Laserfiche WebLink
B CFM <br />ARIES <br />VAR( <br />BRANCH DUCT - <br />Q O <br />Q O <br />w <br />w <br />CONTROL ROD--_4Y <br />Z <br />(TYPICAL) <br />A (CFM) <br />X <br />NOTE: FOR RETURN AIR FLOW, <br />DELETE SPLITTER DAMPER <br />SCREWS <br />TURNING VANES <br />(TYPICAL) <br />C CFM <br />BRANCH DUCT <br />SPLITTER DAMPER <br />(TYPICAL) <br />MAIN DUCT <br />TO SIZE SPLITTER: <br />Y = (B/A) (X) <br />Z = X-Y <br />DEPTH REMAINS <br />CONSTANT <br />1 Splitter Detail <br />Scale: None <br />F. <br />MIN. BAND OF SAME SIZE <br />AS HANGER STRAP <br />NOTE: <br />HANGER STRAP SIZE PER SMACNA. <br />HANGER <br />STRAP <br />2 Rectangular/Round Duct Hanger Detail <br />Scale: None <br />MOUNT CAP LEVEL <br />BIRD SCREEN <br />CAULKING BEAD OR GASKET FULL <br />ANCHOR W/ CADMIUM / PERIMETER OF CURB BY HVAC. <br />PLATED SCREWS 12" TREATED WOOD NAILER <br />O.C. <br />13-1/2" PREFABRICATED <br />CURB FURNISHED BY HVAC <br />- INSTALLED BY GENERAL <br />FLASHING BY ROOFER -� i _ CONTRACTOR <br />ROOF <br />E SUPPORT ANGLES AS <br />REQUIRED BY GENERAL <br />CONTRACTOR <br />1 1/2" EXTERNAL- - <br />INSULATION <br />SEAL WATERTIGHT 211 <br />3 Gravity Roof Vent Detail <br />Scale: None <br />4'-0" MAXIMUM <br />MAXIMUM SAG 1/2" PER FOOT <br />OF SUPPORT SPACING. <br />FLEXIBLE DUCT <br />NOTES: <br />1. DUCT SHOULD EXTEND STRAIGHT FOR <br />SEVERAL INCHES FROM A CONNECTION <br />BEFORE BENDING. <br />2. SUPPORT SYSTEM MUST NOT DAMAGE DUCT <br />OR CAUSE OUT OF ROUND SHAPE. <br />4 Flex Duct Support Detail <br />Scale: None <br />eI InBI V III Il+T 0131KI IAI CITTIAIl-I <br />ROUND METAL DUCT <br />(EXTERNAL INSULATION) <br />CEILING <br />METAL STRAP <br />1-1/2" MINIMUM <br />INSULATED ROUND <br />FLEXIBLE DUCT <br />(MAX. 8'-0" LONG) <br />SIZE TO MATCH <br />DIFFUSER NECK. <br />' CEILING DIFFUSER <br />MAX. 20' TRANSITION <br />ul <br />CONICAL FITTING WITH <br />LOCKING TYPE VOLUME <br />DAMPER. <br />FLEX DUCT OR ROUND SHEET METAL <br />DUCT. FLEX DUCT MAX. V-0" LONG, <br />USE CLAMP TO ATTACH FLEX DUCTS <br />AND SEAL. SUPPORT DUCT EVERY <br />FOUR FEET FROM STRUCTURE <br />6 Branch Duct Detail <br />Scale: None <br />0.25 D (4" MIN. <br />PER SMACNA) <br />RECTANGULAR <br />DUCT <br />VOLUME <br />DAMPER <br />HVAC SYMBOLS <br />SYMBOL <br />DESCRIPTION <br />NEW DUCT WORK <br />FLEXIBLE DUCT <br />B <br />SUPPLY AIR DUCT WORK UP THRU PLAN <br />RETURN AIR OR EXHAUST DUCT WORK UP THRU PLAN <br />DUCT WORK TRANSITION <br />90' ELBOW WITH TURNING VANES <br />MANUAL AIR VOLUME CONTROL DAMPER <br />®OR® <br />SUPPLY AIR DEVICE <br />zRETURN <br />AIR DEVICE <br />® <br />EXHAUST AIR DEVICE <br />O <br />WALL MOUNTED THERMOSTAT <br />SD <br />DUCT SMOKE DETECTOR <br />A-100 <br />DIFFUSER DEVICE TYPE - AIR QUANTITY <br />RTU �10 <br />EQUIPMENT DESIGNATION TAG <br />s - R - s <br />REFRIGERATION PIPING <br />CONDENSATE PIPING <br />CZMechanical Floor Plan <br />Scale:1/8"=V-0" <br />I <br />MECHANICAL GENERAL NOTES <br />1. CONTRACTOR TO VISIT SITE AND VERIFY ALL CLEARANCES BEFORE FABRICATION OF DUCTWORK AND <br />16. VERIFY VOLTAGE WITH ELECTRICAL CONTRACTOR BEFORE ORDERING EQUIPMENT. <br />PROVIDE ADDITIONAL OFFSET AND/OR CHANGES IN DUCT SIZES TO MEET FIELD CONDITIONS AND COORDINATE <br />WITH ELECTRICAL, PLUMBING AND FIRE PROTECTION SUBCONTRACTOR BEFORE ANY CONSTRUCTION WORK. <br />17. VERIFY EXISTING TRAP IN ALL CONDENSATE PIPING LOCATED AT AIR HANDLING UNITS. SLOPE <br />CONDENSATE LINES 1/8" PER FOOT. CONDENSATE LINES SHALL BE PVC SCH. 40. ALL CONDENSATE DRAIN <br />2. SUPPLY, RETURN AND OUTSIDE AIR DUCTWORK SHALL BE EXTERNALLY INSULATED SHEET METAL <br />PIPING SHALL BE PROPERLY SUPPORTED. <br />CONSTRUCTION IN ACCORDANCE WITH LATEST SMACNA STANDARDS. INSULATION SHALL HAVE VAPOR <br />BARRIER AND AN INSTALLED MINIMUM THERMAL RESISTANCE (R) VALUE OF 6.0. ALL EXHAUST DUCTWORK <br />18. ALL MECHANICAL WORK SHALL MEET ALL THE REQUIREMENTS OF THE 2007 FLORIDA BUILDING CODE, <br />SHALL BE UNINSULATED SHEET METAL CONSTRUCTION IN ACCORDANCE WITH LATEST SMACNA STANDARDS. <br />MECHANICAL AND 2009 SUPPLEMENT. <br />ALL JOINTS SHALL BE SECURELY TAPED WITH 3" WIDE GLASS FABRIC TAPE WITH FOSTER 30/35 MASTIC OR <br />EQUAL. <br />19. GUARANTEE; FOR ONE YEAR AFTER DATE OF ACCEPTANCE BY THE OWNER, ALL EQUIPMENT, <br />MATERIALS AND WORKMANSHIP TO BE FREE FROM DEFECT. <br />3. DUCT SHALL BE SECURELY SUPPORTED, HUNG OR SUSPENDED IN ACCORDANCE WITH THE LATEST SMACNA <br />EDITION AND SECTION 603 OF THE 2007 FLORIDA BUILDING CODE, MECHANICAL WITH 2O09 SUPPLEMENT. <br />20. DO NOT CUT STRUCTURAL MEMBERS WITHOUT PRIOR WRITTEN APPROVAL OF THE STRUCTURAL <br />ENGINEER OR ARCHITECT. ARRANGE FOR REPAIRS REQUIRED TO RESTORE OTHER WORK, BECAUSE OF <br />4. ROOFTOP UNIT OUTSIDE AIR INTAKE SHALL MAINTAIN A MINIMUM OF 10'-01, FROM ANY EXHAUST OR <br />DAMAGE CAUSED AS A RESULT OF MECHANICAL INSTALLATIONS. <br />SANITARY VENT THROUGH ROOF PIPING. ALL TRANSFER DUCTWORK LEADING TO REST ROOMS SHALL HAVE A <br />ZERO LEAKAGE BACK DRAFT DAMPER AS SHOWN ON MECHANICAL DRAWINGS. <br />21. FLEXIBLE AND RIGID ROUND DUCT TAKE -OFFS FOR DIFFUSERS SHALL BE THE SAME SIZE AS DIFFUSER <br />NECK, MAXIMUM FLEXIBLE DUCT LENGTH SHALL BE 8'4'. FLEXIBLE DUCT SHALL BE THERMAFLEX TYPE M-KC <br />5. PROVIDE ALL MECHANICAL EQUIPMENT WITH MANUFACTURER'S RECOMMENDED SERVICE AREA <br />OR EQUAL.FLEXABLE DUCT SHALL BE INSULATED FIBERGLASS, R-6, CLASS 1, UL181 LISTED AND COMPLY <br />CLEARANCES. <br />WITH NFPA 90A AND NFPA 90B. <br />6. ALL ROOFTOP UNITS SHALL BE REINFORCED TO WITHSTAND LOCAL WIND LOAD DESIGN. SEE STRUCTURAL <br />22. ALL WALL MOUNTED THERMOSTATS SHALL BE INSTALLED AT AN ELEVATION OF 541, ABOVE FINISHED <br />DRAWING(S) FOR DETAIL(S) /CONSULT WITH BUILDING STRUCTURAL ENGINEER. <br />FLOOR TO THE TOP UNLESS OTHERWISE NOTED ON DRAWINGS. LOCATION OF THE WALL MOUNTED <br />THERMOSTAT SHALL BE COORDINATED WITH OTHER TRADES FOR A NEAT APPEARANCE. FINAL LOCATION <br />7. DUCT SMOKE DETECTORS SHALL BE FURNISHED BY THE FIRE ALARM CONTRACTOR, INSTALLED IN DUCT BY <br />OF THERMOSTAT SHALL BE SUBJECT TO THE APPROVAL OF THE ENGINEER OR HIS REPRESENTATIVE IN THE <br />THE MECHANICAL CONTRACTOR AND WIRED BY THE FIRE ALARM CONTRACTOR. SMOKE DETECTORS SHALL BE <br />FIELD. <br />INSTALLED IN ACCORDANCE WITH NFPA 72, NATIONAL FIRE ALARM CODE; NFPA 90A, STANDARD FOR <br />INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS, 2007 FLORIDA BUILDING CODE, MECHANICAL <br />23. ALL UNITS SHALL BE BALANCED TO WITHIN 10 PERCENT OF THE DESIGN AIR QUANTITY. BALANCE <br />WITH 2O09 SUPPLEMENT AND THE MANUFACTURER'S INSTALLATION IN STRUCTIONS. COORDINATE LOCATION <br />DIFFUSERS AND REGISTERS TO WITHIN 10 PERCENT OF QUANTITIES SHOWN ON DRAWINGS. <br />OF SMOKE DETECTORS WITH FIRE ALARM CONTRACTOR. PROVIDE A VISIBLE/AUDIBLE NOTIFICATION PANEL. <br />MAKE: SYSTEM SENSOR SSK451 OR EQUAL, COMPATIBLE WITH BUILDING FIRE ALARM SYSTEM. <br />24. PROVIDE FLEXIBLE NEOPRENE DUCT CONNECTORS ON THE DISCHARGE AND ENTERING SIDES OF ALL <br />VIBRATING EQUIPMENT TO WHICH DUCTWORK IS ATTACHED. <br />8. IN GENERAL, PLANS AND DIAGRAMS ARE SCHEMATIC ONLY AND SHOULD NOT BE SCALED. <br />25. CONTRACTOR SHALL PROVIDE 3 COPIES OF A TEST AND BALANCE REPORT. AIR BALANCING SHALL BE <br />9. HVAC CONTRACTOR IS RESPONSIBLE FOR ANY ADDED ELECTRICAL COSTS WHICH MAY RESULT FROM <br />PERFORMED BY AN INDEPENDENT TESTING AND BALANCING CONTRACTOR WHICH SHALL BE QUALIFIED AND <br />SUBSTITUTED EQUIPMENT. <br />CERTIFIED BY EITHER ASSOCIATED AIR BALANCE COUNCIL (AABC) OR NATIONAL ENVIRONMENTAL <br />BALANCING BUREAU (NEBB). THIS REPORT MUST BE REVIEWED AND APPROVED BY THE ENGINEER PRIOR <br />10. DUCTWORK INSULATION SHALL BE FOIL FACED FIBERGLASS DUCT WRAP WITH A MINIMUM THERMAL <br />TO THE FINAL INSPECTION. <br />RESISTANCE (R) OF 6.0. INSULATION SHALL HAVE VAPOR BARRIER. INSTALL PER MFR. REQUIREMENTS. <br />26. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL TRADES' INSTALLATION SCHEDULES. <br />11. COORDINATE AIR DEVICE LOCATIONS WITH LIGHTING FIXTURES. <br />COORDINATE WORK SCHEDULE WITH GENERAL CONTRACTOR. <br />12. TURNING VANES SHALL BE PROVIDED IN ALL SUPPLY DUCT RECTANGULAR ELBOWS WITH ANGLES <br />27. WHEN THE INTENT OF THE DRAWINGS AND SPECIFICATIONS IS NOT CLEAR, OR IS CAPABLE OF MORE <br />BETWEEN 15 DEGREES AND LESS THAN 90 DEGREES PER FIG. 2-5 OF THE SMACNA MANUAL. <br />THAN ONE INTERPRETATION, SUCH MATTERS WILL BE BROUGHT TO THE ATTENTION OF THE <br />ARCHITECT/ENGINEER IN WRITING BEFORE THE SUBMISSION OF BIDS. THE ARCHITECT/ENGINEER SHALL <br />13. DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS. DUCTWORK, DIFFUSERS, <br />MAKE CORRECTION OR EXPLANATION IN WRITING. <br />REGISTERS, GRILLES, AND OTHER ITEMS OF THE AIR HANDLING SYSTEM SHALL NOT BE SUPPORTED BY THE <br />CEILING OR CEILING SUSPENSION SYSTEM. <br />28. PLANS AND SPECIFICATIONS ARE INTENDED AS A GENERAL DESCRIPTION OF THE WORK TO BE <br />PERFORMED. ALL ITEMS NOT SPECIFICALLY MENTIONED OR SHOWN, BUT NECESSARY FOR THE <br />14. UNLESS OTHERWISE NOTED, INSTALL DUCTWORK AS HIGH AS POSSIBLE, TIGHT TO BOTTOM OF <br />COMPLETION OF THE INSTALLATION, SHALL BE FURNISHED AND INSTALLED BY THIS CONTRACTOR. THIS <br />STRUCTURE. COORDINATE DUCT ELEVATION WITH STORM LEADERS, WATER PIPING, SANITARY DRAINS AND <br />CONTRACTOR SHALL THOROUGHLY ACQUAINT HIMSELF WITH THE MECHANICAL, ARCHITECTURAL, <br />MAJOR ELECTRICAL CONDUITS. <br />STRUCTURAL AND ELECTRICAL PLANS BEFORE SUBMITTING HIS FINAL BID. NO ADDITIONAL COMPENSATION <br />WILL BE ALLOWED DUE TO THE CONTRACTOR'S FAILURE TO FAMILIARIZE HIMSELF/ HERSELF WITH THE <br />15. CONTRACTOR TO PROVIDE ALL SUPPLEMENTARY STEEL REQUIRED TO SUSPEND MECHANICAL EQUIPMENT <br />PLANS. <br />& MATERIALS. INSTALLATION OF EQUIPMENT SHALL COMPLY WITH MANUFACTURER'S SPECIFICATIONS AND <br />CLEARANCE REQUIREMENTS FOR SERVICING OF EQUIPMENT. <br />MECHANICAL KEY <br />PLAN NOTES: <br />10 UNDERCUT DOOR 1" TO ALLOW FOR TRANSFER OF AIR TO <br />BATHROOM. <br />O2 VERIFY THAT THERE IS AN EXISTING SMOKE DUCT <br />DETECTOR IN THE SUPPLY DUCT. IF THE SMOKE <br />DETECTOR IS NOT INSTALLED, REFER TO MECHANICAL <br />GENERAL NOTE # 7. THE GC SHALL BE RESPONSIBLE FOR <br />COORDINATING THE EXACT SCOPE OF WORK REQUIRED <br />BETWEEN THE MECHANICAL SUB AND THE ELECTRICAL <br />SUB PRIOR TO BIDDING. NO CHANGE ORDERS WILL BE <br />APPROVED FOR FAILURE TO VERIFY EXISTING <br />CONDITIONS OR COORDINATE BETWEEN SUBS, <br />30 CEILING MOUNTED BATHROOM EXHAUST FAN. <br />COORDINATE EXACT LOCATION OF PENETRATION WITH <br />ARCHITECTURAL PLAN. INSTALL GALVANIZED DUCT <br />WORK DOWN FROM GRAVITY ROOF VENT. SIZE OF DUCT <br />TO MATCH SIZE OF GRAVITY ROOF VENT OPENING. RUN <br />DUCT IN CEILING/JOIST SPACE AND CONNECT TO CEILING <br />MOUNTED EXHAUST FAN PER MANUFACTURERS <br />RECOMMENDATIONS. <br />REFER TO SPLITTER DETAIL ON THIS SHEET. INSTALL <br />SPLITTER BELOW UNIT IN CEILING SPACE. CONTRACTOR <br />TO INSTALL AT AN ELEVATION ENSURING THE LEAST <br />AMOUNT OF OFFSETS AND DEVIATIONS IN THE DUCT <br />WORK. <br />05 RELOCATE EXISTING THERMOSTAT SUPPLIED IN SHELL <br />PROJECT TO LOCATION SHOWN. <br />© SUPPLY AND RETURN DUCT SIZE UP TO THE RTU SHALL <br />BE THE SAME AS THE UNIT OPENING. <br />FAN SCHEDULE <br />EXT. STATIC <br />MARK <br />SERVICE <br />CFM <br />PRESSURE (IN. <br />FAN TYPE <br />DRIVE <br />SONES <br />WATTS <br />RPM <br />V/0 <br />MANUFACTURER <br />MODEL <br />NOTES <br />WATER) <br />EF-1 <br />EXHAUST <br />1 100 <br />0.375 <br />CEILING <br />DIRECT <br />1 3.2 <br />1 98 <br />1 1100 <br />1 120/1 <br />1 COOK <br />GC-144 <br />1,2 <br />NOTES: <br />1. WITH PLUG-IN DISCONNECT. <br />2. PROVIDE CONTROL BY MANUAL LIGHT WITH OCCUPANCY SENSOR. COORDINATE WITH ELECTRICAL DRAWINGS FOR LOCATION OF SWITCH. <br />OUTSIDE AIR CALCULATION <br />AREA <br />PEOPLE / 1,000 <br />CFM / <br />CFM /SQFT <br />CFM <br />CFM <br />AREA SERVED <br />(SQFT) <br />(SQFT) (1) <br /># PEOPLE <br />PERSON (1) <br />(1) <br />CALCULATED <br />SUPPLIED <br />B8 <br />1,200 <br />- <br />0.3 <br />360 <br />360 <br />(1) PER TABLE 403.3 - FLORIDA BUILDING CODE - MECHANICAL 2007 <br />(2) BALANCE OUTSIDE AIR OF EXISTING RTU TO QUANTITY SHOWN <br />GRAVITY ROOF VENT SCHEDULE <br />THROAT <br />TYPE <br />CFM <br />SERVICE <br />MANUFACTURER <br />MODEL <br />NOTES <br />SIZE <br />GRV-1 <br />100 <br />EXHAUST <br />0.394 <br />COOK <br />PR 8 <br />1,2 <br />NOTES: <br />1. PROVIDE MANUFACTURER'S ROOF CURB. COORDINATE WITH ROOF TYPE. <br />2. PROVIDE INSECT SCREEN. <br />AIR DEVICE SCHEDULE <br />TAG <br />MFG./CAT. # <br />TYPE <br />NECK <br />FRAME <br />FINISH <br />NOTES <br />0-125CFM = 6" RND <br />12x12 <br />130 -150 CFM = 6" RND <br />A <br />TITUS - TMS-AA <br />CD <br />160 - 275 CFM = 8" RND <br />BAK. WHT. ENAMEL <br />1,2,3,4,5 <br />280 - 390 CFM =10" RND <br />24 x 24 <br />400 - 600 CFM =12" RND <br />B <br />TITUS - 50F <br />I RAR <br />22 x 22 (MAX 1280 CFM) <br />24 x 24 <br />BAK. WHT. ENAMEL <br />1,2,4,E <br />DEVICE TYPE LEGEND: <br />CD = CEILING DIFFUSER <br />RAR = RETURN AIR REGISTER <br />EAR = EXHAUST AIR REGISTER <br />SAG = SUPPLY AIR GRILLE <br />NOTES: <br />1. PROVIDE CEILING DEVICES WITH PROPER FRAME STYLE TO MATCH CEILING TYPE AS CALLED FOR BY <br />ARCHITECT. <br />2. DEVICES SHALL BE PROVIDED WITH FACTORY FINISH. <br />3. CEILING DIFFUSERS SHALL BE 4-WAY THROW UNLESS NOTED OTHERWISE OR SHOWN ON PLANS WITH <br />DIRECTIONAL ARROW(S). <br />4. IF NECESSARY, PROVIDE TOP HAT FOR GRILLES REGISTERS AND DIFFUSERS. <br />5. PROVIDE EQUALIZING GRID (TITUS MODEL EG). FOR DIFFUSERS TAPPED DIRECTLY FROM BOTTOM <br />OF DUCT, PROVIDE OPPOSED BLADE DAMPER (TITUS MODEL D-57). <br />6. PROVIDE OPPOSED BLADE DAMPER FOR REGISTERS. <br />TYPICAL SEQUENCE OF OPERATION <br />THE A/C UNIT SHALL BE STARTED AND STOPPED FROM A ROOM THERMOSTAT. ON A CALL FOR <br />COOLING, THE THERMOSTAT SHALL ENERGIZE THE COMPRESSOR(S) TO MAINTAIN SET POINT. ON A <br />CALL FOR HEATING, THE THERMOSTAT SHALL ENERGIZE THE ELECTRIC HEAT IN STAGE(S) TO <br />MAINTAIN SET POINT. SUPPLY FAN SHALL RUN CONTINUOUSLY DURING OCCUPIED HOURS. <br />DRAWING INDEX <br />SHEET NUMBER <br />TITLE <br />M101 <br />Mechanical General Information & <br />Floor Plan <br />O <br />Cn <br />C <br />0 <br />E <br />E <br />0 <br />U <br />L <br />co <br />C <br />CO J <br />m m <br />Y <br />CD <br />Ua <br />�J <br />Cu <br />Q; <br />_juO � <br />m J <br />Lu <br />}� J = <br />�ji <br />Q <br />�0_Z <br />U <br />ory <br />C N <br />�P_N <br />_Cu <br />L <br />_0 <br />L"L <br />C <br />0 <br />Cu <br />E <br />L <br />V <br />Cu <br />U <br />Cu <br />w U. <br />J <br />C- � W ^, <br />H C <br />w c <br />w <br />o <br />, <br />o <br />z <br />rn <br />p <br />W <br />U <br />coo <br />CD <br />z <br />N <br />w <br />N <br />F <br />U <br />0 <br />0 <br />U <br />5 Ceiling Diffuser Runout Detail m 101 <br />Scale: None <br />