PLUMBING NOTES:
<br />Notes:
<br />PLUMBING FIXTURE SCHEDULE NOTE: ALL FIXTURE APPURTENANCES SHALL BE
<br />SUPPLIED BY THE MANUFACTURER
<br />FIXTURE
<br />FIXTURE
<br />PROTOTYPE NAME AND
<br />NUMBER
<br />CONNECTION SIZES
<br />SYMBOL
<br />TYPE
<br />BASIC FIXTURE
<br />MATERIAL VALVE FAUCET
<br />REMARKS
<br />W
<br />V
<br />CW HW
<br />MC
<br />A.D.A
<br />CAROMA MFG.
<br />VITREOUS CHINA DUAL FLUSH TANK WATER SAVING DUAL 1.6 AND 0.8 GAL PER
<br />4"
<br />2"
<br />1/2* --
<br />1 D
<br />COMPLIANT
<br />SIDNEY 270 ELONGATED
<br />COLOR: WHITE (TYPE 0.8 OR 1.6 GAL iFLUSH WITH ELONGATED CHURCH MFG.
<br />TOILET
<br />"EASY HEIGHT"
<br />FLUSH 439OTL OPEN FRONT SEAT WITH LID
<br />NO EQUAL ACCEPTED
<br />L
<br />A.D.A.
<br />KOHLER K-2005
<br />VITREOUS CHINA DELTA MODEL iMcGUIRE SUPPLIES, STOPS, 1-1/2" P-TRAP
<br />2"
<br />2"
<br />1 2 1 2
<br />1 D
<br />COMPLIANT
<br />"KINGSTON"
<br />COLOR: WHITE I523-WF-HGMHDF 'DRAIN OFFSET AND TAILPIECE. PROVIDE
<br />LAVATORY
<br />WITH 0.5 GPM AERATOR !TRUEBRO 102W & 102W INSULATION KIT.
<br />]�
<br />ICEMAKER
<br />C.P. INDUSTRIES
<br />PLASTIC 1 4 SHUT OFF VALVE MOUNT 12 AFF. 1 4 INLET WITH WATER
<br />__
<br />__
<br />1 2
<br />1
<br />BOX
<br />"WATER TITE"
<br />COLOR: WHITE 'HAMMER ARRESTER
<br />SINGLE
<br />JUST MFG.
<br />18 GAUGE ,JUST MFG. ;McGUIRE SUPPLIES, STOPS, 1-1/2" P-TRAP
<br />2"
<br />2"
<br />1 2 1 2
<br />1 D
<br />COMP. SINK
<br />#SL-ADA- 1921 -A-GR
<br />STAINLESS STEEL #JTR-51-W4-ADA TAILPIECE AND BASKET STRAINER. 1 /4" CW
<br />A.D.A.
<br />(OFFSET DRAIN)
<br />,WITH J-ADA-35 WITH 'SUPPLY, AND FILTER FOR COFFEE MAKER.
<br />11.0 GPM DOLE FLOW �iTRUEBRO 102W & 102W INSULATION KIT.
<br />(CONTROL AERATOR
<br />GCO
<br />FLOOR
<br />ZURN Z-1400
<br />COATED CAST IRON -- ROUND SCORIATED TOP
<br />3" --
<br />-- --
<br />CLEANOUT
<br />ADJUSTABLE TO FINISHED GRADE IN
<br />18"L X 180W X 6"D CONCRETE PAD.
<br />JCS
<br />ADA
<br />OASIS
<br />18 GAUGE FLEXIBLE BUBBLER McGUIRE SUPPLIES, STOPS, 1-1 2 P-TRAP
<br />2" 2"
<br />1 D
<br />COMPLIANT
<br />#P8ACSL AND
<br />STAINLESS STEEL AND TAILPIECE. MOUNT FIXTURE LIP PER
<br />WTR COOLER
<br />A # PFACSL
<br />'ADA HEIGHT, CONNECT SHELL UNIT TO CHILLED
<br />',UNIT FOR HI/LO CONFIG.
<br />'6
<br />EWH
<br />ELECTRIC
<br />A.O. SMITH
<br />INSULATED TANK 3/4- T&P VALUE GAL., 1.5 KW, 120 1 60 WALL MOUNTED
<br />__ __
<br />3/4", 3 4
<br />1
<br />WATER
<br />MODEL DEL-6
<br />WITH JACKET PREMANUFACTURED SHELF. PROVIDE
<br />HEATER
<br />'VACUUM BREAKER TANK DRAIN VALVE.
<br />MOP BASIN
<br />FIAT MSB 2424
<br />MOLDED STONE (FAUCET FIAT PROVIDE 3" DEEP SEAL P-TRAP, QUICK
<br />3" 2"
<br />3/4 3/4
<br />1
<br />830-AA, I DRAIN CONNECTOR: FIAT QDC-3SN AND
<br />HOSE & BRACKET: MOP HANGER: FIAT 889-CC
<br />832-AA
<br />(2) SS SPLASH PANELS
<br />EQ
<br />FLOOR DRAIN
<br />JAY R. SMITH
<br />COATED CAST --- ,SQUARE BRASS TOP, ADJUSTABLE
<br />3"
<br />1
<br />#2010-04-PO50IRON
<br />70 FINISH FLOOR
<br />WALL HYDRANT
<br />ZURN TYPE
<br />BRONZE FINISH --- MILD CLIMATE TYPE, ANTI -SIPHON,
<br />-- --
<br />3/4`1
<br />1
<br />Z-1333
<br />AUTO DRAINING, KEY OPERATOR, 12" AFF
<br />$Q,
<br />ROOF
<br />JAY R. SMITH
<br />CAST IRON --- 6" ROOF DRAIN WITH DECK CLAMP
<br />6" --
<br />-- --
<br />1
<br />DRAIN
<br />#1010-06-C
<br />EXP-1
<br />EXPANSION
<br />POTABLE WATER
<br />AMTROL ST-5 --- !2 GALLON CAPACITY
<br />-- --
<br />3/4
<br />TANK
<br />EXPANSION TANK
<br />NOTE: SET TIMER ON RECIRC. PUMP TO OPERATE BETWEEN THE HOURS
<br />OF 8:30 AM & 5:30 PM. SET FOR 20—MINUTE ON/OFF INTERVALS.
<br />DIAL THERMOMETER — RANGE TO 16V F.
<br />RE —CIRCULATION PUMP (GRUNDFOS #
<br />UP 10-16BN5 ATLC "COMFORT" PUMP,
<br />120/1/60, 1 20 H.P., 3 GPM
<br />LAWLER VALVE CO. 3/4- SERIES 61
<br />THERMOSTATIC MIXING VALVE, FLOW
<br />RANGE FROM .5 GPM TO 25 GPM, SET
<br />DELIVERY TEMPERATURE TO 110' F.
<br />a 110
<br />bc
<br />DIAL THERMOMETER — RANGE TO 160' F.
<br />VACUUM RELIEF VALVE: WATTS 36N,
<br />ABOVE TOP OF WATER HEATER.
<br />ELECTRIC WATER
<br />HEATER, LOW BOY
<br />TYPE. SET WATER �I
<br />r
<br />TEMP TO 140'F.
<br />T&P RELIEF VALVE �-
<br />EXPANSION
<br />3/4" DRAIN VALVE TO
<br />� TANK, EXP-1
<br />WATER HEATER PAN
<br />3/4" T&P DRAIN TO
<br />TERMINATE ABOVE
<br />WATER HEATER PAN
<br />\_ 3/4" WATER HEATER PAN
<br />WATER HEATER PAN
<br />DRAIN TO DISCHARGE ABOVE
<br />MOP SINK WITH A 1 "
<br />SECURE BRACKET TO WALL
<br />AIR GAP
<br />W/ LAG SCREWS (MIN. 6)
<br />} _ ._`
<br />MOUNT TOP OF
<br />1 /8"X2"GUSSET '_r
<br />BRACKET TIGHT
<br />EXPANDED METAL
<br />TO CEILING.
<br />CLEAN, PRIME AND
<br />PAINT ALL STEEL NOTE: PROVIDE DRIP PAN BELOW WATER HEATER
<br />1-1 /2'X1-1 /2"X1 /8" MAINTAIN 72" CLEAR BELOW SUPPORT
<br />ANGLE FRAME Wall Mounted
<br />Electric
<br />Water Heater
<br />Detail (EWH-1)
<br />Not to Scale
<br />30"
<br />�
<br />Not to Scale
<br />• o•
<br />MOP HANGER
<br />SERVICE FAUCET
<br />WITH VACUUM
<br />BREAKER.
<br />MOP (BY OTHERS)
<br />APPLY SILICONE
<br />SEALANT AROUND
<br />TOP AND SIDES OF
<br />BASIN AT WALLS
<br />AND FLOOR.
<br />MOP BASIN
<br />QUICK DRAIN
<br />CONNECTOR.
<br />FINISHED FLOOR.
<br />1 THE PLUMBING CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL,
<br />AND EQUIPMENT REQUIRED FOR THE COMPLETION AND OPERATION OF
<br />ALL SYSTEMS IN THIS SECTION OF WORK IN ACCORDANCE WITH ALL
<br />APPLICABLE CODES.
<br />2 THE PLUMBING CONTACTOR SHALL FURNISH AND INSTALL A COMPLETE
<br />DOMESTIC COLD WATER, HOT WATER, AND SANITARY SEWER SYSTEM
<br />TO ALL FIXTURES AND OR EQUIPMENT REQUIRING SUCH. VERIFY ALL
<br />ROUGH —IN LOCATIONS AND COORDINATE PIPING LOCATIONS WITH WORK
<br />UNDER OTHER DIVISIONS OF THE SPECIFICATIONS TO AVOID
<br />CONFLICTS.
<br />3 THE PLUMBING CONTRACTOR SHALL SECURE ALL PERMITS, INSPECTION
<br />CERTIFICATES, ETC. AND PAY ALL CHARGES CONNECTED WITH THE
<br />SAME.
<br />4 THE PLUMBING CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS
<br />PRIOR TO CONSTRUCTION AND NOTIFY THE ENGINEER OF RECORD OF
<br />ANY DISCREPANCIES BETWEEN THE PLANS AND EXISTING CONDITIONS
<br />AND / OR POTENTIAL PROBLEMS HE OBSERVES BEFORE CONTINUING
<br />WORK.
<br />5 DO NOT SCALE THE PLANS. SEE ARCHITECTURAL PLANS FOR EXACT
<br />LOCATION OF DOORS, WINDOWS, FIXTURES, WALL DIMENSIONS, ETC.
<br />6 ALL FIXTURES SHALL BE COMPLETE AND INCLUDE SUPPLIES, STOPS,
<br />VALVES, FAUCETS, DRAINS, TRAPS, TAIL PIECES, ESCUTCHEONS, ETC.
<br />TRAPS FOR ALL LAVS SHALL BE REMOVABLE. LOCATE VALVES IN A
<br />READILY ACCESSIBLE LOCATION.
<br />7 ALL VALVES, CLEANOUTS, ETC. SHALL BE SO LOCATED AND INSTALLED
<br />TO PERMIT ACCESS FOR SERVICE WITHOUT DAMAGE TO BUILDING OR
<br />FINISHED MATERIALS.
<br />8 ALL MATERIALS SHALL BE NEW AND SHALL FIT THE SPACE AVAILABLE.
<br />VERIFY DIMENSIONS AT SITE.
<br />9 ALL PIPING, APPARATUS, EQUIPMENT, ETC. SHALL BE PROPERLY
<br />SUPPORTED, BRACED VERTICALLY AND HORIZONTALLY IN ACCORDANCE
<br />WITH APPLICABLE CODES AND AS REQUIRED TO PREVENT EXCESSIVE
<br />MOVEMENT DURING SEISMIC CONDITIONS.
<br />10 SANITARY WASTE AND VENT PIPING SHALL BE SCHEDULE 40 PVC;
<br />(ASTM D 2665) WITH SCHEDULE 40 SOCKET —TYPE PIPE FITTINGS;
<br />(ASTM D 3311), UNLESS PROHIBITED BY THE LOCAL CODES.
<br />11 WHEN PVC PIPING IS PROHIBITED BY THE LOCAL CODES, THEN
<br />SANITARY WASTE AND VENT PIPING SHALL BE HUB AND SPIGOT,
<br />SERVICE WEIGHT CAST IRON SOIL PIPE; (ASTM A 74) WITH HUB AND
<br />SPIGOT, SERVICE WEIGHT CAST IRON SOIL PIPE FITTINGS; (ASTM A 74)
<br />OR HUBLESS, SERVICE WEIGHT CAST IRON SOIL PIPE FITTINGS; (CISPI
<br />301) UPON APPROVAL BY THE BUILDING OFFICIAL.
<br />12 PVC PIPING SHALL NOT BE INSTALLED IN RETURN AIR PLENUMS.
<br />PIPING IN RETURN AIR PLENUMS SHALL BE SERVICE WEIGHT CAST
<br />IRON OR GALVANIZED STEEL PIPING UPON ARRIVAL BY THE BUILDING
<br />OFFICIAL.
<br />13 ALL SANITARY WASTE PIPING 2-1/2" AND SMALLER SHALL BE SLOPED
<br />AT 1 /4" PER FOOT MINIMUM. ALL SANITARY WASTE PIPING 3" AND
<br />LARGER SHALL BE SLOPED AT 1/8" PER FOOT MINIMUM.
<br />14 EXPOSED WASTE PIPING IN REST ROOM AREAS SHALL BE CHROME
<br />PLATED BRASS, WITH MATCHING STOPS AND ESCUTCHEONS.
<br />15 DOMESTIC WATER PIPING SHALL BE WROUGHT SEAMLESS COPPER,
<br />TYPE "L" WITH 95-5 SILVER SOLDERED JOINTS; (ASTM B 88).
<br />16 STERILIZE DOMESTIC WATER PIPING IN ACCORDANCE WITH HEALTH
<br />DEPARTMENT REGULATIONS AND AMERICAN WATER WORKS
<br />ASSOCIATION'S SPECIFICATIONS.
<br />17 ALL DOMESTIC WATER PIPING SHALL BE HUNG LEVEL WITHOUT PITCH.
<br />18 COPPER PIPING SHALL BE PROTECTED AGAINST CONTACT WITH
<br />DISSIMILAR METALS. ALL HANGERS, SUPPORTS, ANCHORS, AND CLIPS
<br />SHALL BE COPPER OR COPPER PLATED. WHERE COPPER PIPING IS
<br />CARRIED ON IRON TRAPEZE HANGERS WITH OTHER PIPING,
<br />SATISFACTORY AND PERMANENT ELECTROLYTIC ISOLATION MATERIAL
<br />SHALL PREVENT CONTACT WITH OTHER METALS.
<br />19 COPPER PIPING SHALL BE PROTECTED AGAINST CONTACT WITH ALL
<br />MASONRY. WHERE COPPER IS SLEEVED THROUGH MASONRY, COPPER
<br />OR RED BRASS SLEEVES SHALL BE USED. WHERE COPPER MUST BE
<br />CONCEALED IN OR AGAINST MASONRY PARTITIONS, CONTACT SHALL BE
<br />PREVENTED BY COATING THE COPPER HEAVILY WITH ASPHALTIC
<br />ENAMEL AND 15#ASPHALT SATURATED FELT BETWEEN THE PIPE AND
<br />THE MASONRY PARTITION.
<br />20 ALL WATER PIPING ABOVE GRADE SHALL BE INSULATED WITH 1" RIGID
<br />FIBERGLASS IN AN ALL —SERVICE JACKET WITH ALL JOINTS AND SEAMS
<br />SEALED WITH A VAPOR BARRIER MASTIC, OR SHALL BE INSULATED
<br />WITH 1 /2" FLEXIBLE FOAM INSULATION. FLEXIBLE FOAM INSULATION
<br />SHALL NOT BE SPLIT AND SHALL BE TAPED AT ALL THE BUTT JOINTS.
<br />21 ALL WATER PIPING BELOW GRADE SHALL BE INSULATED WITH 1/2-
<br />FLEXIBLE FOAM INSULATION. FLEXIBLE FOAM INSULATION SHALL NOT
<br />BE SPLIT AND SHALL BE TAPED AT ALL THE BUTT JOINTS.
<br />22 WATER PIPING SHALL NOT BE RUN IN AREAS SUBJECT TO FREEZING
<br />TEMPERATURES. WATER PIPING IN EXTERIOR WALLS SHALL BE RUN
<br />ON CONDITIONED SIDE OF THE WALL INSULATION.
<br />23 PROVIDE SIZE ` "A" WATER HAMMER ARRESTERS (P.P.P MFG. OR
<br />EQUAL), SUPPLIES AND STOPS. EXPOSED STOPS SHALL BE CHROME
<br />PLATED.
<br />24 PROVIDE DRAIN VALVES AT ALL LOW POINTS OF DOMESTIC WATER
<br />PIPING SYSTEMS FOR COMPLETE DRAINAGE AND INDICATE LOCATION
<br />OF SAME ON RECORD DRAWINGS.
<br />25 PROVIDE VACUUM BREAKERS AS REQUIRED BY CODE.
<br />26 INCOMING WATER PRESSURE SHALL BE LIMITED TO 50 PSI. MAXIMUM.
<br />27 — 39 NOT USED.
<br />40 A. REGULATORY REQUIREMENTS: PROVIDE ALL WORK TO MEET OR
<br />EXCEED MINIMUM REGULATORY REQUIREMENTS INCLUDING:
<br />FLORIDA BUILDING CODE: 2004 EDITION, WITH 2O06
<br />SUPPLEMENT
<br />FLORIDA FIRE PREVENTION CODE: 2006 EDITION
<br />ADVISE THE ARCHITECT OF ANY CHANGES IN THE CONTRACT
<br />DOCUMENTS THAT MAY BE REQUIRED IN ORDER TO MEET CODE,
<br />PRIOR TO WORK (ORDERING, ROUGHING, OR INSTALLATION).
<br />B. COORDINATION: COORDINATE WITH OTHER WORK (INCLUDING FIRE
<br />PROTECTION, MECHANICAL, ELECTRICAL, STRUCTURAL AND
<br />ARCHITECTURAL) FOR AVAILABLE SPACE, SEQUENCE OF
<br />INSTALLATION, AND INSTALLATION REQUIREMENTS, PRIOR TO
<br />COMMENCING CONSTRUCTION. ADVISE THE ARCHITECT OF ANY
<br />CHANGES IN THE CONTRACT DOCUMENTS THAT MAY BE REQUIRED
<br />FOR THE WORK TO BE PERFORMED.
<br />C. DEVICE LOCATIONS: REFER TO ARCHITECTURAL DRAWINGS FOR
<br />EXACT LOCATION OF PLUMBING FIXTURES, PLUMBING DEVICES,
<br />AND FIXTURE INSTALLATION HEIGHTS. LOCATE ALL PIPING IN
<br />FINISHED ROOMS OR SPACES WITHIN CONCEALED LOCATIONS
<br />(FURRED CHASES OR SUSPENDED CEILINGS, AS AVAILABLE). DO
<br />NOT LOCATE PIPING ABOVE ELECTRICAL SWITCHBOARDS OR
<br />PANELBOARDS. PROVIDE METALLIC DRIP SHIELDS BELOW ALL
<br />PIPING (INCLUDING ROOF DRAINS AND STORM PIPES) IN
<br />TELEPHONE AND ELECTRICAL ROOMS.
<br />D. SIZES: WHEN A PIPE SIZE IS NOT INDICATED, SIZE THAT PIPE
<br />USING THE LARGER UPSTREAM ADJACENT SIZE, UNLESS A
<br />SMALLER SIZE IS APPROVED BY THE ARCHITECT. PROVIDE 3/4
<br />INCH MINIMUM PIPE SIZE, UNLESS SPECIFICALLY NOTED
<br />OTHERWISE. FOR SIZES NOT INDICATED ON PLANS, REFER TO
<br />EQUIPMENT DETAILS, FLOW DIAGRAMS, RISER DIAGRAMS, AND
<br />OTHER LOCATIONS IN THE CONTRACT DOCUMENTS (DRAWINGS
<br />AND SPECIFICATIONS) FOR INFORMATION.
<br />E. SEALS: REFER TO ARCHITECTURAL DRAWINGS FOR LOCATION OF
<br />FIRE RATED PARTITIONS. SEAL ALL PENETRATIONS OF RATED
<br />PARTITIONS.
<br />41 A. PROVIDE ALL NECESSARY FEES AND PERMITS. REVIEW
<br />OPERATION OF EACH SYSTEM WITH OWNER'S REPRESENTATIVE.
<br />PROVIDE ONE YEAR WARRANTY ON ENTIRE SYSTEM. PROVIDE
<br />RECORD DRAWING (CONTRACTOR FURNISHED SEPIA).
<br />SUBMITTALS: SUBMIT PRODUCT DATA FOR EACH NEW PLUMBING
<br />DEVICE.
<br />B. ACCESS DOORS: PROVIDE 18 INCH X 18 INCH (MINIMUM)
<br />PAINTED ALUMINUM ACCESS DOORS (WITH FULL HINGE AND KEY)
<br />FOR ACCESS TO VALVES, EQUIPMENT AND ACCESSORIES IN
<br />PLASTER, DRYWALL, OR IN ACCESSIBLE CEILINGS OR IN WALLS.
<br />GROUP DEVICES AT ONE LOCATION, AS AVAILABLE.
<br />C. FINISHES: PROVIDE CHROMED FINISH ON ALL EXPOSED PIPING
<br />IN FINISHED ROOMS.
<br />42 — 49 NOT USED.
<br />50 BURIED 4 INCH SANITARY PIPING (19 DFU). PROVIDE A TWO WAY
<br />CLEANOUT AND MAKE CONNECTION TO CIVIL (SITE) SANITARY PIPING.
<br />INVERT = 3'-0" BELOW FINISH FLOOR.
<br />51 BURIED 1-1/4 INCH COLD WATER PIPING (19 WSFU, 20 GPM).
<br />MAKE CONNECTION TO CIVIL (SITE) CW PIPING.
<br />52 BURIED 6 INCH STORM PIPING (2,010 SF CONNECTED). PROVIDE A
<br />TWO WAY CLEANOUT AND MAKE CONNECTION TO CIVIL (SITE) STORM
<br />PIPING. INVERT = 3'-6" BELOW FINISHED FLOOR.
<br />53 BURIED 6 INCH STORM PIPING (2,520 SF CONNECTED). PROVIDE A
<br />TWO WAY CLEANOUT AND MAKE CONNECTION TO CIVIL (SITE) STORM
<br />PIPING. INVERT = 3'-6" BELOW FINISHED FLOOR.
<br />54 NOT USED.
<br />55 1-1/4" CW RISER UP TO CEILING SPACE. PROVIDE AN ISOLATION
<br />VALVE IN THE RISER NEAR THE FLOOR (12" ABOVE FINISH FLOOR).
<br />56 PROVIDE A WALL MOUNTED ELECTRIC WATER HEATER. REFER TO THE
<br />EWH DETAIL ON DRAWING PO.1.
<br />57 ROUTE THE EWH SAFETY PAN DRAIN AND THE P&T RELIEF VALVE
<br />DRAIN (EACH FULL SIZE BUT 3/4" MINIMUM) DOWN WITHIN WALL AND
<br />TERMINATE 6" ABOVE THE GRADE.
<br />58 ROUTE A 1 /2" BURIED CW FROM THE TRAP PRIMER, LOCATED AT THE
<br />LAVATORY, TO THE FLOOR DRAIN.
<br />59 PROVIDE A 3/4" HOT WATER LOOP DOWN IN WALL.
<br />3" VTR
<br />ROOF
<br />2
<br />N e e M
<br />S N> N N> 1D N> 1D yN N> 1D yN WC
<br />1D 1D
<br />MS WC FD FD
<br />FLOOR 1 > 1 D > e 1 03"
<br />4" p 3"3 43"
<br />=-\--, 3p S� ="- �-
<br />SANITARY RISER DIAGRAM
<br />NO SCALE
<br />PLUMBING LEGEND
<br />SYMBOL DESCRIPTION
<br />ABOVEGROUND PIPING (TYPICAL ALL SYSTEMS)
<br />BURIED PIPING (TYPICAL ALL SYSTEMS)
<br />S SANITARY PIPING
<br />VENT PIPING
<br />DOMESTIC COLD WATER PIPING
<br />DOMESTIC HOT WATER PIPING
<br />1---HWRC---i DOMESTIC HOT WATER RECIRCULATING PIPING
<br />DIRECTION OF FLOW
<br />—�Q— ISOLATION VALVE
<br />PIPE RISE
<br />D PIPE DROP
<br />T DROP
<br />] PIPE CAP
<br />WCO __II WALL CLEANOUT
<br />00 GCO GRADE CLEANOUT
<br />® RECIRCULATING PUMP
<br />HANDICAPPED/FL,ADA
<br />1D ACCESSIBLE FIXTURE
<br />wC WATER CLOSET TYPE
<br />1D
<br />L LAVATORY TYPE
<br />1D
<br />eELECTRIC WATER HEATER TYPE
<br />S SINK TYPE
<br />1D
<br />IM ICEMAKER BOX TYPE
<br />EWC ELECTRIC WATER COOLER TYPE
<br />1D
<br />MS MOP SINK TYPE
<br />eFLOOR DRAIN TYPE
<br />1
<br />eWALL HYDRANT TYPE
<br />O DRAWING NOTE: REFER TO NOTES ON EACH
<br />DRAWING
<br />ABBREVIATION DESCRIPTION
<br />AFF ABOVE FINISHED FLOOR
<br />CLG CEILING
<br />CO CLEANOUT
<br />CW
<br />COLD WATER
<br />DFU
<br />DRAINAGE FIXTURE UNITS
<br />DN
<br />DOWN
<br />ELECT
<br />ELECTRICAL
<br />FIN FL ELEV
<br />FINISHED FLOOR ELEVATION
<br />FCO
<br />FLOOR CLEANOUT
<br />FT
<br />FEET
<br />GPM
<br />GALLONS PER MINUTE
<br />HVAC
<br />HEATING, VENTILATING, AND AIR CONDITIONING
<br />HW
<br />HOT WATER
<br />IN
<br />INCH
<br />INV
<br />INVERT
<br />P&T
<br />PRESSURE AND TEMPERATURE
<br />SAN
<br />SANITARY
<br />VB
<br />VACUUM BREAKER
<br />V
<br />VENT
<br />VTR
<br />VENT THROUGH ROOF
<br />WFU
<br />WATER FIXTURE UNITS
<br />WCO
<br />WALL CLEANOUT
<br />TWO—WAY GCO
<br />4" SAN
<br />k. 4" Sty (19 DFU )
<br />Revisions:
<br />Seal:
<br />Consultants:
<br />0
<br />ARCHITECTURAL ENGINEERING INCORPORATED
<br />3442 EAST LAKE ROAD, PALM HARBOR, FL 34685
<br />CONSULTING ENGINEERS (727) 784-1472
<br />CERTIFICATE OF AUTHORIZATION: FL 3886
<br />W. RONALD MCILVEEN FL PE 30270
<br />zZ I MUT 07=77-TAT-T-14,►►+�
<br />WACHOVIA ZEPHYR
<br />COMMONS
<br />PARCEL 6
<br />US ROUTE 301
<br />ZEPHYw- FLORIDA
<br />
|