Laserfiche WebLink
METAL PROTECTION RIGID <br />SHIELDS- MOLDED <br />SUPPORT FIBERGLASS <br />CHAIR INSULATION <br />BOLTED TO <br />CHANNEL <br />HANGING RODS INSULATED <br />Y" MIN...--- PLUMBING <br />PIPES. <br />NUTS & <br />LOCK <br />WASHERS <br />STEEL <br />CHANNEL - <br />ADEQUATE TO <br />CARRY LOAD <br />SEISMIC NOTES: <br />SEISMIC BRACING SHALL BE INSTALLED UNDER THE FOLLOWING CONDITIONS: <br />1)GAS PIPING 1" DIAMETER AND GREATER. <br />2)ALL PIPING 2.5" DIAMETER AND GREATER. <br />3)EXCEPTION: ALL PIPING SUSPENDED BY INDIVIDUAL HANGERS 12" OR LESS IN <br />LENGTH FROM THE TOP OF PIPE TO THE POINT OF ATTACHMENT OF THE <br />HANGER TO THE STRUCTURE DOES NOT REQUIRE SEISMIC BRACING. THE SIZE, <br />TYPE, SPACING, AND METHOD OF INSTALLATION OF SEISMIC BRACING SHALL <br />BE IN ACCORDANCE WITH THE LATEST "SMACNA SEISMIC RESTRAINT <br />MANUAL -GUIDELINES FOR MECHANICAL SYSTEMS". GAS PIPINGIS TO BE <br />CLASSIFIED UNDER "SEISMIC HAZARD LEVEL A" AND ALL OTHER PIPING SYSTEMS <br />"SEISMIC HAZARD LEVEL C" IN THE SMACNA MANUAL. <br />GENERAL NOTES: <br />1)PROTECTION SADDLES SHALL BE COPPER CLAD IF COPPER TUBE IS USED. <br />2)PROVIDE INTERMEDIATE HANGING ROD SUPPORT WHERE NUMBER OF PIPES <br />EXCEED FIVE(5). <br />DETAIL -TRAPEZE HANGER <br />NO SCALE <br />LAVATORY OR SINK <br />y"CW <br />Y2" HW <br />TRAP PRIMER- J.R. <br />SMITH MODEL N0. <br />STOP VALV2698 <br />1'-0"' <br />A.F.F. <br />Y2"0 COPPER <br />TUBING THRU WALL <br />FINISH <br />FLOOR <br />Y2"0 COPPER TUBING <br />TO FLOOR DRAIN <br />NOTES: <br />1) FOR THE TRAP PRIMER SERVING THE <br />FLOOR DRAIN <br />IN THE JANITOR'S AREA & LOUNGE, <br />USE THE LOUNGE <br />ROOM SINK DRAIN, <br />4 DETAIL -TRAP PRIMER <br />P-2 NO SCALE <br />1-1/4" DOMESTIC <br />WATER TO TENANT <br />1" DRAIN OFF <br />W/HOSE CONN. <br />AND V.B. <br />FINISH FLOOR. <br />-PRESSURE GAUGE <br />- PRESSURE REGULATING <br />VALVE (SEE NOTE #2) <br />-BACKFLOW PREVENTER <br />-UNION (TYP.) <br />- PRESSURE GAUGE <br />-ANCHOR PIPE TO <br />FLOOR <br />- FINISH GRADE <br />1Y2" MASTER <br />WATER METER 5'-6" <br />STRAINER MIN.COVER <br />SLEEVE - CAULK <br />WATER TIGHT -1/4" TYPE K <br />CONC. THRUST BLOCK COPPER <br />1'X1'X1' LONG PIPE SLEEVE (4" DIA.) <br />NOTES: <br />1. ALL MATERIALS TO BE FURNISHED & INSTALLED BY PLUMBING <br />CONTRACTOR. <br />2. IF INCOMING SERVICE IS 80 PSI OR GREATER, PROVIDE PRESSURE <br />REGULATING VALVE SET TO <br />ALLOW 65 PSI DOWNSTREAM. <br />3. PROVIDE BACKFLOW PREVENTER IF REQUIRED BY LOCAL AUTHORITIES. <br />4. PROVIDE BYPASS IF REQUIRED BY LOCAL AUTHORITIES. <br />g DETAIL -WATER ENTRANCE <br />P-2 NO SCALE <br />ADD FRAMING CHANNEL x <br />OR ANGLE WHEN "L" IS <br />GREATER THAN MAX. Gi <br />LENGTH. <br />_ J <br />1 Y4r. <br />SAME AS <br />OPPOSITE SIDE r PIPE HANGER ROD CLIP <br />CONNECTION <br />PIPE ADD PIPE SLEEVE THAT <br />HANGER HAS AN INSIDE DIAMETER, <br />Y4" t LARGER THAN <br />SEISMIC NOTES: OUTSIDE DIA. <br />SEISMIC BRACING SHALL BE INSTALLED UNDER THE FOLLOWING CONDITIONS: <br />1) GAS PIPING 1- DIAMETER AND GREATER. <br />2) ALL PIPING 2.5" DIAMETER AND GREATER. <br />3) EXCEPTION: ALL PIPING SUSPENDED BY INDIVIDUAL HANGERS 12" OR LESS IN <br />LENGTH FROM THE TOP OF PIPE TO THE POINT OF ATTACHMENT OF THE <br />HANGER TO THE STRUCTURE DOES NOT REQUIRE SEISMIC BRACING. THE SIZE, <br />TYPE, SPACING, AND METHOD OF INSTALLATION OF SEISMIC BRACING SHALL <br />BE IN ACCORDANCE WITH THE LATEST "SMACNA SEISMIC RESTRAINT <br />MANUAL -GUIDELINES FOR MECHANICAL SYSTEMS". GAS PIPiNGIS TO BE <br />CLASSIFIED UNDER "SEISMIC HAZARD LEVEL A" AND ALL OTHER PIPING SYSTEMS <br />"SEISMIC HAZARD LEVEL C" IN THE SMACNA MANUAL. <br />SMACNA SEISMIC MANUAL_ NOTES: <br />1) REFER TO CHAPTER 3 FOR GENERAL REQUIREMENTS. <br />2) SEE PAGE 4.14 FOR LONGITUDINAL BRACING. <br />3) SEE TABLE 5-4, 6-4 OR 7-4 FOR VERTICAL HANGERS DIAGONAL BRACING, <br />SIZE, CONNECTION TO SUPPORTING STRUCTURE, AND SPACING OF BRACING. <br />DETAIL -CABLE BRACING <br />P-2 NO SCALE <br />MIXING VALVE SPARCO <br />MODEL #102C 3/4" HOT WATER TO <br />Y4" HW (140 DEG. F) FIXTURES (110 DEG. F) <br />TEMPERATURE VACUUM <br />--z BREAKER <br />& PRESSURE <br />RELIEF VALVE <br />3/4"CW <br />SHUT-OFF VALVES -TYPICAL <br />SEISMIC STRAP (IF I I <br />REQUIRED BY CODE ° ° EXPANSION TANK -SEE SPEC. <br />DRAIN VALVE CHECK VALVE <br />I <br />UNION (TYPICAL) <br />RELIEF DRAIN DISCHARGE <br />TO FLOOR DRIAN o <br />Y4" DRAIN - DISCHARGE <br />TO FLOOR DRIAN <br />MOP SINK <br />FINISHED <br />FLOOR <br />-SHIE: <br />PIPE SI <br />Y" TO <br />8" TO 1. <br />16 GA. GAL\ <br />"7JUSTABLE <br />-EVIS <br />\NGER <br />BERGLASS <br />ISULATION <br />1'PICAL FOR <br />LL INSULATED <br />IPING <br />!PE <br />LENGTH OF SHIELD <br />SEE SCHEDULE <br />SEISMIC NOTES: <br />SEISMIC BRACING SHALL BE INSTALLED UNDER THE FOLLOWING CONDITIONS: <br />1)GAS PIPING 1" DIAMETER AND GREATER. <br />2)ALL PIPING 2.5" DIAMETER AND GREATER. <br />3)EXCEPTION: ALL PIPING SUSPENDED BY INDIVIDUAL HANGERS 12" OR LESS IN <br />LENGTH FROM THE TOP OF PIPE TO THE POINT OF ATTACHMENT OF THE <br />HANGER TO THE STRUCTURE DOES NOT REQUIRE SEISMIC BRACING. <br />THE SIZE, TYPE, SPACING, AND METHOD OF INSTALLATION OF <br />SEISMIC BRACING SHALL BE IN ACCORDANCE WITH THE <br />LATEST "SMACNA SEISMIC RESTRAINT MANUAL -GUIDELINES <br />FOR MECHANICAL SYSTEMS". GAS PIPING IS TO BE <br />CLASSIFIED UNDER "SEISMIC HAZARD LEVEL A" AND ALL <br />OTHER PIPING SYSTEMS "SEISMIC HAZARD LEVEL C" IN <br />THE SMACNA MANUAL. <br />j3:) DETAIL -SINGLE PIPE HANGER <br />P-2 NO SCALE <br />DETAIL -ELECTRIC WATER HEATER <br />NO SCALE <br />CONDUIT OR <br />SPEED CLAMP <br />GALVANIZED OR CADMIUM <br />PLATED UNISTRUT <br />GAS PIPE PAINTED <br />PAINTED SCH. 40 PVC <br />SAFTEY YELLOW <br />SLEEVE, MINIMUM 4" LONG <br />AT EACH CLAMP LOCATION, <br />ONE SIZE LARGER THAN O.D. <br />ADDITIONAL LAYER <br />OF GAS PIPE TO ALLOW FOR <br />ROOF <br />OF ROOFING <br />GAS PIPE EXPANISON <br />MATERIAL UNDER <br />PRESSURE TREATED <br />BLOCK <br />4"x 4" OR 4"x 6" <br />NUT, BOLT, AND <br />GAS PIPE <br />PRESSURE TREATED <br />LOCKWASHER <br />ALV. OR CADMIUM BLOCK <br />PLATED UNISTRUT <br />CONDUIT <br />4"X4" OR 4"X6" PRESSURE <br />OR SPEED <br />CLAMP <br />TREATED BLOCK <br />ROOF4� <br />LAG BOLTS 1Y" LONG <br />�9 2 <br />�8' MIN <br />DDITIONAL LAYER OF ROOFING <br />TERIAL UNDER PRESSURE <br />-� <br />12' MIN <br />T TED BLOCK <br />NOTE: PROVIDE UPPORTS AT A MAXIMUM 8'-0" <br />ON CENT AND AT EACH CHANGE OF <br />DIRECTION T A MAXIMUM OF 2'-0" ON <br />EACH SIDE <br />7 DE AIL -ROOF GAS PI SUPPORT <br />P-2 NO StALE <br />1000NCRETE SP H BLC <br />NOTE: MIN OF 1" ON <br />ALL CONDENSATE <br />DRAIN AND VENT <br />LINES <br />CEILING <br />TOP <br />)OF CURB <br />ROOF <br />j®-� DETAIL-RTU CONDEN§ATE DRAIN <br />P-2 NO SCALE <br />LINK SEAL TYPE <br />FLOOR SLEEVE(USE <br />GALV. STEEL PIPE <br />SLEEVE WHERE LINK <br />SEAL TYPE FLOOR <br />SLEEVE IS NOT USED <br />0 <br />Ll <br />IUBBARD ENTERPRISES <br />IUICKSTAND <br />40-SWHP <br />9.8"x2.5" 16 GA <br />ALV. STL. DIAGONAL <br />RACES <br />/2" THREADED ROD <br />Y GC <br />4GA GALV. STL. <br />ORNER BRACKETS <br />1 /2" <br />2GA GALV. STL. <br />'ATER HEATER <br />LATFORM 27"x27" <br />'VC DRAIN BODY <br />" MIPTx 1" FS <br />BITUMASTIC PACKING. <br />MODULAR RUBBER <br />SEAL OPTIONAL. <br />BOLT <br />RISER CLAMP <br />SLAB ON <br />GRADE <br />WATER STOP <br />& ANCHOR <br />COLLAR <br />OAKUM PACKING <br />(OMIT IF RUBBE <br />SEAL IS USED.) <br />..;;�:v. a:v .6:v :va <br />pe ; .p•. ; .p�¢ ; .pOF <br />DETAIL -PIPE SLEEVE(SLAB ON GRADE <br />NO SCALE <br />ASPHAULT GRADE CLEANOUT <br />GRADE SMITH MODEL #426L <br />IV <br />a a <br />°a �r�11 ° a ° <br />o a �\ <br />EARTH FIL ° 4 as 11 I o 4 0. <br />6" MIN. THICK BED OF <br />3/8"-1/2" CRUSHED <br />STONE <br />ANCHOR FLANGED - <br />S NG W POURED <br />HOU I / tAS <br />SANITARY PIPE PROVIDED <br />CONCRETE 24" X 24" PART OFSHELL TIED <br />X 8" DEEP O 6" PIPE PROVIDED AS <br />RT OF CIVIL/SITE WORK. <br />11 DETAIL -GRADE CLEANOUT <br />P-2 NO SCALE <br />RE: DWG P-1 <br />FOR CONTINUATION <br />PLUMBING FIXTURE SCHEDULE <br />ITEMS <br />DESCRIPTION <br />WASTE <br />VENT <br />COLD <br />HOT <br />REMARKS j OR EQUAL MANUFACTURER <br />WC-1 <br />WATER CLOSET <br />4" <br />4" <br />1-1/4" <br />- <br />WALL MOUNTED / AMERICAN STANDARD "AFWALL" 2257.103 <br />WC-2 <br />WATER CLOSET (HANDICAP) <br />4" <br />2" <br />1-1/4" <br />- <br />WALL MOUNTED (ADA) / AMERICAN STANDARD "AFWALL" 2257.103 <br />UR-11 <br />URINAL (HANDICAP) <br />2" <br />2." <br />Y4" <br />-- <br />WALL HUNG (ADA) / AMERICAN STANDARD "ALLBROOK" 6541.132 <br />L-1 <br />LAVATORY (HANDICAP) <br />2" <br />2" <br />Y" <br />Y" <br />- <br />WALL HUNG, (ADA) j AMERICAN STD LUCERNE 0356.015 W/ SPEAKMAN SC-3004-LD FAUCETS <br />S-1 <br />LOUNGE SINK <br />2" <br />2" <br />Y" <br />Y" <br />COUNTER MOUNTED / ELKAY GECR-2521-R W/ SPEAKMAN SC-5763 FAUCETS <br />MS-1 <br />MOP SINK <br />3" <br />2fl' <br />Y4" <br />Y4" <br />FLOOR MOUNTED / FIAT TSB100 W/ SPEAKMAN SC-5811 FAUCETS & 6' HOSE EXTENSION <br />EWC <br />ELECTRIC WATER COOLER <br />2" <br />2" <br />Y" <br />- <br />HI-LO, WALL HUNG (ADA) / OASIS P8ACSL <br />FD-1 <br />FLOOR DRAIN <br />3" <br />2" <br />_ <br />_ <br />WITH GRATE AND TRAP PRIMER / JOSAM,ZQ9k-A <br />FD-2 <br />FLOOR DRAIN <br />3" <br />2" <br />_ <br />_ <br />WITH GRATE AND TRAP PRIMEP, / JOSA 32100 <br />WH <br />WALL HYDRANT <br />- <br />- <br />4" <br />- <br />-� <br />FREEZELESS, LOOSE KEY / WOODFORD 865 <br />WATER HEATER SCHEDULE - - <br />DESlG. <br />SERVICE <br />RECOVERY GPH <br />0 80'F RISE <br />STORAGE <br />CAPACITY <br />GALLONS <br />TEMPERATURE <br />ELECTRIC ELEMENT(S) <br />MANUFACTURER & MODEL NO. <br />�� <br />IN 'F <br />-- <br />OUT "F <br />WATTS <br />VOLTS/ <br />PHASE <br />EWH <br />JAN. RM <br />10 <br />10 <br />40 <br />110 <br />1Y0 2000 <br />120/1 <br />_ <br />STATE -- MIDGET NO. P6-10-10-MS-K <br />PLUMBING <br />LEGEND <br />SYMBOL <br />DESCRIPTION <br />SYMBOL <br />DESCRIPTION <br />-SAPS <br />SANITARY <br />ABC <br />ABOVE CEILING <br />=SAN- <br />SANITARY DRAIN <br />ATC <br />AT CEILING <br />BELOW FLOOR <br />OF <br />UNDER FLOOR <br />- - - - <br />VENT <br />UW <br />UNDERGROUND WASTE <br />= CW - <br />COLD WATER <br />SA <br />BELOW FLOOR <br />SHOCK ARRESTORS <br />-- <br />COLD WATER <br />-�I WCO <br />WALL CLEANOUT <br />--- <br />HOT WATER <br />FCO <br />FLOOR CLEANOUT <br />G <br />NATURAL GAS <br />fl <br />ELBOW UP <br />m GCO <br />GRADE CLEANOUT <br />J <br />ELBOW DOWN <br />FLOOR DRAIN WITH P-TRAP <br />s- <br />DIRECTION OF <br />30 <br />P-TRAP <br />FLOW <br />HOSE BIB/ WALL HYDRANT <br />DIRECTION OF <br />SLOPE DOWN <br />® <br />PLUMBING FIXTURE <br />T&P RELIEF VALVE <br />GAS METER <br />- SD <br />STORM DRAIN <br />D4 <br />BALL VALVE <br />- CD <br />CONDENSATE DRAIN <br />GAS SHUT-OFF VALVE <br />RD <br />ROOF DRAIN <br />EWH OVER MOP SINK. <br />SEE WATER <br />HEATER DETAIL 5/P-2 <br />13 WATER RISER DIAGRAM <br />P-2 NO SCALE <br />2'v <br />2� <br />2'V <br />2'V I � <br />M <br />" N 4"SAN <br />SA <br />PLUMBING NOTES <br />1. THE WORK SHALL BE EXECUTED IN STRICT CONFORMITY WITH <br />BASE BUILDING SPECIFICATION AND WITH THE LATEST EDITION <br />OF THE PREVAILING STATE PLUMBING AND BUILDING CODES <br />AND ALL LOCAL REGULATIONS THAT MAY APPLY. IN CASE OF <br />CONFLICT BETWEEN THE CONTRACT DOCUMENTS AND A GOVERNING <br />CODE OR ORDINANCE THE MORE STRINGENT STANDARD SHALL APPLY. <br />2. ALL PLUMBING WORK SHALL BE COORDINATED WITH ALL OTHER <br />TRADES BEFORE PROCEEDING WITH INSTALLATION. <br />3. CHECK INVERT ELEVATIONS AND EXACT LOCATIONS OF ALL <br />OUTSIDE UTILITIES BEFORE INSTALLING ANY UNDERGROUND <br />STORM &SANITARY LINES. <br />4. NO CHANGES ARE TO BE MADE IN PLUMBING LAYOUT WITHOUT <br />WRITTEN PERMISSION BY STAPLES. <br />5. NO PIPING SHALL RUN EXPOSED IN SALES OR FINISHED AREAS. <br />INSTALL RAIN WATER LEADERS AS CLOSE AS POSSIBLE TO <br />COLUMNS OR WALLS. <br />6. ROUGHING DIMENSIONS OF TOILET FIXTURES MUST BE <br />COORDINATED WITH LANLORD G.C. AND FIELD SUPERVISOR. <br />7. PLUMBING JOB TERMINATES 5'-0" FROM THE BUILDING UNLESS <br />OTHERWISE NOTED. LANDLORD SHALL COORDINATE CONTINUATION <br />ON SITE WITH SPECIFIC CIVIL DRAWINGS, <br />8. WALL HYDRANTS ARE TO BE INSTALLED .APPROXIMATELY 2'-0" <br />ABOVE FINISHED GRADE. ALIGNED WITH BRICK COURSES. <br />9. INSTALL ALL VENTS THRU ROOF 10'-0" MINIMUM FROM EDGE OF ROOF. <br />10. INSTALL BALL VALVES ON ALL BRANCH SUPPLY LINES. <br />11. INSTALL SLEEVES AT LEAST 2 PIPE SIZES LARGER FOR ALL <br />PIPES PASSING THRU MASONRY WALLS. CAULK ALL EXTERIOR <br />SLEEVES WATER TIGHT. <br />12. ALL ACCESS PANELS SHALL BE BY LANDLORD. <br />13. INSTALL ALL FLOOR CLEANOUTS TO CLEAR EQUIPMENT AND FIXTURES. <br />14. ALL WORK SHALL BE PROPERLY TESTED, BALANCED AND CLEANED. <br />PROVIDE A. ONE YEAR WARRANTY FROM DATE OF FINAL INSPECTION <br />ON ,ALL PARTS AND LABOR. <br />15. INSULATE ALL EXPOSED PIPING UNDER CABINETS AND LAVATORY SINKS. <br />16. WASTE AND VENT PIPING IN PLENUM SPACE SHALL BE SERVICE <br />WEIGHT CAST IRON, NO HUB. <br />k'yfR <br />4" VENT THRU ROOF SHALL <br />BE A MIN. OF 10'-0" AWA <br />FROM EDGES OF BLDG. AND , <br />20'-0" AWAY FROM EQUIP. <br />/'FRESH AIR INTAKES. <br />�1� 2 <br />2'y <br />L\� <br />2'V rN <br />2'V <br />4'V <br />KS) F `1 <br />3,Sp,N <br />3"SpN <br />"TAN <br />EXISTING 41/ SAN 0 "SAN <br />1/8" SEE DWG. <br />P-1 FOR <br />CONTINUATION. -� <br />4yS <br />2"V AN <br />NOTE: <br />FOR TRAP PRIMER <br />CONNECTIONS, <br />SEE DETAIL THIS DRAWING. <br />14 WASTE RISER DIAGRAM <br />P-2 NO SCALE <br />6� <br />w <br />o <br />rn <br />o; <br />h•�9 <br />18 <br />i <br />•� <br />o <br />o <br />Y <br />aG <br />as t� <br />®`O <br />3 <br />N <br />a 3 <br />6 <br />W <br />O <br />rL <br />V <br />c�0o <br />C <br />U <br />-0 U- U <br />ui <br />V- <br />EN N <br />2 d LL <br />z <br />Lm d(D <br />w <br />cc 4.1 <br />� M H U) <br />J <br />U <br />L <br />f-+ <br />cn <br />_W <br />Q <br />�CU <br />V ) <br />I <br />W <br />O <br />E <br />E <br />O <br />U <br />L <br />Q <br />N <br />�+ 0 <br />ca <br />U <br />on LL C <br />=cO <br />Zw <br />°es U <br />U <br />>, 8 <br />.55 <br />•� N fl. N <br />m2Nd <br />IL <br />w <br />U) <br />z <br />R <br />U) <br />cn <br />W <br />U) <br />W <br />0 <br />-1 E <br />L: =3 <br />w <br />w <br />u- - <br />uj <br />� a <br />o <br />0 <br />a <br />z <br />rn <br />o <br />a <br />h- <br />Uco <br />-w, <br />m <br />� <br />w <br />m <br />z <br />o <br />U <br />2 <br />�c <br />0 <br />0 <br />0 <br />