N <br />16 <br />12 <br />16 <br />12 <br />16 <br />12 <br />16 <br />12 <br />( :)Ii <br />Electrical Power Plan <br />1 N Scale 1/8"=V-0" <br />O <br />CUT OFF AND CAP AT TOP OF <br />FLOOR SLAB OR ABOVE <br />CEILING ANY EXISTING <br />CONDUIT STUB INS THAT ARE <br />NO LONGER BEING USED. <br />1O EXISTING ELECTRICAL POWER RISER. <br />2O EXISTING TENANT ELECTRICAL PANEL D4. <br />O3 NEW TENANT ELECTRICAL PANEL D3. LOCATE PANEL AS CLOSE AS POSSIBLE TO EXISTING CONDUIT <br />STUB IN. EDGE OF PANEL SHALL BE 12" MIN. FROM CMU OPENING OF REAR DOOR. <br />O4 EXISTING JUNCTION BOX FOR FUTURE TENANT SIGN TO REMAIN WIRED AS IS TO PANEL D4. <br />O5 EXISTING JUNCTION BOX FOR FUTURE TENANT SIGN TO BE REWIRED FROM PANEL D4 TO PANEL D3. <br />O6 EXISTING SHOW WINDOW RECEPTACLE TO REMAIN WIRED AS IS TO PANEL D4. <br />O7 EXISTING SHOW WINDOW RECEPTACLE TO BE REWIRED FROM PANEL D4 TO PANEL D3. <br />O8 EXISTING 5 TON RTU WITH EXISTING FACTORY INSTALLED DISCONNECT AND EXISTING FACTORY <br />INSTALLED POWERED CONVENIENCE OUTLET (CONTRACTOR SHALL CONFIRM OUTLET INSTALLATION <br />IS PER SECTION 210.63 OF THE NEC). CONTRACTOR SHALL VERIFY THAT THERE IS AN EXISTING <br />SMOKE DUCT DETECTOR IN THE SUPPLY DUCT. IF THERE ISN'T, REFER TO MECHANICAL GENERAL <br />NOTE # 7 ON SHEET M101. THE GC SHALL BE RESPONSIBLE FOR COORDINATING THE EXACT SCOPE <br />OF WORK REQUIRED BETWEEN THE MECHANICAL SUB AND THE ELECTRICAL SUB PRIOR TO BIDDING. <br />NO CHANGE ORDERS WILL BE APPROVED FOR FAILURE TO VERIFY EXISTING CONDITIONS OR <br />COORDINATE BETWEEN SUBS, <br />O9 EXISTING RTU TO REMAIN WIRED AS IS TO PANEL D4. <br />10 EXISTING RTU TO BE REWIRED FROM PANEL D4 TO PANEL D3. <br />11 EXISTING RECEPTACLE TO REMAIN WIRED AS IS TO PANEL D4. <br />12 EXISTING RECEPTACLE TO BE REWIRED FROM PANEL D4 TO PANEL D3. <br />13 NEW POWER RECEPTACLES TO BE WIRED TO PANEL D3. <br />14 NEW POWER RECEPTACLES TO BE WIRED TO PANEL D4. <br />15 PROVIDE ONE NEW CAT-V CONNECTION PORT NEXT TO EACH QUAD RECEPTACLE. PROVIDE 1/2" <br />CONDUIT W/ PULL CORD UP TO SPACE ABOVE CEILING OUTSIDE OF DEMISING WALL. CAP ABOVE <br />CEILING FOR FUTURE TENANT CONNECTION. <br />16 EXISTING COMMUNICATION / DATA OUTLET TO BE DISCONNECTED FROM THE SPACE D4 <br />COMMUNICATION SYSTEM. EXISTING CABLE SHALL BE COILED AND LEFT DIRECTLY ABOVE OUTLET <br />ABOVE THE CEILING FOR FUTURE TENANT CONNECTION. <br />17 EXISTING COMMUNICATION / DATA OUTLET TO BE LEFT CONNECTED AS IS TO THE EXISTING SPACE D4 <br />COMMUNICATION SYSTEM. <br />18 THE EXISTING COMMUNICATION / DATA SYSTEM FOR SPACE D4 SHALL REMAIN AS IS. ANY EXISTING <br />COMMUNICATION / DATA OUTLETS IN SPACE D3 SHALL BE DISCONNECTED FROM THE SPACE 04 <br />SYSTEM (RE: KEY NOTE 16). NO NEW COMMUNICATION / DATA EQUIPMENT FOR SPACE D3 WILL BE <br />PROVIDED AS PART OF THIS SCOPE OF WORK. ALL NEW EQUIPMENT AND CONNECTION OF EXISTING <br />OUTLETS SHALL BE BY THE FUTURE TENANT. <br />4 Building Power <br />Riser Diagram <br />SCALE: NTS <br />METERING NOTES: <br />1. CONTRACTOR SHALL COORDINATE EXACT <br />REQUIREMENTS FOR METERING EQUIPMENT TYPES <br />AND SYSTEM TOPOLOGY WITH THE LATEST <br />STANDARDS OF THE LCOAL ELECTRIC UTILITY PRIOR <br />TO ORDERING AND INSTALLATION OF EQUIPMENT. <br />Tj RANz.. ; mm 4 <br />C <br />EF 28 <br />X .. 27 <br />22 ® <br />22w: <br />D3- 5 <br />-` <br />I <br />D3-3 <br />NL <br />A 25 <br />NL <br />EM ,5 <br />EM <br />23 y 22 <br />fNA <br />25 <br />D3-7 24 <br />D4` <br />D4-9 <br />0 <br />0q <br />22 <br />€A <br />22 <- <br />D13- <br />A <br />::... <br />22 D4-1 <br />ftA <br />_'M <br />; a� <br />- <br />€ <br />A <br />D3-1 <br />25 <br />EM <br />21 21 <br />2 Electrical Lighting Plan <br />NScale 1/8"=V-0" <br />21 EXISTING DECORATIVE SCONCE FIXTURES SHALL REMAIN WIRED AS IS TO THE EXISTING HOUSE PANEL. <br />22 EXISTING LIGHT FIXTURES SHALL REMAIN WIRED AS IS TO THE EXISTING TENANT PANEL D4. <br />23 NEW EXIT LIGHT FIXTURE (X) OR EMERGENCY LIGHT FIXTURE (EM). TIE INTO EXISTING CIRCUIT # 1 ON <br />TENANT PANEL D4. <br />24 EXISTING LAY -IN LIGHT FIXTURES. RE -WIRE FROM EXISTING PANEL D4 TO NEW PANEL D3 VIA NEW LIGHT <br />SWITCH LOCATED NEXT TO D3 REAR DOOR ON THE LATCH SIDE. <br />25 EXISTING EXIT / EMERGENCY / NIGHT LIGHT FIXTURES TO BE RE -WIRED FROM EXISTING PANEL D4 TO <br />NEW PANEL D3. <br />26 NEW EXIT LIGHT FIXTURE (X) OR EMERGENCY LIGHT FIXTURE (EM) WIRED TO NEW PANEL D3. <br />27 EXISTING EXTERIOR LIGHT FIXTURE. RE -WIRE FROM EXISTING PANEL D4 TO NEW PANEL D3 VIA EXISTING <br />LIGHT SWITCH. <br />28 NEW RESTROOM LIGHT FIXTURE AND EXHAUST FAN WIRED TO NEW PANEL D3 VIA NEW LIGHT SWITCH. <br />Light Fixture Schedule <br />TYPE <br />MANUFACTURER <br />CATALOG NO. <br />VOLT <br />LAMPS <br />MOUNTING & OPTION <br />NOTE <br />A <br />DAYBRITE <br />2TG8-3-32-01-UNV-1/3-EB <br />120 <br />(3) 32W T8 <br />GRID MOUNTED <br />1-3,5-6 <br />C <br />NITE BRITES <br />WCR-050-M-MT <br />120 <br />- <br />EXISTING TO REMAIN <br />EM <br />BEGHELLI <br />XLP-S1 <br />120 <br />- <br />WALL MTD AT 9'-O"AFF <br />2 & 4 <br />X <br />BEGHELLI <br />VA4-R-SA <br />120 <br />LED (INCLUDED) <br />UNIVERSAL <br />2 & 4 <br />ALTERNATE FIXTURES MAY BE COOPER, LITHONIA, GENLYTE, HUBBELL, OR THOMAS. FIXTURE <br />SUBSTITUTIONS MUST BE APPROVED BY OWNER BEFORE THEY ARE SUBMITTED TO THE ENGINEER. <br />1. ALL FLUORESCENT LIGHTING FIXTURES SHALL HAVE ENERGY SAVING LAMPS AND ELECTRONIC BALLASTS. <br />2. PROVIDE NECESSARY MOUNTING HARDWARE AND ACCESSORIES FOR ALL FIXTURES. <br />3. PROVIDE .125 MIN. THICK LENSES FOR FLUORESCENT FIXTURES. <br />4. ALL EMERGENCY, EXIT AND NIGHT LIGHT FIXTURES SHALL BE CONNECTED AHEAD OF LOCAL SWITCHES. <br />UNLESS OTHERWISE NOTED. <br />5. ALL ALTERNATE FIXTURES SHALL BE SUBMITTED FOR PRIOR APPROVAL, SEE SPECIFICATIONS. <br />6. CONTACT SESCO LIGHTING (407) 629-6100 DAN SCHULMAN <br />7. VENDOR SHALL VERIFY ALL FIXTURE QUANTITIES AND LOCATIONS (RE: REFLECTED CEILING PLAN). <br />8. MOUNTING HEIGHTS INDICATED ARE TO THE CENTER LINE OF DEVICE OR FIXTURE U.O.N. <br />9. ALL FIXTURES TO BE CENTERED ON 2X4 CEILING GRID U.O.N. <br />10. ALL FIXTURES TO BE PROVIDED BY, RECEIVED, STORED & INSTALLED BY ELECTRICAL CONTRACTOR. <br />11. CONTRACTOR SHALL PROVIDE OWNER 10% ADDITIONAL SPARE OF ALL LAMP TYPES AT END OF JOB. <br />12. CIRCUIT BREAKERS USED AS SWITCHES IN 120V AND 277V FLUORESCENT LIGHTING CIRCUITS SHALL BE <br />LISTED AND SHALL BE MARKED SWD OR HID. <br />RISER KEY NOTES®: <br />1. NEW METER AND DISCONNECT LOCATED AS CLOSE AS POSSIBLE TO <br />THE LOCATION SHOWN ON THE RISER DIAGRAM. EXACT LOCATION <br />TO BE DETERMINED BY THE CONTRACTOR IN THE FIELD. <br />2. (1) SET OF NEW (4) # 3/0 & (1) # 310 G, IN NEW 2" CONDUIT <br />3. (1) SET OF NEW (4) # 3/0 & (1) # 6 G, IN NEW 2" CONDUIT <br />4. (1) NEW 4" TO 2" REDUCER <br />5. (1) SET OF NEW (4) # 3/0 & (1) # 6 G, IN EXISTING 4" CONDUIT <br />6. (1) NEW 7-DAY, 4 CIRCUIT PROGRAMMABLE TIME CLOCK <br />EXISTING1ZX12 _ R3 _140ANWITHKEYsir <br />r. <br />€ <br />€ <br />O ` , <br />I <br />I <br />3 Fire Alarm Plan <br />NScale 1/8"=T-O" <br />31 EXISTING FIRE ALARM EQUIPMENT. <br />32 NEW FIRE ALARM EQUIPMENT. <br />EXISTING FIRE ALARM EQUIPMENT SHALL BE RELOCATED / REWIRED AS <br />NEEDED AND NEW FIRE ALARM EQUIPMENT SHALL BE PROVIDED AS NEEDED IN <br />ORDER TO PROVIDE COMPLETE SEPARATE FIRE ALARM SYSTEMS FOR TENANT <br />SPACES D3 AND D4. <br />ALL FIRE ALARM EQUIPMENT IS SHOWN FOR REFERENCE PURPOSES ONLY. <br />THE COMPLETE AND FINAL FIRE ALARM SYSTEM SHALL BE DESIGNED BY THE <br />CONTRACTOR, THROUGH SHOP DRAWINGS THAT ARE SIGNED AND SEALED BY <br />A STATE OF FLORIDA LICENSED AND REGISTERED ENGINEER. SIGNED AND <br />SEALED SHOP DRAWINGS SHALL BE SUBMITTED TO THE LOCAL JURISDICTION <br />AS REQUIRED FOR PERMITTING. <br />ALL WIRING SHALL BE COPPER ONLY. <br />CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR <br />TO SUBMITTING BIDS. IF EXISTING CONDITIONS ARE NOT AS <br />SPECIFIED, CONTRACTOR SHALL NOTIFY THE ARCHITECT / <br />ENGINEER IMMEDIATELY. <br />D3 <br />I , <br />D2 <br />DA <br />NEW DIS- <br />D5,06 <br />` <br />y EXISTING £ <br />STD <br />CONNECT <br />A€ _ !IINC <br />I <br />,. <br />2AMP <br />2`00 .' ` 1 <br />q <br />I 200 A B -vir = <br />S ' <br />[ DIS- ( <br />200 <br />,r Ii E: i <br />_ _... a. <br />NI'.E' <br />emuNNE "" <br />3. <br />� ¢ONs�� <br />i <br />200 <br />' <br />I <br />, <br />EN(Si�N �, NCr. T � X,_,€€gem <br />M. pub, E . € , . _S A T PAN'-' NAW "R <br />€ <br />75 <br />RANSFORNREER <br />E ": AW <br />EX <br />ELECTRICAL LEGEND <br />MOUNTING HEIGHTS SHOWN ARE MAX. / MIN. HANDICAPPED ACCESSIBILITY STANDARDS - THEY SHALL NOT BE ALTERED WITHOUT WRITTEN AUTHORIZATION. <br />NOT ALL DEVICES <br />SHOWN IN LEGEND ARE REQUIRED. REVIEW POWER & LIGHTING PLANS AND DETAILS FOR ITEMS WHICH APPLY TO THIS PROJECT. <br />AQa <br />FLUORESCENT LIGHT FIXTURE, LETTER INDICATES TYPE. SEE FIXTURE <br />SCHEDULE. LOWER CASE LETTER INDICATES SWITCH USED) <br />(IF <br />� LIGHTING, POWER, FRCP PANELBOARD OR TELE. TERM. CABINET. <br />ME NL <br />NIGHT LIGHT FIXTURE (NL) <br />`0 DISCONNECT SWITCH <br />® X <br />EXIT LIGHT (SHADE AREA INDICATES DIRECTION) LETTER INDICATES TYPE <br />SEE LIGHT FIXTURE SCHEDULE TO CONFIRM TYPE AND MOUNTING. <br />�F <br />FIRE ALARM PULL STATION <br />t9 <br />BATTERY POWERED EMERGENCY LIGHT <br />HORN/STROBE <br />SINGLE POLE SWITCH, LOWER CASE LETTER INDICATES LIGHTS <br />CONTROLLED. LETTER NOT SHOWN IF SELF EVIDENT, MOUNT <br />O2 SMOKE DETECTOR <br />a <br />48" A.F.F. U.O.N. <br />F <br />SINGLE POLE SWITCH. FAN CONTROLLER, MOUNT 48" A.F.F. U.O.N. <br />EF ® EXHAUST FAN <br />DUPLEX RECEPTACLE, MOUNT 18" AFF LION <br />THERMOSTAT. PROVIDE SINGLE GANG BOX WITH 1/2" C. STUBBED <br />OT INTO CEILING SPACE, MOUNT 60" AFF LION (COORDINATE WITH <br />GROUND FAULT INTERRUPTER RECEPTACLE, LEVITON #6898-I, MOUNT <br />MECHANICAL DRAWINGS PRIOR TO ROUGH -IN) <br />�GFI <br />ABOVE COUNTER HEIGHT U.O.N. <br />ABBREVIATIONS <br />DUPLEX RECEPTACLE, MOUNTED ABOVE STOREFRONT WINDOWS <br />AFF ABOVE FINISH FLOOR NF NON -FUSED <br />O <br />JUNCTION BOX (FLUSH MOUNT IN FINISHED AREAS U.O.N.) <br />AFG ABOVE FINISH GRADE NIC NOT IN CONTRACT <br />C/T CURRENT TRANSFORMER NL NIGHT LIGHT <br />> <br />QUAD RECEPTACLE, MOUNT 18" AFF UON <br />DE DUAL ELEMENT FUSE NTS NOT TO SCALE <br />CONDUIT CONCEALED IN WALL, BELOW SLAB, OR ABOVE CEILING. <br />EC EMPTY CONDUIT OS OCCUPANCY SENSORS <br />E/F-EF EXHAUST FAN RTU ROOF TOP UNIT <br />A-1,3 <br />CONDUIT RUN CONCEALED IN WALLS BELOW SLAB, OR CEILING SPACES. <br />EG EQUIPMENT GROUND TTB TELEPHONE TERMINAL BOARD <br />ARROWS INDICATE HOMERUN. SMALL HASHMARKS INDICATE NUMBER OF <br />EM EMERGENCY LIGHT TTC TELEPHONE TERMINAL CABINET <br />HOT CONDUCTORS, AND LARGE HASHMARK INDICATES NEUTRAL. <br />SUBSCRIPT INDICATES PANEL AND CIRCUIT NUMBERS. GROUND <br />EWC ELECTRIC WATER COOLER TYP TYPICAL <br />CONDUCTOR REQUIRED IN ALL CONDUITS BUT NOT INDICATED. <br />EWH ELECTRIC WATER HEATER LION UNLESS OTHERWISE NOTED <br />A-37:39:41 <br />SUBSCRIPT INDICATES PANEL -AND NUMBERS WITH COLONS <br />EX EXISTING DEVICE TO REMAIN VTC VIA TIME CLOCK <br />INDICATE 2 OR 3 POLE CIRCUITS. <br />FACP FIRE ALARM CONTROL PANEL WP WEATHERPROOF <br />100/3/60 <br />DISCONNECT DESIGNATION (SIZE/POLES/FUSE) "NF" INDICATES <br />GFI GROUND FAULT INTERRUPTER X EXIT LIGHT <br />NON -FUSED; "DE" INDICATES DUAL ELEMENT FUSES. <br />LB LOCK BREAKER <br />MANUFACTURER SQUARE 0 *INC NAME-, TENANT PANEL TW <br />MAIN BREAKER 3 PHASE <br />MAJN LUG& 200 AMP 4 WIRE PROJECT; NAME: REFER TO <br />r <br />� <br />I <br />i �,■ <br />i-. <br />� ♦ <br />0 <br />Q <br />0 THE, R (Okfi <br />GENERAL LIGHTII <br />SQUARE FOOT, LOAD; <br />LIGHTING DEMAND LOAD IS BASED ON THE LARGER OF THE TWO <br />(CONNECTED VS. TABLE 220. 3a, NEC 2002. <br />**LARGER ABC LOAD, 6.2 KVA. <br />I }LENGTH 0......._KVA <br />MAIN LUGS: <br />200 AMP <br />4 WIRE <br />PROJECT NAME�. REFER <br />TO TITLE BLOCK ON SHEET <br />K.AJ,Ct: <br />42 <br />1202D8 VOLTS <br />PROJECT NUMBER REFER TO TITLE BLOCK ON SHEET <br />MOUNTEa <br />SURFACE <br />FED ; <br />LOAD <br />PHASE <br />(KVA) <br />rp�y <br />111M91 <br />Wag <br />_' <br />_ <br />.. <br />.. - <br />- • <br />Wgimr.Awe <br />RECEPTACLES <br />RECEPTACLES <br />*IIIIT E ONLYs <br />ONLY: <br />u� <br />29 SPACE ONLY <br />- <br />f <br />aMOW".► <br />o r <br />I <br />I <br />## <br /># <br />t <br />O <br />U <br />�a <br />00 <br />00 <br />U <br />N •--� <br />M p <br />l <br />n <br />U <br />o <br />>o <br />ao <br />�� <br />1364 <br />U <br />6 <br />6 1 <br />0 <br />CL <br />0 <br />L. <br />Uw <br />�Z00 <br />VQM <br />._0M <br />�0U_ <br />a "E � .: <br />LNG <br />H <br />U <br />CD <br />0 <br />E <br />E <br />0 <br />U <br />N <br />Co <br />Qm <br />0 Y <br />M Q <br />Do <br />m <br />C J LL <br />CML-Q <br />C <br />0 J <br />♦�WJ <br />� do <br />w <br />Z <br />CU 06_ <br />U <br />L <br />N <br />a <br />0 <br />--=a <br />CU <br />E <br />CU <br />co <br />to <br />CU <br />0- <br />CU <br />.L <br />Uw <br />w <br />w <br />x <br />m <br />H <br />w <br />m <br />w <br />n. <br />0 <br />C? <br />0 <br />w4 <br />�I <br />O <br />W <br />N <br />J <br />W <br />Q' <br />co <br />CD <br />Z <br />0 <br />O <br />Z <br />� <br />W <br />z <br />LU <br />N <br />W <br />N <br />CC9 <br />U <br />d <br />U <br />E101 <br />