />All sizes, etc. are Publix minimum and if local code requirements are higher, <br />the work shall be bid and installed accordingly. <br />1.1.1.1 Obtain and pay for all permits, bonds, inspection. <br />1.1.1.2 Provide 2-1/2" water service line, with water meter and 2-1/2" <br />backflow preventer. <br />1.1.1.3 Provide hot and cold water mains and distribution piping, all overhead <br />and concealed except main water supply into building and where <br />indicated on the Drawings. No PVC pipe allowed above floor slab, <br />(except plumbing waste piping, unless not code approved). <br />1.1.1.4 Provide a system of soil and waste drains, vents, and connections to <br />all sewer, and water mains and all fixtures. <br />1.1.1.5 Plumbing Fixtures: Provide and adjust, except as herein specified. <br />1.1.1.E Provide Grease Interceptors as specified and as required by local <br />codes. <br />1.1.1.7 Provide all piping hanging and hangers. <br />1.1.1.8 Provide gas piping and all indirect drains required for equipment <br />furnished in other sections, and by Owner, except provide indicated <br />drains (floor drains, hub drains, floor sinks, etc.) for refrigerated cases, <br />walk-in coolers, and freezers. <br />1.1.1.9 Provide rough -in plumbing for fixtures indicated as furnished by <br />Publix or others, and make required connections. Include uncrating <br />equipment, moving into place, and installing complete. <br />1.1.1. I0 Coordinate plumbing work with all other trades including <br />Refrigeration Contractor's work. <br />1.1.1. I 1 Provide all other materials and services required for a complete <br />working installation described in Contract Documents. <br />1.1.2 All apparatus shall be installed at exact height and locations as shown on the <br />Architectural Drawings, or if not shown, at heights and locations determined <br />by applicable codes and laws. <br />1.1.3 Perform all excavation and backfill required for services, and for all plumbing <br />and work inside and outside the building. Cutting of curbs, walks, concrete and <br />paving required for excavation shall be done by appropriate trade. <br />1.1.4 All store cases, coolers, and freezers will be furnished and set in place by <br />Publix. The Refrigeration Contractor shall make all condensate waste <br />connections required to Plumbing Contractors stub ups. Check equipment <br />drawings against Drawings in order to verify exact locations. Provide gas <br />piping as indicated. <br />1.2. Definitions: Explanation and Precedence of Documents: <br />1.2.1 For purposes of clarity and legibility, Plumbing Drawings are essentially <br />diagrammatic and, although size and location of equipment are drawn to scale <br />wherever possible, Contractor shall make use of all Contract Documents. <br />1.2.2 The Drawings indicate size, connection points and routes of pipe. It is not <br />intended, however, that all offsets, rises and drops are shown. Install piping as <br />required to fit structure, avoid obstructions, and retain clearance, headroom, <br />openings and passageways. <br />1.2.3 Carefully examine all existing conditions, existing piping and premises and <br />compare the Drawings with the existing conditions. Submittal of bid indicates <br />that the Contractor has examined the site and Drawings and has included all <br />required work in his bid. No allowances will be made for any error resulting <br />from Contractor's failure to visit Job Sites and to review Drawings. <br />1.2.4 Conflicts, discrepancies, interferences and omissions in documents shall be <br />brought to the attention of the Architect for clarification prior to <br />commencement of work. <br />1.3. Submittals: <br />1.3.1 Submit LOI in accordance with Section 0133 00 Submittal Procedures. <br />1.3.2 Within 30 days of Contract Commencement (Authorization to Proceed), submit <br />for Publix' Architect's approval: <br />Fixtures and trim with cuts including rough -in dimensions. <br />Equipment (water heaters, expansion tanks, other items) <br />Drains and cleanouts (floor and wall) <br />Valves, stops, hose bibbs <br />Miscellaneous <br />Roof flashing <br />Piping, piping diagrams <br />Other items required to complete the Work <br />1.3.3 Submit six identical bound copies of all items. Arrange categories in order <br />listed above. <br />1.3.4 All cuts for the above shall have rough -in dimensions, connection sizes, and <br />any special installation requirements. In addition, furnish motor horsepower <br />voltage and phase for all equipment. <br />1.3.5 Project Record Drawings: Comply with Section 01 78 39. <br />1.3.6 Do not order materials or proceed with work untill all submittals have been <br />reviewed, and approved. <br />1.3.7 Confirm electrical and other requirements with other contractors. <br />1.4. Quality: <br />1.4.1 Subcontractor: <br />1.4.1.1 The Plumbing Subcontractor shall be a reputable firm regularly <br />engaged in this type of work, employing skilled workmen, and with <br />proper equipment. <br />1.4.1.2 Upon request Subcontractor shall show evidence of at least two <br />similar jobs, of comparable size and character, installed and operating <br />within the previous two years prior to bid opening. <br />1.4.1.3 Publix reserves the right to refuse any Subcontractor with or without <br />disclosing cause. <br />1.4.2 Personnel: <br />1.4.2.1 Employ an experienced Superintendent to oversee all operation. <br />1.4.2.2 Work shall not proceed without adequate supervision present at all <br />times. <br />1.4.2.3 Work shall be accomplished by workers certified in their trade as <br />masters, journeymen, and apprentices in accordance with regulations <br />of the governing authority or customary practice. Utilize workers with <br />skills in proportion to complexity of tasks required. <br />1.4.2.4 Publix reserves the right to refuse assignment of workers to Publix <br />work with or without disclosing cause. <br />1.4.3 Quality Standards <br />1.4.3.1 Work shall be accomplished to ensure leak -proof installation. <br />1.4.3.2 Work will be judged by Publix in comparison to work of similar <br />types. Substandard construction as judged by Publix Representative <br />will not be accepted. <br />1.4.3.3 Neatness counts: Make all joints, connections, unions, etc. with proper <br />care to insure that tight connections are made without excess material, <br />well secured to supports. <br />1.4.3.4 Install piping with runs straight, accurately formed radiuses at bends, <br />and adequate supports. <br />1.4.4 Regulations: Comply with applicable provisions of the following codes (latest <br />version adopted by governing agencies): <br />State Sanitary Code <br />Local Building Code <br />ASME Code for Unfired Pressure Vessels <br />International Plumbing Code <br />Florida State Plumbing Code <br />OSHA - for construction <br />Other applicable laws and regulations. <br />1.4.5 Coordination: Work shall be accomplished along with the work of other trades. <br />Cooperate with others to benefit the job as a whole. <br />1.4.6 Participate in the Pre -Construction Conference. <br />1.5. Sequencing: <br />1.5.1 Notify General Contractor, or any others, of all required chases, sleeves and <br />openings required so that the work can be accomplished without delay. Provide <br />necessary sleeves, etc., to be installed. Otherwise, Plumber shall pay for <br />appropriate trades to perform cutting and patching. <br />1.5.2 Joists, girders, beams, columns or reinforcing steel shall not be cut. <br />1.5.3 Where construction necessitates the routing of piping through structural <br />members, framing or under footings, permission to make such installation shall <br />first be obtained from the Publix Field Representative <br />1.6. Temporary Operation: - <br />1.6.1 The Owner may require operation of parts or all of the installation prior to <br />Final Acceptance. <br />1.6.2 Cost of utilities for such operation shall be paid by the Contractor. This <br />operation does not constitute acceptance of the Contractor's work. <br />1.6.3 All gas and water used for construction shall be paid for by the General <br />Contractor. Furnish and install all temporary water piping required for <br />construction purposes and remove piping when use is no longer required. <br />Restore site and piping to original conditions. <br />1.7. The Owner reserves the right to make emergency repairs as required to keep <br />equipment in operation without voiding the Contractor's guarantee nor relieving the <br />Contractor of his responsibilities during the guarantee period. <br />1.8. Operating Instructions and Service Manual: , <br />1.8.1 Provide two (2) neatly bound copies of maintenance and instructions book, <br />parts lists pertaining to all equipment furnished. <br />1.8.2 Each section shall be indexed and include parts lists, instruction books, <br />suppliers' phone numbers and addresses, and individual equipment guarantees <br />all in separate sections. <br />1.8.3 Representatives of the Owner shall be instructed by the Contractor as to <br />complete care and operation of the plumbing system. Inform the Architect in <br />writing as to the persons who received the instructions and the date that this <br />was done. <br />2. Products: <br />2.1. Materials: <br />2.1.1 All materials shall be new, full weight, of the best quality with the same brand <br />or manufacturer used for each class of materials or equipment. All similar <br />materials such as valves, pumps, boilers, fixtures, shall be of the same type and <br />manufacturer unless otherwise designated. <br />2.1.2 All plumbing fixtures shall be "first quality" as defined and set forth in <br />Commercial Standard CS 20-36 As Promulgated By The U.S. Department of <br />Commerce. <br />2.2. Fixtures <br />2.2.1 Provide cast iron fixtures with acid resisting white enamel where possible. <br />Otherwise provide vitreous china fixtures (unless otherwise noted). <br />2.2.2 American Standard product designations have been used for consistency. <br />Equivalent fixtures by Crane, Kohler, Toto, or Eljer may be accepted. <br />2.3. Equipment <br />2.3.1 Grease Interceptor: Rectangular, pre -cast concrete, all in accordance with state <br />and local codes. Two cast iron traffic tops with traffic cast iron cleanouts are <br />required. Tanks shall be designed for an H-20 traffic load. <br />2.3.2 Drains, Cleanouts: As scheduled. Approved manufacturers: <br />Smith <br />Zurn <br />2.4. Pipe and Fittings: <br />2.4.1 Hot and cold water piping: ASTM B88 type "L" seamless copper tubing. Main <br />service type "K" with red lion seal cote coating, or approved equal. <br />2.4.1.1 Fittings: Wrought copper solder fittings, solder with silvaloy, <br />streamline 122, phos-copper or approved equal no -lead solder. <br />2.4.1.2 Alternate: Copper press fittings shall conform to the material and <br />sizinge requirements of ASME B16.18 or ASME B16.22. O-rings for <br />copper press fittings shall be EPDM. Approved Manufactueres: <br />Viega <br />Rigid Tool Co. <br />2.4.2 Gas Piping: Shall be schedule 40-A-120 black steel pipe with black banded <br />malleable iron fittings, pipe shall be welded. Grounding by Electrical <br />Contractor. <br />2.4.2.1 Indoors: ASTM A53 steel pipe, schedule 40, black forged steel weld <br />fittings. <br />2.4.2.2 Outdoors: ASTM A53 steel pipe, schedule 40, mill galvanized, <br />fittings as require& <br />2.4.3 Plastic Gas Piping: Used underground only. Shall conform to the <br />requirements of ASTM D2513 for medium -density polyethylene pipe and <br />tubing. Fittings shall comply with the requirements of ASTM D2683 for <br />socket type, ASTM D3261 for butt fusion and ASTM F1055 for electrofusion. <br />Pipe shall be yellow and marked in accordance with ASTM D2513. <br />2.4.4 Soil, Waste, Vent Pipe: <br />2.4.4.1 PVC DWV pipe (where allowed by codes): Unplasticized, ASTM <br />D2665, Type I, Grade 1, solvent cement joints, DWV fittings. <br />schedule 40 unless indicated otherwise on the Drawings, all elbows <br />shall be long sweep type. <br />2.4.4.2 ABS DWV pipe (where allowed by codes): Unplasticized, ASTM <br />D2661, Type I, Grade 1, solvent cement joints, DWV fittings. <br />schedule 40 unless indicated otherwise on the Drawings, all elbows <br />shall be long sweep type. Use only where indicated on the drawings. <br />2.4.4.3 Cast Iron Pipe: Coated service weight cast iron soil pipe using coated <br />service weight cast iron fittings. <br />2.4.4.4 Vent Piping Option: All vent piping above grade may be copper <br />DW V, with copper drainage fittings, solder as for hot and cold water. <br />2.4.5 Provide field fabricated DWV copper or cast brass traps with an integral clean <br />out at bottom of traps for stainless steel utility sinks, except those which <br />discharge to a floor sink. <br />2.5. Valves, Stops, Specialties <br />2.5.1 Materials: Valves 2 inch and smaller shall be bronze, screwed ends. Valves 2- <br />1/2 inch and larger shall be iron body bronze mounted 125 lb. ASA flanged, <br />faced and drilled. Bronze castings shall be material meeting ASTM A-126 <br />specification. Furnish union adjacent to all screwed central valves and at all <br />connections to equipment. <br />2.5.2 Hot and cold water and other fluids operating below 200 psig: Valves rated 125 <br />lb. steam, 200 lb. cold water or oil. <br />2.5.3 Gate Valves: <br />2.5.3.1 2 inches and smaller: <br />Milwaukee 105 <br />Jenkins 992 <br />Stockham B-103 <br />Crane 438 <br />Nibco T-113 <br />2.5.3.2 2-1/2 inches and larger: <br />Milwaukee F2882 <br />Jenkins 326C <br />Stockham G-612 <br />Crane 461 <br />Nibco F-619 <br />2.5.4 Mixing Valves: Combination thermostatic and prP-��re balanced, with liquid <br />filled motor. Bronze body with stainless steel piston, integral checks and stops. <br />Symmon <br />Lawler <br />Bradley <br />2.5.5 Swing Check Valves: Use only on non pulsating service lines. Where <br />compression or pulsation affects line flow, lift checks or piston type checks <br />shall be used. <br />2.5.5.1 Swing Check Valves 2 inches and smaller: <br />Milwaukee 509T <br />Stockham B-319 <br />Crane 37 <br />Nibco T-413Y <br />2.5.5.2 Swing Check Valves 2-1/2 inches and larger: <br />Milwaukee F2974 <br />Stockham G931 <br />Crane 373 <br />Nibco F-918B <br />2.5.6 Ball Valves shall be as follows, sized as required: <br />Hammond 8604 <br />Milwaukee BA-300 <br />Nibco T-590Y <br />2.5.7 Gas Valves: ANSI Z21.15, Nibco T-580-70-UL 1-1/4" - 3", Nibco T-585-70- <br />UL 1" , or comparable by other manufacturer listed above. <br />2.5.8 Mechanical Gas Valve with Remote Pull: ASCO Automatic Switch Co., Model <br />as indicated on Drawings. <br />2.5.9 Interior Hose Bibbs and Stops <br />2.5.9.1 Stops: <br />Eastman Type SM12, Brasscraft, McGuire, all brass construction <br />2.5.9.2 Interior Hose Bibbs: <br />Chicago #397 Brass 3/4" R.C.P W/Watts No. 8BC Vacuum Breaker, <br />or T&S Brass B-0737-POL. <br />2.5.10 Exterior Hose Bibbs and Hydrants: <br />2.5.10.1 Description: All shall have integral vacuum breakers and an integral <br />stop valve. If an integral stop valve is not available, provide an in -line <br />gate valve. <br />2.5.10.2 Approved Manufacturers: <br />Acorn <br />J.R. Smith <br />Zum. <br />2.5,11 Flush Valves: <br />2.5.11. I Description: Cast brass or bronze body with corrosion -resistant <br />internal components; non -hold open, control stop with check valve; <br />vacuum breaker and copper or brass tubing; polished, chrome -plated <br />finish on exterior parts; vandal -resistant stop cap; ADA compliant <br />handle. <br />2.5.11.2 Manufacturers: <br />Toto <br />Sloan - Royal <br />Zum - Z6000AV <br />2.5.12 Faucets: <br />2.5.12.1 Description: Cast brass body with corrosion -resistant internal <br />components; polished, chrome -plated finish. <br />2.5.12.2 Manufacturers: <br />Chicago Faucet <br />T & S Brass <br />2.5.13 Hand Sinks: <br />2.5.13.1 Description: Wall hanging; 18 gauge, 304 stainless steel, polished <br />finish, basin with radius comers; back for faucet; integral side support <br />panels, approximate size - 17"xl6"x5" with 2-3/16" drain outlet. <br />2.5.13.2 Manufacturers: <br />Eikay <br />Just <br />Amtekco <br />2.6. Miscellaneous: <br />2.6.1 Faucet (Janitor Room). Sink faucet with top brace, 9" - 10" rigid spout with <br />bucket hook vacuum breaker and integral stops; at 36" above floor. <br />T&S Brass <br />Chicago Faucet <br />2.6.2 Vacuum Breakers: Shall be installed on all fixtures where required <br />2.6.3 Unions: Malleable iron ground joint equivalent and similar to Crane 519, up to <br />and including 2 inch. Over 2 inch shall be cast iron flanged with a Garlock <br />7022 Gasket. <br />2.6.4 Reducing and Regulation: Water, air, gas; Watts or approved equal, model as <br />indicated on the Drawings. <br />2.6.5 A shut off valve shall be placed near the building on the water main. It shall be <br />placed in a box or file pipe and have a removable plate cover of cast iron, equal <br />to Mckinley Iron Works, Fort Worth, Texas; Type MB14, for 80009loading. <br />2.7. Pipe Insulation <br />2.7.1 Rigid fiberglass pipe insulation: <br />2.7.1.1 Heavy density molded insulation from inorganic glass fibers bonded <br />with a thermosetting resin; jacketed with a reinforced, wrinkle - <br />resistant, all -service vapor retarder facing and a factory -applied <br />longitudinal double -pressure adhesive closure system. Use factory <br />butt strips to complete joints. Thermal conductivity [`K' Factor <br />(BTU-inch/ftz-hr-°F) at 75°F mean] shall be 0.23 r� i-m. <br />2.7.1.2 Manufacturers: <br />. Owens-Corning <br />Johns Manville <br />CertainTeed <br />2.7.2 Flexible pulyethylene/polyolefin pipe insulation: <br />2.7.2.1 Unicellular polyethylene thermal plastic, preformed pipe insulation; <br />white color, 25/50 rated, pre -slit with factory -applied adhesive on both <br />surfaces. Use factory adhesive for gluing butt joints. Thermal <br />conductivity [`K' Factor (BTU-inch/ft2-hr-°F) at 75DF mean] shall be <br />0.23 maximum. <br />2.7.2.2 Manufacturers: <br />Armacell <br />Nomaco K-Flex <br />2.8. Pipe Hangers and Supports: <br />2.8.1 Piping shall be firmly held -in place by adjustable, Grinnell #CT-99C split ring <br />malleable iron hangers, supports and pipe rests, located adjacent fittings, at <br />each offset or change of direction, at the ends of branches over 5 feet long, at <br />riser pipes and along piping where necessary to prevent sags, bends, or <br />vibration. <br />2.8.2 Pipe straps shall be heavy gauge galvanized iron factory fabricated to fit <br />against supporting surface when installed. Makeshift devices are not <br />acceptable. No plumbing tape is allowed Use insulation shields at each pipe <br />hanger and support. <br />2.8.3 Stainless steel pipe straps and hangers shall be used for all exposed piping and <br />underslab piping where structural slabs are provided <br />2.8.4 The maximum spacing between hangers or supports measured along the piping <br />shall be as listed below: <br />Steel Copper PVC <br />H V H V H V <br />3/4" and 1/2" 5 ft. 15 ft. 6 ft. 10 ft. 4.0 ft. 10 ft. <br />1" and 1-114" 7 ft. 15 ft. 6ft. 10 ft. 4.0 ft. 10 ft. <br />1-1/2", 2" & 2-1/2" 9 ft. 15 ft. 10 ft. 10 ft. 4.0 ft 10 ft. <br />3" 12ft. 15ft. loft. loft. 4.0ft loft.. <br />4" 12 ft. 15 ft. 10 ft. 10 ft. 4.0 ft. 10 ft. <br />6" 12 ft. 15 ft. 10 ft. 10 ft. 4.0 ft. 10 ft. <br />2.9. Roof flashings: All vent and roof drains shall be flashed by Roofing Contractor with <br />lead flashing furnished by the Plumbing Contractor. Flashing shall turn down 2" into <br />vent pipes. <br />2.10. Isolating Couplings: Provide dielectric protection for gas and water main risers inside <br />building. Isolate connections of copper and steel pipe with cathodic isolating unions. <br />Acceptable Manufacturers: <br />EPCO <br />W & K Dielectric <br />F.H. Maloney <br />3. Execution <br />3.1. Examination: <br />3.1.1 Verify all field dimensions and locations of equipment and fixtures within the <br />layout as established by the General Contractor to insure close, neat fit, with <br />other trades work. <br />3.1.2 Examine all work of others. Notify Architect in writing if any conditions exist <br />which will prevent satisfactory installation of materials or equipment. Start of <br />work without notification indicates acceptance of work in place. <br />3.2. Excavation: <br />3.2.1 Perform excavation for trenches under slab and outside building lines as <br />required for installation. Excavate true to lines and grades shown to achieve <br />adequate fall on drain lines and as needed for refrigeration drainage. <br />3.2.2 Bell holes shall be dug to allow soil pipe to lie fully supported. <br />3.2.3 Rock shall be excavated 3 inches below the laying depth, and the trench shall <br />be backfilled with sand 3 inches deep. <br />3.2.4 Over -excavation shall be added in 12 inch lifts (max) and mechanically <br />compacted. Flooding or puddling not permitted <br />3.2.5 All piping which will be under walks, planters, arcades, parking lots, concrete <br />or asphalt shall be mechanically compacted in 12 inch lifts (max). <br />3.3. Interface with Site Utilities: <br />3.3.1 Coordinate with other work. Connect to site supplies and storm drain at 5'-O" <br />demising line. <br />3.3.2 Provide waste connection to site sewer at 5'-O" demising line. Provide grease - <br />bearing waste connection to grease trap and from grease trap to waste line <br />located as shown on the Drawings or otherwise indicated. <br />3.4. Pipe Installation: <br />3.4.1 Install horizontal sanitary and drain piping, to a uniform grade of not less than <br />1/8" per foot, unless otherwise noted. <br />3.4.2 Openings in pipes, drains, fitting, apparatus and equipment shall be kept <br />covered or plugged to prevent accumulating obstructions in the piping. <br />3.4.3 Run piping free of traps, sags, bends or other defects. grade and valve for <br />complete drainage and control of the system. <br />3.4.4 All waste, vent and water lines shall be concealed, and all water lines shall be <br />overhead. <br />3.4.5 Maintain headroom and keep passageways clean. offset to maintain the <br />required clearance and conform. with architectural and structural features of <br />building. Run parallel and straight with adjacent walls or ceilings to present a <br />uniform appearance. Group long runs together. Run concealed in finished <br />rooms. <br />3.4.6 All rough -ins shall be set exactly to measurements furnished by manufacturer. <br />Batteries of fixtures shall have rough outlets set in straight lines at equal <br />spacing. <br />3.4.7 Flush out all lines to insure that they are clear of obstructions prior to the <br />setting of refrigerated cases. If lines are not clear and a case is set, the <br />Plumbing Contractor shall be responsible for the removal and re -set cost. <br />3.4.8 Water piping shall not be embedded in concrete nor concealed within the floor <br />slab within the building. unless shown on drawings). Isolate copper piping <br />from concrete with tar paper or felt. <br />3.4.9 All piping shall be installed to prevent unusual noise from the flow of water <br />under normal conditions. Install pipe isolators at ring hangers consisting of a <br />metal sheath with end flanges assuring positive retention in the ring hangers. <br />Separate cold lines from hot lines by 6". <br />3.4.10 Provide dirt pockets on low point of vertical gas piping. Install full pipe size <br />drip pockets at low point in change of grade. . <br />3.4.11 For refrigeration case drains, stub up a 3" line 1 ". above floor; no hub required. <br />3.5. Pipe, joints, fittings, and connection -installation <br />3.5.1 Cast Iron SoilPipe: Pack tight with first quality oakum to within 1 inch of end <br />hub. Fill remaining space with one pouring of molten lead and caulk tight; or <br />make-up with neoprene gaskets. <br />3.5.2 Screwed Piping: Make up with pipe dope, applied only to male thread. Remake <br />leaky joints with new material without use of thread cement or caulking. Paint <br />exposed threads of all pipe with asphaltic paint. <br />3.5.3 Copper Tubing: . <br />3.5.3.1 Solder with 95-5 (no -lead solder) and a noncorrosive flux. Thoroughly <br />clean inside and outside surfaces with sandpaper or wire brush before <br />assembly. Defective joints shall be dismantled, cleaned, and <br />resoldered. Do not use acid Solder. <br />3.5.3.2 Press Connections: Copper perss fittings shall be made in accordance <br />with the manufacturer's installation instructions. The tubing shall be <br />fully inserted into the fitting and the tubing marked at the shoulder of <br />the fitting. The fitting alignment shall be checked against the mark on <br />the tubing to assure that the tubing is fully engaged (inserted) in the <br />fitting. The joints shall be pressed using the tool approved by the <br />manufacturer. <br />3.5.4 Copper, brass pipe and chromed, polished or painted connections from fixtures <br />shall show no tool marks. <br />3.5.5 PVC Joints: Clean socket and pipe ends with cleaner recommended by cement <br />manufacturer. Liberally apply solvent cement to both socket and pipe ends. <br />Make up joint firmly. <br />3.5.6 Gas Piping: <br />3.5.6.1 Black iron schedule 40, welded except at equipment connections. <br />Certified welding is required. <br />3.5.6.2 At each piece of equipment, provide shut-off valve, union, dripleg <br />(mininmum 4 times pipe diamenter, capped) and flexible pipe <br />connection. <br />3.5.7 Springing, bending or forcing of pipe will not be allowed. Use fittings for all <br />offsets or changes in alignment of piping. Center hubs so cast iron will lay <br />straight without pinched joints. <br />3.5.8 Street elbows, bushings, and long screw fittings will not he allowed <br />3.5.9 Cleanly cut pipe and tubing and remove burrs to full diameter of pipe. <br />Excessive reaming will not be permitted. Remove metal particles from ends of <br />pipe and clear each section of foreign material before assembling. <br />3.5.10 Cut pipe threads to full depth of die and screw up tight to fully engage thread in <br />fitting. Threads to comply with ASA No B 2.1, and be cut with clean sharp <br />dies. <br />3.5.11 Cleanouts: Cleanouts shall be placed as shown on Drawings, or max. 50' o.c., <br />at bases of stacks, at major changes in direction, and at the ends of all lines that <br />have 2 or more openings going into that line, or as required by code. Cleanouts <br />shall be as indicated on Drawings. If PVC. is used include hub adaptor. <br />3.5.12 Provide shut-off valves in access panels to allow shut down of area of fixtures <br />where indicated on Drawings, <br />3.5.13 Provide shock absorbers with isolating gate or ball valves as indicated on the <br />Drawings. Mount in the vertical position as recommended by the manufacturer. <br />3.5.14 The inside of all pipes shall be clean, reamed smooth with no burrs, fins or <br />other obstructions. All drains including trap under utility sinks shall be copper <br />with soldered joints. No pipe shall be run exposed, unless approved by Publix <br />Representative. <br />3.6. Pipe Insulation <br />3.6.1 Sealed at all joints and seams with adhesive in accordance with insulation <br />manufacturer's recommendations. Pipe supports shall be on the outside of the <br />insulation with 6" minimum length saddles of galvanized sheet metal. <br />3.6.2 Fiberglass seams shall be sealed with factory furnished self sealing lap and butt <br />joints in accordance with manufacturer's recommendation. <br />3.6.3 Polyolefin seams shall be sealed with factory -furnished, self -adhering, pressure <br />sensitive seams. Butt joints shall also be glued with factory -furnished <br />adhesive. <br />3.7. Fixture Installation <br />3.7.1 Stub out to the exact location of the fixtures. All stubs shall be set <br />symmetrically with fixture. <br />3.7.2 Install fixtures and trim supplied by Publix or others. Connect to plumbing as <br />required. Finish out and trim fixtures as needed for complete installation. <br />3.7.3 Caulking: All plumbing fixtures shall be bedded and caulked along joint at <br />walls, and other intersecting surfaces with butyl caulking compound, counter <br />tops and brass shall be caulked with "plumbers putty". <br />3.7.4 Backing shall be of 2 x 6 pressure treated wood flush with stud face and <br />extending to next stud beyond fixture on each side. Secure as required <br />3.8. Inspection: <br />3.8.1 The Work shall be installed under the inspection and with the approval of <br />Publix' Authorized Representative. <br />3.8.2 Notify the Publix' Representative two days in advance of baclffilling, <br />enclosing, or covering all plumbing lines so that he may inspect installation. <br />3.8.3 Do not cover or enclose plumbing until inspection is made and installation is <br />acceptable. Correct deficiencies in installation as directed by Publix' <br />Representative. <br />3.9. Tests and Adjustments <br />3.9.1 All soil, waste, and vent piping shall be filled with water to the highest point in <br />each system with all air removed The lines shall be flushed by removing the <br />test plug. Piping may be tested in sections providing that all portions to be <br />concealed shall be subjected to not less than a 10 ft. head for 24 hours with no <br />leaks. Standpipe installed for head test shall be 2 in. minimum diameter. <br />3.9.2 Sewer piping shall be filled with water to it's highest point. <br />3.9.3 Water piping shall be flushed out, tested at 100 psi and shall be left under <br />pressure of supply main for the balance of the construction period. <br />3.9A Plumbing fixtures shall be filled with water and checked for leaks or retarded <br />flow. <br />3.9.5 All flush valves, loose key stops, valves and similar equipment shall be <br />adjusted and balanced to provide for the proper operation of the various <br />systems. <br />3.9.6 Each piece of plumbing equipment and the entire plumbing system shall be <br />adjusted and readjusted as required to insure proper functioning and shall be <br />left in first class operating condition. <br />3.9.7 Gas piping, shall be tested at 15 psi air pressure for 24 hours, in excess of the <br />requirements of NFPA 54. <br />3.10. Disinfection: <br />3.10.1 Purge system of all deleterious material before proceeding with disinfection. <br />a II <br />S U P E R M A R K E T S <br />CORPORATE OFFICES <br />FACILITIES DESIGN <br />BOX A07, LAKELAND, FL 33802 <br />(863) 680-5295 <br />PHYSICAL ADDRESS: <br />3300 AIRPORT RD., LAKELAND, FL 33811 <br />PUBLIX FACILITIES <br />DESIGN DEPARTMENT <br />DAVID TAULBEE, AIA <br />ARCHITECT - FL. REG. 91318 <br />DAVID RUBIN, AIA <br />ARCHITECT -FL. REG.92557 <br />GA. REG.] 1881 <br />SC. REG.7477 <br />AL. REG. 623A <br />JOHN W. KITCHENS, PE <br />CIVIL/STRUCTURAL- FL. REG. 45277 <br />GA. REG,020251 <br />SC. REG.16340 <br />AL. REG. 20382 <br />TN. REG. 101507 <br />PAUL C. HARMAN, PE <br />STRUCTURAL- FL. REG. 51959 <br />GA. REG.2774Q <br />SC. REG. 21754 <br />AL. REG.24905 <br />TN. REG.107882 <br />JOHN J. CARAMALIS, PE <br />MECHANICAL- FL. REG.43889 <br />GA. REG. 021246 <br />SC. REG.16521 <br />AL REG.20581 <br />TN.REG.108507 <br />ANTHONY CLEMENTI, PE <br />MECHANICAL • FL. REG. 54781 <br />GA. REG.31882 <br />SC.REG.25591 <br />AL. REG. 2SA69 <br />TN. REG. 111382 <br />RAYMOND J. SIRIANNI, PE <br />ELECTRICAL- FL. REG. 54085 <br />GA. REG. 025636 <br />SC. REG. 19743 <br />AL. REG. 23065 <br />TN.REG.108038 <br />NORMAN MEIER, PE <br />ELECTRICAL- FL REG.59422 <br />GA. REG. 31 d92 <br />SC. REG. 25290 <br />AL REG- 28079 <br />© COPYRIGHT 2008 <br />PUBLIX SUPER MARKETS, INC. <br />THESE CONSTRUCTION DOCUMENTS ARE THE <br />PROPERTY OF PUBLIX SUPER MARKETS, INC. AND <br />ARE NOT TO BE COPIED OR REUSED FOR ANY <br />SPECIFIC BUILDING WITHOUT WRITTEN PERMISSION. <br />THESE DRAWINGS SHALL NOT BE DUPLICATED <br />WITHOUT PRIOR WRITTEN PERMISSION OF <br />PUBLIX SUPER MARKETS, INC. <br />THE DESIGN INDICATED IN THESE CONSTRUCTION <br />DOCUMENTS DOES, TO THE BEST OF MY KNOWLEDGE, <br />INFORMATION, AND BELIEF, COMPLY WITH THE <br />APPLICABLE MINIMUM BUILDING CODES <br />PLOT DATE: <br />]0 JAN 08 <br />REVISION DATA: <br />#12A5 (REPL. #0390) <br />ZEPHYR COMMONS <br />PRETTY POND RD. <br />& HWY. 301 <br />ZEPHYRHILLS, PASCO CO., <br />FLO.RI DA <br />54.4 <br />DRAWING TITLE: <br />Version 07.2 <br />