Laserfiche WebLink
ELEC <br />METER <br />FIRST FLOOR ELECTRICAL PLAN (ELEVATIONS A & B <br />1 /411 = 1'-0„ <br />A/C <br />DISCONNECT <br />WP <br />GFI <br />ELECTRICAL NOTES: <br />1. GFCI'S ARE TO BE INSTALLED IN THE FOLLOWING <br />LOCATIONS AS SPECIFIED PER NFPA 70 (NEC) 2017 <br />A) BATHROOMS <br />B) GARAGES, AND ALSO ACCESSORY BUILDINGS THAT <br />HAVE A FLOOR LOCATED AT OR BELOW GRADE LEVEL <br />NOT INTENDED AS HABITABLE ROOMS AND LIMITED TO <br />STORAGE AREAS, WORK AREAS, AND AREAS OF <br />SIMILAR USE. <br />C) CRAWL SPACES AT OR BELOW GRADE. <br />D) KITCHENS - WHERE THE RECEPTACLES ARE <br />INSTALLED TO SERVE THE COUNTERTOP SURFACES. <br />E) LAUNDRY, UTILITY, AND WET BAR SINKS - WHERE <br />THE RECEPTACLES ARE INSTALLED WITHIN 6 FEET OF <br />THE OUTSIDE EDGE OF THE SINK. <br />2. ARCH FAULT OUTLETS ARE REQUIRED PER NFPA 70 <br />(NEC) 2017, INCLUDING ARTICLES 210 AND 400. <br />3. ANY CONFLICTS BETWEEN LOCATION OF <br />MECHANICAL FIXTURES ON PLANS AND THE ABILITY TO <br />LOCATE THEM IN THE FIELD MUST BE REPORTED TO THE <br />ARCHITECT PRIOR TO INSTALLATION. <br />4. RECEPTACLE OUTLETS IN GARAGE MUST BE <br />SERVED BY SEPARATE BRANCH CIRCUIT THAT DOES NOT <br />SUPPLY OTHER OUTLETS. <br />5. CM MUST BE AT LEAST 3' FROM BATH DOOR AND AT <br />LEAST 6' FROM KITCHEN RANGE/OVEN. <br />NOTES: <br />UNLESS OTHERWISE NOTED <br />1. ELECTRICAL OUTLET HEIGHTS AS MEASURED FROM FINISHED <br />FLOOR TO CENTERED LINE OF THE BOX TO BE: 12" AFF <br />(GENERAL) <br />KITCHEN <br />44" AFF <br />BATHROOM <br />39" AFF <br />LAUNDRY ROOM <br />36" AFF <br />EXTERIOR WATERPROOF <br />12" AFF <br />GARAGE GENERAL PURPOSE <br />42" AFF <br />RANGE <br />2" AFF <br />2. ALL TRIM PLATES & DEVICES rO BE GANGED, WHERE <br />POSSIBLE. <br />3. ELECTRICAL SWITCHES TO BE AT 42" CENTERLINE ABOVE <br />FINISHED FLOOR <br />4. ELECTRICAL PLAN IS INTENDED FOR BID PURPOSES ONLY. <br />ALL WORK SHALL. BE DONE IN STRICT ACCORDANCE WITH THE <br />NATIONAL ELECTRIC CODE, LATEST EDITION, BY A LICENSED <br />ELECTRICAL CONTRACTOR WHO SHALL BE RESPONSIBLE FOR <br />THE INSTALLATION & SIZING OF ALL ELECTRICAL, WIRING & <br />ACCESSORIES. <br />5. SMOKE DETECTORS SHALL BE INSTALLED AS DIRECTED BY <br />THE 2016 NFPA 72 NATIONAL FIRE ALARM CODE. <br />6. ALL ELECTRICAL IN THE LIVING ROOMS, DINING ROOMS, <br />SUNROOMS, FAMILY ROOMS, DENS, LIBRARIES, SLEEPING ROOMS, <br />PARLORS AND SIMILAR ROOMS OR AREAS SHALL BE ON AN A.F.C.I. <br />PROTECT CIRCUIT PER NFPA 70 (NEC) 2017. <br />7. IN ALL AREA SPECIFIED IN NFPA 70 (NEC) 2017 210.52, ALL 125 <br />VOLT, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED <br />TAMPER -RESISTANT RECEPTACLES. <br />METER <br />MAIN <br />0 <br />200 amp <br />150 amp <br />Disconnect <br />POWER CO. FEED <br />200A INDOOR PANEL <br />CENTER <br />#15 copper to lights & outlets <br />#12 copper to 20 amp ckts <br />#10-2 copper to WH <br />#10-3 copper to Dryer <br />2/0 or 4/0 SER Alu <br />4 Bare Cu Ground <br />Footer STEEL <br />Groundrod tied to footer steel <br />OR <br />4 Bare attached to footer steel <br />GROUNDING PER 250.50 AND <br />250.52 NEC <br />TYPICAL 150-200 AMP ELECTRICAL RISER DIAGRAM <br />NTS <br />CT 8 2022 <br />Virtual Review Assist. Inc. <br />Mans Review completed and approved <br />for compliance with the 2020 FOC 7th Ed Ion <br />by Oebra Anne Klahr PX2300 <br />ELECTRICAL DETAIL: <br />INTERCOM <br />SPEAKER <br />ALIGNED W/ <br />EDGE OF <br />SWITCH <br />io <br />SWITCH ° <br />4 1/2" <br />DOORJAMB DUPLEX <br />OUTLET Fh <br />TRIM <br />BASE <br />NOTE: <br />ALL DIMENSIONS ARE FROM ROUGH FRAMING <br />SMOKE DETECTOR LOCATION: <br />WALL <br />oZ <br />kS <br />SMOKE DETECTOR <br />V-0" <br />MIN. <br />ELECTRICAL LEGEND: <br />NOTE: ALL HEIGHTS ABOVE FINISH FLOOR <br />110V DUPLEX OUTLET AT 12" <br />110V DUPLEX OUTLET AT 39" NOTE: ALL <br />RECEPTACLES <br />110V DUPLEX OUTLET AT 43" ABOVE <br />COUNTERS <br />110V DUPLEX OUTLET AT 45" SHALL BE <br />SPLIT 110V DUPLEX OUTLET MOUNTED <br />AT 12" - TOP PLUG IS HOT HORIZONTAL <br />110V QUAD OUTLET AT 12" <br />WEATHERPROOF GFCI OUTLET AT 12" <br />220V OUTLET AT 30" <br />110V DUPLEX FLOOR OUTLET <br />OUTLET - VERIFY W/MANUF. SPECS <br />FOR LOCATION & TYPE <br />TELEPHONE OUTLET AT 12" OR AS NOTED <br />TELEVISION OUTLET AT 12" - WIRE FOR <br />CABLE & SATELLITE <br />STRUCTURED WIRE OUTLET <br />-6- SWITCH AT 36" <br />6 3 WAY SWITCH AT 36" <br />-641- 4 WAY SWITCH AT 36" <br />.0 PUSH BUTTON FOR GARAGE DOOR OPENER <br />--o DIMMER SWITCH AT 36" <br />- fl PUSH-BUTTON DOORBELL <br />CLG MNT LT FIXTURE <br />-}- CLG MNT PREWIRE - FIXTURE BY OWNER <br />SURFACE MNT FIXTURE <br />-- WALL MNT FIXTURE <br />NOTE: <br />C ND OPALEX - ALTERNATE <br />TUB/SHOWERCANS MAY BE <br />(4� 50W PAR30 NFL 6" WHITE BAFFLE USED IF <br />APPROVED BY <br />50W MR16 4" LOW VOLTAGE OWNER <br />50W PAR20 NFL 4" MINI ROUND RECESS <br />0' 50W PAR20 NFL 6" RD REGRESSED BAFFLE EYEBALL <br />-0 CLG FAN PREWIRE AND SWITCH <br />COMBINATION CARBON MONOIXED DETECTOR/ <br />Cos SMOKE DETECTOR <br />C SMOKE DETECTOR <br />cU-18= UNDER CABINET 18" <br />=S-18= SINGLE 18" FLUOR STRIP <br />=U-24= UNDER CABINET 24" <br />=S-24= SINGLE 24" FLUOR STRIP <br />=D-24= DOUBLE 24" FLUOR STRIP <br />U-36 = UNDER CABINET 36" <br />S-36 = SINGLE 36" FLUOR STRIP <br />= D-36 = DOUBLE 36" FLUOR STRIP <br />S-48 SINGLE 48" FLUOR STRIP <br />D-48 DOUBLE 48" FLUOR STRIP <br />24 24"CLG MNT WRAPPED FLUOR LIGHT <br />48 48"CLG MNT WRAPPED FLUOR LIGHT <br />�_" 24 :P 24" VANITY LIGHTING <br />97-- 36 36" VANITY LIGHTING <br />48 48" VANITY LIGHTING <br />® EXHAUST FAN/LIGHT <br />0 EXHAUST FAN <br />4p DOUBLE FLOOD LIGHT W/ COVERS AND <br />U 150W PAR 38 FL <br />® INTERCOM SPEAKER AT 5'-0" ABV FINISH FLOOR <br />O CEILING MNT SPEAKER <br />I3 CHIMES (DELETE W/ INTERCOM) <br />= MASTER STATION <br />11115ZI ELEC PANEL <br />VACUM OUTLET AT 12" <br />CEILING RETURN AIR <br />® A/C REGISTER <br />THERMOSTAT <br />011 SECURITY PAD <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR LOCATION PURPOSES. <br />o <br />M00 U <br />W 2 <br />N <br />In <br />V O O2 u a <br />E` La <br />Zoo 2g <br />p ti a C Q <br />'0? < <br />•— <br />to <br />�1 <br />w O <br />QN C <br />7W� <br />V <br />60 O E � <br />~ a <br />LLI W <br />W <br />0 LLI Uj W 0 <br />H~ X�_j X< <XYzIY Z <br />x 2-, d�WLL00p_jO <br />Q Q <br />I- <br />U <br />H <br />J a) (% <br />> O O d z LL LL 0 z M 0 O~ d d <br />oLu WozowoImz: U <br />of <br />O <br />Z <br />cn o- cn w w cn Q d <br />Q<Qpw<— LUZOwaoa. <br />LL <br />Ow �E-� 2W2i Q <br />OQ OQ d <br />o <br />LL H d LL <br />i <br />O <br />Z N <br />OF_ <br />D 5 t.- <br />M O <br />QOn M � <br />U-- ti <br />F-�0-c'r) <br />�0-�� <br />00 <br />ZV< <br />W <br />W <br />JQ <br />M <br />CO <br />co <br />I <br />I <br />I <br />I <br />I <br />I <br />� <br />I <br />C)O <br />O <br />O <br />p <br />N <br />O <br />N <br />O <br />N <br />N <br />C)o <br />N <br />O <br />= <br />rn <br />Co <br />N <br />C4 <br />C <br />C,C)00 <br />Z <br />Co <br />0 <br />o <br />o <br />' <br />O <br />N'^ <br />Lr) <br />w ♦ <br />W <br />W <br />o <br />0 <br />cV <br />0 <br />ri <br />0 <br />v <br />0 <br />Lri <br />'q- <br />co <br />N <br />Q z <br />C)w <br />z <br />1- 0 <br />O <br />W <br />W O O <br />UU U <br />O <br />O F- <br />�� <br />Q <br />Z <br />I-- <br />fu � m <br />Q <br />Lr) <br />= <br />(' <br />m=W <br />L <br />I-F-2 <br />N <br />zo= <br />N <br />W <br />CF- <br />mo <br />O <br />zwo <br />0a. <br />z <br />Z <br />Z <br />� z <br />F- <br />pU <br />_oa <br />W <br />z <br />c' <br />W <br />� <br />Wco <br />CD <br />0 <br />Q <br />LAST PLOT DATE <br />O <br />• <br />August 8, 2022 <br />z <br />0 <br />1 ST FLOOR <br />'= <br />ELECTRICAL PLAN <br />