N <br />Design No. U419 (November 14, 2007) <br />in. thick) shall be attached to furring channels as described in Item 6. One layer of gypsum board panels (1/2 in. <br />Nonbearing Wall Ratings — 1, 2, 3 or 4 Hr (See Items 4 & 5) <br />or 5/8 in. thick) attached to opposite side of stud without furring channels as described in Item 6. <br />\< <br />5A. Gypsum Board* — (As an alternate to Item 5) — 5/8 in. thick, 24 to 54 in. wide, applied horizontally as <br />the outer layer to one side of the assembly. Secured as described in Item 6. - Canadian Gypsum Co — Type <br />_ a <br />SHX.; US Gypsum Co —Type FRX-G, SHX.; USG Mexico S A DE C V —Type SHX. <br />h <br />5B. Gypsum Board* — (As an alternate to Item 5 when used as the base layer on one or both sides of wall, For <br />direct attachment only, not to be used with Item 3) - Nom 5/8 in. thick lead backed gypsum panels with <br />beveled, square or tapered edges, applied vertically. Vertical joints centered over studs and staggered min 1 <br />stud cavity on opposite sides of studs. Wallboard secured to studs with 1 1/4 in. long Type 5-12 steel screw <br />spaced 8 in. OC at perimeter and 12 in. OC in the field. -Ray-Bar Engineering Corp —Type RB-LBG <br />6. Fasteners — (Not shown) — For use with Item 2 - Type S or S- 12 steel screws used to attach panels to studs <br />i <br />(Item 2) or furring channels (Item 7). Single layer systems: 1 in. long for 1/2 and 5/8 in. thick panels or 1-1/4 <br />in. long for 3/4 in. thick panels, spaced 8 in. OC when panels are applied horizontally, or 8 in. OC along <br />vertical and bottom edges and 12 in. OC in the field when panels are applied vertically. Two layer systems: <br />1. Floor and Ceiling Runners — (Not shown) — For use with Item 2 - Channel shaped, fabricated from min <br />First layer- 1 in. long for 1/2 and 5/8 in. thick panels or 1-1/4 in. long for 3/4 in. thick panels, spaced 16 in. <br />25 MSG corrosion -protected steel, min width to accommodate stud size, with min 1 in. long legs, attached to <br />OC. Second layer- 1-5/8 in. long for 1/2 in., 5/8 in. thick panels or 2-1/4 in. long for 3/4 in. thick panels, <br />floor and ceiling with fasteners 24 in. OC max. <br />spaced 16 in. OC with screws offset 8 in. from first layer. Three -layer systems: First layer- 1 in. long for 1/2 <br />IA. Floor and Ceiling Runners* — Not shown - In lieu of Item 1 — For use with Item 2A, proprietary <br />in., 5/8 in. thick panels, spaced 24 in. OC. Second layer- 1-5/8 in. long for 1/2 in., 5/8 in. thick panels, spaced <br />channel shaped, min. 3-5/8 in. wide with 1 in. long legs, fabricated from min. 0.0150 in. (0.0146 in., min bare <br />24 in. OC. Third layer- 2-1/4 in. long for 1/2 in., 5/8 in. thick panels or 2-5/8 in. long for 5/8 in. thick panels, <br />metal thickness) galvanized steel, attached to floor and ceiling with fasteners 24 in. OC max. - Dietrich <br />spaced 12 in. OC. Screws offset min 6 in. from layer below. Four -layer systems: First layer- 1 in. long for <br />Industries Inc — U1traSTEEL®. <br />1B. Floor and Ceiling Runners — (Not shown - In lieu of Item 1) — For use with Item 2A, proprietary <br />1/2 in., 5/8 in. thick panels, spaced 24 in. OC. Second layer- 1-5/8 in. long for 1/2 in., 5/8 in. thick panels, <br />channel shaped, min. 2-9/16 in. wide with 1-3/16 in. wide flanges, fabricated from min. 0.0150 in. galvanized <br />spaced 24 in. OC. Third layer- 2-1/4 in. long for 1/2 in. thick panels or 2-5/8 in. long for 5/8 in. thick panels, <br />p y g p g <br />steel, attached to floor and ceiling fasteners 24 in. OC. max. -Dietrich Industries Inc — UltraSTEEL®. <br />spaced 24 in. OC. Fourth layer- 2-5/8 in. long for 1/2 in. thick panels or 3 in. long for 5/8 in. thick panels, <br />2. Steel Studs —Channel shaped, fabricated from min 25 MSG corrosion -protected steel, min width as <br />spaced 12 in. OC. Screws offset min 6 in. from layer below. <br />indicated under Item 5, min 1-1/4 in. flanges and 1/4 in. return, spaced a max of 24 in. OC. Studs to be cut 3/8 <br />6A. Fasteners (Not shown) —For use with Item 2A - Type S or 5-12 steel screws used to attach panels to <br />to 3/4 in. less than assembly height. <br />studs (Item 2). Single layer systems: 1 in. long for 1/2 and 5/8 in. thick panels or 1-1A in. long for 3/4 in. <br />2A. Steel Studs* an In lieu of Item 2 - Pro Proprietary channel shaped studs min. width as indicated under Item 5 <br />p ry p <br />thick panels, spaced 8-1/2 in. OC with additional screws 1 in, and 2-1/2 in. from edges of the board when <br />min. 1-1/4 in. long legs and 1/4 in. long folded back return flange legs, fabricated from min. 0.0 15 5 in. <br />panels are horizontally. or 8 in. OC along vertical and bottom edges and 12 in. OC in the field when panels <br />(0.0149 in., min bare metal thickness) galvanized steel, spaced a max of 24 in. OC. Studs to be cut 3/8 to 3/4 <br />area lied vertically. Two layer systems applied vertically: First layer- 1 in. long for 1/2 and 5/8 in. thick <br />pp y y y pp y y g <br />in. less than assembly height. Allowable use of studs is shown in the table below. For direct attachment of <br />panels or 1-1/4 in. long for 3/4 in. thick panels, spaced 16 in. OC. Second layer- 1-5/8 in. long for 1/2 in., 5/8 <br />gypsum board only. -Dietrich Industries Inc — U1traSTEEL�. <br />in. thick panels or 2-1/4 in. long for 3/4 in. thick panels, spaced 16 in. OC with screws offset 8 in. from first <br />2B. Steel Studs — (As an alternate to Item 2, For use with Item SB) Channel shaped, fabricated from min 20 <br />layer. Two layer systems applied horizontally: First layer- 1 in. long for 1/2 and 5/8 in. thick panels or 1-1/4 <br />MSG (0.0327 in. thick) corrosion -protected or galv steel, 3-1/2 in. min width, min 1-1/2 in. flanges and 1/4 in. <br />in. long for 3/4 in. thick panels, spaced 16 in. OC starting 8 in. from each edge of the board with an additional <br />return, spaced a max of 16 in. OC. Studs friction -fit into floor and ceiling runners. Studs to be cut 5/8 to 3/4 <br />screw placed 1-1/4 in. from each edge of the board. Second layer- 1-5/8 in. long for 1/2 in., 5/8 in. thick <br />in. less than assembly height. <br />panels or 2-1/4 in. long for 3/4 in. thick panels, spaced 16 in. OC starting 8 in. from each edge of the board <br />3. Wood Structural Panel Sheathing(Optional, For use with Item 5 Only.)- of Shown 4 ft wide 7/16 <br />— ( p y )- ) <br />with an additional screw placed 1-1/4 in. from each edge of the board with screws offset 8 in. from first layer. <br />in. thick oriented strand board (OSB) or 15/32 in. thick structural 1 sheathing (plywood) complying with DOC <br />Three -layer systems: First layer- 1 in. long for 1/2 in., 5/8 in. thick panels, spaced 24 in. OC. Second layer - <br />PSI or PS2, or APA Standard PRP-108, manufactured with exterior glue, applied horizontally or vertically to <br />1-5/8 in. long for 1/2 in., 5/8 in. thick panels, spaced 24 in. OC. Third layer- 2-1/4 in. long for 1/2 in., 5/8 in. <br />the steel studs. Vertical joints centered on studs, and staggered one stud space from wallboard joints. Attached <br />thick panels or 2-5/8 in. long for 5/8 in. thick panels, spaced 12 in. OC. Screws offset min 6 in. from layer <br />to studs with flat -head self -drilling tapping screws with a min. head diam. of 0.292 in. at maximum 6 in. OC. <br />below. For all layers, an additional screw shall be placed 1-1/4 in. from each edge of the board. Four -layer <br />in the perimeter and 12 in. OC. in the field. <br />systems: First layer- 1 in. long for 1/2 in., 5/8 in. thick panels, spaced 24 in. OC. Second layer- 1-5/8 in. long <br />4. Batts and Blankets* — (Required as indicated under Item 5) — Mineral wool batts, friction fitted between <br />for 1/2 in., 5/8 in. thick panels, spaced 24 in. OC. Third layer- 2-1/4 in, long for 1/2 in. thick panels or 2-5/8 <br />studs and runners. Min nom thickness as indicated under Item 5. See Batts and Blankets (BKNV or BZJZ) <br />in. long for 5/8 in. thick panels, spaced 24 in. OC. Fourth layer- 2-5/8 in. long for 1/2 in. thick panels or 3 in. <br />Categories for names of Classified companies. <br />long for 5/8 in. thick panels, spaced 12 in. OC. Screws offset min 6 in. from layer below. For all layers, an <br />additional screw shall be placed 1-1/4 in. from each edge of the board. <br />4A. Batts an Blankets* — <br />dO (Optional) Placed m stud cavities, an la fiber r iinsulation <br />(p ) c es, y glass be o mineral wool <br />bearing the UL Classification Marking as to Surface Burning Characteristics and/or Fire Resistance. See Batts <br />7. Furring Channels — (Optional, not shown, for single or double layer systems) — Resilient furring channels <br />and Blankets (BKNV or BZJZ) Categories for names of Classified companies. <br />fabricated from min 25 MSG corrosion -protected steel, spaced vertically a max of 24 in. OC. Flange portion <br />5. Gypsum Board* — Gypsum panels with beveled, r r tapered <br />yp yp p b e ed, square o ape ed edges, applied vertically or horizontally. <br />attached to each intersecting stud with 1/2 in. long Type S- 12 steel screws. Not for use with Item 5A. <br />Vertical joints centered over studs and staggered one stud cavity on opposite sides of studs. Vertical joints in <br />7A. Steel Framing Members Not Shown)* — (Optional on or both sides not shown for single r 1 <br />g e ( ) ( p o g e o double <br />adjacent layers multila er systems) staggered one stud cavity. Horizontal joints need not be backed b steel <br />y ( y y ) gg ry' y <br />layer systems) — As an alternate to Item 7, furring channels and Steel Framing Members as described below: <br />framing. Horizontal edge joints and horizontal butt joints on opposite sides of studs need not be staggered. <br />. Furring Channels — Formed of No. 25 MSG galv steel. 2-3/8 in, wide by 7/8 in. deep, spaced max. 24 <br />ain. <br />Horizontal edge joints and horizontal butt joints in adjacent layers (multilayer systems) staggered a min of 12 <br />OC perpendicular to studs. Channels secured to studs as described in Item b. Gypsum board attached to <br />in. The thickness and number of layers for the 1 hr, 2 hr, 3 hr and 4 hr ratings are as follows: <br />furring channels as described in Item 6. Not for use with Item SA. <br />b. Steel Framing Members* — Used to attach furring channels (Item 7Aa) to studs (Item 2). Clips spaced <br />Wallboard Protection on Each Side of Wall <br />max. 48 in. OC. RSIC-1 clips secured to studs with No. 8 x 1-1/2 in. minimum self -drilling, S- 12 steel <br />screw through the center grommet. RSIC-V clips secured to studs with No. 8 x 9/16 in. minimum self- <br />„- "-..... ---------- . <br />drilling, S- 12 steel screw through the center hole. Furring channels are friction fitted into clips. - PAC <br />Min Min No. of Min <br />International Inc — Types RSIC-1, RSIC-V. <br />Stud Stud Layers Thkns of <br />7B. Steel Framing Members (Optional, Not Shown)* — As an alternate to Item 7, furring channels and Steel <br />Depth, Depth, &Thkns Insulation <br />Framing Members on only one side of studs as described below: <br />Rating „ Item 2 Item 2A of Panel (Item 4) <br />a. Furring Channels — Formed of No. 25 MSG galv steel, spaced 24 in. OC perpendicular to studs. <br />,,... <br />""" """` <br />Channels secured to studs as described in Item b. Batts and Blankets placed in stud cavity as described in <br />1 3 1/2 3 5/8 1 layer, 5/8 in. thick 111Optional <br />Item 5. Two layers of gypsum board attached to furring channels as described in Item 5. Not for use with <br />1 2 1/2 3 5/8 1 layer, 1/2 in. thick 1 1/2 in. <br />Item 5A. <br />b. Steel Framing Members* — Used to attach furring channels (Item 7Ba) to one side of studs (Item 2) <br />1 1-5/8 3-5/8 1 layer, 3/4 in, thick 1 Optional <br />only. Clips spaced 48 in. OC., and secured to studs with two No. 8 x 2-1/2 in. coarse drywall screws, one <br />through the hole at each end of the clip. Furring channels are friction fitted into clips. - Kinetics Noise <br />2 1 5/8 2 1/2 2 layers, 1/2 in. thick ; Optional <br />Control Inc —Type Isomax <br />2 1 5/8 2 1/2 2 layers, 5/8 m thick ; Optional <br />8. Joint Tape and Compound — Vinyl or casein, dry or premixed joint compound applied in two coats to <br />joints and screw heads of outer layers. Paper tape, nom 2 in. wide, embedded in first layer of compound over <br />2 3-1/2 3-5/8 1 layer, 3/4 in. thick 3 m <br />all joints of outer layer panels. Paper tape and joint compound may be omitted when gypsum panels are <br />...... <br />supplied with a square edge. <br />3 1-5/8 ° 2-1/2 3 layers, 1/2 in. thick = Optional j <br />9, Siding, Brick or Stucco — (Optional, not shown) — Aluminum, vinyl or steel siding, brick veneer or <br />m ....... m:....:, m.:, . <br />3 1 5/8 2 1/2 2 layers, 3/4 m thick ; Optional <br />stucco, meeting the requirements of local code agencies, installed over gypsum panels. Brick veneer attached <br />to studs with corrugated metal wall ties attached to each stud with steel screws not more than each sixth <br />l 3 1-5/8 i 2-1/2 3 layers, 5/8 in. thick Optional <br />course of brick. <br />....................................... <br />Caulking and Sealants* (Optional not shown) A bed of acoustical sealant applied around the <br />10. — s ) — a a 1' <br />4 z 1-5/8 2-1/2 4 layers, 5/8 in. thick Optional <br />partition perimeter for sound control. - US Gypsum Co — Type AS <br />4 1 5/8 2 1/2 4 layers, 1/2 m thick ' Optional <br />11. Lead Batten Strips — (Not Shown, For Use With Item 5B) - Lead batten strips, min 1-1/2 in. wide, max 10 <br />,,,,,,,. . ......... . ......... ,:.,: ......:. _,,.,.,.. ...,., ,,.,.,,,, ,.,,,,,,. ,.,,,,,,,� ,.,,,,,. ,,,,,,,,. .,.,,., <br />ft long with a max thickness of 0.125 in. Strips placed on the interior face of studs and attached from the <br />4 2-1/2 2-1/2 J, 2 layers, 3/4 in. thick 2 in. <br />exterior face of the stud with two 1 in. long Type S- 12 pan head steel screws, one at the top of the strip and <br />•�, --- - - �� m - - �` m- r. , ., .,° <br />one at the bottom of the strip. Lead batten strips to have a purity of 99.9% o meeting the Federal specification <br />CANADIAN GYPSUM COMPANY — 1/2 in. thick Type C, IP-X2 or IPC-AR; WRC, 5/8 in. thick Type AR, <br />QQ-L-201f, Grade "C". Lead batten strips required behind vertical joints of lead backed gypsum wallboard <br />C, IP-AR, IP-Xl, IP-X2, IPC-AR, SCX, SHX, WRX or WRC; 3/4 in. thick Types IP-X3 or ULTRACODE <br />(Item 5B) and optional at remaining stud locations. Required behind vertical joints. <br />United States Gypsum CO — 1/2 in. thick Type C, IP-X2, IPC-AR or WRC; 5/8 in. thick Type SCX, SHX, <br />12. Lead Discs or Tabs — (Not Shown, For Use With Item 513) - Used in lieu of or in addition to the lead <br />WRX, IP-X1, AR, C, WRC, FRX-G, IP-AR, IP-X2, IPC-AR ; 3/4 in. thick Types IP-X3 or ULTRACODE <br />batten strips (Item 11) or optional at other locations - Max 3/4 in. diam by max 0.125 in. thick lead discs <br />USG MEXICO S A DE C V — 1/2 in. thick Type C, IP-XZ, IPC-AR or WRC; 5/8 in. thick Type AR, C, IP- <br />compression fitted or adhered over steel screw heads or max 1/2 in. by 1-1/4 in. by max 0.125 in. thick lead <br />tabs placed on gypsum boards (I±em SB) underneath screw locations prior to the installation of the screws. <br />AR, IP-XI, IP-X2, IPC-AR, SCX, SHX, WRX, WRC or; 3/4 in. thick Types IP-X3 or ULTRACODE <br />Lead discs or tabs to have a purity of 99.9% meeting the Federal specification QQ-L-201f, Grade "C". <br />When Item 7B, Steel Framing Members*, is used, Nonbearing Wall Rating is limited to 1 Hr. Min. stud depth is <br />*Bearing the UL Classification Mark <br />3-1/2 in., min. thickness of insulation (Item 4) is 3 in., and two layers of gypsum board panels (1/2 in. or 5/8 <br />UL Detail - U419 <br />SCALE: N.T.S. <br />System No. HW-S-0001 (December 01,1999) <br />Assembly Ratings —1 & 2 Hr (See Item 3B) <br />{ <br />1. Floor Assembly — The fire -rated fluted steel deck/concrete floor assembly shall be constructed of the materials and <br />in the manner described in the individual Floor -Ceiling Design in the UL Fire Resistance Directory and shall <br />include the following construction features: <br />A. Steel Floor and Form Units* — Max 3 in. deep galv steel fluted floor units. <br />B. Concrete — Min 2-1/2 in. thick reinforced concrete, as measured from the top plane of the floor units. <br />IA. Roof Assembly — As an alternate to Item 1, Floor Assembly, the fire -rated roof assembly shall be constructed of <br />the materials and in the manner described in the individual P700, P800 or P900 series Roof -Ceiling Designs in the <br />UL Fire Resistance Directory and shall contain max 1-1/2 in. deep galv steel fluted roof units. The hourly fire rating <br />of the roof assembly shall be equal to or greater than the hourly fire rating of the wall assembly. In the case of <br />spray -applied protection materials on the steel roof units, the joint system shall be installed prior to the spray - <br />applied protection material. <br />2. Wall Assembly — The 1 or 2 hr fire -rated gypsum wallboard/steel stud wall assembly shall be constructed of the <br />materials and in the manner described in the individual U400-Series Wall and Partition Designs in the UL Fire <br />Resistance Directory and shall include the following construction features: <br />A. Steel Floor And Ceiling Runners — Floor and ceiling runners of wall assembly shall consist of min 25 ga <br />galv steel channels sized to accommodate steel studs (Item 2B). Ceiling runner to be provided with 1-1/2 in. <br />flanges. Ceiling runner secured to valleys of steel floor units (Item 1 A) with steel fasteners or by welds spaced <br />max 12 in. OC. <br />B. Studs — Steel studs to be min 2-1/2 in. wide. Stud spacing not to exceed 24 in. OC. <br />C. Gypsum Board* — Wallboard sheets installed to a min total thickness of 1/2 or 1 in. on each side of wall for 1 <br />or 2 ratings, respectively. Wall to be constructed as specified in the individual Wall and Partition Design in the <br />UL Fire Resistance Directory. Wallboard to be butted tight to the bottom of the steel floor units. <br />3. Joint System — The joint system consists of a forming material and a fill material in the flutes of the steel floor <br />units, as follows: <br />A. Forming Materials* — Min 2-1/2 in. thickness of min 4 pcf density mineral wool batt insulation firmly packed <br />into flutes of steel floor units above ceiling runner as a permanent form. Forming material to be recessed from <br />edges of ceiling runner on each side of wall as required to accommodate the required thickness of fill material. - <br />Thermafiber Inc — Type SAF <br />B. Fill, Void or Cavity Material* — Dry mix material mixed with water at a rate of 2.1 parts dry mix to 1 part <br />water, by weight, in accordance with accompanying installation instructions. A min 1/2 in. thickness of fill <br />material installed on each side of the wall in the flutes of the steel floor units, flush with each surface of the <br />wallboard for the 1 hr Assembly Rating. A min 1 in. thickness of fill material is required on each side of the <br />wall for the 2 hr Assembly Rating. - US Gypsum Co — Type FC <br />B1. Fill, Void or Cavity Material* (Not Shown) — 2 component fill material used as an alternate to Item 3B. <br />Ready -mixed component mixed with accelerator component at a rate of 66:1 (ready -mixed component to <br />accelerator component by weight) in accordance with the accompanying installation instructions. Applied as <br />described in Item 3B to a min thickness of 1/2 in. for the 1 hr Assembly Rating, and to a min thickness of 1 in. <br />for the 2 hr Assembly Rating. - US Gypsum Co — Type RFC <br />*Bearing the UL Classification Mark <br />2 UL Detail t it S0001 <br />HW <br />SCALE: N.T.S. <br />System No. W-L-1001 (June 15, 2005) <br />F Ratings —1, 2, 3 and 4 Hr (See Items 2 and 3) T Ratings — 0, 1, 2, 3, and 4 Hr (See Item 3) <br />L Rating At Ambient — less than 1 CFM/sq ft L Rating At 400 F — less than 1 CFM/sq ft <br />SECTION A -A <br />1. Wall Assembly — The 1, 2, 3 or 4 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and <br />in the manner described in the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory <br />and shall include the following construction features: <br />A. Studs — Wall framing may consist of either wood studs (max 2 h fire rated assemblies) or steel channel studs. Wood studs <br />to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC with nom 2 by 4 in. (51 by 102 mm) <br />lumber end plates and cross braces. Steel studs to be min 3-5/8 in. (92 mm) wide by 1-3/8 in. (35 mm) deep channels <br />spaced max 24 in. (610 mm) OC. <br />B. Gypsum Board* —Nom 1/2 or 5/8 in. (13 or 16 mm) thick, 4 ft. (122 cm) wide with square or tapered edges. The gypsum <br />wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 <br />or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 26 in. (660 mm). <br />2. Through -Penetrant — One metallic pipe, conduit or tubing installed either concentrically or eccentrically within the firestop <br />system. The annular space between pipe, conduit or tubing and periphery of opening shall be min of 0 in / (0 mm). (point <br />contact) to max 2 in. (51 mm) Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following <br />types and sizes of metallic pipes, conduits or tubing may be used: <br />A. Steel Pipe — Nom 24 in. (6 10 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. <br />B. Iron Pipe — Nom 24 in. (610 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 12 in (305 mm) <br />diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe. <br />C. Conduit — Nom 6 in. (152 mm) diam (or smaller) steel conduit or nom 4 in (102 mm) diam (or smaller) steel electrical <br />metallic tubing <br />D. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing <br />E. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. <br />F. Through Penetrating Product* — Flexible Metal Piping The following types of steel flexible metal gas piping may be <br />used: <br />1. Nom 2 in. (51 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be <br />removed on both sides of floor or wall assembly. OMEGA FLEX INC <br />2. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be <br />removed on both sides of floor or wall assembly. GASTITE, DIV OF TITEFLEX <br />3. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be <br />removed on both sides of floor or wall assembly. WARD MFG INC <br />3. Fill, Void or Cavity Material* — Caulk or Sealant — Min 5/8., 1-1/4,1-7/8 and 2-1/2 in. (16, 32, 48 and 64 mm) thickness <br />of caulk for 1, 2, 3 and 4 hr rated assemblies, respectively, applied within annulus, flush with both surfaces of wall. Min 1/4 in. <br />(6 mm) diam bead of caulk applied to gypsum board/penetrant interface at point contact location on both sides of wall. The <br />hourly F Rating of the firestop system is dependent upon the hourly fire rating of the wall assembly in which it is installed, as <br />shown in the following table. The hourly T Rating of the firestop system is dependent upon the type or size of the pipe or <br />conduit and the hourly fire rating of the wall assembly in which it is installed, as tabulated below: <br />Max Pipe <br />F <br />T <br />or Conduit <br />Rating <br />Rating <br />Diam In (mm) <br />Hr <br />Hr <br />1 (25) <br />1 or 2 <br />0+, 1 or 2 <br />1 (25) <br />3 or 4 <br />3 or 4 <br />4 (102) <br />1 or 2 <br />0 <br />6 (152) <br />3 or 4 <br />0 <br />12 (305) <br />1 or 2 < <br />0 <br />+When copper pipe is used, T Rating is 0 h. <br />3M COMPANY — CP 25WB+ or FB-3000 WT. <br />*Bearing the UL Classification Mark <br />3 UL <br />W1 <br />L1 00 <br />SCALE. N.T.S. <br />2 <br />2�1 <br />fn <br />0 <br />E <br />E <br />0 <br />U <br />i <br />0- <br />N � <br />C J <br />CO <br />Y <br />� Q <br />0 <br />J <br />M <br />CU J UL <br />�0(6 <br />J <br />}oCOJ <br />w <br />a <br />��� <br />U <br />�Ua. <br />0 <br />UJ <br />H °N <br />a <br />w <br />Cn <br />F- <br />w <br />a <br />0 <br />LLJ <br />a <br />o <br />W <br />N <br />J <br />w <br />Of <br />co <br />O <br />Z <br />C <br />Ir <br />w <br />Z <br />N <br />w <br />N <br />0 <br />C.i <br />m <br />1= <br />Q <br />a:a <br />o <br />o <br />U <br />Al 03 <br />