Laserfiche WebLink
ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11.In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />w P <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />I <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />3 <br />THREE-WAY SWITCH <br />?4 <br />FOUR-WAY SWITCH <br />�R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />Q <br />EXHAUST FAN <br />'TWOEXHAUST <br />FAN/LIGHT COMBINATION <br />®D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />5 <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />D9 <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />© <br />TELEVISION (OPTIONAL) <br />TV 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />M <br />ELECTRIC METER <br />owl <br />PANEL <br />i <br />DISCONNECT SWITCH <br />G J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G J <br />OPT. CEILING FAN <br />G�) <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />j - I HANSON <br />BOX <br />I I <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />I <br />OPT. <br />LAV <br />LAV <br />I �.1 <br />I I <br />Ii -1-1W/C <br />LAV <br />,U 1 3° SHOWER <br />TUB/ <br />W/C SHOWER <br />STUDOR <br />VENTI 1 DBL SINK <br />TI W/ DISP. <br />LAV I W/C <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />UNIT-C 1624 (1624) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1625 S.F. <br />4875 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10875 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />SUBTOTAL: 23060 <br />TOTAL: 33935 <br />1st 10 KW at 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9574 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />5200 <br />TOTAL: 31878 <br />LOAD WATTS --- 240 VOLTS <br />r AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Optional Overhead Service 200A <br />Same As Underground Indoor Panel <br />150 Or 200 Amp Service Center <br />NEMA1 <br />200 AMP <br />� =TC� AAA Ai <br />1 0-200 A P Serial Cable <br />NEMA <br />3R <br />Power Co. Feed - I I L 'r #4 Solid COPPER Ground <br />(I <br />Intersystem Bonding <br />Termination Per <br />NEC 17, 250.94 5/8" Galvanized Driven Ground <br />Rods at least 6' apart <br />Typical 150-200 Amp Electrical Riser Diagram <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 - 17, LOCAL CODES AND THE LOCAL POWER CO. <br />C.O. <br />DB & GFI TO <br />BE ALIGNED <br />VERTICALLY <br />0 <br />------------------------- <br />OUTDOOR LIVING <br />INSTALL LIGHT �\��> <br />ROUGH -IN <br />FOR OPT.� <br />FAN/LIGHT i J N GFI <br />.n% <br />QV QDGFI <br />_ I <br />1 <br />DINING <br />KITCHEN I <br />I <br />FI 0 <br />GFI <br />SWITCH FOR <br />DISPOSAL IN CAB <br />UNDER SINK <br />GREAT ROOM <br />/,,>ROUGH -IN\ <br />FOR OPT. <br />FAN/LIGHT' <br />r� <br />I <br />*\ <br />VTRY Iv <br />GHT AS 0 <br />=R SPECS <br />I <br />f <br />I <br />W <br />W <br />L <br />Al i <br />I <br />I <br />I <br />I <br />I <br />I <br />,q1_� <br />C.M <br />DISCONNECT <br />►:DEDICATED <br />p�0RECEPTACLE . <br />♦. MICROWAVE <br />.m. <br />4 RANGE <br />SPECS <br />►'�' <br />►A! <br />1 UPSTAIRS r <br />GFI <br />@ 44" <br />` \ <br />W.H. <br />A.F.F. <br />' <br />` 0 <br />I <br />(GARAGE <br />1 <br />GARAGE <br />LIGHT AS <br />PER SPECS <br />GARAGE <br />DOOR <br />GFI <br />r----------------- <br />I I <br />I <br />I <br />J <br />I <br />I <br />IpUJ <br />Z <br />I <br />ip Q <br />IQ a <br />I <br />I <br />ID Q <br />I <br />IW J <br />I <br />5 W <br />I <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />1ST ELECTRICAL - UNIT-C 1624 <br />SCALE: Y4"=1'-0" <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />2ND ELECTRICAL - UNIT-C 1624 <br />SCALE: X"=1'-0" <br />e <br />00 <br />as <br />� w <br />Q <br />C (4 C? N <br />�+ -a j- <br />3 m <br />I� <br />`. E <br />Ei v <br />N <br />0 <br />0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural <br />plans and specifications contained within <br />these <br />drawings comply with the 2020 <br />Florida Building Code <br />- <br />Residential 7th Edition. Engineer's signature and seal <br />is only <br />for <br />the structural <br />engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />WWv <br />EE <br />O M 8 <br />N 26 's)WN <br />0 <br />N <br />C? <br />h <br />0 <br />J <br />"iVZpi <br />c <br />� V LL <br />2 <br />C—i LL� L�U <br />la.Ji <br />. <br />W <br />� FU 04 o O <br />Z <br />C/5 T m W <br />L mZ ¢ J <br />Z <br />N O U U <br />W <br />110 <br />0 <br />V M n <br />Z N M <br />0 0 <br />z <br />^ <br />M <br />z �O <br />X4-j <br />LL <br />w m <br />0 <br />L L' s <br />Gn <br />w <br />� <br />allw <br />J E <br />i.i o <br />III Ij'i <br />c W <br />— <br />¢ N � <br />sm <br />o <br />W <br />co <br />Jz <br />o <br />U- <br />E <br />iZ O <br />w <br />z <br />oa <br />rd <br />XO <br />00 <br />0 <br />O E <br />CD <br />N <br />ap <br />ao <br />¢ <br />aZ <br />�W <br />L <br />Ui ♦_Y <br />O <br />0 <br />mro <br />O <br />z <br />- C <br />N <br />om <br />z <br />¢w <br />�z <br />S� <br />gz <br />a`ni <br />uw <br />a <br />r_w <br />U <br />'p <br />Nw <br />Z <br />r� <br />o <br /><a <br />0 <br />;o <br />CD co <br />�w <br />a ti <br />= O <br />—17 <br />a� <br />N <br />N <br />Co <br />N <br />LO <br />N <br />T <br />Cr <br />U <br />00 <br />m <br />C'V <br />4-1 <br />!— <br />0 <br />iLn <br />04 <br />O <br />-0 <br />04 <br />y <br />1 <br />r <br />O <br />o <br />z <br />cc <br />Z <br />E N <br />is <br />rcc <br />CoE <br />o m <br />0, <br />U J <br />Q <br />J <br />JOB <br />NO: 22-08387-08382 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />11.2 <br />