ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to centered line of the box to be: 16" AFF <br />(general). In a Flood Zone, all electrical equipment to be at or above DFE. <br />kitchen 44" AFF <br />bathroom 39" AFF <br />laundry room 36" AFF <br />exterior waterproof 12" AFF <br />garage general purpose 44" AFF <br />range 2" AFF <br />2. All trim plates & devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance With the <br />national electric code, latest edition, by a licensed electrical contractor who shall be responsible for the <br />installation & sizing of all electrical, Wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the <br />branch circuits in all dwelling units per NFPA 70 and the 2014 NEC. <br />7. Provide Tamper Resistant Receptacles as required by the 2014 NEC. <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling <br />units in accordance With FBC R315 and NFPA 70. Such devices shall be listed by the appropriate <br />standard, either ANSI/UL 2034, standard for single and multiple station cc alarms or UL 2075, gas and <br />vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and <br />labeled by a Nationally Recognized Testing Laboratory, <br />10. Keep all smoke detectors minimum of 36" from bathroom doors <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and <br />shall be equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffits <br />is not acceptable. <br />13. All doors and windows providing direct access from the home to the pool shall be equipped with an <br />exit alarm complying With UL 2014 that has a minimum sound pressure rating of 85 DBA at 10 feet, and <br />either hardwired or of the plug-in type. The exit alarm shall produce a continuous audible warning <br />when the door or window are opened.. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed <br />within 6' of the outside edge of a sink. This would include the receptacle installed for a washing <br />machine. Receptacles outlets shall not be required on a wall directly behind a range or sink to fulfill the <br />requirement for an outlet every 24". The width of the sink or range is not to be included in the spacing <br />of the outlets unless the distance from the sink or range is greater the 12" for straight counter tops and <br />18" for sinks and ranges installed in corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />Fpc <br />DUPLEX OUTLET ABOVE COUNTER <br />QwP <br />WEATHERPROOF DUPLEX OUTLET <br />0GFI <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />13 <br />THREE-WAY SWITCH <br />?4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />LED <br />LED CEILING MOUNTED LIGHT FIXTURE <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />+PC <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />O <br />EXHAUST FAN <br />'Iwo <br />EXHAUST FAN/LIGHT COMBINATION <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />[Eg <br />PUSH BUTTON SWITCH (OPTIONAL) <br />HD <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />® <br />CARBON MONOXIDE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />® <br />TELEVISION (OPTIONAL) <br />® 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />��� <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G J <br />OPT. CEILING FAN <br />69 <br />(1) PHONE LINE, (1) DATA PORT <br />200A INDOOR PANEL <br />NEMA1 <br />200 AMP <br />#14 copper to lights & outlets <br />#12 copper to 20 amp ckta <br />#10.2 copperto WH <br />0103 copper to Dryer <br />n <br />w <br />oraro sER au <br />200 amp <br />150 amp <br />Disconnect <br />POWER CO. FEED <br />INTERSYSTEM <br />4 Bare Cu Ground <br />BONDING <br />#4 GROUNDING WIRE <br />TERMINATION PER <br />WITH CODE APPROVED <br />NEC 14, 250.94 <br />CLAMP PER 250.50 AND <br />250.52 OF THE 2014 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram (Updated 7-1-14) <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70 - 2014, LOCAL CODES AND THE LOCAL POWER CO. <br />r------------------------------------------------------ <br />f <br />I <br />I <br />t <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />L— — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />UPPER FLOOR ELECTRICAL PLAN <br />SCALE:1/4'=1'-0" <br />0 <br />0 <br />N <br />sr <br />CD <br />To the best of the Engineer's knovAedge, information and belief, <br />the structural plans and specifications contained wihn these <br />drawings comply with the 2017 <br />Florida Building Code <br />- <br />Residential Oth Edition. Engineers signature and seal <br />Is only for <br />the structural engineering potions of the drawing papas bearing <br />Engineers signature and seal. <br />� <br />E <br />V <br />Lo <br />J <br />CCMr1 N0 0) LL <br />Cn <br />°f rr�IaJ <br />_(D <br />IJL LL a <br />LL <br />�LL a <br />00 Z <br />�tnCD 0 0 o <br />0CS <br />W <br />moo <br />co `��`r <br />Z <br />�, CL <br />Oti9NoG� <br />SMZ <br />Z <br />Nwc <br />O J <br />❑❑❑ <br />W <br />Ur <br />z <br />z <br />Q <br />rL <br />Q1z <br />.c <br />U' LL <br />U <br />� <br />O <br />N <br />c <br />U <br />• <br />o <br />CID <br />W <br />a <br />Q <br />CL o <br />U <br />_ 2 <br />Ni <br />o< <br />r <br />W Z <br />r0 <br />a) <br />' 0 <br />N <br />O� <br />Z <br />� J <br />i7 a <br />g <br />>: <br />Wa <br />C 3 <br />fi <br />LL <br />Z <br />=G <br />�_ <br />CC)oo <br />� <br />y <br />2I� <br />it <br />U <br />r <br />121 <br />= <br />> (y <br />CC <br />� <br />W <br />�-- <br />0o <br />T <br />Q <br />C <br />CD <br />00 <br />a <br />Q <br />7'! <br />O O <br />Q <br />00LID <br />00 <br />.� <br />N <br />E <br />C` T <br />04 <br />o <br />Z <br />cc <br />E Q <br />H <br />•' <br />` <br />ro <br />a. <br />E <br />a <br />v w3 <br />¢ o <br />c <br />JOB <br />NO: <br />20-3569 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />4.1 <br />