ELECTRICAL NOTES: <br />1. GFCI'S ARE TO BE INSTALLED IN THE FOLLOWING <br />LOCATIONS AS SPECIFIED PER NFPA 70 (NEC) 2017 <br />A) BATHROOMS <br />B) GARAGES, AND ALSO ACCESSORY BUILDINGS THAT <br />HAVE A FLOOR LOCATED AT OR BELOW GRADE LEVEL <br />NOT INTENDED AS.HABITABLE ROOMS AND LIMITED TO <br />STORAGE AREAS, WORK AREAS, AND AREAS OF <br />SIMILAR USE. <br />C) CRAWL SPACES AT OR BELOW GRADE. <br />D) KITCHENS - WHERE THE RECEPTACLES ARE <br />INSTALLED TO SERVE THE COUNTERTOP SURFACES. <br />E) LAUNDRY, UTILITY, AND WET BAR SINKS - WHERE <br />THE RECEPTACLES ARE INSTALLED WITHIN 6 FEET OF <br />THE OUTSIDE EDGE OF THE SINK. <br />2. ARCH FAULT OUTLETS ARE REQUIRED PER NFPA 70 <br />(NEC) 2017, INCLUDING ARTICLES 210 AND 400. <br />3. ANY CONFLICTS BETWEEN LOCATION OF <br />MECHANICAL FIXTURES ON PLANS AND THE ABILITY TO <br />LOCATE THEM IN THE FIELD MUST BE REPORTED TO THE <br />ARCHITECT PRIOR TO INSTALLATION. <br />4. RECEPTACLE OUTLETS IN GARAGE MUST BE <br />SERVED BY SEPARATE BRANCH CIRCUIT THAT DOES NOT <br />SUPPLY OTHER OUTLETS. <br />5. CM MUST BE AT LEAST 3' FROM BATH DOOR AND AT <br />LEAST 6'FROM KITCHEN RANGE/OVEN. <br />NOTES: <br />UNLESS OTHERWISE NOTED <br />1. ELECTRICAL OUTLET HEIGHTS AS MEASURED FROM FINISHED <br />FLOOR TO CENTERED LINE OF THE BOX TO BE: 12" AFF <br />(GENERAL) <br />KITCHEN <br />44" AFF <br />BATHROOM <br />39" AFF <br />LAUNDRY ROOM <br />36" AFF <br />EXTERIOR WATERPROOF <br />12" AFF <br />GARAGE GENERAL PURPOSE <br />42" AFF <br />RANGE <br />2" AFF <br />2. ALL TRIM PLATES & DEVICES TO BE GANGED, WHERE <br />POSSIBLE. <br />3. ELECTRICAL SWITCHES TO BE AT 42" CENTERLINE ABOVE <br />FINISHED FLOOR <br />4. ELECTRICAL PLAN IS INTENDED FOR BID PURPOSES ONLY <br />ALL WORK SHALL. BE DONE IN STRICT ACCORDANCE WITH T�E <br />NATIONAL ELECTRIC CODE, LATEST EDITION, BY A LICENSED <br />ELECTRICAL CONTRACTOR WHO SHALL BE RESPONSIBLE FOR <br />THE INSTALLATION & SIZING OF ALL ELECTRICAL, WRING & <br />ACCESSORIES. <br />5. SMOKE DETECTORS SHALL BE INSTALLED AS DIRECTED BY <br />THE 2016 NFPA 72 NATIONAL FIRE ALARM CODE. <br />6. ALL ELECTRICAL IN THE LIVING ROOMS, DINING ROOMS, <br />SUNROOMS, FAMILY ROOMS, DENS, LIBRARIES, SLEEPING ROOMS, <br />PARLORS AND SIMILAR ROOMS OR AREAS SHALL BE ON AN A.F.C.I. <br />PROTECT CIRCUIT PER NFPA 70 (NEC) 2017. <br />7. IN ALL AREA SPECIFIED IN NFPA 70 (NEC) 2017 210.52, ALL 125 <br />VOLT, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED <br />TAMPER -RESISTANT RECEPTACLES. <br />SECOND FLOOR ELECTRICAL PLAN (ALL ELEVATIONS) <br />1/411 = 1 1-011 <br />ELECTRICAL DETAIL: <br />INTERCOM <br />SPEAKER <br />ALIGNED W/ <br />EDGE OF <br />SWITCH--,,-- <br />SWITCH- <br />4 1/2" <br />DUPLEX <br />DOORJAMB 19 <br />OUTLET 2�) <br />TRIM — <br />BASE --- <br />NOTE: <br />ALL DIMENSIONS ARE FROM ROUGH FRAMING <br />I SMOKE DETECTOR LOCATION: <br />I s <br />�c_'SMOKE DETECTOR <br />MIN, <br />ELECTRICAL LEGEND: <br />NOTE: ALL HEIGHTS ABOVE FINISH FLOOR <br />11 OV DUPLEX OUTLET AT 12" <br />11 OV DUPLEX OUTLET AT 39" NOTE: ALL <br />RECEPTACLES <br />11 OV DUPLEX OUTLET AT 43" ABOVE <br />COUNTERS <br />11 OV DUPLEX OUTLET AT 45" SHALL BE <br />SPLIT 11 OV DUPLEX OUTLET MOUNTED <br />AT 12" - TOP PLUG IS HOT HORIZONTAL <br />11 OV QUAD OUTLET AT 12" <br />WEATHERPROOF GFCI OUTLET AT 12" <br />@E 220V OUTLET AT 30" <br />jj= 11 OV DUPLEX FLOOR OUTLET <br />OUTLET -VERIFY W/MANUF. SPECS <br />FOR LOCATION & TYPE <br />TELEPHONE OUTLET AT 12" OR AS NOTED <br />TELEVISION OUTLET AT 12" - WIRE FOR <br />CABLE & SATELLITE <br />STRUCTURED WIRE OUTLET <br />SWITCH AT 3611 <br />69 3 WAY SWITCH AT 36" <br />-W- 4 WAY SWITCH AT 36" <br />-0 PUSH BUTTON FOR GARAGE DOOR OPENER <br />DIMMER SWITCH AT 36" <br />PUSH-BUTTON DOORBELL <br />CLG MNT LT FIXTURE <br />CLG MNT PREWIRE - FIXTURE BY OWNER <br />SURFACE MNT FIXTURE <br />WALL MNT FIXTURE NOTE: <br />40W A 6" ROUND OPALEX - ALTERNATE <br />3 TUB/SHOWER CANS MAY BE <br />40 50W PAR30 NFL 6" WHITE BAFFLE USED IF <br />APPROVED BY <br />06 50W MR1 6 4" LOW VOLTAGE OWNER <br />08 50W PAR20 NFL 4" MINI ROUND RECESS <br />010 50W PAR20 NFL 6" RD REGRESSED BAFFLE EYEBALL <br />-0 CLG FAN PREWIRE AND SWITCH <br />Cos COMBINATION CARBON MONOIXED DETECTOR/ <br />SMOKE DETECTOR <br />os SMOKE DETECTOR <br />cU-18m UNDER CABINET 18" <br />cS-18= SINGLE 18" FLUOR STRIP <br />=U-24= UNDER CABINET 24" <br />=S-24= SINGLE 24" FLUOR STRIP <br />-D-24= DOUBLE 24" FLUOR STRIP <br />- U-36 - UNDER CABINET 36" <br />- S-36 - SINGLE 36" FLUOR STRIP <br />- D-36 - DOUBLE 36" FLUOR STRIP <br />—S-48— SINGLE 48" FLUOR STRIP <br />--- D-48 DOUBLE 48" FLUOR STRIP <br />24"CLG MNT WRAPPED FLUOR LIGHT <br />1 48 48"CLG MNT WRAPPED FLUOR LIGHT <br />9-m 24:R 24" VANITY LIGHTING <br />9;;F 36:;;R 36" VANITY LIGHTING <br />48 48" VANITY LIGHTING <br />EXHAUST FAN/LIGHT <br />Q EXHAUST FAN <br />ZC� DOUBLE FLOOD LIGHT W/ COVERS AND <br />15OW PAR 38 FL <br />INTERCOM SPEAKER AT 6-0" ABV FINISH FLOOR <br />CEILING MNT SPEAKER <br />M CHIMES (DELETE W/ INTERCOM) <br />= MASTER STATION <br />IN&] ELEC PANEL <br />VACUM OUTLET AT 12" <br />CEILING RETURN AIR <br />ED A/C REGISTER <br />THERMOSTAT <br />SECURITY PAD <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR LOCATION PURPOSES. <br />ee <br />-Z <br />0 <br />U., <br />0 <br />cz <br />L*1 <br />a) LO, E <br />C c, <br />IN o <br />%00 u <br />Cy) cq <br />4— <br />V) <br />c) P <br />D C3 0100 z In <br />U _0 -0 r— —0 c" <br />C: <br />E -= 2 cm) <br />:) 0 2 8 <br />75 M: 8 9 < <br />U ". a) < <br />(D <br />C3 <br />uj o _" c: <br />cO <br />0 E �2 <br />000 <br />CL <br />LIJ Lu <br />LU <br />C6 ui 0 <br />L-u �U_j W W zo W <br />W z <br />LU < < o 0 <br />9 2 _.' o ?� LL 0 LL <br />< <br />j <br />a R _j (1) W (n <br />0 00 <br />j OgZLLLL-zm-j <br />9zowoomoz <br />OWWW Z <br />OWEL8wWwwoww<o� <br />:0 L) <br />0 0 <br />o z <br />_j (D IL z �2 o I- z LL 0 <br />I < < W I z <br />F- mc) <br />W _5 <br />C, CL <br />LL <br />0 W F- � W <br />�4 z <br />0 D 0 9 <br /><L <br />< <br />� < <br />LL 0 LL <br />c:) <br />0 <br />z 04 <br />Lu <br />J P. <br />> C/) 0 <br />(o c:) <br />z <br />Fz cv) a <br />co P_ <br />u') <br />_j <br />C/) <br />LL <br />z <br />Lij < u� <br />cy) <br />00 <br />Z C) <br />z <br />W <br />W <br />_j Q <br />c:) <br />A <br />(o <br />0 <br />N <br />0 <br />N <br />a <br />N <br />N <br />N <br />N <br />0 <br />N <br />CD <br />N <br />C-14 <br />C'\1 <br />0 <br />0 <br />CD <br />0 <br />0 <br />0 <br />0 <br />N <br />W> <br />C_� <br />0 <br />0 <br />C1 <br />0 <br />Lo <br />Lo <br />. <br />C4 <br />c'i <br />4 <br />6 <br />6 <br />qq <br />cr <br />co <br />Z F- <br />< Z <br />LLI <br />C) 4_0 <br />W <br />Z U) <br />z z <br />coo <br />4-1 <br />o <br />C) <br />w - <br />() 0 (n <br />Lo <br />F- <br />0 <br />=) z 5; <br />own <br />0�< <br />z <br />W-EL <br />x <br />Lr) <br />LIJ F- <br />LU F <br />Lr) <br />Co & Lu <br />F- <br />r'-4 <br />I= <br />0 0 <br />z6m <br />W <br />>_ z: U) <br />00 <br />0 <br />zaco <br />:5 Lu W <br />Z U. <br />z <br />a. <br />U) z <br />< <br />3e. <br />z <br />L) <br />< <br />0 0 <br />cn <br />z <br />A602 <br />z <br />W <br />0) <br />>0 <br />LAST PLOT DATE <br />. a <br />April 4, 2023 <br />z <br />0 <br />2ND FLOOR <br />ELECTRICAL PLAN <br />ABKL&M <br />