ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11, In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />?4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />O <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />®D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />[Eg <br />PUSH BUTTON SWITCH (OPTIONAL) <br />HB <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />© <br />TELEVISION (OPTIONAL) <br />©2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" R.F.F. <br />THERMOSTAT <br />�]M <br />ELECTRIC METER <br />a <br />ELECTRIC PANEL <br />Mai <br />DISCONNECT SWITCH <br />%�7 <br />G J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />T J <br />OPT. CEILING FAN <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />I I <br />I I <br />I I <br />� I I <br />LAV <br />� I <br />L TUB/ <br />W/C SHOWER <br />LAV <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />I <br />I OPT, <br />LAV <br />ILAV <br />I <br />I <br />W/C <br />SHOWER <br />STUDOR DBL SINK <br />VENT LTJ W/ DISP. <br />W/C <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />Unit -B- (1516) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1505 S.F. <br />4515 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10515 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33575 <br />1st 10 KW at 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9430 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />5200 <br />TOTAL: 31734 <br />LOAD WATTS --- 240 VOLTS <br />AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Optional Overhead Service 200A <br />Same As Underground Indoor Panel <br />150 Or 200 Amp Service Center <br />L M NEMA1 <br />200 AMP <br />TER MA N <br />1 0-200 A P 1. Serial Cable <br />NEMA <br />3R <br />Power Co. Feed � j 1#4 Solid COPPER Ground <br />Intersystem Bonding <br />Termination Per <br />NEC 08, 250.94 5/8" Galvanized Driven Ground <br />Rods at least 6' apart <br />Typical 150-200 Amp Electrical Riser Diagram <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 - 17, LOCAL CODES AND THE LOCAL POWER CO. <br />C.O. <br />DISCONNECT <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE <br />RANGE HOOD PER <br />SPECS <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />0 <br />BE ALIGNED <br />VERTICALLY <br />1ST ELECTRICAL —UNIT—B 1516 <br />SCALE: A"=V-0" <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />F— — — — — — — — — — — — — ___1 <br />2ND ELECTRICAL — UNIT—B 1516 <br />SCALE: Ja"=V-0" <br />O <br />co, <br />`5 <br />fi <br />S C: s: <br />y <br />:.y j <br />�y <br />N <br />N <br />0 <br />N <br />0 <br />0 <br />0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida Building <br />Code - <br />Residential 7th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineers signature and seal. <br />N <br />W aE <br />0 co a 8 <br />0 Ncb <br />0 tog r�i <br />0 <br />ti <br />�M,OzS <br />C J Z <br />is LL <br />LL Lu <br />JLLLL 55 <br />W (L <br />Z m c <br />9 <br />o <br />W 'cc N tD <br />-�a'm <br />ZLOCl) ZLL <br />ILW <br />m w <br />J <br />0 O U <br />Z <br />ElI� <br />M to <br />N <br />Z <br />0 <br />Q <br />z <br />�C <br />J <br />IZ N <br />-- 4 <br />to z <br />N CD <br />,--, <br />LU <br />� D <br />', r <br />V) <br />U <br />u' <br />oeo <br />L U <br />t <br />i <br />x� <br />Z <br />III c U) <br />Q N m <br />0 <br />m <br />o <br />C <br />W <br />CO <br />o <br />Z <br />U_ <br />Q.E <br />� � <br />w- <br />� <br />� <br />z <br />� <br />" <br />ona <br />N <br />O <br />7 <br />F- <br />C' E <br />X U <br /><r <br />O <br />o � <br />Z <br />N <br />z <br />wo <br />¢ <br />n, <br />Ww <br />W <br />yam+ L <br />C <br />O <br />Z <br />.Y <br />i <br />mp <br />OLL <br />z <br />Z <br />J <br />¢ <br />W. <br />�' <br />w <br />og <br />�� <br />Z , <br />go <br />a <br />nw <br />W <br />�LL <br />�3 <br />_Z <br />�¢ <br />=H <br />o <br />IIIIIIIIIII� <br />o <br />to <br />~ <br />r< <br />a = <br />0 <br />?i <br />o f <br />ui <br />C�V <br />cQ <br />r- <br />c <br />O <br />lM <br />r <br />o <br />C m <br />OLEO <br />00 <br />O <br />r <br />`Ci CN <br />LO <br />o <br />Q <br />O <br />to <br />4 <br />r <br />00 <br />a� <br />v <br />Lid <br />m <br />C) <br />o <br />Z <br />Z <br />3 y <br />E v <br />c <br />@ <br />a <br />E <br />U 0 <br />JOB <br />NO: 22-06603-06596 <br />SCALE : AS NOTED <br />SHEET NO. <br />14 <br />