WF-=-FF �o RoaF i=� <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-16 <br />ZONE 1 = 58.00 PSF (88.00) <br />ZONE 3 = 66.50 PSF (76.50) <br />ZONE 2e = 88.50 PSF (76.50) <br />ZONE 3e = 76.60 PSF (86.60) <br />ZONE 2n -76.60 PSF (8660) <br />ZONE 3r = 91.70 PSF (101.70) <br />ZONE 2r = 76.60 PSF (SiISO) <br />"A"- 4'-0' END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />EXPOSURE CATEGORY: "C" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT: */-0.18 <br />ROOF DMPHPAGM <br />FOR ASPHALT SHINGLE ROOF USE MIN IQ=STRLUCTURAL SHEATHING <br />EXP 1 (40120), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN. <br />19132" STRUCTURAL SHEATHING EXP 1 (4020).(SEE TABLE FOR FIELD <br />AND EDGE SPACING) SEE DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SHANK GUN <br />NAILS 0 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS WIN W OF <br />GABLE END. <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />SIZE <br />HEAD <br />LENGTH <br />CIA <br />TENSILE STR. <br />SHANK <br />ASTM <br />10d <br />RING SHANK <br />212' <br />0,131 <br />F1667 <br />170,000 <br />RING <br />(16-20 RINGS <br />RSRS-03 <br />Bd <br />RING SHANK, <br />2 3/8' <br />0.113 <br />F1687 <br />SCREW SHANKPER <br />INCH) <br />RSRS-01 <br />8d <br />RING SHANK <br />PNEUMATIC <br />2 3/8" <br />0.113 <br />F1667 <br />SCREW-NALS <br />RSRS-01 <br />EXTERIOR SHEATHING <br />USE 1Y1" CDX OR 7/16" O.S.B. PLY WITH Sd RING SHANK GUN NAILS AT 4" <br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOPS <br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT 8" O C. AT <br />INTERMEDIATE SUPPORTS OR 7116" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />ROOF SHEATHING ATTACF®rOfi SPACM <br />ZONE 1'. Iod NAILS 04. <br />O.C. ON EDGE AND B' O.C. IN FIELD <br />ZONE 2e, 21, 21 1od NAILS @ 4" O.C. ON EDGE AND C O.C. INFIELD <br />ZONE 3,3e, 3, Tod NAILS ® 4" O.0GE . ON EDGE AND 4" O.C. IN FIELD <br />IPgM ROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7.16 <br />M RMG SHMlK GUN NA 04 OC <br />TOP A BOTTON EJX£S <br />0� <br />�o <br />�o <br />3' <br />8 <br />J <br />z <br />tag <br />TYP. EXT. SHEATHINGATTACHMENT <br />RAFTER OR TRUSS <br />ROOF SHEATHING <br />O 0 <br />)v BUILDING LENGTH U <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />NOTE: GABLES -DROP GABLE END 8 (1)ADD-DROPPED <br />TRUSS 2.4 02 SYP OUTLOOKER RAFTER W BLOCKING <br />18"O.C. IF NO DROPPED GABLE END, ATTACH 2x4 02 SYP <br />BLOCKING N 16" O.C. FIRST 4 BAYS W (2)12d NAILS EA <br />END. ATTACH ROOF SHEATHING TO RAFTERS 21 <br />BLOCKING PER NAILING SCHEDULE <br />10d RING SHANKGUN NAILS <br />SEE "ROOF SHEATHING ATTACHMENT' <br />TABLE FOR FIELDS PACING \ <br />N8 2" DECK SCREWS M 6"A" O.C. MAX <br />EDGES 8 12" O.C. MAX IN FIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING ` <br />TYP. 3/4" TBG SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES. <br />ALL AGGREGATE USED IN CONCRETE WALL CONFORM TO ASTM C33fC33M. MA)OMUM AGGREGATE SZE STALL BE VIr <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION MATH JOB SPECIFICATIONS AND <br />WOOD. <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />PROVIDE 6%AR ENTRAINED CONCREfEEXP05®TO EARTH ORNFATHBt <br />NOWBEARING WOOD WALLS TOP PLATES 8 STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON <br />ON STRUCTURAL DRAWINGS APPLICABLE BUILDING CODE STANDARDS'. FBC4R 2020, 7th EDITION <br />ALL OF CONCRETE ARE TO BE CFMAFERE0311'. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PIN_ NO. 2 OR BETTER Fb - 1100 PSI ANDA MODULUS OF <br />FOR STRUCTURAL CONCRETE, TMS 402/802-18 ANSI SPECIFICATION FOR THE DESIGN OF <br />PROW OE 84NL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEYBRAEUOERILL &LABSONGROlH1 WIEEINpCATEOON <br />ELASTICITY = 1,400.000 PSI. ALL WOOD IN CONTACT WI CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 ANDAISC SPECIFICATIONS <br />DRAWINGS - MS LAPPED 61NCHES ANDGFMH7 NATM /OFfSIYE TAPE <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORMWORK <br />SHALL BE RATED TO RETENTION LEVELS OF 0,25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISOOIUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 POT FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH AG 347 LATEST <br />N DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITIOWRECOMMENDED PRACTICE FOR CONCRETE FOR AWORK. <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAW NGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PUNS; <br />MINIMUM NAIUNG PER FBCR 2020, 751 EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTU7ALDEPENDIW <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND MOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REOURED BUT ARE BY OTHERS. <br />SYP 82. <br />IS COMPLETE. IT IS THE CONTRACTORS RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SMALL NOT BE INDIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WEL�O . <br />AT BEARING LOCATIONS W THOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK TIE -DES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, CAWS ORR TIE-W W15. <br />WELDED WRE MESH, SHALL BE ASTM AT OWA1064M, GRADE 65 AND BE PLACED IN ACCORDANCE WTH THE <br />�D ���5' <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />AV TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />BE SUPPORTED WTH 2' CHAIRS SPACED 3'-0' OCT EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS S FOR <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BV THE NFPA. TRUSS DESIGNS SHALL BE SIGNED ANO <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0. 038' AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />RESAR SHALL BE ASTM A815A615M GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />MEETING THE REQUIREMENTS OF ASTM A446/A446M, GRADE A, AND SHALL BE HOT4DPPED GALVANIZED. <br />DESIGN LOADS: <br />W1 THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE AG STANDARDS AND SPECIFICATIONS <br />DESIGN FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE NTH TPI-14, "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWNGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />STANDARDS FOR METAL-PLATECONNECTEDYVOOD TRUSS CONSTRUCTION', AND 'SCSI LATEST EDITION <br />ROOF'. LIVE LOAD FLOOR: UVE LOAD 40 pd <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEERS <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />20 pd TOP CHORD nonranwner4 <br />REVIEW <br />TYP. MIN LAPS SHALL BE AS FOLLOWS. 04 BAR - 25" 06 BAR - 36" <br />WOOD TRUSSES. <br />10 pef BIM CHORD nanconou-t <br />e5 BAR - W 97 BAR - 42" <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 36'x 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIEDTO EACH BEAM REBAR SEE DETAILS <br />LOCATIONS WTH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE NTH ANSUASCE 7 88: 1990. <br />15 pd TOP CHORD 20 pBf TOP CHORD <br />(7 pd W ASPHALT SHINGLES) (10 pd vA ND GVPCRETE) <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURERS INSTRUCTIONS, <br />10 P-f BTM CHORD - 5 pd BIM CHORD <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST VIAND UPLIFT. loped <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAW TUGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 Pd <br />WALL. <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 PSI <br />HIND DEAD LOAD SPEED=10) MPH GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF 8 FLOOR LAYOUTS PROVIDED ON THESE PUNS ARE TO BE USED AS A GUIDE FOR BEARING <br />SURE C, RI <br />(ASCE 7-16 ABBE R2020) EXPOSURE C, RISK CATEGORY II) <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES VWIEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY 8 ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LIVE LOADS: UNINHABITABLE ABIABLE ATTIC WITHOUT STORAGE: WTM LIMITED <br />LAYOUT, SPANS 8 ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />3ATTIC <br />WTH FIXED STAIRS <br />STORAGE: 20pIf, HABITABLE ATTICS AND ATTICS SERVED WTH FIXED STAIRS: 30pd, BALCONES (EXTERIOR) <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS: 40pd, GUARDS AND HIANDRAILS. 20000, GUARD IN -FILL COMPONENTS: 50pef PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES50psf, ROOMS OTHER THAN SLEEPING ROOM: 40PW, SLEEPING ROOMS: 3OPd, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAW NGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40pd <br />MASONRY- <br />PLAN SHOW NOCOMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WTH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW; <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED TRUSS ENGINEER. <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL BLOCK WALLS SHALL BE TWOCELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />HE T ST <br />TTRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCOM THOSE <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BV THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WTH ASTM CAD, GRADE f = 2000 PSI. BLOCK SHALL BE PLACED USING <br />NENT <br />OF THE DELEGATED TRUSS ENGINEER. VIAND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-18 RESPONSIBLE FOR <br />AND CLADDING HIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAW NOS SUBMITTED W THOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAW NGS IN THE FORM <br />RUNNING BOND UNLESS OTHERW SE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CONTRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN FROM THE ENGINEER. ALL INSTANCES, THE CONTRACT <br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />RN THE SHOP D <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />L <br />SPECIFICALLY NOTED OTHERWISE FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BEE PLACED N A SLUMP OF 8" TO 10'. USE ONLY MECHANICAL VIBRATION <br />ATI <br />TO CONSOLIDATE GROUT. <br />FOUNDATIOW SITE PREPARATION' <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 pef, FOOTING <br />TYPE 'M"OR'S'MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SUBGRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE SHALL BE 34W THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERM NED IN ACCORDANCE WTH ASTM D-1557. TREATALL CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GE -TECHNICAL ENGINEERS REQUIREMENTS SHALL BE RECOMPACTED AND RETESTED AT THE <br />CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH ENGINEER. <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS <br />2.500 P31 REGULAR WEIGHT FOR FOOTINGS, AND SLABONGRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5- STRUCTURAL TERRACE SLAB, <br />CCNTRM.TOR SHALL SUBMT PROPOSED MX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED F d- PRIOR TO THE ADDITION OF PLASTICIZER <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C9NC9411 OR MEASURING, MANG. TRANSPORTING, <br />ETC. CONCRETE TICKETS SHALL BE TIMESTAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM W-EN <br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES, IF FORANY REASON <br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT 9 1L <br />BE THE PESPONSIBUTY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE WTH THE ABOVE <br />REQUIRED CONCRETE COVERAGE OVER REBAR SWILL E AS FOLLOWS <br />A T FOR CONCRETE CAST AGAINST AND PERMANBNRY E(POS® TO EARTH FOLMM11 NS) <br />B FOR CONCRETE EXPOSED TO EARTH ADOR WEATHER <br />1-1(! FOR 05 AND SMA19R <br />Z FOR MI6 ARID LARGER <br />C. FOR CONCRETE NOT EVOSED TO WEATHER <br />3/4' FOR SLABS, WALLS AND JOISTS <br />1-10* FOR BEAR AND COI.UAN PRIMARY PEINFOPCBAENT, TIES STIRRRPS <br />FILL CMU CELLS SOLID NTH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS ANCOR VERTICAL <br />REINFORCING. <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS), U.N.0 <br />STRUCTURALSTEEL- <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A38/A38M, FY = 38 ku FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM <br />A500/ASOOM, GRADE B, Fy - 46 kw. STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE 8, TYPE E OR S, Fy = <br />351mi. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WTH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM F3125F3125M BOLTS WTH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURNOFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. JAOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK FASTENERS <br />FASTENER <br />APRIGTp1 <br />YZE <br />ivPE <br />REMMK <br />MASOruRawcro <br />NRY ICONIC <br />c°BEH�Roa.ccu <br />° OTC <br />T I.eornr <br />STEFHi <br />° pC <br />EBBED. �Eronsr, <br />117EDGEDI3T <br />SOD. AL EXL DOORS <br />a IT SEE-1tt?LONG. <br />CFSE HAlABI®COx <br />e'OC <br />SIAOGBWEO <br />Ww0ONv0DIXtl FASTER® <br />iMORMeOMv,WNC <br />GARAGE DOIXR a°% <br />TO RMSOMV/NNC <br />�'Q°� <br />xSt=m <br />EFPAN&ON BOIi <br />IB'OA'IBT 01A) <br />2°-OC 11?OV.1 <br />O °'@DOSi. <br />BEpGEOmT <br />wwoow Bxx <br />c.sEnwoaEocox <br />B-oc <br />wwoow0ooru PASTENm <br />WE-- <br />CONTACT THIS ENGINEER <br />FOR SPACING <br />1. PT. SEENOLEe <br />HALT Ia La+G <br />S_.m <br />iN*oµ soFn.rcnBc <br />nsoNRrlcoNc <br />REQUIREMENTS <br />- E%T WOR <br />BUCK 2F PT, SEE-1 NO WA9RB1 FASTFBt - /:-EDGE OiBT <br />WwDOWe.1G 01118-21A- 0-OiC <br />PT TO STEEL NL. SEE WA�1fA ST GGEREO , <br />NOTES <br />NOW <br />II STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND/OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS HIDE OR W DER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWIG DOOR WITH A WOOD DOOR FRAME. tx MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED W TAPCONS OR PAF TO THE SUBSTRATE. <br />L441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 401-77445078 <br />FAX: 407-774.4078 <br />www.abdeo4Mmup.com <br />L AA x: 0003325 J <br />g <br />i <br />sO <br />v <br />R <br />st sDly. all HAT <br />ABBOTT PARK <br />LOT #45 <br />BLK 7 <br />PRO TO <br />0418 . 00-4 071 <br />MODZU <br />4EHB <br />"2605-HAYDEN" <br />GARAOs OWDM: <br />RIGHT <br />PALM <br />DETAILS <br />60 MPH EXP. <br />Q�4 <br />mm" <br />Dw M 09/22/21 <br />sOALL': 1/4-=1'-0" <br />9193IM' <br />S N1 <br />