ELECTRICAL SPECIFICATIONS <br />A. THE WORK. APPARATUS AND MATERIALS WHICH SHALL BE FURNISHED UNDER THESE SPECIFICATIONS <br />AND ACCOMPANYING DRAWINGS SHALL INCLUDE ALL ITEMS SPECIFIED HEREINAFTER AND SHOWN ON THE <br />DRAWINGS. ALL OTHER MATERIALS NECESSARY FOR THE COMPLETE INSTALLATION SHALL BE FURNISHED <br />AND INSTALLED BY THE CONTRACTOR. CONTRACTOR TO PROVIDE COMPLETE ELECTRICAL SYSTEMS AS <br />INDICATED ON THE DRAWINGS AND AS SPECIFIED HEREIN. <br />B. THE CONTRACTOR SHALL EXTEND THE SERVICE FROM THE POINT OF SERVICE ATTACHMENT <br />FURNISHING ALL PROTECTIVE DEVICES, CONDUCTORS, SUPPORTS, RACEWAYS, ETC. TO PROVIDE <br />COMPLETE INTERIOR ELECTRICAL SYSTEMS TO SERVE MOTOR LOADS, LIGHTING LOADS AND <br />MISCELLANEOUS ELECTRICAL LOADS, AS SHOWN ON THE DRAWINGS AND AS SPECIFIED HEREINAFTER. <br />THE WORK SHALL INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING AT THE COMPLETION OF <br />THE WORK AND MAKING ANY MINOR CONNECTION CHANGES OR ADJUSTMENTS NECESSARY FOR THE <br />PROPER FUNCTIONING OF THE SYSTEM AND EQUIPMENT. ALL WORKMANSHIP SHALL BE OF THE HIGHEST <br />QUAUIY AND NO SUBSTANDARD WORK WILL BE ACCEPTED. <br />C. VERIFY CONDITIONS AT THE FIELD PRIOR TO PRICING THE JOB. CONTRACTOR SHALL VISIT THE SITE <br />AND FAMILIARIZE HIMSELF WITH ALL DETAILS OF THE WORK AND EXISTING CONDITIONS. <br />D. CONTRACTOR SHALL REFER TO INTERIOR ARCHITECTURAL DRAWINGS FOR EXACT MOUNTING HEIGHTS <br />AND/OR LOCATIONS OF ALL LIGHTING FIXTURE SWITCHES, OUTLETS AND WIRING DEVICES AND SHALL <br />PERFORM ALL WORK NOTED ON PLANS, IN NOTES OR IN DETAILS RELATED TO ELECTRICAL <br />CODES <br />A. THE WORK UNDER THE REQUIREMENTS OF THESE SPECIFICATIONS SHALL BE IN <br />CONFORMANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE. <br />THE INSTALLATION SHALL ALSO COMPLY WITH ALL APPLICABLE RULES AND <br />REGULATIONS OF LOCAL AND STATE LAWS AND ORDINANCES, <br />INTERFERENCES <br />A. THE PLANS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL COORDINATE THE WORK <br />WITH THE DIFFERENT TRADES SO THAT INTERFERENCES BETWEEN CONDUITS. PIPING, EQUIPMENT, <br />ARCHITECTURAL AND STRUCTURAL WORK WILL BE AVOIDED. ALL NECESSARY OFFSETS IN RACEWAYS, <br />FITTINGS, ETC. REQUIRED TO PROPERLY INSTALL THE WORK SHALL BE FURNISHED SO AS TO TAKE UP A <br />MINIMUM SPACE, AND ALL MATERIALS REQUIRED TO ACCOMPLISH THIS SHALL BE FURNISHED AND <br />INSTALLED BY THE CONTRACTOR WITHOUT ADDITIONAL EXPENSE TO THE OWNER. IN CASE INTERFERENCE <br />DEVELOPS, THE OWNER'S AUTHORIZED REPRESENTATIVE WILL DECIDE WHICH EQUIPMENT, PIPING, ETC., <br />MUST BE RELOCATED, REGARDLESS OF WHICH WAS INSTALLED FIRST. <br />MATERIALS <br />A. IN GENERAL, MATERIALS AND APPARATUS SHALL COMPLY WITH ALL APPLICABLE TESTS, RATINGS, <br />SPECIFICATIONS, AND REQUIREMENTS OF THE IEEE AND NEMA AND SHALL BEAR THE APPROVED DEVICE <br />LABEL OF THE UNDERWRITERS' LABORATORIES, INC. <br />B. ANY MATERIAL OR PRODUCT SPECIFIED HEREIN OR ON THE DRAWINGS BY MANUFACTURER AND <br />CATALOG NUMBER AFTER WHICH THE TERM "OR EQUAL" DOES NOT APPEAR SHALL BE INTERPRETED AS <br />LIMITING SUCH ITEMS BY A PREDETERMINED SELECTION AS STATED. IN SUCH INSTANCES NO <br />SUBSTITUTIONS WILL BE ALLOWED. ANY MANUFACTURER AND CATALOG NUMBER FOLLOWED BY THE TERM <br />"OR EQUAL" SHALL BE INTERPRETED TO MEAN EQUAL IN QUALITY, VALUE, AND INTEGRAL PROPERTIES <br />AND SIMILAR IN APPEARANCE, DESIGN, AND FUNCTIONS. THE CONTRACTOR MAY IN THESE INSTANCES <br />AFTER OBTAINING WRITTEN APPROVAL OF THE OWNER, SUBSTITUTE MATERIALS OR PRODUCTS OTHER <br />THAN THE ONE NAMED. <br />C. THE CONTRACTOR SHALL SUBMIT A LIST OF PRINCIPAL MATERIAL ITEMS, GIVING MANUFACTURER'S <br />NAMES AND CATALOG NUMBERS. APPROVAL OF THE LIST SHALL BE OBTAINED FROM THE OWNER <br />BEFORE ORDERS ARE PLACED. <br />GUARANTEE <br />A. CONTRACTOR SHALL GUARANTEE ALL WORK FOR A PERIOD OF ONE YEAR FROM DATE OF <br />SUBSTANTIAL COMPLETION. CONTRACTOR SHALL RECTIFY ANY DEFECTS DUE TO FAULTY MATERIALS OR <br />WORKMANSHIP AND PAY FOR ANY DAMAGE TO OTHER WORK RESULTING THEREFROM WITHIN SAID <br />PERIOD. THE OWNER WILL GIVE NOTICE OF DEFECTS WITH REASONABLE PROMPTNESS. <br />IDENTIFICATION OF EQUIPMENT <br />A. IDENTIFICATION OF EQUIPMENT SHALL BE PROVIDED FOR ALL ELECTRICAL EQUIPMENT INSTALLED BY <br />THE CONTRACTOR. ENGRAVED LAMINATED PLASTIC NAMEPLATES SHALL BE PROVIDED AND IDENTIFICATION <br />SHALL CLEARLY DESCRIBE THE EQUIPMENT AND FUNCTION. COORDINATE NAMES ABBREVIATIONS AND <br />OTHER DESIGNATIONS USED IN ELECTRICAL IDENTIFICATION WORK WITH CORRESPONDING DESIGNATIONS <br />SHOWN, SPECIFIED OR SCHEDULED. PROVIDE NUMBERS, LETTERS AND WORDING AS INDICATED OR IF NOT <br />OTHERWISE INDICATED, AS RECOMMENDED BY MANUFACTURER OR AS REQUIRED FOR PROPER <br />IDENTIFICATION AND MAINTENANCE OF ELECTRICAL SYSTEMS AND EQUIPMENT. <br />B. INSTALL LABEL TAGS ON ALL WIRE AND CABLE IN JUNCTION BOXES, WIREWAYS AND WIRING GUTTERS <br />OF PANELS. TAGS SHALL IDENTIFY WIRE OR CABLE CIRCUIT NUMBER AND/OR EQUIPMENT SERVED AS <br />SHOWN ON DRAWINGS. <br />C. ALL JUNCTION BOXES TO BE DESIGNATED WITH PERMANENT MARKER INDICATING PANELBOARD AND <br />CIRCUIT NUMBERS OF BRANCH CIRCUIT WIRING CONTAINED WITHIN. <br />D. PANELBOARD DIRECTORIES SHALL BE UPDATED/TYPEWRITTEN WITH ACCURATE AND CURRENT <br />INFORMATION BY THE CONTRACTOR AT THE END OF CONSTRUCTION. DIRECTORIES SHALL REFLECT <br />EXISTING UNCHANGED AND NEW RECORD CONDITIONS AND INCLUDE CIRCUIT NUMBER, TENANT NAME, <br />TYPE AND LOCATION OF LOAD. <br />RACEWAYS AND FITTINGS <br />A. CONDUITS RUN EXPOSED ON EXTERIOR OF THE BUILDING OR BELOW GRADE SHALL BE RIGID STEEL <br />CONDUIT. SCH 40 PVC CONDUIT IS ACCEPTABLE BELOW GRADE PROVIDED RIGID STEEL CONDUIT ELBOWS <br />AND RISERS ARE USED. <br />B. ALL CONDUIT SHALL BE PROPERLY ALIGNED, GROUPED AND SUPPORTED. EXPOSED CONDUIT SHALL <br />BE INSTALLED AT RIGHT ANGLES TO OR PARALLEL TO THE PRINCIPAL STRUCTURAL MEMBERS. ALL <br />CONDUIT SHALL BE SUPPORTED AT INTERVALS NOT EXCEEDING 8 FEET. PROVIDE SUPPORT A MINIMUM <br />OF 18" FROM BENDS AND OUTLET BOXES AND ON INTERVALS NOT TO EXCEED 8'-0". CONDUIT <br />IS NOT TO SPAN ANY SPACE UNSUPPORTED. ALL CONDUIT SHALL BE SUPPORTED FROM STRUCTURE <br />AND NOT FROM CEILING SUPPORT SYSTEM. <br />C. PROVIDE NYLON PULL CORD AND LEAVE IN PLACE IN EACH EMPTY CONDUIT. <br />D. THIN WALL CONDUIT: <br />1. THIN WALL CONDUIT SHALL BE UNDERWRITERS' APPROVED GALVANIZED ELECTRICAL METALLIC TUBING. <br />COUPLINGS AND CONNECTORS FOR CONDUIT SHALL BE STEEL HEX —NUT, ZINC OR CADMIUM PLATED <br />SET SCREW TYPE FITTINGS. <br />E. FLEXIBLE METALLIC CONDUIT: <br />1. FLEXIBLE METALLIC CONDUIT IN DRY LOCATIONS SHALL BE UNDERWRITERS' APPROVED, ZINC COATED, <br />SINGLE STRIP TYPE. FITTINGS SHALL BE AS MANUFACTURED BY THOMAS AND BETTS "TITE—BITE", <br />STRAIGHT OR ANGLE CONNECTORS OR APPROVED EQUAL. <br />2. FLEXIBLE CONDUIT IN DAMP OR WET LOCATIONS SHALL BEUNDERWRITERS,APPROVED FLEXIBLE, , <br />LIQUID —TIGHT METAL CONDUIT. FITTINGS SHALL BE AS MANUFACTURED BY APPLETON, CROUSE—HINDS <br />OR THOMAS AND BETTS. <br />F. RIGID STEEL CONDUIT: <br />1. RIGID STEEL CONDUIT SHALL BE UNDERWRITERS' APPROVED HOT —DIP GALVANIZED, ZINC METALIZED. <br />OR SHERADIZED. THE THREADED ENDS OF THE CONDUIT SHALL BE ZINC COATED AND SHALL BE <br />THREADED TYPE. DOUBLE LOCK NUTS SHALL BE USED ON ALL CONDUIT TERMINATIONS EXCEPT <br />THREADED HUBS. <br />2. ALL CONDUIT SHALL BE MADE UP TIGHT AND NO RUNNING THREADS WILL BE PERMITTED, "ERICSON" <br />COUPLINGS BEING USED WHERE NECESSARY. ALL CONDUIT RUNS BELOW GRADE OR UNDER FLOORS ON <br />GRADE SHALL BE GIVEN A HEAVY COAT OF ASPHALTIC TYPE PAINT <br />BOXES <br />A. ALL BOXES SHALL BE RIGIDLY MOUNTED AND SHALL BE EQUIPPED WITH SUITABLE SCREW FASTENED <br />COVERS. OPEN KNOCK —OUTS OR HOLES IN BOXES SHALL BE PLUGGED WITH A SUITABLE BLANKING <br />B. OUTLET BOXES FOR EXPOSED WALL MOUNTING, AND OUTDOOR INSTALLATIONS SHALL BE CAST METAL <br />TYPE "FS" OR "FD" BOXES WITH SUITABLE GALVANIZED SHEET COVERS, OR CAST METAL WEATHERPROOF <br />OR VAPOR TIGHT COVERS WHEN NOTED ON THE DRAWINGS. WEATHERPROOF RECEPTACLE COVERS SHALL <br />HAVE SPRING HINGE LIDS AND IN USE COVERS. <br />CONDUCTORS <br />A. UNLESS OTHERWISE INDICATED, ALL BRANCH CIRCUIT CONDUCTORS SHALL BE NO. 12 AWG. BRANCH <br />CIRCUITS RUN OVER 75 FEET IN LENGTH. MEASURING ONE WAY FROM THE FIRST OUTLET OF THE <br />CIRCUIT TO THE PANEL, SHALL BE NO. 10 AWG FOR THE ENTIRE CIRCUIT <br />B. SPLICES, TAPS AND ATTACHMENT FITTINGS AND LUGS SHALL BE ELECTRICALLY AND MECHANICALLY <br />SECURE AND SOLDERLESS FOR CONDUCTORS SIZES NO. 8 AWG AND LARGER. THERE SHALL BE PLENTY <br />OF SLACK CABLE IN BOXES. OUTLETS AND CABINETS TO INSURE THAT THERE IS NO BINDING AT THE <br />BUSHINGS. ALL LUGS SHALL BE OF THE CORRECT SIZES FOR THE CONDUCTORS JOINED AND IN NO <br />CASE SHALL STRANDS BE CUT FROM A CONDUCTOR IN ORDER TO FIT THE CONDUCTOR INTO A LUG. <br />TAPING OF JOINTS SHALL BE WITH VINYL PLASTIC ELECTRICAL TAPE TO SECURE INSULATION STRENGTH <br />EQUAL TO THAT OF THE CONDUCTORS JOINED. <br />C. ALL CONDUCTORS SHALL BE COPPER. CONDUCTOR INSULATION SHALL BE DUAL TYPE THHN/THWN <br />75 C. (167 F.) FOR DRY, DAMP & WET LOCATIONS. CONDUCTOR INSULATION WITH SINGLE TYPE <br />MARKING THHN 90 C. (194 F.) MAY BE USED FOR DRY LOCATIONS ONLY. ALL CONDUCTORS SHALL BE <br />COLOR CODED AS REQUIRED BY NEC AND FURTHER IDENTIFIED AND CODED AS SPECIFIED HEREINAFTER. <br />COLOR CODING SHALL BE BY MEANS OF COLORED INSULATING MATERIAL, COLORED BRAID OR JACKET <br />OVER THE INSULATION OR BY MEANS OF SUITABLE COLORED, PERMANENT, NON —AGING, INSULATING <br />TAPE APPLIED TO CONDUCTORS AT EACH CABINET OR JUNCTION POINT. THE COLOR CODING SHALL BE <br />ACCOMPLISHED AS THE CONDUCTORS ARE INSTALLED. THE FOLLOWING SYSTEMS OF COLOR CODING <br />SHALL BE STRICTLY ADHERED TO: <br />1) ISOLATED GROUND LEADS: GREEN AND YELLOW <br />2) GROUND LEADS: GREEN <br />3) GROUNDED NEUTRAL LEADS: WHITE FOR 120/208V, GRAY FOR 277/480V <br />4) 120/208 VOLT, UNGROUNDED PHASE WIRES: BLACK, RED, BLUE <br />5) 277/480 VOLT, UNGROUNDED PHASE WIRES: BROWN, ORANGE, YELLOW <br />THE COLOR CODE ASSIGNED TO EACH PHASE WIRE SHALL BE CONSISTENTLY FOLLOWED THROUGHOUT. <br />NOTE: WHERE EXISTING BASE BUILDING COLOR CODING DIFFERS FROM COLOR COOING ASSIGNED <br />HERE --IN. CONTRACTOR SHALL USE EXISTING COLOR COOING AS REQUIRED TO MAINTAIN CONSISTENCY. <br />ADVISE ENGINEER (IN WRITING) OF COLOR CODING TO BE USED. <br />D. ALL WIRING IN CEILING SPACE OR IN AIR HANDLING PLENUMS NOT IN CONDUIT SHALL BE UL LISTED <br />AS SUITABLE FOR PLENUM USE. <br />E. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL CONTRACTOR AND MAKE ALL <br />REQUIRED CONNECTIONS TO SERVE MECHANICAL EQUIPMENT FURNISHED. <br />F. MODIFY EXISTING ELECTRICAL WORK ABOVE THE CEILING SPACE (CONDUIT, WIRING, EQUIPMENT, BOXES, <br />ETC.) TO COORDINATE WITH NEW LIGHTS AND HVAC WORK. <br />G. THE CONTRACTOR SHALL REMOVE ALL EXISTING WIRING AND EQUIPMENT MADE UNNECESSARY BY THE <br />NEW INSTALLATION, ALL MATERIALS REMOVED AND NOT REUSED IN NEW TENANT RETROFIT. SHALL BE <br />RETURNED TO BUILDING STOCK. <br />H. REUSE EXISTING JUNCTION BOXES, CONDUITS AND WIRING TO FEED RECEPTACLES AND LIGHTING <br />FIXTURES WHERE APPLICABLE. REMOVE AND DISPOSE OF ALL UNUSED CONDUIT AND WIRING BACK TO <br />LAST ACTIVE DEVICE OR PANEL, <br />I. ALL CONDUITS AND WIRING PENETRATING RATED FLOORS AND WALLS SHALL BE SEALED TO MAINTAIN <br />FIRE RATING AND INTEGRITY OF SEPARATION. <br />GROUNDING <br />A. THE INTERIOR ELECTRICAL SYSTEMS SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS <br />REQUIRED BY THE NEC AND AS SPECIFIED HEREINAFTER. <br />B. ALL METALLIC RACEWAYS SHALL BE MECHANICALLY AND ELECTRICALLY SECURE AT ALL JOINTS AND <br />AT ALL BOXES, CABINETS, FITTINGS, AND EQUIPMENT. METALLIC RACEWAYS SHALL BE CONNECTED TO A <br />DIRECT GROUND AT THE POINT OF ELECTRICAL SERVICE ENTRANCE AND SHALL BE ELECTRICALLY <br />CONTINUOUS THROUGHOUT THE ENTIRE SYSTEM. <br />C. ALL GROUND CONDUCTORS SHALL BE INSULATED COPPER UNLESS OTHERWISE NOTED. <br />D. ALL RACEWAYS WITH N0. 10 OR 12 AWG PHASE CONDUCTORS FOR RECEPTACLES, LIGHTING FIXTURES <br />AND SIMILAR CIRCUITS (NEW BRANCH CIRCUITS) SHALL BE PROVIDED WITH A PARITY SIZED GREEN <br />EQUIPMENT GROUND CONDUCTOR. GROUND CONDUCTOR SHALL BE INSTALLED IN ENTIRE RACEWAY <br />SYSTEM INCLUDING WALL SWITCHES AND FLEXIBLE CONDUIT TO LIGHT FIXTURES. EQUIPMENT GROUND <br />CONDUCTOR SIZES FOR CIRCUITS WITH PHASE CONDUCTORS LARGER THAN NO. 12 AWG ARE INDICATED <br />ON DRAWINGS. GROUND CONDUCTORS SHALL BE CONNECTED TO GROUND BUSS IN PANELBOARDS. <br />E. TERMINATE FEEDER AND BRANCH CIRCUIT INSULATED EQUIPMENT GROUNDING CONDUCTORS WITH <br />GROUNDING LUG, BUS, OR BUSHING. CONDUCTORS LOOPED UNDER SCREW OR BOLT HEADS WILL NOT BE <br />PERMITTED. <br />F. INSTALL CLAMP —ON CONNECTORS ON CLEAN METAL CONTACT SURFACES TO ENSURE ELECTRICAL <br />CONDUCTIVITY AND CIRCUIT INTEGRITY. <br />G. PROVIDE GROUNDING BUSHING AND A CONTINUOUS COPPER BONDING JUMPER FROM THE BUSHING TO <br />THE EQUIPMENT GROUND BUS IN ALL FEEDERS. THE BONDING JUMPER SHALL BE THE SAME SIZE AS <br />THE EQUIPMENT GROUND CONDUCTOR. <br />CIRCUIT PROTECTIVE DEVICES <br />A. GENERAL: <br />1. UNLESS OTHERWISE INDICATED, PROTECTIVE DEVICES SHALL BE MOUNTED WITH TOP OF CABINET OR <br />ENCLOSURE 6'— 6" ABOVE FINISHED FLOOR, SHALL BE PROPERLY ALIGNED, AND SHALL BE <br />ADEQUATELY SUPPORTED INDEPENDENTLY OF THE CONNECTING RACEWAYS, ALL STEEL SHAPES, ETC., <br />NECESSARY FOR THE SUPPORT OF THE EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY THE <br />CONTRACTOR. UNLESS OTHERWISE INDICATED, ALL BRANCH CIRCUIT PROTECTIVE DEVICES ENCLOSURES <br />SHALL BE NEMA TYPE I, GENERAL PURPOSE TYPE. CIRCUIT PROTECTIVE DEVICES INSTALLED OUTDOORS <br />OR EXPOSED TO THE WEATHER SHALL HAVE WEATHERPROOF ENCLOSURES, NEMA TYPE 3R OR TYPE 4 <br />2. INSTALL DISCONNECT SWITCHES FOR USE WITH MOTOR —DRIVEN APPLIANCES, AND MOTORS AND <br />CONTROLLERS WITHIN SIGHT OF CONTROLLER POSITION UNLESS OTHERWISE INDICATED. <br />3. SUBMIT MANUFACTURER'S DATA (MINIMUM 5 COPIES) ON CIRCUIT AND MOTOR DISCONNECT SWITCHES <br />AND/OR MOTOR STARTERS, SUBMIT SHOP DRAWINGS IN BOOKLET FORM WITH SEPARATE SHEET FOR <br />EACH DEVICE. PROVIDE EQUIPMENT IDENTIFICATION AS DESIGNATED ON PLANS FOR EACH SHOP DRAWING <br />CUT SHEET SUBMITTED. <br />B. CIRCUIT BREAKERS: <br />1. CIRCUIT BREAKERS FOR MOUNTING IN EXISTING PANELBOARD SHALL BE MOLDED PLASTIC CASE, AIR <br />CIRCUIT BREAKER TYPE. BREAKERS SHALL HAVE THERMAL MAGNETIC TRIP UNITS AND MULTI —POLE <br />BREAKERS SHALL HAVE A COMMON TRIP BAR SO THAT THE TRIPPING OF ONE POLE WILL <br />AUTOMATICALLY TRIP ALL POLES OF THE BREAKER. BREAKERS SHALL BE TRIP FREE AND TRIP <br />INDICATING AND SHALL HAVE QUICK —MAKE, QUICK —BREAK CONTACTS. <br />C. SAFETY SWITCHES: <br />1. ALL SAFETY SWITCHES SHALL BE HEAVY DUTY TYPE. SWITCH MECHANISM SHALL BE QUICK —MAKE, <br />QUICK —BREAK. COVER SHALL BE INTERLOCKED WITH MECHANISM TO PREVENT OPENING UNLESS SWITCH <br />IS IN THE "OFF" POSITION. ALL ENCLOSURES SHALL BE PRIMED AND FINISHED TO RESIST RUSTING AND <br />CORROSION. SWITCHES SHALL BE ITE, GENERAL ELECTRIC, SQUARE—D, OR CUTLER —HAMMER. (MATCH <br />BUILDING STANDARD WHERE APPLICABLE) <br />D. FUSES: <br />1. ALL FUSES FOR SWITCHES SHALL BE DUAL ELEMENT, CARTRIDGE TYPE. FUSES SHALL BE BUSSMAN <br />"FUSETRON" OR CHASE SHAWMUT "TRIONIC". THE CONTRACTOR SHALL FURNISH AND INSTALL PROPER <br />SIZE FUSES WHERE REQUIRED FOR ALL FUSIBLE EQUIPMENT AND SHALL FURNISH TO THE OWNER A <br />DUPLICATE CARTRIDGE FOR EACH FUSE INSTALLED. <br />E. MOTOR STARTERS: <br />1 COMBINATION MAGNETIC. FULL VOLTAGE STARTERS FOR 3 MOTORS SHALL BE THREE POLE <br />HORSEPOWER RATED. MAGNETICALLY OPERATED SWITCHES, WITH THREE THERMAL OVERLOAD UNITS AND <br />FOUR EXTRA AUXILIARY CONTACTS. CONTROL VOLTAGE SHALL BE 1 20V. SUPPLIED FROM A CONTROL <br />POWER TRANSFORMER, A THREE POLE HORSEPOWER RATED, NON —FUSIBLE DISCONNECT SWITCH SHALL <br />ALSO BE INCLUDED IN THE ENCLOSURE. AN HOA SWITCH SHALL BE MOUNTED IN FRONT COVER. <br />STARTERS SHALL BE SQUARE—D CLASS 8538. <br />2. MANUAL MOTOR STARTERS FOR 115V., 1 MOTORS (1) HORSEPOWER AND SMALLER, SHALL BE <br />SINGLE POLE, HORSEPOWER RATED SWITCHES WITH THERMAL OVERLOAD UNITS AND HEATERS. <br />STARTERS SHALL BE SQUARE—D CLASS 2510, WITH STAINLESS STEEL COVER PLATES. <br />3. MAGNETIC FULL VOLTAGE STARTERS FOR 3 MOTORS SHALL BE THREE POLE, HORSEPOWER RATED, <br />MAGNETICALLY OPERATED WITH THREE THERMAL OVER LOAD UNITS AND FOUR EXTRA AUXILIARY <br />CONTACTS. CONTROL VOLTAGE SHALL BE 120V. SUPPLIED FROM A CONTROL POWER TRANSFORMER, A <br />HAND —OFF —AUTOMATIC, HOA SWITCH SHALL BE MOUNTED IN FRONT COVER. STARTERS SHALL BE <br />SQUARE—D CLASS 8536. <br />DRY —TYPE DISTRIBUTION TRANSFORMERS: <br />A. ALL TRANSFORMERS SHALL BE DESIGNED FOR HIGH HARMONIC LOADS—ULK-1 3 RATED. <br />B. TRANSFORMERS SHALL HAVE FOUR (4) 2 1/2 PERCENT TAPS, TWO ABOVE AND TWO BELOW <br />PRIMARY VOLTAGE AND UNLESS NOTED OTHERWISE SHALL BE 115C TEMPERATURE RISE ABOVE 40C <br />AMBIENT, <br />C. LIMIT TRANSFORMER SURFACE TEMPERATURE RISE TO MAXIMUM OF SOC RISE ABOVE A 40C <br />AMBIENT. PROVIDE WIRING CONNECTORS SUITABLE FOR COPPER OR ALUMINUM WIRING. <br />CUSHION —MOUNT TRANSFORMERS WITH EXTERNAL VIBRATION ISOLATION SUPPORTS; SOUND —LEVEL <br />RATINGS NOT TO EXCEED 45DB FOR TRANSFORMERS 15 TO 45 KVA AND 50DB FOR 50 TO 150 KVA <br />AS DETERMINED IN ACCORDANCE WITH ANSI/NEMA STANDARDS, ELECTRICALLY GROUND CORE AND <br />COILS TO TRANSFORMER ENCLOSURE BY MEANS OF FLEXIBLE METAL GROUNDING STRAP. PROVIDE <br />TRANSFORMERS WITH FULLY —ENCLOSED SHEET STEEL ENCLOSURES. <br />D. SUBMIT MANUFACTURER'S TECHNICAL PRODUCT DATA; (MIN. 5 COPIES) INCLUDING RATED KVA, <br />FREQUENCY, PRIMARY AND SECONDARY VOLTAGE AND PERCENT TAPS. ACCEPTABLE MANUFACTURERS <br />ARE: G.E., SQUARE D AND CUTLER HAMMER. MATCH <br />BUILDING STANDARD WHERE APPLICABLE, <br />PANELBOARDS: <br />A. PANELBOARDS SHALL BE CONNECTED DISTRIBUTED PHASE WITH CIRCUIT NUMBERING AS INDICATED <br />ON THE DRAWINGS. PANELBOARDS SHALL HAVE CIRCUIT DIRECTORY CARDS SHALL BE COMPLETED WITH <br />A TYPEWRITER BY THE CONTRACTOR TO INDICATE NEW AND EXISTING AREAS AND/OR DEVICES SERVED <br />BY EACH CIRCUIT. <br />B. CIRCUIT BREAKERS FOR MOUNTING IN NEW AND EXISTING PANELBOARDS OR DISTRIBUTION SECTION <br />OF SWITCHBOARD SHALL BE MOLDED PLASTIC CASE, AIR CIRCUIT BREAKER TYPE. BREAKERS SHALL <br />HAVE THERMAL —MAGNETIC TRIP UNITS AND MULTI —POLE BREAKERS. BREAKERS SHALL HAVE A <br />COMMON TRIP BAR. SO THAT THE TRIPPING OF ONE POLE WILL AUTOMATICALLY TRIP ALL POLES OF <br />THE BREAKER. BREAKERS SHALL BE TRIP FREE AND TRIP —INDICATING AND SHALL HAVE QUICK —MAKE, <br />QUICK BREAK CONTACTS. <br />C. PANELBOARDS SHALL BE INSTALLED COMPLETE WITH CONNECTORS AND ASSOCIATED HARDWARE FOR <br />ALL CIRCUIT BREAKERS AND SPACES LISTED IN THE PANELBOARD SCHEDULE. <br />D. WHEN CONNECTING EQUIPMENT TO EXISTING PANELBOARDS, THE NEW AND EXISTING CIRCUIT <br />BREAKERS SHALL BE IDENTIFIED. A NEW CIRCUIT DIRECTORY CARD SHALL BE PROVIDED. <br />E. PANELBOARDS TO BE DEADFRONT TYPE, WITH COPPER BUS BARS, WITH BOLT —ON TYPE BRANCH <br />CIRCUIT BREAKERS EQUAL TO SQUARE—D TYPE NQOD, NF, OR I —LINE AS APPLICABLE. ALL CIRCUIT <br />BREAKERS SHALL BE CONCEALED BEHIND A HINGED, LOCKABLE DOOR INSTALLED ON THE FRONT <br />PANELBOARD COVER, <br />F. ALL PANELBOARDS TO BE IDENTIFIED WITH ENGRAVED PLASTIC LAMINATE SIGNS. COORDINATE NAMES <br />USED FOR IDENTIFICATION WITH CORRESPONDING DESIGNATIONS SHOWN, SPECIFIED OR SCHEDULED. <br />FASTEN WITH SELF TAPPING STAINLESS STEEL SCREWS, OR CONTACT TYPE PERMANENT ADHESIVE <br />WHERE SCREWS CAN NOT OR SHOULD NOT PENETRATE SUBSTRATE. <br />G. SUBMIT MANUFACTURER'S DATA ON PANELBOARDS AND ENCLOSURES. SHOP DRAWINGS SHALL <br />INDICATE ARRANGEMENT OF BUSSES, BRANCH CIRCUITS, ENCLOSURES, DIMENSIONS, ETC. (MINIMUM 5 <br />COPIES) ACCEPTABLE MANUFACTURER'S: GE, SQUARE—D. SIEMENS AND CUTLER —HAMMER. (MATCH <br />BUILDING STANDARD HERE APPLICABLE. <br />N N D W ) <br />H. INSTALL PANELBOARDS AND ENCLOSURES AS INDICATED, IN ACCORDANCE WITH MANUFACTURER'S <br />WRITTEN INSTRUCTIONS, APPLICABLE REQUIREMENTS OF NEC STANDARDS AND NECA'S "STANDARDS OF <br />INSTALLATION", AND IN COMPLIANCE WITH RECOGNIZED INDUSTRY PRACTICES TO ENSURE THAT <br />PRODUCTS FULFILL REQUIREMENTS. <br />RECEPTACLES <br />A. ALL RECEPTACLES SHALL BE THE GROUNDING TYPE WITH GROUND CONNECTION MADE THROUGH AN <br />EXTRA POLE WHICH SHALL BE PERMANENTLY CONNECTED TO GROUND CONDUCTOR.. <br />B. RECEPTACLES FOR 20 AMPERE, 120V SERVICE SHALL BE THREE —WIRE, TWO POLE RECEPTACLES <br />RATED 20 AMPERES AT 120 VOLTS. ALL NEW RECEPTACLES SHALL BE THAT OF HUBBELL OR <br />PRE —APPROVED EQUAL. <br />C. WHERE EXISTING RECEPTACLES ARE SHOWN TO BE REMOVED FROM PARTITIONS BEING REMOVED, <br />CONTRACTOR SHALL MAINTAIN SERVICE TO REMAINING OUTLETS. <br />D. WALLPLATES: PROVIDE WALLPLATES FOR SINGLE AND COMBINATION WIRING DEVICES, OF TYPES, <br />SIZES, AND WITH GANGING AND CUTOUTS AS INDICATED. SELECT PLATES WHICH MATE AND MATCH <br />WIRING DEVICES TO WHICH ATTACHED. CONSTRUCT WITH METAL SCREWS FOR SECURING PLATES TO <br />DEVICES; SCREW HEADS COLORED TO MATCH FINISH OF PLATES, WALLPLATES COLORED TO MATCH <br />WIRING DEVICES. <br />E. ELECTRICAL CONTRACTOR SHALL CONFIRM RECEPTACLE CONFIGURATION, VOLTAGE, PHASE AND <br />AMPERAGE FOR ALL EQUIPMENT FURNISHED AND INSTALLED FOR THIS WORK. ADVISE ENGINEER IF <br />REQUIRED. <br />LIGHTING FIXTURES: <br />A. THE CONTRACTOR SHALL FURNISH AND INSTALL COMPLETE IN ALL RESPECTS ALL NEW AND <br />RELOCATED LIGHTING FIXTURES SHOWN ON THE PLANS. <br />B. LIGHT FIXTURES SHALL BE SELECTED BY THE OWNER <br />C. BALLASTS FOR FLUORESCENT LAMPS SHALL BE HIGH FREQUENCY ELECTRONIC FOR USE WITH OTIC <br />TYPE (265MA) LAMPS. THE TOTAL HARMONIC DISTORTION ( 7THD) SHALL BE LESS THAN 207.1. THE <br />POWER FACTOR SHALL BE .95 OR HIGHER. <br />ELECTRONIC BALLASTS FOR FLUORESCENT LAMPS SHALL BE OSRAM SYLVANIA, QUICKTRONIC. ALL <br />BALLASTS SHALL BE INDIVIDUALLY FUSED ON THE LINE SIDE OF THE BALLAST. ALL BALLASTS SHALL <br />BE ENERGY SAVING, HIGH POWER FACTOR TYPE AND SHALL BEAR ETL/CBM AND UL LABELS. <br />D. T-8 AND T-5 FLUORESCENT LAMPS SHALL BE 3500K RAPID START. COMPACT FLUORESCENT <br />LAMPS SHALL BE 3500K.INCANDESCENT LAMPS SHALL BE 120V. GENERAL PURPOSE TYPE. UNLESS <br />OTHERWISE NOTED ALL LAMPS SHALL BE TCLP COMPLIANT AND MANUFACTURED BY OSRAM SYLVANIA. <br />U—SHAPED LAMPS SHALL HAVE 6" SPACING BETWEEN ENDS, <br />E. ALL FIXTURES SHALL BE PROPERLY AND CAREFULLY SUPPORTED AND ALIGNED, AND THE <br />CONTRACTOR SHALL FURNISH AND INSTALL ALL NECESSARY STEEL SHAPES, ETC., FOR SUPPORT OF <br />FIXTURES AS REQUIRED AND DETAILED ON THE DRAWINGS. LIGHTING FIXTURES SHALL BE CLEAN AND <br />NON —OPERATING LAMPS REPLACED WITH NEW LAMPS AT THE TIME OF FINAL INSPECTION. <br />F. CONTRACTOR SHALL WEAR PROTECTIVE COTTON GLOVES WHEN HANDLING FIXTURES WITH LOW <br />IRIDESCENT PARABOLIC LOUVERS. DO NOT HANDLE FIXTURES IN ANY WAY THAT WILL PUT FINGER <br />PRINTS ON LOUVERS. <br />ELEG"I RICAL CIFICATIONS <br />101 SCALE: NOT TO SCALE <br />LEGEND MOUNTING <br />SYMBOL: DESCRIPTION: HEIGHT: <br />LIGHTING <br />2' x 4' FLUORESCENT FIXTURE. UPPER CASE LETTER DENOTES FIXTURE CEILING <br />TYPE, LOWER CASE LETTER INDICATES SWITCH CONTROL. REFER TO <br />' IGHTING FIXTURE SCHEDULE' FOR FIXTURE SPECIFICATIONS <br />TYPICAL FOR ALL FIXTURES ON A CIRCUIT). <br />C33M <br />1' x 4' FLUORESCENT FIXTURE. <br />CEILING <br />F- 0—I <br />FLUORESCENT STRIP LIGHTING FIXTURE. <br />AS SPECIFIED <br />0 <br />CEILING <br />EEC FICAGHTING FIXTURE, SEE LIGHTING FIXTURE SCHEDULE FOR <br />CEILING <br />Q <br />WALL MOUNTED LIGHT FIXTURE. <br />AS SPECIFIED <br />EXIT LIGHT SINGLE FACE UNIVERSAL MOUNT AS SPECIFIED IN THE <br />CEILING OR WALL <br />FIXTURE SCHEDULE. LETTER INDICATES IXTURE TYPE. BLACK QUADRANT <br />INDICATES DIRECTION OF FACE, ARROW(S� INDICATE DIRECTION OF <br />TRAVEL. <br />EXIT LIGHT DOUBLE FACE UNIVERSAL MOUNT AS SPECIFIED IN THE <br />CEILING OR WALL <br />N <br />FIXTURE SCHEDULE. LETTER INDICATES FIXTURE TYPE. BLACK QUADRANT <br />INDICATES DIRECTION OF FACE, ARROW(S) INDICATE DIRECTION OF <br />TRAVEL. <br />BATTERY OPERATED EMERGENCY LIGHT FIXTURE. <br />8'-0" AFF <br />COMBINATION EXIT SIGN AND BATTERY OPERATED EMERGENCY LIGHT <br />8'-0" AFF <br />u <br />FIXTURE. <br />DW <br />BATTERY OPERATED EMERGENCY LIGHT FIXTURE, CEILING MOUNTED. <br />CEILING <br />SINGLE POLE SWITCH. <br />48" AFF <br />SM <br />b <br />E CTRONIC TIME CLACK MASTER 0 ER —RIDE SWITCH CONSULT MFR <br />SMALL LETTER DESIGNATION INDICATES LIGHTING ZODE <br />48" AFF <br />LC <br />LIGHTING CONTACTOR. <br />AS NOTED <br />POWER <br />& <br />DUPLEX RECEPTACLE. <br />18" AFF <br />@ =IG <br />DUPLEX RECEPTACLE. IG=ISOLATED GROUND. <br />18" AFF <br />DUPLEX RECEPTACLE, MTD 48" AFF OR 6" ABOVE COUNTER BACKSPLASH. <br />DUPLEX RECEPTACLE, MOUNTED IN CEILING. <br />CEILING <br />QUADRAPLEX RECEPTACLE (DOUBLE DUPLEX), MOUNTED IN CEILING.. <br />CEILING <br />QUADRAPLEX (DOUBLE DUPLEX) RECEPTACLE. <br />18" AFF <br />QUADRAPLEX (DOUBLE DUPLEX) RECEPTACLE, MTD. 48" AFF OR 6" ABOVE COUNTER. <br />DUPLEX GROUND FAULT CIRCUIT INTERRUPTED RECEPTACLE. <br />18" AFF <br />CF1 <br />GF1 <br />48eLAFFGORu6 ABOVE COUNTERNBACKSPLASRECEPTACLE—MOUNTED <br />® <br />SPECIAL PURPOSE OUTLET, NEMA CONFIGURATION AS SHOWN. <br />18" AFF <br />PANELBOARD. <br />6"-6" TO TOP <br />IOW <br />RECESSED FLUSH—MOUNTEQ PANELBOARD. FRONT OF PANEL INDICATED <br />6"-6" TO TOP <br />BY LONGER EDGES OF SYMBOL. <br />DISTRIBUTION PANELBOARD. <br />6"-6" TO TOP, <br />M® <br />METER SOCKET, PROVIDE PER UTILITY COMPANY REQUIREMENTS. 4'-0" <br />MIN. TO 5'-0" MAX. <br />TC <br />TIME CLOCK <br />54" AFF <br />0 <br />SHUNT TRIP PUSH BUTTON. <br />54" AFF <br />EQUIPMENT SYMBOLS <br />I� <br />CONNECTION SCHED.ECOORDINATEYWITH <br />MOTOR INSTALLED EQUIPMENT. <br />=1­11 <br />SAFETY DISCONNECT SWITCH-30A, 3 , 250V, NF, HD, NEMA 1, U.N.O. <br />CEP <br />MOTOR CONTROLLER <br />XH <br />COMBINATION MOTOR STARTER & FUSED DISCONNECT SWITCH, U.N.O. <br />SPECIAL CABINET OR EQUIPMENT AS NOTED, RECESED MOUNTED. <br />$M <br />MANUAL MOTOR gTARTER WITH OVERLOAD HEATERS FOR 120V, 1 <br />FRACTIONAL HP. MOTORS. <br />Ep <br />ENCLOSED CIRCUIT BREAKER IN NEMA 1 ENCLOSURE, U.N.O. <br />T•E <br />DRY TYPE TRANSFORMER (NUMBER INDICATES KVA RATING). <br />CONDUIT, RACEWAY AND WIRING <br />CAru rlDrl IIT ZWAl I r(1KIQIQT Or7 DUAQc kill ITDAI Akin r'_P01 Kin ('0KIN 1r TnDC <br />HOME UN TO SHALL BE B 0 AWG, ASH M3/4 ARMINIMU 1CATES NUMBER OF CIRCUITS. <br />---�IU GROUNDING CONDUCTOR. <br />T—T WALL MOUNTED GROUND BAR. (24"W X 3"H X 1/4"T U.N.O.). <br />CONDUIT IN/UNDER SLAB. <br />CONDUIT CAP. <br />----o DN CONDUIT STUB —DOWN. <br />-0 UP CONDUIT STUB —UP. <br />A DETAIL NUMBER. <br />E-1 ELECTRICAL SHEET NUMBER. <br />GENERAL NOTES <br />APPLIES TO ALL DIVISION 16000 DRAWINGS) <br />WHERE THE REQUIREM NTS OF ANOTHER DIVISION SECTION, OR PART OF THE SPECIFICATIONS <br />EXCEED THE REQUIREMENTS OF THIS DIVISION T OSE REQUIREMENTS SHALL GOVERN. ENGINEER <br />SHALL HAVE FINAL DECISION OF WHICH REWIRE ENT SHALL GOVERIy. <br />2. ALL FLOOR, WALL AND ROOF PENETRATIONS SHALL MAINTAIN THE ENVIRONMENTAL AND FIRE <br />RATING OF THE STRUCTURE. ROOF PENETRATIONS SHALL BE COORDINATED WITH THE ROOFING <br />CONTRACTOR TO MAINTAIN THE ROOFING WARRANTY. PITCH POCKET ROOF PNETRATIONS ARE <br />NOT PER ITTED. <br />3. ALL MOU <br />TING HEIGHTS SHOWN SHALL BE TO CENTER <br />LINE OF DEVICE BACKBOX, <br />4. ALL COM <br />UNICATION CONDUIT SHALL <br />HAVE y IDE SyyEEPING <br />BENDS. <br />AND AT <br />5. ALL COM <br />UNICATION CONDUIT SHALL <br />BE IDENTIFIED BY <br />A DISTINCTIVE NUMBER LABELED <br />6. ALL CO <br />DUIT IN SLAB/BEL( SLAB <br />SHALL BE 3/4" MINIMUM. <br />7. ALL SYMBOLS <br />PRESENTED M Y NOT <br />NECESSARILY BE <br />USED ON THESE DRAWINGS. <br />ABBREVIATIONS <br />A AMPS/AMPERAGE <br />MMS <br />MANUAL MOTOR STARTER <br />AFF ABOVE FINISHED FLOOR <br />NEC <br />NATIONAL ELECTRICAL CODE <br />AHJ AUTHORITY HAVING JURISDICTION <br />NF <br />NON —FUSED <br />AHU AIR HANDL <br />C. CDT. CONDUIT <br />C.B. CIRCUIT BREAKER <br />CU CON ENSING UNIT <br />AFLACONTRACTOR <br />IT WATER EATER <br />CONTRACTOR <br />FAULT INTERRUPTER <br />E SODIUM <br />VgTED S,&CH <br />METAL CONDUIT <br />S WATER HEATER <br />SyTyU ROOF—TOP <br />TTRIP <br />UNIT <br />TTBTWI <br />ELEPHONE TER <br />TVSS TRANSIENT VOL' <br />LIGHTNING ARRE <br />U�TNOTEDWWTS <br />VPyLERPROOF <br />VOLTS <br />PHASE <br />O1 DRAWING NOTE <br />BACKBOARD <br />SURGE SUPPRESSOR/ <br />(NEMA 3R) <br />REVISIONS <br />BY <br />Q0 <br />8 <br />a� ro ti °v <br />N <br />E cxy <br />U <br />erg_ <br />U N <br />Q b <br />ti <br />d rn o <br />00 3 <br />ti <br />3 � 3 <br />. <br />0 rCn <br />ti <br />N <br />Ch <br />I <br />1 <br />w <br />a <br />j 3 <br />rq� <br />3 <br />Z Z � <br />fl Q0 <br />5 <br />U �N� <br />J <br />W <br />I <br />Z� <br />_ W <br />a J H- <br />WUWa° <br />JU :v <br />C Q (f) O <br />a U W .�.. LL. <br />w <br />O <br />O <br />< v <br />o �0 �s <br />O <br />O N CL <br />� W 00 <br />C� PO <br />Q 0� <br />JD <br />m L.L_ <br />Date: 06. 12. 12 <br />Scale: AS NOTED <br />Project Mgr: AAY <br />Drawn: WR <br />Job: 10-61 <br />Sheet <br />E6 <br />