ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />comer counters. <br />ELECTRICAL KEY <br />L <br />DUPLEX CONVENIENCE OUTLET <br />PqF <br />DUPLEX OUTLET ABOVE COUNTER <br />FEFw.P. <br />WEATHERPROOF DUPLEX OUTLET <br />tt�G <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$,3 <br />THREE-WAY SWITCH <br />24 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />} O <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />--� <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />lO <br />EXHAUSTFAN <br />;Q <br />P. <br />EXHAUST FAN/LIGHT COMBINATION <br />�D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />TELEVISION (OPTIONAL) <br />© 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />]M <br />ELECTRIC METER <br />awl <br />PANEL <br />—� <br />DISCONNECT SWITCH <br />G J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G J <br />OPT. CEILING FAN <br />GD <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />3" VTR AIL <br />JIC. <br />I I <br />I <br />I I <br />I I <br />--I I OPT. <br />I I <br />I I LAV <br />LAV <br />j I HANSON I <br />BOX I <br />I i ` <br />W/C <br />LAV <br />SHOWER <br />til TUB/ <br />W/C SHOWER -� <br />3rr \'end F, fi�R <br />STUDOR <br />VENT DBL SINK <br />W/ D, <br />SP. <br />2" <br />LAV W/C err <br />r <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />Unit -A- (1532) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1533 S.F. <br />4599 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10599 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />OTHER LOAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33659 <br />1st 10 KW at 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9464 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />1 5200 <br />TOTAL: 31768 <br />LOAD WATTS --- 240 VOLTS <br />I AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />)ptional Overhead Service 200A <br />tame As Underground Indoor Panel <br />50 Or 200 Amp Service Center <br />P I NEMA1 <br />200 AMP <br />n Tco n." ni <br />1 �0-200 AMP I I T /-Serial Cable <br />Power Co. Feed --\ <br />1-1 Lit— #4 Solid COPPER Ground <br />11 <br />Intersystem Bonding <br />Termination Per <br />NEC 08, 250.94 5/8" Galvanized Driven Ground <br />Rods at least 6' apart <br />typical 150-200 Amp Electrical Riser Diagram <br />TOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />'HE NFPA 70 - 17, LOCAL CODES AND THE LOCAL POWER CO. <br />C.O. <br />DB & GFI TO <br />BE ALIGNED <br />VERTICALLY <br />O <br />- OUTDOORLIVING <br />INSTALL LIGHT �`��> <br />ROUGH -IN <br />FOR OPT. <br />FAN/LIGHT GFI <br />rrn <br />DISCONNECT <br />dbGFI <br />DEDICATED <br />jGFI RECEPTACLE FOR <br />MICROWAVE <br />I RANGE HOOD PER <br />DINING I SPECS <br />IP <br />KITCHEN) <br />1 <br />171 <br />I <br />FI I 0 rSaFJ--� <br />_� <br />--- GFI 6 --- <br />SWITCH FOR <br />DISPOSAL IN CAB <br />UNDER SINK C.M <br />�� II <br />I <br />I <br />GREAT ROOM <br />/,>ROUGH -IN\ <br />FOR OPT. CH <br />f FAN/LIGHT' <br />I r <br />I ' UPSTAIRS <br />- FOYER <br />I <br />G <br />O <br />GFI <br />@ 44" W.H. <br />_- <br />A.F.F. ` 0 <br />/ <br />I I <br />I <br />ENtRY I WPDB <br />I GARAG E <br />LIGHT AS FI <br />I I <br />PER SPECS <br />GARAGE <br />LIGHT AS <br />PER SPECS <br />_ GARAGE <br />DOOR <br />GFI <br />Ii--------------- <br />— <br />1 <br />I I <br />I i <br />� <br />W� <br />Ip z I <br />I�Q i <br />IVa I <br />LU <br />Imo ¢ I <br />�OCr <br />wILL <br />ICU I <br />I> I <br />W I <br />> _j <br />1> w <br />F <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />1ST ELECTRICAL — UNIT —A 1532 <br />SCALE: Y4'=1'-0" <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />2ND ELECTRICAL — UNIT -A 1532 <br />SCALE: Y"=1'-0" <br />cD O <br />ti0 <br />�, tFDi'� <br />® - <br />t U4 '0. <br />>r <br />r C-) <br />i I �' <br />3 ;1y ;• ti ,� �� <br />_5 >_ <br />,0 <br />f <br />N <br />N <br />0 <br />m <br />0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code - <br />Residential <br />7th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's <br />signature and seal. <br />9) <br />� <br />E <br />o <br />vQ) <br />0 <br />1�8 <br />i�m0� <br />- 00 <br />H <br />th <br />in�ti <br />N <br />Q <br />M v 3 u_ <br />� w <br />__j-a <br />Z <br />13 <br />=a a- S2 <br />=Yn <br />Co N <br />Z <br />ILLLW <br />11 0 . <br />LO m J J <br />�n <br />N <br />Q C� <br />Z <br />U U) <br />W <br />o0 <br />c <br />ism <br />z N M <br />co <br />o g <br />Va <br />z o � <br />M <br />+-d <br />f6 <br />W <br />V <br />OLU <br />g <br />Vl <br />� <br />U) <br />�(� <br />o �' <br />wig�.r <br />r— E <br />�I <br />8 <br />= w d <br />= <br />C) o <br />Cl) <br />e <br />Q � <br />¢ N <br />w <br />Cl) <br />CID2 <br />y � <br />a <br />Z <br />u <br />oaZ® <br />t— rp <br />Xo <br />SOU <br />ZN <br />E <br />fd <br />o <br />¢ $ <br />w <br />d <br />CO< <br />M g <br />0 <br />O R� <br />Z <br />J <br />r� 2 <br />N C <br />R <br />�w <br />oa <br />�N <br />go <br />W <br />Q <br />a <br />�W <br />LL <br />w� <br />7 5 <br />>° <br />o <br />C <br />- <br />zC� <br />d <br />° <br />0 <br />o � <br />ai <br />CC> <br />f` <br />ECD <br />cfl <br />d' <br />� <br />o <br />O�--- <br />C: in <br />00 <br />O <br />O <br />CD <br />_ <br />N <br />COO <br />r <br />00 <br />ui <br />o <br />Z <br />M <br />Z <br />� <br />E O <br />N <br />a. <br />E <br />0 <br />2 m <br />Q <br />JOB <br />NO: 22-06603-06596 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />13 <br />