4
<br />3
<br />2 1 1
<br />SUPPLY/ RETURN / EXHAUST DUCT
<br />ATTACH HANGERS TO STRUCTURE.
<br />E 1" WIDE GALVANIZED STRAP
<br />FLEXIBLE DUCT INSTALLED 48" O.C. MAX
<br />48" LONG MAX RIGID HARD PIPE
<br />RIGID 90 DEGREE FITTING AND RISER.
<br />ADJUST HEIGHT TO MEET TAKE -OFF
<br />ELEVATION. NO FLEX IN DROP ALLOWED.
<br />WRAP ALL UNINSULATED PORTIONS
<br />OF AIR DEVICE AND NECK PER
<br />ADJUST HEIGHT OF RISER TO SPECIFICATIONS ON M-901.
<br />MEET TAKE -OFF ELEVATION OVERLAP ALL JOINTS BY 3". DO NOT
<br />TAPE INSULATION TO THE GRID.
<br />'GALVANIZED STRAP `-SEE SPIN -IN COLLAR
<br />INSTALLED PER SMACNA DETAIL THIS SHEET
<br />SAG/RAG/GRILLE TAKE -OFF
<br />NOT TO SCALE
<br />FABRICATE 18 GA STAINLESS NOZZLE. NOZZLE
<br />INLET FULL SIZE OF FAN DISCHARGE. MINIMUM
<br />NOZZLE HEIGHT 1'4'. EXTEND NOZZLE AS NEEDED
<br />TO TERMINATE 0'-2" ABOVE TOP OF ALL CONDENSING
<br />UNITS, RTUS, AND PARAPETS WITHIN 10'-0".
<br />10 DEGREES
<br />BOLTED
<br />AND
<br />GASKETED
<br />FACTORY NEMA 3R
<br />DISCONNECT
<br />INSIDE HOUSING -
<br />CONTRACTOR IS RESPONSIBLE
<br />FOR DESIGN AND SUPPLY OF
<br />ALL CURB ATTACHMENT o
<br />C DETAILS IN ACCORDANCE WITH o
<br />APPLICABLE BUILDING CODES, o
<br />AND TO SUBMIT CURB AND
<br />ATTACHMENT INFORMATION AS
<br />NOTED ON 'G' SHEET
<br />SUBMITTAL SCHEDULE.
<br />B
<br />EQUIPMENT RAIL 10
<br />INSTALL ROOFTOP SOLUTIONS G2 \-- PROVIDE 1.5 PCF
<br />DRIP GUARD AS CLOSE AS POSSIBLE BATT INSULATION,
<br />TO FAN SCROLL DRAIN. EXTEND MINIMUM 4" THICK.
<br />DRAIN TO CENTER OF DRIP GUARD.
<br />KITCHEN HOOD EXHAUST FANS
<br />NOT TO SCALE
<br />SECURE FAN TO CURB WITH HEX WASHER HEAD SELF -
<br />DRILLING SCREW (#12 x 2"). THE FASTENERS SHALL BE 2"
<br />FROM EACH CORNER OF THE FAN BASE AND THE
<br />DISTANCE BETWEEN FASTENERS SHALL BE 4" OR LESS.
<br />MINIMUM 5 FASTENERS PER SIDE OF CURB. ALL
<br />FASTENERS ARE TO BE HIGH QUALITY CORROSION
<br />RESISTANT STEEL OR STAINLESS STEEL.
<br />SECURE CURB TO WOOD ROOF STRUCTURE WITH STEEL
<br />LAG BOLTS NOMINAL SIZE OF 5/16" DIA. OR LARGER.
<br />WOOD IS TO BE 4" NOMINAL SIZE OR GREATER. THE BOLT
<br />SHALL HAVE A MINIMUM OF 3" THREAD ENGAGEMENT AND
<br />SHALL BE AT LEAST 1-1/2" FROM MATERIAL EDGE.
<br />MINIMUM 5 FASTENERS EACH SIDE OF CURB.
<br />ELECTRICAL
<br />DISCONNECT
<br />LOCATED
<br />INSIDE MOTOR
<br />COMPARTMENT
<br />BIRDSCREEN '
<br />PRE -FABRICATED 1'-0" MIN.
<br />CURB l
<br />TRANSITION OUT
<br />TO ALLOW
<br />BACKDRAFT
<br />CLEAR ACCESS
<br />DAMPER BY
<br />TO ELECTRICAL
<br />MECHANICAL.
<br />RACEWAY IN FAN
<br />COORDINATE
<br />LOCATION
<br />FLEXIBLE CONDUIT THRU
<br />DUCT UP TO FACTORY
<br />WITH CONDUIT.
<br />RACEWAY IN FAN
<br />RESTROOM EXHAUST
<br />FAN
<br />NOT TO SCALE
<br />CHICK-FIL-A HAS A NATIONAL ACCOUNT WITH TOM BARROW COMPANY FOR THE ROYAL
<br />METAL PRODUCTS START COLLARS FOR BOTH WITH AND WITHOUT A MANUAL BALANCING
<br />DAMPER. THE MECHANICAL CONTRACTOR IS REQUIRED TO PURCHASE THE ROYAL METAL
<br />PRODUCTS START COLLARS DIRECTLY FROM TOM BARROW COMPANY. CONTACT MR. SCOTT
<br />GEORGE AT 404-351-1010 FOR PRICING AND AVAILABILITY. ROYAL METAL PRODUCTS START
<br />COLLARS NOT PURCHASED THRU TOM BARROW COMPANY WILL NOT BE ACCEPTED,
<br />DAMPER CONTROL HANDLE MUST BE
<br />EXPOSED, LOCATED ON THE LEFT OR RIGHT
<br />(9 OR 3 O'CLOCK) SIDE WHEN INSTALLED ON
<br />HORIZONTAL DUCTS, AND LOCATED ON THE
<br />BOTTOM (6 O'CLOCK) WHEN INSTALLED ON
<br />VERTICAL DUCTS. DAMPER CONTROL
<br />HANDLES NOT INSTALLED IN THE CORRECT
<br />ORIENTATION AS SPECIFIED ABOVE WILL
<br />NOT BE ACCEPTED. ATTACH YELLOW
<br />FLUORESCENT CONSTRUCTION RIBBON TO
<br />THE HANDLE. RIBBON MUST BE 12" LONG
<br />AND BE EASILY IDENTIFIABLE FOR TEST AND
<br />BALANCE CONTRACTOR.
<br />ROYAL METAL PRODUCTS
<br />STICK -ON START COLLAR.
<br />START COLLAR
<br />NOT TO SCALE
<br />ALL DUCTWORK AND UNFINISHED METAL ON ROOF EXCEPT STAINLESS SHALL BE PREPARED
<br />WITH TWO COATS OF SHERWIN WILLIAMS B66-200 SERIES DTM WHITE ACRYLIC SEMI -GLOSS
<br />INDUSTRIAL MAINTENANCE COATING. DEGREASE AND PRIME BARE METAL SURFACE WITH
<br />ONE COAT OF SHERWIN WILLIAMS DTM ACRYLIC PRIMER PRIOR TO PAINTING.
<br />KEYED NOTES:
<br />O EQUIPMENT CURB/RAILS AND CURB CAP (WHERE APPLICABLE) SHALL BE PROVIDED
<br />BY GENERAL CONTRACTOR. WHERE CURB IS USED: WIDTH OF CURB SHALL BE 4"
<br />WIDER THAN FAN FOOTPRINT IN BOTH DIRECTIONS. HEIGHT OF CURB/RAILS SHALL
<br />BE SUCH THAT NO PART OF ANY DUCT SHALL BE WITHIN 18" OF ROOF SURFACE.
<br />O2 ALL DUCT ON ROOF TO BE SUPPORTED WITH MIRO STANCHIONED DUCT SUPPORT
<br />SYSTEM FOR SEISMIC APPLICATIONS AT 6'-0" INTERVALS MAXIMUM. SECURE
<br />STANCHION BASE TO ROOF WITH MIN. (4) 3/8" LAG BOLTS. BOLT LENGTH SHALL BE
<br />SUCH TO PROVIDE MINIMUM 3" PENETRATION IN BLOCKING BELOW THE PLYWOOD
<br />ROOF DECK. PROVIDE A DUCT SUPPORT STAND AT EACH ROOF PENETRATION.
<br />O MINIMUM 12" HIGH INSULATED CURB PROVIDED BY GENERAL CONTRACTOR.
<br />CONTRACTOR TO PROVIDE 16 GA MINIMUM CURB CAP.
<br />BOLTED AND GASKETED
<br />TO FAN. 150OF RATED.
<br />0/1
<br />a JD
<br />24" MIN. FROM ROOF DECK.
<br />ROOF ROOF
<br />DECK-\ SURFACE -�
<br />DO NOT APPLY START
<br />COLLAR OVER DUCT WRAP
<br />MINIMUM 1'-0" OF RIGID
<br />DUCT AFTER SPIN -IN.
<br />2" STANDOFF BRACKET
<br />*--DAMPER CONTROL HANDLE
<br />MAIN OR BRANCH MAIN
<br />STICK -ON FITTINGS MUST
<br />AIR FLOW BE SECURED WITH A
<br />SCREW AT EVERY
<br />PREPUNCHED HOLE.
<br />SEE M-250 FOR GREASE SEE ROOF PLAN FOR
<br />EXHAUST DUCT SIZE. GREASE ACCESS DOOR
<br />QUANTITY AND TYPE, TYP.
<br />4 D SEE ROOF PLAN FOR GREASE
<br />ACCESS DOOR QUANTITY AND
<br />TYPE, TYP.
<br />FULL PERIMETER LIQUID TIGHT WELD
<br />BETWEEN CURB CAP AND DUCT.
<br />GREASE EXHAUST DUCT IS
<br />CONTINUOUS THRU CURB CAP.
<br />BLOCKING BY GENERAL CONTRACTOR
<br />SUPPORT DUCT FROM STRUCTURE WITH
<br />1-1/2"X1/8" STEEL ANGLE OR B-LINE B24
<br />STRUT AND 3/8" ATR ON 6'-0" CENTERS, TYP.
<br />TURNING VANE SCHEDULE
<br />R
<br />SP
<br />GA
<br />2"
<br />1.5"
<br />24
<br />1. NO TRAILING EDGE.
<br />2. SINGLE THICKNESS
<br />CONSTRUCTION.
<br />CE
<br />i
<br />450 FITTING 900 FITTING
<br />TURNING VANES
<br />NOT TO SCALE
<br />CURB FOR DUCTS SERVING EF#1:
<br />22.5" SQ. INSIDE CLEAR MINIMUM
<br />CURB FOR DUCTS SERVING EF#2:
<br />19.5" SQ. INSIDE CLEAR MINIMUM
<br />CONTACT
<br />CLOSUF
<br />WHEN C
<br />OPENS.
<br />ROOF SEE PLAN FOR
<br />DECK-� DUCT SIZE
<br />GAS FIRED ROOFTOP UNIT SCHEDULE
<br />TOTAL
<br />SENSIBLE
<br />HEATING
<br />HEATING
<br />COOLING
<br />COOLING
<br />INPUT
<br />OUTPUT
<br />MODEL
<br />MARK
<br />MBH
<br />MBH
<br />MBH
<br />MBH
<br />STAGES
<br />SUPPLY
<br />O.A.
<br />HP
<br />ESP
<br />R-410A
<br />MANUFACTURER
<br />REMARKS
<br />AC#1
<br />288.4
<br />219.2
<br />480
<br />384
<br />1 2 3
<br />9500
<br />1180
<br />10
<br />0.80
<br />LG H 300S4 B
<br />LENNOX
<br />1, 3,4, 5, 7, 8, 9,10,11,12,13,14,15,16
<br />AC#2
<br />208.9
<br />160.9
<br />240
<br />192
<br />1 2
<br />1 5300
<br />1152513
<br />0.65
<br />LG H210 H4B
<br />LENNOX
<br />1, 3, 4, 5, 7, 8, 9,10,11,12,13,14,15,16
<br />AC#3
<br />247.3
<br />192.9
<br />480
<br />384
<br />1 2
<br />1 6000
<br />1175015
<br />0.65
<br />LG H240 H4B
<br />LENNOX
<br />1, 3, 4, 5, 7, 8, 9,10,11,12,13,14,15,16
<br />NOTES
<br />0
<br />COOLING CAPACITIES ARE GROSS, BASED ON ENTERING: 80FDB/67FWB, OUTDOOR: 95FDB, AND 400 CFM PER TON.
<br />•
<br />CHICK-FIL-A MAINTAINS A NATIONAL ACCOUNT FOR EQUIPMENT WITH LENNOX CORPORATION. CONTACT LENNOX
<br />NATIONAL ACCOUNTS AT 800-367-6285 (OR BY FAX AT 972-497-5112) FOR PRICING, ORDERING AND AVAILABILITY.
<br />•
<br />MECHANICAL CONTRACTOR TO VERIFY LENNOX SUBMITTAL WITH CONSTRUCTION DOCUMENTS.
<br />REMARKS
<br />1.
<br />PROVIDE DIFFERENTIAL ENTHALPY ECONOMIZER WITH POWER EXHAUST.
<br />2.
<br />NOT USED.
<br />3.
<br />PROVIDE 14" HIGH ROOF CURB.PROVIDE CURBS PLUS RESTRAINT CLIP KIT.
<br />4.
<br />SEE DETAIL 2/M-501 FOR SETTING OF PRODIGY M3 BOARD CONTROL PARAMETERS BY MC.
<br />5.
<br />PROVIDE FACTORY INSTALLED AND UNIT POWERED 115V GFI SERVICE OUTLET.
<br />6.
<br />NOT USED.
<br />7.
<br />PROVIDE FACTORY INSTALLED RETURN SIDE SMOKE DETECTOR.
<br />8.
<br />PROVIDE FACTORY INSTALLED NON -FUSED DISCONNECT.
<br />9.
<br />PROVIDE 2" MERV 8 THROW AWAY FILTERS.
<br />10.
<br />PROVIDE HINGED PANELS FOR FILTER ACCESS, FAN MOTOR ACCESS, COMPRESSOR ACCESS AND CONTROL
<br />COMPARTMENT ACCESS.
<br />11.
<br />ADJUST GAS MANIFOLD PRESSURE AT LOCATIONS WHERE ELEVATION EXCEEDS 2000' ABOVE SEA LEVEL AS
<br />RECOMMENDED BY MANUFACTURER.
<br />12.
<br />PROVIDE FACTORY COIL HAIL GUARD, FIELD INSTALLED.
<br />13.
<br />PROVIDE FACTORY INSTALLED CONDENSATE PAN DRAIN OVERFLOW SWITCH.
<br />14.
<br />PROVIDE HUMIDITROL OPTION WITH FACTORY WALL MOUNTED HUMIDITY SENSOR.
<br />15.
<br />PROVIDE FACTORY INSTALLED BELT TENSIONER.
<br />16.
<br />PROVIDE FACTORY CONFIGURED PHASE LOSS PROTECTION.
<br />EXHAUST FAN SCHEDULE
<br />MARK
<br />CFM
<br />ESP
<br />RPM
<br />Tip Speed
<br />HP
<br />Area Served
<br />MODEL
<br />MANUFACTURER
<br />REMARKS
<br />EF#1
<br />1912
<br />0.75
<br />1,331
<br />5,231
<br />3/4
<br />HOOD#1L & HOOD#1R
<br />150 CPS
<br />LOREN COOK
<br />1,2,3,4,5,6,7,8,9,10,11,17
<br />EF#2
<br />1091
<br />0.85
<br />1,311
<br />4,637
<br />1/2
<br />HOOD#2 & HOOD#3
<br />135 CPS
<br />LOREN COOK
<br />1,2,3,4,5,6,7,8,9,10,11,17
<br />EF#3
<br />300
<br />0.375
<br />1 1,294
<br />3,091
<br />1/8
<br />RESTROOMS
<br />ACED-90C 15DH
<br />I LOREN COOK
<br />3,11,12,13,14,15,16
<br />NOTES
<br />0
<br />GREASE EXHAUST FAN RPM BASED ON 80 DEGREE F AIR AT 1000 FEET ABOVE SEA LEVEL.
<br />•
<br />GREASE EXHAUST FANS TO BE U.L. 762 LISTED.
<br />•
<br />CHICK-FIL-A HAS A NATIONAL ACCOUNT WITH TOM BARROW COMPANY FOR THE FAN/CURB PACKAGE. THE MECHANICAL
<br />CONTRACTOR IS REQUIRED TO PURCHASE THE FAN/CURB PACKAGE DIRECTLY FROM TOM BARROW COMPANY. CONTACT MR.
<br />SCOTT GEORGE AT 404-351-1010 FOR PRICING AND AVAILABILITY. FANS AND CURBS NOT PURCHASED THRU TOM BARROW
<br />COMPANY WILL NOT BE ACCEPTED.
<br />REMARKS
<br />1.
<br />UPBLAST, ARRANGEMENT 10, CCW ROTATION. SEE PLANS TO CONFIRM CONFIGURATION.
<br />2.
<br />PROVIDE FACTORY STEEL FAN WHEEL.
<br />3.
<br />PROVIDE FACTORY INSTALLED, PRE -WIRED, NEMA 3 NON -FUSED DISCONNECT.
<br />4.
<br />PROVIDE FACTORY STEEL INLET FLANGE AND INLET COMPANION FLANGE.
<br />5.
<br />PROVIDE AND INSTALL ROOFTOP SOLUTIONS G2 DRIP GUARD. MECHANICAL CONTRACTOR TO CONTACT
<br />ROOFTOP SOLUTIONS AT 800-913-7034.
<br />6.
<br />PROVIDE FACTORY WEATHER HOUSING W/ HINGED ACCESS DOOR.
<br />7.
<br />PROVIDE FACTORY DRAIN CONNECTION.
<br />8.
<br />PROVIDE FACTORY BOLTED ACCESS DOOR ON SCROLL.
<br />9.
<br />PROVIDE FACTORY INSTALLED BELT DRIVE WITH ADJUSTABLE MOTOR SHEAVE AND SPARE BELT..
<br />10.
<br />PROVIDE FACTORY STEEL OUTLET COMPANION FLANGE.
<br />11.
<br />INTEGRAL THERMAL OVERLOAD WITH AUTOMATIC RESET.
<br />12.
<br />PROVIDE BIRDSCREEN.
<br />13.
<br />BACKDRAFT DAMPER IN DUCT BY MECHANICAL CONTRACTOR AS SHOWN ON 4/M401.
<br />14.
<br />STARTER BY ELECTRICAL CONTRACTOR. INTERLOCK WITH LIGHTS BY ELECTRICAL CONTRACTOR.
<br />15.
<br />PROVIDE 12" HIGH CURB.
<br />16.
<br />PROVIDE FACTORY INSTALLED AND WIRED SPEED CONTROLLER.
<br />17.
<br />UTILITY SET FAN CURB AND ASSOCIATED EXHAUST DUCT CURB PROVIDED BY TOM BARROW COMPANY.
<br />30.00 MINA\ '�4 /30.00 MIN.
<br />SEE PLAN FOR PLENUM SIZE
<br />0 0
<br />co
<br />CEILING APPROX.10"
<br />TAKE -OFF,
<br />TYP.
<br />RETURN DROP GEOMETRY
<br />NOT TO SCALE
<br />LEGEND
<br />18 AWG MIN LOW VOLTAGE WIRING BY MC, U.N.O.
<br />22 AWG LOW VOLTAGE WIRING PROVIDED BY
<br />TORMAX. WIRING INSTALLED BY MC.
<br />- - - - - - - - - 7
<br />POWERED AIRE REMOTE AUTO I
<br />FAN ON/AUTO SWITCH L 1
<br />MOUNTED ON WALL BY MC P I
<br />- - - - -
<br />r ON 1
<br />L - - - -
<br />_ -- I I
<br />TORMAX DOOR AIR CURTAIN
<br />LOW VOLTAGE CONTROL _
<br />CIRCUIT MICRO SWITCH I-
<br />Z L
<br />w - -
<br />o E_
<br />N.O. O
<br />o ED - - BLACK - -
<br />N.C. r _
<br />CAP WHITE WIRE I
<br />I
<br />POWERED AIRE REMOTE
<br />HEAT ON/OFF SWITCH - J
<br />MOUNTED ON WALL BY MC. �L-----
<br />AIR CURTAIN WIRING DIAGRAM
<br />NOT TO SCALE
<br />POWERED AIR TERMINAL BOARD
<br />-
<br />1
<br />FAN ON/AUTO (AUTO)'.
<br />®
<br />2
<br />DOOR SWITCH
<br />-
<br />3
<br />FAN ON/AUTO (ON)
<br />4
<br />FAN ON/AUTO (COM) I,I
<br />6
<br />DOOR SWITCH
<br />-
<br />7
<br />HEAT ON/OFF
<br />-
<br />8
<br />HEAT ON/OFF
<br />AIR DOOR SCHEDULE
<br />MARK
<br />CFM
<br />VELOCITY
<br />HEATING CAP
<br />HP
<br />AREA SERVED
<br />MODEL
<br />MANUFACTURER
<br />REMARKS
<br />AD#1
<br />1543
<br />2240 FPM
<br />10 KW
<br />3/4 HP
<br />DRIVE THRU
<br />CHA 1-48
<br />Powered Aire
<br />1,2,3
<br />AD#2
<br />3867
<br />4220 FPM
<br />N/A
<br />3/4 HP
<br />REAR DOOR
<br />RBT-1-48
<br />Powered Aire
<br />4
<br />NOTES
<br />CHICK-FIL-A HAS A NATIONAL ACCOUNT WITH TOM BARROW COMPANY FOR THE AIR DOORS. THE
<br />MECHANICAL CONTRACTOR SHALL PURCHASE THE AIR DOORS DIRECTLY FROM TOM BARROW
<br />COMPANY. CONTACT MR. SCOTT GEORGE AT 404-351-1010, FOR PRICING AND AVAILABILITY. AIR
<br />DOORS NOT PURCHASED THRU TOM BARROW COMPANY WILL NOT BE ACCEPTED.
<br />REMARKS
<br />1. FACTORY PROVIDED, WIRED, AND UNIT MOUNTED SPEED CONTROLLER LOCATED ABOVE
<br />CEILING.
<br />2. FACTORY WIRED DISCONNECT.
<br />3. FACTORY PROVIDED, FIELD INSTALLED BY MC, REMOTE WALL SWITCHES FOR HEATING ON/OFF
<br />AND FAN ON/AUTO SWITCH. SEE DETAIL, AIR CURTAIN WIRING DIAGRAM, THIS SHEET.
<br />4. FACTORY PROVIDED MAGNETIC DOOR CONTACT WITH FACTORY INSTALLED LOW VOLTAGE
<br />CONTROLS LOCATED IN AIR DOOR CABINET.
<br />AIR DEVICE SCHEDULE
<br />NECK
<br />FACE
<br />FRAME
<br />MARK
<br />DESCRIPTION
<br />LOCATION
<br />SIZE
<br />SIZE
<br />TYPE
<br />REMARKS
<br />A
<br />PRICE MODEL APDC ALUMINUM SUPPLY AIR
<br />DINING/
<br />VARIES
<br />24"x24"
<br />LAY -IN
<br />1,7
<br />DIFFUSER WITH INDIVIDUALLY ADJUSTABLE
<br />OFFICE/
<br />CURVED AIR PATTERN CONTROLLERS.
<br />KITCHEN
<br />C
<br />PRICE MODEL SMCD STEEL SUPPLY AIR
<br />ENTRY
<br />14"x14"
<br />19"x19"
<br />BEVELLED
<br />1,3,5,E
<br />DIFFUSER FIELD ADJUSTABLE AIR PATTERN
<br />CONTROLLERS.
<br />F
<br />PRICE MODEL 80 EGGCRATE RETURN AIR GRILLE
<br />DINING/
<br />VARIES
<br />24"x24"
<br />LAY -IN
<br />1,7
<br />WITH REMOVABLE WHITE CORE, FACTORY FLAT
<br />OFFICE/
<br />BLACK BACKPAN AND ROUND NECK.
<br />KITCHEN
<br />J
<br />PRICE MODEL SMCD STEEL SUPPLY AIR
<br />RESTROOMS
<br />10"x10"
<br />15"x15"
<br />BEVELLED
<br />1,2,3,5,E
<br />DIFFUSER FIELD ADJUSTABLE AIR PATTERN
<br />CONTROLLERS.
<br />K
<br />PRICE MODEL APDDR ALUMINUM PERFORATED
<br />RESTROOMS/
<br />14"x14"
<br />16"x16"
<br />SURFACE
<br />1,4,5,E
<br />FACE RETURN AIR GRILLE.
<br />ENTRY
<br />NOTES
<br />CHICK-FIL-A HAS A NATIONAL ACCOUNT WITH TOM BARROW COMPANY FOR THE AIR
<br />DEVICES. THE MECHANICAL CONTRACTOR SHALL PURCHASE THE AIR DEVICES DIRECTLY
<br />FROM TOM BARROW COMPANY. CONTACT MR. SCOTT GEORGE AT 404-351-1010, FOR
<br />PRICING AND AVAILABILITY. AIR DEVICES NOT PURCHASED THRU TOM BARROW COMPANY
<br />WILL NOT BE ACCEPTED.
<br />REMARKS
<br />1. STANDARD OFF WHITE FINISH.
<br />2. PROVIDE MODEL VCS3 NECK DAMPER.
<br />3. SEE DRAWING M-201 FOR THROW.
<br />4. PROVIDE MODEL VCR7 NECK DAMPER ON GRILLES IN RESTROOMS SERVING EXHAUST
<br />FAN.
<br />5. PROVIDE BACKPAN. MC TO SEAL JOINTS WITH MASTIC AND INSULATE EXTERNALLY.
<br />6. FIELD INSULATE BACKPAN AS SHOWN ON DETAIL 1/M-401.
<br />7. FACTORY INSULATED R-6 BACKPAN.
<br />L
<br />J
<br />C
<br />B
<br />:> o
<br />f e
<br />Chick-fil-A
<br />5200 Buffington Road
<br />Atlanta, Georgia
<br />30349-2998
<br />Kurzynske
<br />& Associates
<br />2900 Lebanon Pike, Ste 201
<br />Nashville, Tennessee 37214
<br />Telephone: (615) 255-5203
<br />Fax: (615) 255-5207
<br />Email: mail@kurzynske.com
<br />MARK T. KURZYNSKE
<br />FLORIDA LICENSE # 53568
<br />KU `�10111111'�f�1,F
<br />• r
<br />Auz
<br />0 STATE • �.;
<br />I.
<br />�Baleeeettl%
<br />03/29/2 1
<br />Q M
<br />> M
<br />W J
<br />J LL
<br />0 co
<br />inJ
<br />J J
<br />J =
<br />Q�
<br />a�
<br />O =
<br />a, a
<br />W
<br />t` N
<br />FSR#04040
<br />BUILDING TYPE / SIZE: P13 LC ALL
<br />RELEASE: v2.20.02
<br />REVISION SCHEDULE
<br />NO. DATE DESCRIPTION
<br />Z
<br />O
<br />V
<br />CONSULTANT PROJECT# 20090.CC.S
<br />A /A
<br />PRINTED FOR FOR CONSTRUCTION
<br />z
<br />DATE
<br />07/29/2020
<br />ODRAWN
<br />BY BLM
<br />Information contained on this drawing and in all digital files
<br />produced for above named project may not be reproduced in
<br />any manner without express written or verbal consent from
<br />authorized project representatives.
<br />SHEET
<br />HVAC DETAILS AND
<br />LL
<br />SCHEDULES
<br />SHEET NUMBER
<br />M=401
<br />4 I 3 I 2
<br />1
<br />
|