ELECTRICAL SPECIFICATIONS. <br />1. THE ELECTRICAL INSTALLATION SHALL CONFORM TO THE REQUIREMENTS OF NEC 2014. <br />A.CLEARANCE NEC 110-26 (2) <br />B.DEDICATED SPACES FOR SWITCHBOARDS AND PANEL BOARDS INCLUDING. <br />2. THE ELECTRICAL CONTRACTOR SHALL PROVIDE GROUNDING WHICH COMPLIES <br />WIYH THE CODE AND INSPECTION AUTHORITY. <br />3. THE E.C. SHALL INSTALL ELECTRICAL DEVICES AND EQUIPMENT TO WITHSTAND THE <br />SHORT CIRCUIT CURRENT AVAILABLE THE CURRENT PROTECTIVE DEVICE RATING FOR <br />EQUIPMENT SHALL BE VERIFIED PRIOR TO BID. <br />4, ALL CIRCUITS TO BE NUMBERED AND IDENTIFIED ON ELECTRICAL PANEL <br />5. RECEPTACLES AND SWITCH PLATES TYPE & COLOR SHALL BE SELECTED BY OWNER <br />6. ALL BREAKERS TO BE SIZED ACCORDING TO MAN UFACTURER'SSPECIFICATIONS. <br />7. ELECTRICAL CONTRACTOR PRIOR TO INSTALLATION OF ROUGH ELECTRICAL WIRING <br />CHECK NAMEPLATE DATA OF ALL EQUIPMENT . APPLIANCES TO OBTAIN CORRECT <br />SIZES AND OVER CURRENT PROTECTION. <br />8. VERIFY MANUFACTURER'S SPECIFICATIONS AS TO THE EXACT LOCATION OF <br />RECEPTACLES/JUNCTION BOX FOR APPLIANCES AND OTHER EQUIPMENT. <br />9—THE CONTRACTOR SHALL FURNISHALL LABOR, MATERIAL AND EQUIPMENT FOR A <br />COMPLETE ELECTRICAL :INSTALLATION IN ACCORDANCE WITH THESE DRAWING AND SPECIFICATIONS. <br />10—THE CONTRACTOR SHALL FURNISH ALL MATERIAL & WORKMANSHIP FREE OF DEFECTS FOR A PERIOD <br />OF NOT LESS THAN ONE YEAR FROM THE DATE OF ACCEPTANCE. THE GUARANTEE SHALL BE WRITING <br />1 1—THE CONTRACTOR SHALL OBTAIN ALL NECESSARY BUILDING PERMIT, LICENSES AND INSURANCE FOR <br />WORK UNDER THIS CONTRACT. <br />12—THE CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE HIMSELF WITH ALL EXISTING CONDITION. <br />13—COMPLY WITH THE NATIONAL ELECTRICAL CODE 2008 AND THE FLORIDA BUILDING CODE 2010 <br />(F.B.C.)OR ANY OTHER LOCAL CODE OR REGULATION IN ITS CURRENT EDITION. <br />14—PROVIDE TEMPORARY POWER AND LIGHT OUTLETS FOR USE BY OTHER TRADES. <br />115—PROVIDE EMPTY CONDUITS AS REQUIRED FOR TELEPHONE LINES INCLUDING WIRING <br />16—ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE <br />PROGRESS OF CONSTRUCTION. <br />17—COORDINATE ALL OUTLETS LOCATION WITH BUILDING ARCHITECTURAL FEATURES. <br />18—ALL MOUNTING HARDWARE SHALL BE BY CONTRACTOR_ <br />NOTES: <br />1.-PROVIDE A DISCONECTIVE MEANS INSTALLED IN ACCESSORY LOCATION FOR SERVICING OR MAINTAINING <br />THE BALLAST OF ALL FLUORESCENT FIXTURES PER NEC 2014 - 410.130 (G) <br />2.-THIS IS NOT A HEALTH CARE FACILITY <br />3.-3M FIRE BARRIER SEALENT, CP 25 WB+(UL 1479) & CAN/ULC S115 UP TO 4 HRS AS PER <br />ASTM E 814 <br />4.-COMMERCIAL LIGTHING TO COMPLY WITH FBC ENERGY. <br />I EXHAUST FAN SPECS <br />NEW EF-1 "GREENHECK" MODEL SP 50 CFM <br />©1/4" WC, 115 VOLTS, 50 WATTS CEILING MOUNTED <br />W/B.D.D. BUILT—IN. <br />IXH UNDER — <br />LAVATORY (E) <br />EXIT 8c EMERGENCY LIGHTS NOTE: <br />EXIT & EMERGENCY LIGHT W/ BATTERY <br />BACKUP TO BE CONNECTED AT HEAD OF <br />SWITCH OF THE CIRCUIT OF THE AREA OF EXIT <br />& EMERGENCY LIGHT. <br />FLUORESCENT LIGHTING SENSORS NOTE. - <br />ALL FLUORESCENT LIGHTING FIXTURES THAT UTILAZE DOUBLE -ENDED LAMP AND CONTAIN <br />BALLAST SHALL BE PROVIDED WITH AN EXTERNAL DISCONNECT MEAN TO BE SERVICE IN <br />PLACE. <br />FLASH PROTECTION NOTE <br />SWITCHBOARDS, PANELBOARDS, INDUSTRIAL CONTROL PANELS, <br />METER SOCKET ENCLOSURES, AND MOTOR CONTROL CENTERS <br />THAT ARE IN ORDER THAN DWELLING OCCUPANCIES AND ARE <br />LIKELY TO REQUIRE EXAMINATION, ADJUSTMENT, SERVICING, OR <br />MAINTENANCE WHILE ENERGIZED SHALL BE FIELD MARKED TO <br />WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC FLASH <br />HAZARDS. THE MARKING SHALL BE LOCATED SO AS TO BE <br />CLEARLY VISIBLE TO QUALIFIED PERSONS BEFORE EXAMINATION, <br />ADJUSTMENT, SERVICING, OR MAINTENANCE OF THE EQUIPMENT. <br />GROUND —FAULT CIRCUIT INTERRUPTER PROTECTION <br />ALL 125-VOLT, SINGLE PHASE, 15 AND 20 AMPERE RECEPTACLES INSTALLED <br />IN THE LOCATION SUCH AS, BATHROOMS, COMERCIAL KITCHENS, ROOF TOPS, <br />OUTDOORS ( HEATING AIR-CONDITIONING AND REFRIGERATION EQUIPMENT <br />OUTLET), SHALL HAVE GROUND -FAULT CIRCUIT -INTERRUPTER PROTECTION FOR <br />PERSONNEL. <br />ELECTRICAL SCOPE OF WORK <br />-EXISTING TENANT SPACE WITH INTERIOR REMODELING, FIXTURES ARE ALL NEW AND WIIL <br />BE INSTALLED ACCORDING NEW LAYOUT. A NEW PANEL IS BEING PROPOSED 200 AMPS <br />PANEL(MLO) AND THERE IS AN EXISTING 200 AMPS SERVICE IN 120/208 30 THAT WILL <br />REMAIN AS <br />IT IS. <br />G\osslf,eOW <br />UK <br />s t e(` <br />I <br />2 Hour Fire Rated Through <br />Penetration Firestop for <br />Plastic Pipe through <br />Gypsum walls using <br />intumescent devices <br />3735 Graen Rd. <br />Beachwood, OH, 44122 <br />Drawing not to scale <br />Q 2-Hour Fire Rated gypsum wallboardistud assembly. <br />© Plastic Pipe - 4" dia. (or smaller) sch. 40 PVC pipe for <br />use in closed or vented piping systems, <br />with a nom. annular space of 1/8". <br />(D A) TREMstop WS - wrap strips, tightly wrapped 6 times <br />around pipe. <br />B) TREMstop MCR - steel restricting collar. <br />C) FYRE-SIL - Min. 1/4" thick sealant applied to <br />wall/collar and collar/pipe interfaces. <br />Protect, <br />The products used in die above assembly have <br />The above described assembly and <br />products have been tested anare <br />been tested to accordance with the follo i- : <br />with 8 <br />based on both past and anticipated <br />Location: <br />ASTM E814 (UL1479) Test Netted <br />performance ctitena Tremco shalt <br />for Through Penetration Firestopping, <br />not be liable for arty damages, direct <br />Installer. <br />or consequential, resulting from use <br />Date: 2/26/94 Drawin : 7R—w2083 <br />of this material ar design. Tremco <br />.Signature: <br />be defective. pig <br />Approved by: C. Tuaeo <br />mffishalcriallf and to <br />ELECTRICAL SYMBOL LEGEND <br />((D JUNCTION BOX <br />'�FILJB W/SPECIAL SUPPORT FAN & LIGHT <br />(o HIGH HATS LIGHTING <br />+ MINI HIGH HATS LIGHTING <br />VAPOR PROOF <br />0 CEILING MOUNTED FIXTURE <br />�- WALL MOUNTED FIXTURE <br />MOTOR FOR CHANDELIER <br />L3 PICTURE WALL MOUNTED FIXTURE <br />FLUORESCENT FIXTURE <br />QUADRUPLEX RECEPTACLE <br />GFI RECEPTACLE <br />GFI RECEPTACLE 8" ABOVE COUNTER <br />e- DEDICATED RECEPTACLE <br />F4 2 POLE OUTLET <br />(9-- RECEPTACLE <br />SMTCHABLE DUPLEX RECEPTACLE <br />(� GARBAGE DISPOSAL <br />C� SPOT LIGHT <br />ELECTRIC PANEL <br />LfJ EXHAUST FAN <br />WP WEATHER PROOF <br />$ SWITCH <br />$3 3WAY SWITCH <br />$D LOW VOLTAGE SYSTEM SWITCH (DIMMER) <br />DATA/TELEPHONE OUTLET <br />0 TELEVISION CABLE OUTLET <br />so SMOKE DETECTOR <br />GARAGE DOOR OPENER CONTROLLER <br />INTERCOM <br />FD_B1 DOOR BELL <br />WALL FLUORESCENT FIXTURE <br />q_,N EMERGENCY LIGHT. <br />4_tP, EMERGENCY & EXIT LIGHT. <br />S_ EXIT LIGHT. <br />(E/R) EXISTING RELOCATED <br />(N) NEW <br />(E) EXISTING <br />TYPE: LOADCENTER, NEMA-1 PANEL »A» MAIN BUS: 200 AMPS <br />SERVICE: 1PH, 3 W, S/N. NEUTRAL: 200 AMPS <br />VOLTAGE: 120/240 V (NEW) MAIN : M.L.O <br />MOUNTING: SURFACE AIC: 22,000 <br />°- <br />cn <br />W <br />_J <br />o-Z <br />M. <br />CD <br />oww <br />z N <br />N <br />m in <br />REMARKS <br />o <br />z <br />,- <br />v <br />z <br />Y <br />c� <br />REMARKS <br />ww <br />N <br />v, <br />N z <br />N � <br />o� <br />¢ <br />� � <br />cn <br />30 <br />3 <br />7,500 <br />3/4 <br />8 <br />RTU #1(E) <br />1 <br />2 <br />I.W.H <br />12 <br />1/2" <br />4200 <br />1 <br />20 <br />3 <br />5 <br />4 <br />6 <br />RECEPTACLES <br />12 <br />1/2" <br />1080 <br />1 <br />20 <br />20 <br />1 <br />1 1260 <br />1/2" <br />12 <br />RECEPTACLES <br />7 <br />8 <br />RECEPTACLES <br />12 <br />1/2" <br />720 <br />1 <br />20 <br />20 <br />1 <br />1 900 <br />1/2" <br />12 <br />RECEPTACLES <br />9 <br />10 <br />WATER DISPENSER <br />12 <br />1 2" <br />200 <br />1 <br />20 <br />20 <br />1 <br />1200 <br />1/2" <br />12 <br />LIGHTING <br />11 <br />12 <br />SPACE <br />20 <br />1 <br />700 <br />1/2" <br />12 <br />LIGHTING <br />13 <br />14 <br />20 <br />1 <br />1200 <br />1/2' <br />12 <br />SIGN <br />15 <br />16 <br />20 <br />1 <br />180 <br />1/2' <br />12 <br />GFCI BATH <br />17 <br />18 <br />SPACE <br />19 <br />20 <br />21 <br />22 <br />23 <br />24 <br />25 <br />26 <br />27 <br />28 <br />29 <br />30 <br />31 <br />32 <br />34 <br />36 <br />38 <br />40 <br />42 <br />33 <br />35 <br />37 <br />39 <br />41 <br />TOTAL CONNECTED LOAD: FEEDER: SEE RISER <br />CON11NUOUS LOAD (LIGHTING): = 3,100 VA <br />25% OF CONT LOAD = 775 VA <br />NON. CANT LOAD = 16,040 VA <br />TOTAL DEMAND LOAD: _ 19,915 VA FED FROM: SEE RISER <br />AT 208 / 3 / 60 = 55.32 AMPS <br />- THE ELECTRICAL CONTRACTOR SHALL VERIFY THE <br />EXACT NAME PLATE RATING OF ALL EQUIPMENT <br />BEFORE INSTALLATION & INFORM TO THE <br />ELECTRICAL ENGINEER OF ANY DISCREPANCIES. <br />VACANT <br />SPACE (7898) <br />1136 SF APPROX. <br />A6 <br />A9PA9 <br />A&V WTA 9 <br />2' <br />A87 A8 <br />A8 <br />A <br />TEST A13 <br />BOOTH <br />A9 A13 <br />A7 A7 <br />A11 <br />A7 A7 A7 <br />A11 <br />° <br />A9 <br />Al <br />Al <br />1 <br />-- -- <br />i <br />A13 <br />A9 A13 <br />TEST <br />Al <br />�7=A6 <br />A11 <br />BOOTH <br />Al <br />-' <br />NEW ELECTRICAL <br />A6 A6 <br />l <br />-- <br />PANEL <br />-G <br />t- <br />\ <br />Al 3 5 ` <br />I X'I I I <br />\ <br />O <br />A13 <br />Al <br />Al <br />I \--'� <br />L i i Al <br />Al <br />A11 <br />Al <br />i-----1---J <br />JERSEY <br />MIKES SUBS <br />ELECTRICAL PLANS, NOTES AND RISER <br />SCALE: 1 /4"=V-O" <br />J <br />A15 <br />SIGN CKT VIA <br />TIME CLOCK <br />- ALL CB USED FOR , A/C & REFRIGERATION <br />UNITS SHALL BE HACR U.L. LISTED. <br />NON -CONCURRENT LOAD <br />PROVIDE PERMANENT PLAQUE IN ELECTRICAL <br />ROOM FOR ARC FAULT & SHOCK HAZARD: <br />rWARNINGsh and Shock Hazard <br />iate PPE Required <br />PPE: PERSONAL PROTECTIVE EQUIPMENT <br />NEW RISER DIAGRAM TO REMAIN <br />200 AMP ELECTRICAL <br />4" 120/208 V 30 4W <br />T SPACE 7894 <br />PROVIDE PERMANENT PLAQUE IN ELECTRICAL <br />ROOM FOR ARC FAULT & SHOCK HAZARD: <br />I WARNING <br />Arc Flash and Shock Hazard <br />Appropriate PPE Required <br />PPE PERSONAL PROTECTIVE EQUIPMENT <br />REVISIONS: <br />No,/DATE: <br />No./DATE: <br />THESE DRAWING & SPECIFICATIONS ARE <br />INSTRUMENTS OF SERVICE AND SHALL <br />REMAIN THE PROPERTY OF MDS <br />ENGINEERING CORP. WHETHER THE <br />PROJECT FOR WHICH THEY WERE <br />PREPARED IS EXECUTED OR NOT, THEY <br />ARE NOT TO BE USED IN ANY MANNER <br />ON OTHER PROJECTS OR EXTENSIONS <br />TO THIS PROJECT EXCEPT BY <br />AGREEMENT IN WRITING AND WITH THE <br />APPROPRIATE COMPENSATION TO MDS <br />ENGINEERING CORP. IS PROHIBITED. <br />CONTRACTOR IS RESPONSIBLE FOR <br />VERIFYING ALL SITE CONDITION PRIOR <br />TO PROCEEDING WITH WORK. <br />0' <br />pit, ••.... 5� <br />U <br />CD <br />CD <br />�N a <br />L. J ry t0 <br />o <br />L7�QIJ d- <br />Z U <br />0 c0 <br />00 <br />�/1 Q p US <br />ry <br />Q 0 r o z <br />a � 00 <br />N U n <br />JOB No.: <br />DRAWN BY: M.D.S <br />SCALE: AS SHOW <br />SHUT NWE: <br />ELECTRICAL PLAN <br />Emil <br />SHEET 4 OF 7 <br />MDS ENGINEERING CORPORATION <br />11 1 141.IFIl7�'�]Fna»Ilail <br />