PARTITION OF <br />ROCKWOOL PIPE <br />INSULATION THROUGH <br />PENETRATION (INSU- <br />LATED PIPE ONLY) <br />PIPE INSULATION <br />(WHERE REQUIRED) <br />PIPE SLEEVE FIRESTOP MATERIAL <br />(GONG. OR JTL <br />MASONRY <br />WALL ONLY <br />ELEVATION - WALL PENETRATION <br />1 Firestopping Of Penetrations Through Walls <br />No Scale <br />WATER MOTOR GONG, <br />APPROX.10'ABOVE <br />FINISHED GRADE <br />MAIN RISER ALARM <br />PRESS. SWITCH - <br />RETARDING <br />CHAMBER <br />FIRE DEPARTMENT <br />CONNECTION GRAPHIC SIGN - <br />FDC APPROX. 3 FT. <br />ABOVE FINISHED GRADE <br />TERMINATE 2" MAIN DRAIN <br />AT EXTERIOR WALL WITH <br />45° GALVANIZED ELBOW <br />AND PIPE APPROX. 24" <br />ABOVE FIN. GRADE <br />1" THICK 24"x24" CONC. <br />SPLASH BLOCK ---\ <br />TO SYSTEM <br />CHECK <br />VALVE <br />GROOVED COUPLING <br />WATER PRESSURE <br />GAUGES <br />ALARM CHECK <br />VALVE WITH TRIM <br />2" MAIN DRAIN <br />CONTROL VALVE WITH <br />TAMPER SWITCH, <br />LOCK AND CHAIN <br />n <br />1'-0" <br />FINISHED <br />GRADE <br />2 Fire Protection Alarm Check Valve Detail <br />No Scale <br />3/4" BALL DRIP <br />FLANGED CONN. TO <br />UNDERGROUND FIRE <br />PROTECTION WATER <br />SUPPLY <br />FINISHED FLOOR <br />REAR <br />LEFT RIGHT 1 Fire Protection Floor Plan <br />NScale 1/8"=1'-0" <br />FRONT <br />RETURN BEND FOR DRY <br />OR PREACTION SYSTEM <br />EXTERIOR BUILDING WALL <br />BRANCH LINE <br />1" VALVE NOT <br />OVER T-0" ABOVE <br />FINISHED FLOOR. ! <br />WET SYSTEM <br />1" SIGHT GLASS <br />FINISHED FLOOR <br />1"BALL VALVE -r FINISHEDGRADE/ROOF I <br />31nspector's Test Detail <br />No Scale <br />DRY OR PREACTION <br />SYSTEMS <br />TEMPORARY CONN. <br />PLUG VALVE END <br />WHEN NOT IN USE <br />CAULKING SEALANT <br />SMOOTH BORE, CORROSION <br />RESISTANT OUTLET GIVING <br />FLOW EQUIVALENT TO ONE <br />SPRINKLER. <br />1"-45° ELBOW 24" <br />1" THICK 24"x24" <br />CONC. SPLASH BLOCK <br />FLORIDA ADMINISTRATIVE CODE <br />CHAPTER 61G15-32 NOTES <br />1. THE FIRE PROTECTION SYSTEM SCOPE OF WORK SHALL INCLUDE THE PREPARATION AND <br />DESIGN OF THE FIRE PROTECTION SYSTEM LAYOUT DOCUMENTS (WORKING PLANS). PROVIDE <br />ALL EQUIPMENT, MATERIALS, COMPONENTS, ASSEMBLIES AND SUPPORT SYSTEMS REQUIRED, <br />AS DESCRIBED, IN NFPA 13. THE FIRE PROTECTION CONTRACTOR SHALL CONDUCT A HYDRANT <br />FLOW TEST AND PERFORM HYDRAULIC CALCULATIONS FOR THE DESIGN OF THE FIRE <br />PROTECTION SYSTEM. <br />2, THE FIRE PROTECTION DESIGN, CALCULATIONS, INSTALLATION AND THE ACCEPTANCE TESTING <br />OF THE FIRE PROTECTION SYSTEM SHALL BE IN ACCORDANCE WITH NFPA 13, 2004 EDITION; <br />NFPA 24, 2002 EDITION; THE FLORIDA BUILDING CODE AND THE FLORIDA FIRE PREVENTION CODE <br />2004 EDITION AND ALL LOCAL CODES REQUIRED BY THE AUTHORITY HAVING JURISDICTION. <br />3. AREA OCCUPANCIES AND HAZARD CLASSIFICATIONS ARE LISTED IN THE DESIGN CRITERIA <br />NOTE LOCATED ON THIS SHEET. <br />4. ALL SYSTEM CONTROL VALVES SHALL BE PROVIDED WITH TAMPER SWITCHES AND INTERFACE <br />WITH THE FACP ON THE SUPERVISORY CIRCUIT, ALL FLOW SWITCHES SHALL INTERFACE WITH <br />THE FACP ON THE ALARM CIRCUIT. <br />5. THE FIRE PROTECTION CONTRACTOR SHALL PREPARE AND PROVIDE SIGNED AND SEALED FIRE <br />PROTECTION SYSTEM LAYOUT DOCUMENTS WITH HYDRAULIC CALCULATIONS AND SHALL BE <br />THE ENGINEER OF RECORD. SIGNED AND SEALED FIRE PROTECTION SYSTEM LAYOUT <br />DOCUMENTS WITH HYDRAULIC CALCULATIONS SHALL BE SUBMITTED TO THE <br />ARCHITECT/ENGINEER AND THE LOCAL AHJ FOR ACCEPTANCE PRIOR TO PERMITTING. <br />6. ALL FIRE PROTECTION EQUIPMENT AND COMPONENTS SHALL BE LISTED AND TESTED FOR FIRE <br />PROTECTION USE. ALL FIRE PROTECTION EQUIPMENT AND COMPONENTS SHALL BE THE U.L. <br />LISTED AND FM APPROVED. <br />7. THE POINT OF SERVICE AND THE WATER SUPPLY CHARACTERISTIC'S FOR THE FIRE PROTECTION <br />SYSTEM IS SHOWN ON THE CIVIL SITE PLAN, <br />8. THE WATER SUPPLY FOR THE FIRE PROTECTION SYSTEM HAS NOT SHOWN ANY EVIDENCE OF <br />MICROBIAL INDUCED CORROSION (MIC). THE FIRE PROTECTION CONTRACTOR SHALL NOTIFY THE <br />ARCHITECT/ENGINEER OF ANY EVIDENCE OF MIC AND PROVIDE NECESSARY WATER TREATMENT <br />AS NEED TO REDUCE OR ELIMINATE MIC. <br />9. ALL METERING AND BACK FLOW PRVENTION DEVICES SHALL MEET WITH ALL WATER PURVEYORS <br />REQUIREMENTS. <br />GENERAL NOTES <br />1. THE FIRE PROTECTION SYSTEMS SHALL COMPLY WITH NFPA 13 - 2004 EDITION, THE FLORIDA FIRE PREVENTION CODE AND <br />ALL LOCAL CODES AND REQUIREMENTS. <br />2. FINAL SYSTEM ACCEPTANCE AND APPROVAL SHALL BE CONDUCTED BY STATE FIRE MARSHAL AND ARCHITECTIENGINEER. <br />3. THE CONTRACTOR SHALL PREPARE SYSTEM LAYOUT DRAWINGS PER CHAPTER 14, OF NFPA 13 - 2004 EDITION. THE <br />CONTRACTOR SHALL PERFORM HYDRAULIC CALCULATIONS. CONTRACTOR'S SPRINKLER SYSTEM LAYOUT (SHOP <br />DRAWINGS), HYDRAULIC CALCULATIONS AND MATERIAL DATA SHALL BE SUBMITTED TO THE ARCHITECT/ENGINEER AND <br />AUTHORITY HAVING JURISDICTION FOR APPROVAL PRIOR TO SYSTEM INSTALLATION. <br />4. THE CONTRACTOR SHALL PERFORM HYDRANT -FLOW TEST TO VERIFY WATER PRESSURE REQUIRED FOR HYDRAULIC <br />CALCULATIONS. <br />5. THE FIRE PROTECTION SYSTEMS SHOWN REPRESENT THE DESIGN INTENT OF THE ENGINEER OF RECORD, IN <br />ACCORDANCE WITH STATE REGULATION 61G15-32. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE <br />INSTALLATION WITH ALL OTHER TRADES. THE CONTRACTOR SHALL PROVIDE COMPLETE SPRINKLER SYSTEM LAYOUT <br />DRAWINGS WITH ANY ADDITIONAL OFFSETS, SPRINKLERS OR SYSTEM COMPONENTS AS REQUIRED FOR A COMPLETE AND <br />OPERABLE SYSTEM AND TO AVOID CONFLICTS WITH OTHER TRADES. <br />6. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR CEILING TYPES, HEIGHTS AND ALL ASSOCIATED DATA. <br />7. PROVIDE FIRE STOP ASSEMBLIES FOR ALL PENETRATIONS OF SMOKE/FIRE WALLS, CEILINGS AND FLOORS, FIRE STOP <br />ASSEMBLIES SHALL MEET ASTM E-814. SEE FIRE RATED PIPE PENETRATION DETAILS. <br />8. ALL DRAIN AND DRY PIPE SYSTEM PIPING AND FITTINGS SHALL BE GALVANIZED BOTH INSIDE AND OUTSIDE. <br />9. INSTALL ADDITIONAL SPRINKLERS UNDER ALL EXPOSED DUCTWORK OR OBSTRUCTIONS EXCEEDING 48" IN WIDTH. <br />PROVIDE ADDITIONAL SPRINKLERS AS REQUIRED FOR PROPER COVERAGE OF OBSTRUCTIONS IN ACCORDANCE WITH <br />NFPA 13. <br />10. <br />ALL SPRINKLERS INSTALLED WITHIN MECHANICAL ROOMS, STORAGE ROOMS, JANITORS CLOSETS OR AREAS SUBJECT TO <br />MECHANICAL INJURY SHALL BE PROTECTED WITH LISTED GUARDS. <br />11. <br />COORDINATE PIPE ROUTING WITH DUCT ROUTING, EQUIPMENT LOCATIONS, ELECTRICAL INSTALLATIONS AND BUILDING <br />STRUCTURAL MEMBERS. DO NOT ROUTE PIPING OVER ELECTRICAL PANELS. PIPING ROUTED OVER ELECTRICAL PANELS <br />SHALL BE REROUTED AT NO ADDITIONAL COST. <br />12. <br />PROVIDE TAMPER SWITCHES ON ALL CONTROL VALVES. <br />13. <br />SLOPE ALL PIPING TO THE SYSTEM MAIN DRAIN AS REQUIRED TO INSURE PROPER DRAINAGE. IT IS THE CONTRACTOR'S <br />RESPONSIBILITY TO INSURE THAT ALL PIPING IS DRAINABLE. ADDITIONAL DRAINS AND PLUGS SHALL BE INSTALLED <br />WHERE REQUIRED TO COMPLY WITH THE ABOVE REFERENCED CODES. <br />14. <br />ALL ROLL GROOVED AND CUT GROOVED COUPLINGS AND FITTINGS SHALL BE PROVIDED BYA SINGLE MANUFACTURER. <br />15. <br />SPRINKLERS SHALL BE CENTERED IN CEILING TILES IN AREAS WITH LAY -IN TILES AND VISUALLY ALIGNED IN AREAS WITH <br />SMOOTH CEILINGS. <br />16. <br />THIS BUILDINGS STRUCTURAL SYSTEM HAS BEEN DESIGNED TO SUPPORT THE ADDITIONAL WEIGHT ASSOCIATED WITH <br />THE SPRINKLER SYSTEM. <br />17. <br />PIPING IN AREAS WITH EXPOSED STRUCTURE SHALL BE INSTALLED AS HIGH AS POSSIBLE TO ALLOW THE OWNER <br />MAXIMUM USE OF THE SPACE. <br />18. <br />SPRINKLERS IN AREAS WITH EXPOSED STRUCTURE (OBSTRUCTED CONSTRUCTION) SHALL BE INSTALLED WITH <br />DEFLECTOR 1" BELOW THE BOTTOM OF THE BEAM (MAXIMUM 22" BELOW ROOF DECK). EXPOSED BAR JOISTS THAT HAVE <br />SPRAY -ON FIRE PROOFING THAT MAKES THE JOIST SOLID SHALL BE TREATED LIKE A BEAM WITH THE SPRINKLERS 1" <br />BELOW THE BOTTOM OF THE FIRE PROOFING. <br />19. <br />SLEEVE AND/OR FIRESTOP ALL PENETRATIONS THROUGH RATED WALLS, CEILINGS, AND FLOORS WITH U/L LISTED <br />ASSEMBLIES. FIRESTOP ASSEMBLIES SHALL BE EQUAL OR EXCEED THE RATING OF THE WALL, CEILING OR FLOOR. SEE <br />ARCHITECTURAL DRAWINGS FOR FINAL FINISHES. <br />20. <br />PROVIDE ACCESS PANELS TO ALL VALVES ABOVE NON -ACCESSIBLE CEILINGS AND CHASES. <br />DRAWING CRITERIA <br />THE FOLLOWING PUBLICATIONS SHALL BE USED AS A REFERENCE FOR DESIGN OF THE FIRE <br />SUPPRESSION SYSTEM ON THIS PROJECT. <br />1. NFPA 13, INSTALLATION OF SPRINKLER SYSTEMS <br />2. NFPA 24, PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES <br />3. FLORIDA FIRE PREVENTION CODE - 2004 EDITION <br />ENTIRE BUILDING (EXCEPT AS NOTED): <br />OCCUPANCY CLASSIFICATION: <br />ORDINARY HAZARD GROUP 2 <br />SYSTEM TYPE: <br />WET PIPE <br />DESIGN DENSITY: <br />.20 GPM/SQ. FT. <br />HYDRAULIC REMOTE AREA: <br />1,500 SQ. FT. <br />SPRINKLER ORIFICE SIZE: <br />1/2" <br />SPRINKLER TEMPERATURE RATING: <br />155°F <br />DURATION OF SUPPLY: <br />60 - 90 MIN. <br />MAXIMUM COVERAGEISPRINKLERHERD: <br />130 SQ. FT./QUICK RESPONSE TYPE <br />HOSE STREAM ALLOWANCE: <br />250 GPM <br />BATHROOMS: <br />OCCUPANCY CLASSIFICATION: <br />LIGHT HAZARD <br />SYSTEM TYPE: <br />WET PIPE <br />DESIGN DENSITY: <br />.10 GPMISQ. FT. <br />HYDRAULIC REMOTE AREA: <br />1,500 SQ. FT. <br />SPRINKLER ORIFICE SIZE: <br />1/2" <br />SPRINKLER TEMPERATURE RATING: <br />155°F <br />DURATION OF SUPPLY: <br />30 MIN. <br />MAXIMUM COVERAGE/SPRINKLER HEAD: <br />225 SQ. FT./QUICK RESPONSE TYPE <br />HOSE STREAM ALLOWANCE: <br />100 GPM <br />FIRE PROTECTION SYMBOL LEGEND <br />SYMBOL <br />DESCRIPTION <br />� <br />-CONTROL VALVE W/TAMPER SWITCH <br />N <br />-CHECK VALVE <br />0-0 <br />-FLOW SWITCH <br />-SPRINKLER AND DRAIN RISER <br />-NEW SPRINKLER PIPING <br />Q1 <br />-REVISION REFERENCE <br />1 <br />-DETAIL REFERENCE: TOP -DETAIL#, <br />FP-1 <br />BOTTOM -DRAWING# SHOWN ON <br />NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT <br />FIRE PROTECTION SPRINKLER LEGEND <br />SYMBOL <br />ORF <br />TEMP <br />RESPONSE <br />K-FAG <br />FINISH <br />MODEL <br />STYLE <br />PLATE <br />MFG. <br />• <br />1!2" <br />155° <br />QUICK <br />5.6 <br />CHROME <br />F1FR <br />RECESSED <br />CHROME <br />RELIABLE <br />0 <br />1l2" <br />155° <br />QUICK <br />5.6 <br />BRASS <br />F1FR <br />UPRIGHT <br />HD/GD <br />RELIABLE <br />O <br />112" <br />155° <br />QUICK <br />5.6 <br />BRASS <br />F1FR <br />UPRIGHT <br />NONE <br />RELIABLE <br />DRAWING INDEX <br />N0. <br />TITLE <br />FP001 <br />Fire Protection Floor Plan, Notes, Schedules &Details <br />ikey Plan <br />� I <br />pUS Hwy 3o1 � <br />_N�i <br />E <br />_8 0 <br />o <br />0 <br />U <br />4� a <br />w <br />� <br />o <br />l <br />b� <br />o <br />Ow <br />�/•� <br />� <br />U <br />O <br />O <br />V <br />co <br />w <br />N � <br />Ll- <br />O <br />0 <br />U <br />L <br />�_ <br />N <br />.f.r <br />�� <br />CO Z) N p <br />w <br />>' <br />.N <br />U <br />LU <br />��Y <br />fl. fn <br />W Y Na) <br />o <br />a <br />u.f <br />� co <br />a w <br />1 <br />w <br />0Cn <br />Z <br />0 <br />m <br />W <br />al <br />0 <br />w <br />o <br />� <br />o <br />J <br />W <br />o <br />z <br />CD <br />o <br />W <br />� <br />o <br />c <br />M <br />LO <br />� <br />W <br />� <br />FP001 <br />--� T <br />