FIRE ALARM NOTES: <br />1. REFER TO FLOOR PLAN FOR LOCATION AND QUANTITY OF <br />DEVICES. <br />2. COORDINATE LOCATIONS OF ALL DEVICES WITH INTERIOR <br />ELEVATIONS AND STORE FIXTURES. <br />3. SPRINKLER FLOW AND TAMPER SWITCHES AND DUCT SMOKE <br />DETECTORS SHALL BE MONITORED BY ALARM MONITORING <br />4. X[WORMONITORING VENDOR SHALL PROVIDE NOTIFICATION CIRCUITS <br />FOR PULL STATIONS, STROBES & HORN/STROBE. <br />5. UNDER THE ACTIVATION OF SPRINKLER FLOW OR ANY PULL STATION <br />AND ROOF TOP UNIT DUCT SMOKE DETECTOR THE CONTROL PANEL_ <br />SHALL SHUT—OFF ALL ROOF TOP UNITS AND ACTIVATE STROBE & <br />STROBE/HORN DEVICES. <br />6. FIRE ALARM APPROVED MANUFACTURERS ARE NOTIFIER OR FIRELITE. <br />1 <br />E-3 <br />F_ 71 e <br />® ❑I ' L — J L-.. _J ---- P 1` <br />e <br />, <br />' <br />e <br />'x <br />I SYMBOL LEGEND f <br />[+] MANUAL. PULL STATION 48"AFF <br />t FIRE SPRINKLER FLOW SWITCH <br />,9, FIRE SPRINKLER TAMPER SWITCHES <br />CAN BE <br />HORN/STROBE, 80".AFF ///-- HIGHER IF <br />APPROVED <br />X STROBE ONLY, 80"AFF BY LOCAL <br />AUTHORITY <br />- <br />DUCT SMOKE DETECTOR IN SUPPLY <br />('J DUCT AS REQUIRED BY CODE. <br />-- DETECTOR FURNISHED AND WIRED BY <br />ELECTRICAL CONTRACTOR AND <br />MOUNTED BY H.V.A.C. CONTRACTOR. <br />NOTES BY SYMBOL FOR SHEET E--Z & E--3 <br />OELECTRICAL CONTRACTOR SHALL VERIFY QUANTITY" AND <br />FINAL LOCATION OF GONDALA OUTLETS WITH STAPLES <br />REPRESENTATIVE PRIOR TO ROUGH --IN. (DISTRIBUTE <br />LOAD EVENLY AMONG CIRCUITS.) <br />QWIRING DEVICES MOUNTED ON THIS WALL SHALL. BE IN <br />SURFACE CAST DEVICE BOXES (TYPE FS) WITH EXPOSED <br />SURF -ACE RACEWAYS AND SS PLATES. SEE SHEET E-3 <br />QFINAL LOCATION TO BE FIELD VERIFIED WITH STAPLES <br />PROJECT MANAGER. SEE SHEET E--3 <br />WEATHERPROOF LOW VOLTAGE PUSHBUTTON 48" AFF, <br />EQUAL TO EDWARDS #1786-B. <br />LOW VOLTAGE BUZZER MOUNTED ABOVE DOOR, EQUAL TO <br />v EDWARDS #340-4G5. <br />O6 120VAC-24VAC CONTROL TRANSFORMER FOR DOOR <br />BUZZER MOUNTED ON J-BOX, ABOVE DOOR, EQUAL TO <br />EDWARDS #598. <br />0 FINAL LOCATION OF SIGN J--BOXES TO BE VERIFIED <br />IN FIELD. (COORDINATE WITH SIGN CONTRACTOR FOR FINAL <br />CONNECTION AND REQUIREMENTS FOR REMOTE MOUNTED <br />BALLASTS IN ACCORDANCE WITH NEC.). BOXES TO BE <br />MOUNTED ABOVE SALES AREA LIGHTING. <br />0i TUIT CONTROLLED BY CONTROL RELAY PANEL. REFER <br />8 0, CHEDULE ON SHEET E-1. <br />OPROVIDE COMPLETE CONNECTION 'TO DOCK LEVELER. <br />SE_1 ARCH. DETAIL #3 / A-10 WITH LIMIT SWITCH BY <br />'STARE D' MODEL #9007C62B2. SEE SHEET E-3. <br />�i� <br />fill �11 I� ��11 <br />GENERAL NOTES: <br />1. ALL WIRING DEVICES SHALL BE MOUNTED 18" AFF UNLESS <br />OTHERWISE NOTED. <br />2.. ALL WIRING DEVICES AND COVERPLATES SHALL MATCH WALL <br />FINISH AS SCHEDULED. <br />3. ALL EXPOSED WIRING ABOVE CEILINGS SHALL. BE PLENUM <br />RATED. <br />4. ALL FUSES SHALL BE FERRAZ SHAWMUT TYPE AJT UL CLASS J DUAL_ <br />ELEMENT TIME DELAY, 200,000 AIC. (PROVIDE ONE SPARE SEA' <br />OF EACH SIZE AND TYPE OF FUSE TO STAPLES.). FUSES FURNISHED <br />BY HILL PHOENIX. <br />5. ALL BRANCH CIRCUIT WIRING TO BE FURNISHED WITH SEPARATE <br />GREEN COLORED GROUND WIRE. <br />6. ALL ISOLATED RECEPTACLES BRANCH CIRCUITS WIRING TO BE <br />FURNISHED WITH SEPARATE EQUIPMENT GREEN COLORED GROUND <br />WIRE AND SEPARATE ISOLATED GREEN COLORED GROUND WIRE <br />WITH ORANGE TRACE. <br />7. SEE DWGS. E-1 AND E-2 FOR HVAC WIRING, ROOF -TOP UNITS. <br />NOTE: <br />RECEPTACLES ON EACH GONDOLA ARE SERVED B <br />TWO CIRCUITS OF 20AMP. EACH CIRCUITS CAN <br />HANDLE MAXIMUM LOAD OF 16A/1600 WATTS. <br />FOR GONDOLA WHICH NEED MORE POWER SUCH <br />AS WITH LASER PRINTERS AND DESKTOPS <br />PROVIDE EXTRA BREAKERS_AS REQUIRED. <br />ELECTRICAL POWER PLAN <br />SCALE: 1 /8"=1 "-0" <br />�I®mINJ <br />A" <br />D <br />GONDOLA MOUNTED FLUORESCENT LIGHTING FIXTURE, <br />SEE LIGHTING FIXTURESCHEDULESHEET E-4 <br />' <br />D11 <br />GONDOLA MOUNTED FLUORESCENT LIGHTING FIXTURE, <br />SEE LIGHTING FIXTURE SCHEDULE SHEET E-4 <br />(Df <br />— <br />EXIT LIGHT. <br />20A., 120/277V., SINGLE POLE TOGGLE SWITCH, "3" <br />S S3 <br />INDICATES 3 WAY; "P" INDICATES PILOT LIGHT; "M" <br />SP So <br />INDICATES MOTOR RATED; "0" INDICATES <br />OCCUPANCY SENSOR (UNENCO IWS—ZP--3P--W). MOUNTED <br />AT 48" AFF UNLESS OTHERWISE NOTED. DEVICE <br />AND CO'VERPLAT E TO MATCH WALL, FINISH AS SCHEDULED. <br />PANELBOARD. <br />Q <br />JUNCTION BOX — WALL, CEILING. <br />20A., 125V., 2P., 3W. GROUNDING DUPLEX WALL <br />RECEPTACLE MOUNTED 18" A.F.F. UNLESS OTHERWISE <br />GFI <br />Pwp <br />NOTED. "GFI" INDICATES GROUND FAULT <br />"wp' <br />IG <br />INTERRUPTING; INDICATES WEATHERPROOF; <br />"IG" INDICATES ISOLATED GROUND. DEVICES AND COVERPLATE <br />TO MATCH WAIL FINISH AS SCHEDULED. <br />DOUBLE DUPLEX RECEPTACLE, DEVICES AND <br />COVERPLATF_" TO MATCH WALL FINISH AS SCHEDULED. <br />20A-25OV. 2P, 3W NEMA 6-20R RECEPTACLE <br />MOTOR — HORSEPOWER, VOLTAGE AND PHASE AS <br />NOTED ON DRAWINGS <br />DISCONNECT SWITCH — SIZE AS NOTED ON DRAWINGS. <br />(RATING/POLES/FUSE SIZE, "NF" INDICATES NON FUSED <br />DISCONNECT, "F" INDICATES FUSED, SIZE AS NOTED.) <br />MAGNETIC MOTOR STARTER -- SIZE AS NOTED ON <br />DRAWINGS <br />DOOR BUZZER/TRANSFORMER — EDWARDS CATALOG <br />NUMBER 340-4G5/598 ON SINGLE GANG SURFACE BOX <br />WEATHERPROOF PUSHBUTTON STATION — EDWARDS <br />CATALOG NUMBER 1786—B <br />SS <br />SURGE SUPPRESSOR <br />CONDUIT — CONCEALED ABOVE CEILINGS, IN WALLS <br />IN FINISHED AREAS, OR EXPOSED IN UNFINISHED <br />AREAS. <br />CONDUIT HOMERUN TO PANEL — #12 OR SIZE AS <br />INDICATED (GROUND NOT SHOWN BUT REQUIRED). <br />UNLESS OTHERWISE NOTED, 2—#12,1—#12 G <br />TS <br />TEMPERATURE SENSOR, WIRING BY NOVAR. <br />�T <br />THERMOSTAT <br />�S <br />DUCT SMOKE DETECTOR <br />TELE—POWER ALUMINUM STEEL POLE 20'-0" LONG (2-10'-0" <br />SECTIONS) WITH TWO COMPARTMENTS AND WHITE IN COLOR. <br />PP1 <br />® <br />WIREMOLD #NP620-06031—A <br />HUBBELL HBLPP10A <br />EMS TEMPERATURE SENSOR SUPPLIED WITH ROOF <br />TOP UNIT, FINAL CONNECTIONS BY STAPLES (TYPICAL) <br />TS RTU-6 2 �/ <br />O5 2 5 <br />5 <br />SAVVY <br />TS <br />RTU-4 ] <br />EMS <br />Q <br />EXECUTIVE <br />CONTROLLER <br />TS <br />RTU-3 ] <br />BY STAPLES <br />O <br />TS <br />- RTU-2 ] <br />O <br />TS <br />RTU-1 ] <br />5 TYPICAL <br />1 TYPICAL <br />EMS <br />TYPICAL 6 <br />INTERFACE <br />PANEL <br />BY STAPLES <br />D�OTS OUTDOOR TEMPERATURE AND ANALOG LIGHT <br />ALS SENSOR ASSEMBLY <br />SECURITY ALARM <br />(AT CASH ROOM) <br />2 x 5) ( M )I PULSE METER BY ELECTRICAL CONTRACTOR <br />2 5 PLM PHASE LOSS MONITOR IN ELEC RM <br />BY STAPLES <br />4—#10 & 1—#10G.-3/4"C. TO CIRCUIT <br />IN PANEL "MDP", REFER TO PANEL <br />SCHEDULE, E-1 <br />d- ,n (.0 REMOTE OVERRIDE <br />J J J J SWITCH PLATE (MGR'S <br />`n 0 "' "' 0 `n OFFICE) BY STAPLES <br />2 5 <br />u w w w O O LOW VOLTAGE <br />SWITCH, TYPICAL <br />©OR <br />EMS RISER DIAGRAM NOTES: <br />1. THE EMS EXECUTIVE CONTROLLER/INTERFACE PANEL, <br />OUTDOOR TEMPERATURE, ANALOG LIGHT SENSOR ASSEMBLY <br />AND REMOTE OVERRIDE SWITCH PLATE SHALL BE PROVIDED <br />BY STAPLES. <br />2. E.C. TO PROVIDE EMPTY RACEWAYS WITH PULL STRINGS TO <br />ALL LOCATIONS AS INDICATED. PROVIDE RACEWAY LABELING <br />AS REQUIRED. SEE DWG. E-5 FOR CONDUIT TYPE AND <br />LOCATIONS. <br />3. STAPLES SHALL FURNISH PROGRAMMING & REMOTE <br />COMMUNICATIONS TESTING/CHECKOUT. <br />TYPICAL <br />CONTROL <br />LOW VOLTAGE <br />RELAY <br />LIGHTING <br />TYPICAL <br />CONTROLLED <br />RELAY PANEL <br />CIRCUIT <br />FROM PANEL <br />BY ELECTRICAL <br />"L" OR <br />"P1" <br />CONTRACTOR <br />REFER TO <br />SCHEDULE <br />CIRCUIT <br />TO TYPICAL <br />DWG. E-1 <br />LOAD AS <br />SCHEDULED <br />4. REFER TO MECHANICAL DWGS. FOR MECH. EQUIP. <br />LOCATIONS. REFER TO ELEC. DWGS, FOR EMS <br />SYSTEM & RELATED EQUIPMENT LOCATIONS <br />5• COORDINATE THE INSTALLATION OF EMS/STAPLES <br />SUPPLIED EQUIPMENT WITH EMS CONTRACTOR. <br />6. ALL INQUIRIES PERTAINING TO THE ENERGY <br />MANAGEMENT AND CONTROL SYSTEM SHOULD BE <br />DIRECTED TO STAPLES PROJECT MANAGEMENT <br />TEAM. <br />EMS GENERAL NOTES: <br />O ELECTRICAL CONTRACTOR TO PROVIDE 3/4" CONDUIT WITH PULL STRING FROM <br />TEMPERATURE SENSOR TO ROOF JOIST. <br />O ELECTRICAL CONTRACTOR TO PROVIDE 3/4" CONDUIT WITH PULL STRING <br />BETWEEN DEVICES. <br />E-1 (3 ELECTRICAL CONTRACTOR TO PROVIDE 3/4" CONDUIT WITH PULL STRING <br />FROM EMS CP-1 PANEL TO GENERAL ELECTRIC LOW VOLTAGE RELAY <br />PANEL. SEE 4/E-5. <br />O ELECTRONIC THERMOSTAT MODULE (FACTORY INSTALLED), TYPICAL. <br />DEVICES INSIDE RTU ARE PRE —WIRED BY RTU MFR. FINAL CONNECTION <br />TO RTU ELECTRONIC THERMOSTAT MODULE BY EMS CONTRACTOR. <br />O CABLING FURNISHED AND INSTALLED BY STAPLES LOW VOLTAGE CONTRACTOR. <br />O ELECTRICAL CONTRACTOR TO PROVIDE 1" CONDUIT SLEEVE FROM R.T.U. <br />CONTROL AREA TO CEILING JOIST AREA. SEE NO. 8 OF DETAIL 5/E-5. <br />L_ <br />.O <br />cu <br />- --a <br />i) <br />cn <br />O <br />E <br />E <br />O <br />U - <br />L <br />Q <br />N <br />_�_j CD <br />lu s <br />�n u_ c <br />` 0 <br />O <br />0 <br />mYNa <br />a <br />© <br />m <br />i <br />LU <br />LLI <br />�- <br />Z LL. <br />ca <br />w <br />O <br />Z <br />o <br />w <br />p <br />M <br />Y <br />CD <br />Z <br />LLI <br />N <br />Lu <br />0 <br />O <br />H <br />d <br />p <br />0 <br />