ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />F�FG.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />ITIZZv <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />© <br />RECESSED LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />Q <br />EXHAUSTFAN <br />�Q% <br />R. <br />EXHAUST FAN/LIGHT COMBINATION <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />TELEVISION (OPTIONAL) <br />F 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />' <br />ELECTRIC METER <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />� 7 <br />G J <br />ROUGH -IN FOR OPT. CEILING FAN <br />G ' J <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />OPT. CEILING FAN <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />J I <br />j'' / ► ► HANSON <br />► BOX <br />i I <br />_ I I <br />LAV T� ► W/C <br />j I 3" SHOWER <br />L TUB/ <br />W/C SHOWER <br />STUDOR F\R• <br />VENT DBL SINK <br />W/ DISP. <br />2" <br />LAV W/C z <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />UNIT -A 1532 (1532) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1533 S.F. <br />4599 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10599 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33659 <br />1st 10 KW at 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9464 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />5200 <br />TOTAL: 31768 <br />LOAD WATTS --- 240 VOLTS <br />AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Optional Overhead Service 200A <br />Same As Underground Indoor Panel <br />150 Or 200 Amp Service Center <br />NEMA 1 <br />200 AMP <br />ETER MA N <br />1 0-200 A P j Serial Cable <br />3R <br />Power Co. Feed ---- Id I #4 Solid COPPER Ground <br />ELECTRICAL SPECIFICATION NOTES: <br />3 VTR <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />I <br />I OPT. <br />LAV <br />LAV <br />I I <br />(� <br />I <br />W67 <br />II <br />Intersystem Bonding <br />Termination Per <br />NEC 17, 250.94 5/8" Galvanized Driven Ground <br />Rods at least 6' apart <br />Typical 150-200 Amp Electrical Riser liagram <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 - 17, LOCAL CODES AND THE LOCAL POWER CC). <br />DB & GFI TO <br />BE ALIGNED <br />VERTICALLY <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />DISCONNECT <br />1ST ELECTRICAL — UNIT —A 1532 <br />SCALE: X"=T-0" <br />DEDICATED RECEPTACLE <br />FOR MICROWAVE RANGE <br />HOOD PER SPECS <br />F_— — — — — — — — —I <br />OWNER'S <br />BEDROOM <br />/,>ROUGH -IN <br />FOR OPT. <br />FAN/LIGHT <br />\ <br />\� I <br />I <br />S.D <br />0. BATH <br />BATH 2 <br />N. <br />WIC _ <br />1 <br />I <br />I <br />------------- <br />— — — — — — — — — — , <br />I <br />I <br />\\ /PC! <br />L \V/ JV Y I C I <br />\ L <br />I <br />LOFT `� <br />G <br />\ <br />L — <br />Al <br />S.D. <br />'T7 (ID <br />I <br />1 <br />/^TROUGH -IN <br />FOR OPT. <br />FAN/LIGHT <br />\BEDROOM 2 <br />2ND ELECTRICAL — UNIT —A 1532 <br />SCALE: Ya'=T-0" <br />(.3 d <br />.,..._ <br />� CC �Z _ <br />N E;- <br />CID <br />a u <br />0 <br />CN <br />CV <br />N <br />0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida Building <br />Code - <br />Residential 7th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />a) <br />M <br />N <br />Ch <br />Q N <br />H <br />r <br />N O <br />fii � M V• <br />a <br />J , <br />J U U_ <br />a <br />_ <br />Z r <br />W <br />EL <br />YaN <br />N <br />oY <br />W 01° <br />W co�6jO' <br />m w <br />IL Z NZ <br />Q J <br />ZN o i i <br />OEMW <br />c¢i U) <br />z N M <br />o $ <br />z <br />z <br />J <br />N <br />M <br />Riww <br />U <br />0 L S <br />N <br />' ^ <br />m <br />wwin <br />l0 O <br />I <br />=♦� L N <br />V O y <br />ts, <br />� <br />C1 <br />w <br />co <br />z <br />U_ <br />a E <br />Q <br />=z <br />� -z <br />os <br />wz <br />> � <br />�® <br />F— r6 <br />.. <br />Wa <br />D i; <br />C <br />O C <br />CV <br />a�U0. <br />Qz <br />o <br />°¢ <br />WZ <br />L <br />4 <br />m <br />C <br />OY <br />�m <br />O <br />ZZ <br />>z <br />Z <br />N <br />oa <br />go <br />W <br />Q <br />LL <br />�0 <br />a <br />ww <br />U <br />�� <br />oLL <br />�- <br />�3 <br />2 y <br />= H <br />K � <br />CCD <br />F-~ <br />a0 <br />cF <br />D <br />0 3 <br />c O <br />Q <br />>C.0 <br />o' <br />N <br />O <br />r <br />L <br />� <br />cM <br />('� <br />N <br />LA-) <br />CN <br />Cr <br />60 <br />^�U <br />U) <br />0*4 <br />N <br />LO <br />t=— <br />0 <br />r--� <br />N <br />L0 <br />� <br />.Q O <br />C� <br />N <br />04 <br />co <br />r M <br />,-- <br />! r <br />C:) <br />o <br />z <br />(6 <br />z <br />7 Vl <br />E CV T7 <br />m <br />d <br />E n °) <br />U Q p <br />c <br />c <br />JOB <br />NO: 22-08387-08382 <br />SCALE : AS NOTED <br />SHEET NO. <br />11.1 <br />F1 _ITT— —I- - <br />