ELECTRICAL SPECIFICATIONS.
<br />1. THE ELECTRICAL INSTALLATION SHALL CONFORM TO THE REQUIREMENTS OF NEC 2014.
<br />A.CLEARANCE NEC 110-26 (2)
<br />B.DEDICATED SPACES FOR SWITCHBOARDS AND PANEL BOARDS INCLUDING.
<br />2. THE ELECTRICAL CONTRACTOR SHALL PROVIDE GROUNDING WHICH COMPLIES
<br />WIYH THE CODE AND INSPECTION AUTHORITY.
<br />3. THE E.C. SHALL INSTALL ELECTRICAL DEVICES AND EQUIPMENT TO WITHSTAND THE
<br />SHORT CIRCUIT CURRENT AVAILABLE THE CURRENT PROTECTIVE DEVICE RATING FOR
<br />EQUIPMENT SHALL BE VERIFIED PRIOR TO BID.
<br />4, ALL CIRCUITS TO BE NUMBERED AND IDENTIFIED ON ELECTRICAL PANEL
<br />5. RECEPTACLES AND SWITCH PLATES TYPE & COLOR SHALL BE SELECTED BY OWNER
<br />6. ALL BREAKERS TO BE SIZED ACCORDING TO MAN UFACTURER'SSPECIFICATIONS.
<br />7. ELECTRICAL CONTRACTOR PRIOR TO INSTALLATION OF ROUGH ELECTRICAL WIRING
<br />CHECK NAMEPLATE DATA OF ALL EQUIPMENT . APPLIANCES TO OBTAIN CORRECT
<br />SIZES AND OVER CURRENT PROTECTION.
<br />8. VERIFY MANUFACTURER'S SPECIFICATIONS AS TO THE EXACT LOCATION OF
<br />RECEPTACLES/JUNCTION BOX FOR APPLIANCES AND OTHER EQUIPMENT.
<br />9—THE CONTRACTOR SHALL FURNISHALL LABOR, MATERIAL AND EQUIPMENT FOR A
<br />COMPLETE ELECTRICAL :INSTALLATION IN ACCORDANCE WITH THESE DRAWING AND SPECIFICATIONS.
<br />10—THE CONTRACTOR SHALL FURNISH ALL MATERIAL & WORKMANSHIP FREE OF DEFECTS FOR A PERIOD
<br />OF NOT LESS THAN ONE YEAR FROM THE DATE OF ACCEPTANCE. THE GUARANTEE SHALL BE WRITING
<br />1 1—THE CONTRACTOR SHALL OBTAIN ALL NECESSARY BUILDING PERMIT, LICENSES AND INSURANCE FOR
<br />WORK UNDER THIS CONTRACT.
<br />12—THE CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE HIMSELF WITH ALL EXISTING CONDITION.
<br />13—COMPLY WITH THE NATIONAL ELECTRICAL CODE 2008 AND THE FLORIDA BUILDING CODE 2010
<br />(F.B.C.)OR ANY OTHER LOCAL CODE OR REGULATION IN ITS CURRENT EDITION.
<br />14—PROVIDE TEMPORARY POWER AND LIGHT OUTLETS FOR USE BY OTHER TRADES.
<br />115—PROVIDE EMPTY CONDUITS AS REQUIRED FOR TELEPHONE LINES INCLUDING WIRING
<br />16—ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE
<br />PROGRESS OF CONSTRUCTION.
<br />17—COORDINATE ALL OUTLETS LOCATION WITH BUILDING ARCHITECTURAL FEATURES.
<br />18—ALL MOUNTING HARDWARE SHALL BE BY CONTRACTOR_
<br />NOTES:
<br />1.-PROVIDE A DISCONECTIVE MEANS INSTALLED IN ACCESSORY LOCATION FOR SERVICING OR MAINTAINING
<br />THE BALLAST OF ALL FLUORESCENT FIXTURES PER NEC 2014 - 410.130 (G)
<br />2.-THIS IS NOT A HEALTH CARE FACILITY
<br />3.-3M FIRE BARRIER SEALENT, CP 25 WB+(UL 1479) & CAN/ULC S115 UP TO 4 HRS AS PER
<br />ASTM E 814
<br />4.-COMMERCIAL LIGTHING TO COMPLY WITH FBC ENERGY.
<br />I EXHAUST FAN SPECS
<br />NEW EF-1 "GREENHECK" MODEL SP 50 CFM
<br />©1/4" WC, 115 VOLTS, 50 WATTS CEILING MOUNTED
<br />W/B.D.D. BUILT—IN.
<br />IXH UNDER —
<br />LAVATORY (E)
<br />EXIT 8c EMERGENCY LIGHTS NOTE:
<br />EXIT & EMERGENCY LIGHT W/ BATTERY
<br />BACKUP TO BE CONNECTED AT HEAD OF
<br />SWITCH OF THE CIRCUIT OF THE AREA OF EXIT
<br />& EMERGENCY LIGHT.
<br />FLUORESCENT LIGHTING SENSORS NOTE. -
<br />ALL FLUORESCENT LIGHTING FIXTURES THAT UTILAZE DOUBLE -ENDED LAMP AND CONTAIN
<br />BALLAST SHALL BE PROVIDED WITH AN EXTERNAL DISCONNECT MEAN TO BE SERVICE IN
<br />PLACE.
<br />FLASH PROTECTION NOTE
<br />SWITCHBOARDS, PANELBOARDS, INDUSTRIAL CONTROL PANELS,
<br />METER SOCKET ENCLOSURES, AND MOTOR CONTROL CENTERS
<br />THAT ARE IN ORDER THAN DWELLING OCCUPANCIES AND ARE
<br />LIKELY TO REQUIRE EXAMINATION, ADJUSTMENT, SERVICING, OR
<br />MAINTENANCE WHILE ENERGIZED SHALL BE FIELD MARKED TO
<br />WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC FLASH
<br />HAZARDS. THE MARKING SHALL BE LOCATED SO AS TO BE
<br />CLEARLY VISIBLE TO QUALIFIED PERSONS BEFORE EXAMINATION,
<br />ADJUSTMENT, SERVICING, OR MAINTENANCE OF THE EQUIPMENT.
<br />GROUND —FAULT CIRCUIT INTERRUPTER PROTECTION
<br />ALL 125-VOLT, SINGLE PHASE, 15 AND 20 AMPERE RECEPTACLES INSTALLED
<br />IN THE LOCATION SUCH AS, BATHROOMS, COMERCIAL KITCHENS, ROOF TOPS,
<br />OUTDOORS ( HEATING AIR-CONDITIONING AND REFRIGERATION EQUIPMENT
<br />OUTLET), SHALL HAVE GROUND -FAULT CIRCUIT -INTERRUPTER PROTECTION FOR
<br />PERSONNEL.
<br />ELECTRICAL SCOPE OF WORK
<br />-EXISTING TENANT SPACE WITH INTERIOR REMODELING, FIXTURES ARE ALL NEW AND WIIL
<br />BE INSTALLED ACCORDING NEW LAYOUT. A NEW PANEL IS BEING PROPOSED 200 AMPS
<br />PANEL(MLO) AND THERE IS AN EXISTING 200 AMPS SERVICE IN 120/208 30 THAT WILL
<br />REMAIN AS
<br />IT IS.
<br />G\osslf,eOW
<br />UK
<br />s t e(`
<br />I
<br />2 Hour Fire Rated Through
<br />Penetration Firestop for
<br />Plastic Pipe through
<br />Gypsum walls using
<br />intumescent devices
<br />3735 Graen Rd.
<br />Beachwood, OH, 44122
<br />Drawing not to scale
<br />Q 2-Hour Fire Rated gypsum wallboardistud assembly.
<br />© Plastic Pipe - 4" dia. (or smaller) sch. 40 PVC pipe for
<br />use in closed or vented piping systems,
<br />with a nom. annular space of 1/8".
<br />(D A) TREMstop WS - wrap strips, tightly wrapped 6 times
<br />around pipe.
<br />B) TREMstop MCR - steel restricting collar.
<br />C) FYRE-SIL - Min. 1/4" thick sealant applied to
<br />wall/collar and collar/pipe interfaces.
<br />Protect,
<br />The products used in die above assembly have
<br />The above described assembly and
<br />products have been tested anare
<br />been tested to accordance with the follo i- :
<br />with 8
<br />based on both past and anticipated
<br />Location:
<br />ASTM E814 (UL1479) Test Netted
<br />performance ctitena Tremco shalt
<br />for Through Penetration Firestopping,
<br />not be liable for arty damages, direct
<br />Installer.
<br />or consequential, resulting from use
<br />Date: 2/26/94 Drawin : 7R—w2083
<br />of this material ar design. Tremco
<br />.Signature:
<br />be defective. pig
<br />Approved by: C. Tuaeo
<br />mffishalcriallf and to
<br />ELECTRICAL SYMBOL LEGEND
<br />((D JUNCTION BOX
<br />'�FILJB W/SPECIAL SUPPORT FAN & LIGHT
<br />(o HIGH HATS LIGHTING
<br />+ MINI HIGH HATS LIGHTING
<br />VAPOR PROOF
<br />0 CEILING MOUNTED FIXTURE
<br />�- WALL MOUNTED FIXTURE
<br />MOTOR FOR CHANDELIER
<br />L3 PICTURE WALL MOUNTED FIXTURE
<br />FLUORESCENT FIXTURE
<br />QUADRUPLEX RECEPTACLE
<br />GFI RECEPTACLE
<br />GFI RECEPTACLE 8" ABOVE COUNTER
<br />e- DEDICATED RECEPTACLE
<br />F4 2 POLE OUTLET
<br />(9-- RECEPTACLE
<br />SMTCHABLE DUPLEX RECEPTACLE
<br />(� GARBAGE DISPOSAL
<br />C� SPOT LIGHT
<br />ELECTRIC PANEL
<br />LfJ EXHAUST FAN
<br />WP WEATHER PROOF
<br />$ SWITCH
<br />$3 3WAY SWITCH
<br />$D LOW VOLTAGE SYSTEM SWITCH (DIMMER)
<br />DATA/TELEPHONE OUTLET
<br />0 TELEVISION CABLE OUTLET
<br />so SMOKE DETECTOR
<br />GARAGE DOOR OPENER CONTROLLER
<br />INTERCOM
<br />FD_B1 DOOR BELL
<br />WALL FLUORESCENT FIXTURE
<br />q_,N EMERGENCY LIGHT.
<br />4_tP, EMERGENCY & EXIT LIGHT.
<br />S_ EXIT LIGHT.
<br />(E/R) EXISTING RELOCATED
<br />(N) NEW
<br />(E) EXISTING
<br />TYPE: LOADCENTER, NEMA-1 PANEL »A» MAIN BUS: 200 AMPS
<br />SERVICE: 1PH, 3 W, S/N. NEUTRAL: 200 AMPS
<br />VOLTAGE: 120/240 V (NEW) MAIN : M.L.O
<br />MOUNTING: SURFACE AIC: 22,000
<br />°-
<br />cn
<br />W
<br />_J
<br />o-Z
<br />M.
<br />CD
<br />oww
<br />z N
<br />N
<br />m in
<br />REMARKS
<br />o
<br />z
<br />,-
<br />v
<br />z
<br />Y
<br />c�
<br />REMARKS
<br />ww
<br />N
<br />v,
<br />N z
<br />N �
<br />o�
<br />¢
<br />� �
<br />cn
<br />30
<br />3
<br />7,500
<br />3/4
<br />8
<br />RTU #1(E)
<br />1
<br />2
<br />I.W.H
<br />12
<br />1/2"
<br />4200
<br />1
<br />20
<br />3
<br />5
<br />4
<br />6
<br />RECEPTACLES
<br />12
<br />1/2"
<br />1080
<br />1
<br />20
<br />20
<br />1
<br />1 1260
<br />1/2"
<br />12
<br />RECEPTACLES
<br />7
<br />8
<br />RECEPTACLES
<br />12
<br />1/2"
<br />720
<br />1
<br />20
<br />20
<br />1
<br />1 900
<br />1/2"
<br />12
<br />RECEPTACLES
<br />9
<br />10
<br />WATER DISPENSER
<br />12
<br />1 2"
<br />200
<br />1
<br />20
<br />20
<br />1
<br />1200
<br />1/2"
<br />12
<br />LIGHTING
<br />11
<br />12
<br />SPACE
<br />20
<br />1
<br />700
<br />1/2"
<br />12
<br />LIGHTING
<br />13
<br />14
<br />20
<br />1
<br />1200
<br />1/2'
<br />12
<br />SIGN
<br />15
<br />16
<br />20
<br />1
<br />180
<br />1/2'
<br />12
<br />GFCI BATH
<br />17
<br />18
<br />SPACE
<br />19
<br />20
<br />21
<br />22
<br />23
<br />24
<br />25
<br />26
<br />27
<br />28
<br />29
<br />30
<br />31
<br />32
<br />34
<br />36
<br />38
<br />40
<br />42
<br />33
<br />35
<br />37
<br />39
<br />41
<br />TOTAL CONNECTED LOAD: FEEDER: SEE RISER
<br />CON11NUOUS LOAD (LIGHTING): = 3,100 VA
<br />25% OF CONT LOAD = 775 VA
<br />NON. CANT LOAD = 16,040 VA
<br />TOTAL DEMAND LOAD: _ 19,915 VA FED FROM: SEE RISER
<br />AT 208 / 3 / 60 = 55.32 AMPS
<br />- THE ELECTRICAL CONTRACTOR SHALL VERIFY THE
<br />EXACT NAME PLATE RATING OF ALL EQUIPMENT
<br />BEFORE INSTALLATION & INFORM TO THE
<br />ELECTRICAL ENGINEER OF ANY DISCREPANCIES.
<br />VACANT
<br />SPACE (7898)
<br />1136 SF APPROX.
<br />A6
<br />A9PA9
<br />A&V WTA 9
<br />2'
<br />A87 A8
<br />A8
<br />A
<br />TEST A13
<br />BOOTH
<br />A9 A13
<br />A7 A7
<br />A11
<br />A7 A7 A7
<br />A11
<br />°
<br />A9
<br />Al
<br />Al
<br />1
<br />-- --
<br />i
<br />A13
<br />A9 A13
<br />TEST
<br />Al
<br />�7=A6
<br />A11
<br />BOOTH
<br />Al
<br />-'
<br />NEW ELECTRICAL
<br />A6 A6
<br />l
<br />--
<br />PANEL
<br />-G
<br />t-
<br />\
<br />Al 3 5 `
<br />I X'I I I
<br />\
<br />O
<br />A13
<br />Al
<br />Al
<br />I \--'�
<br />L i i Al
<br />Al
<br />A11
<br />Al
<br />i-----1---J
<br />JERSEY
<br />MIKES SUBS
<br />ELECTRICAL PLANS, NOTES AND RISER
<br />SCALE: 1 /4"=V-O"
<br />J
<br />A15
<br />SIGN CKT VIA
<br />TIME CLOCK
<br />- ALL CB USED FOR , A/C & REFRIGERATION
<br />UNITS SHALL BE HACR U.L. LISTED.
<br />NON -CONCURRENT LOAD
<br />PROVIDE PERMANENT PLAQUE IN ELECTRICAL
<br />ROOM FOR ARC FAULT & SHOCK HAZARD:
<br />rWARNINGsh and Shock Hazard
<br />iate PPE Required
<br />PPE: PERSONAL PROTECTIVE EQUIPMENT
<br />NEW RISER DIAGRAM TO REMAIN
<br />200 AMP ELECTRICAL
<br />4" 120/208 V 30 4W
<br />T SPACE 7894
<br />PROVIDE PERMANENT PLAQUE IN ELECTRICAL
<br />ROOM FOR ARC FAULT & SHOCK HAZARD:
<br />I WARNING
<br />Arc Flash and Shock Hazard
<br />Appropriate PPE Required
<br />PPE PERSONAL PROTECTIVE EQUIPMENT
<br />REVISIONS:
<br />No,/DATE:
<br />No./DATE:
<br />THESE DRAWING & SPECIFICATIONS ARE
<br />INSTRUMENTS OF SERVICE AND SHALL
<br />REMAIN THE PROPERTY OF MDS
<br />ENGINEERING CORP. WHETHER THE
<br />PROJECT FOR WHICH THEY WERE
<br />PREPARED IS EXECUTED OR NOT, THEY
<br />ARE NOT TO BE USED IN ANY MANNER
<br />ON OTHER PROJECTS OR EXTENSIONS
<br />TO THIS PROJECT EXCEPT BY
<br />AGREEMENT IN WRITING AND WITH THE
<br />APPROPRIATE COMPENSATION TO MDS
<br />ENGINEERING CORP. IS PROHIBITED.
<br />CONTRACTOR IS RESPONSIBLE FOR
<br />VERIFYING ALL SITE CONDITION PRIOR
<br />TO PROCEEDING WITH WORK.
<br />0'
<br />pit, ••.... 5�
<br />U
<br />CD
<br />CD
<br />�N a
<br />L. J ry t0
<br />o
<br />L7�QIJ d-
<br />Z U
<br />0 c0
<br />00
<br />�/1 Q p US
<br />ry
<br />Q 0 r o z
<br />a � 00
<br />N U n
<br />JOB No.:
<br />DRAWN BY: M.D.S
<br />SCALE: AS SHOW
<br />SHUT NWE:
<br />ELECTRICAL PLAN
<br />Emil
<br />SHEET 4 OF 7
<br />MDS ENGINEERING CORPORATION
<br />11 1 141.IFIl7�'�]Fna»Ilail