THE MECHANICAL CONTRACTOR SHALL PROVIDE THE <br />LABOR, MATERIALS, AND EQUIPMENT REQUIRED FOR <br />THE HEATING, VENTILATION, AND AIR CONDITIONING <br />SYSTEM(S) AS DESCRIBED IN THE COMPLETE SET OF <br />CONSTRUCTION DOCUMENTS. ALL WORK SHALL <br />CONFORM TO THE REQUIREMENTS OF THE 200i FLORIDA <br />BUILDING CODE AND 2001 FLORIDA ENERGY CODE <br />(INCLUDING THE 200E SUPPLEMENTS), 2005 NATIONAL <br />ELECTRIC CODE, NFPA NATIONAL FIRE CODES, AND ALL <br />OTHER STATE AND LOCAL CODES. <br />THE OWNER SHALL NOT BE RESPONSIBLE FOR ANY <br />PORTION OF THE SCOPE OF WORK UNLESS <br />SPECIFICALLY NOTED IN THE CONSTRUCTION <br />DOCUMENTS. <br />THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE <br />FOR THE INSTALLATION SCHEDULES OF ALL TRADES. <br />FIXED WORK SUCH AS DUCTWORK AND SANITARY AND <br />STORM PIPING SHALL BE INSTALLED PRIOR TO ANY <br />TRADE WORK THAT CAN BE EASILY RELOCATED OR <br />OFFSET SUCH AS ELECTRICAL CONDUIT AND FIRE <br />PROTECTION AND WATER PIPING. ALL ELECTRICAL <br />CONDUIT AND WATER PIPING SHALL BE INSTALLED AS <br />CLOSE TO WALLS AND AS CLOSE TOGETHER AS <br />POSSIBLE TO ALLOW FOR MAXIMUM DUCT <br />ACCESSIBILITY. <br />ALL CONTRACTORS SHALL COORDINATE THE SCOPE OF <br />THEIR WORK AND THEIR CONSTRUCTION SCHEDULES <br />WITH THE OWNER TO PREVENT ANY INTERRUPTIONS <br />UNACCEPTABLE TO THE OWNER THIS MAY REQUIRE <br />WORK AFTER NORMAL OPERATING HOURS AND/OR ON <br />WEEKENDS. <br />2. BIDS, SHOP DRAWINGS, EQUIPMENT SUBMITTALS, AND <br />CHANGE ORDERS <br />EACH PROSPECTIVE CONTRACTOR SHALL EVALUATE <br />THE SCOPE OF WORK THOROUGHLY PRIOR TO <br />SUBMITTING A BID. <br />PRIOR TO STARTING THE PROJECT, THE MECHANICAL <br />CONTRACTOR SHALL STUDY THE COMPLETE SET OF <br />CONSTRUCTION DOCUMENTS AND COORDINATE WITH THE <br />OTHER TRADES AS REQUIRED TO PROVIDE SHOP <br />DRAWINGS TO SUBMIT TO THE MECHANICAL ENGINEER <br />FOR APPROVAL. THE SHOP DRAWINGS MAY BE <br />SUBMITTED AS HAND -DRAWN NOTES UPON A COPY OF <br />THE CONSTRUCTION DOCUMENTS IF PERMISSION IS <br />OBTAINED FROM THE MECHANICAL ENGINEER THE <br />CONSTRUCTION DOCUMENTS ARE DIAGRAMMATIC IN <br />NATURE AND INTENDED SOLELY TO CLARIFY THE <br />SCOPE OF WORK AND INDICATE THE GENERAL <br />ARRANGEMENT OF SYSTEMS. THE CONSTRUCTION <br />DOCUMENTS ARE NOT INTENDED TO ALERT THE <br />CONTRACTOR(S) OF ALL OBSTACLES. THE SHOP <br />DRAWINGS SHALL SHOW THE COORDINATION OF <br />DUCTWORK AND MECHANICAL EQUIPMENT INSTALLATION <br />WITH EXISTING AND NEW OBSTACLES INCLUDING, BUT <br />NOT LIMITED TO, ELECTRICAL CONDUITS, FIRE <br />PROTECTION PIPING, RAIN LEADERS, SANITARY DRAINS, <br />STRUCTURAL MEMBERS, AND WATER PIPING, AS WELL AS <br />THE MECHANICAL EQUIPMENT MANUFACTURER'S' <br />RECOMMENDED CLEARANCES. THE MECHANICAL <br />CONTRACTOR SHALL ALSO SHOW THE EXISTING <br />CONDITIONS ON THE SHOP DRAWINGS WHERE THE <br />EXISTING CONDITIONS ARE DIFFERENT FROM THOSE <br />SHOWN ON THE CONSTRUCTION DOCUMENTS. <br />PRIOR TO STARTING THE PROJECT, THE MECHANICAL <br />CONTRACTOR SHALL STUDY THE COMPLETE SET OF <br />CONSTRUCTION DOCUMENTS AND COORDINATE WITH THE <br />MANUFACTURERS) AS REQUIRED TO PROVIDE <br />EQUIPMENT SUBMITTALS TO SUBMIT TO THE MECHANICAL <br />ENGINEER FOR APPROVAL. THE EQUIPMENT <br />SUBMITTALS SHALL INCLUDE DIMENSIONS, WEIGHTS, <br />SPECIFIED ACCESSORIES AND REQUIRED CLEARANCES, <br />AS WELL AS FAN CURVES, SOUND LEVELS, <br />CONSTRUCTION DETAILS, WARRANTY INFORMATION, AND <br />ALL OTHER RELEVANT DATA PRESENTED IN THE SAME <br />FORMAT AS THE EQUIPMENT SCHEDULES ON THE <br />CONSTRUCTION DOCUMENTS. <br />THE MECHANICAL ENGINEER'S APPROVAL OF THE SHOP <br />DRAWINGS AND EQUIPMENT SUBMITTALS DOES NOT IN <br />ANY WAY RELIEVE THE MECHANICAL CONTRACTOR <br />FROM HIS/HER RESPONSIBILITY TO FURNISH EQUIPMENT <br />AND MATERIALS AND/OR PERFORM WORK AS REQUIRED <br />BY THE CONSTRUCTION DOCUMENTS. THE MECHANICAL <br />ENGINEER MAY REQUIRE THE MECHANICAL <br />CONTRACTOR TO REDO ANY U10RK THAT DOES NOT <br />MEET THE DESIGN INTENT OF THE MECHANICAL <br />ENGINEER OR THE MECHANICAL ENGINEER MAY <br />REQUIRE A CREDIT TO THE OWNER <br />ALTERNATIVES TO THE SCHEDULED EQUIPMENT AND <br />MATERIALS MUST BE EQUAL TO OR EXCEED THOSE <br />SCHEDULED. IF SUBSTITUTIONS FOR SCHEDULED <br />EQUIPMENT AND MATERIALS ARE TO BE MADE, THEN <br />THE MECHANICAL CONTRACTOR SHALL FIRST SUBMIT TO <br />THE MECHANICAL ENGINEER COMPARATIVE LITERATURE <br />CLEARLY SHOWING THE EQUIVALENT OPERATING <br />CAPABILITIES AND OTHER PROPERTIES OF THE <br />SUBSTITUTIONS. ALL DEVIATIONS MST BE CLEARLY <br />IDENTIFIED AND A REQUEST MUST BE MADE SPECIFIC <br />FOR ALL DEVIATIONS. WHEN SUBSTITUTIONS ARE MADE, <br />THE CONTRACTOR ASSUMES FULL RESPONSIBILITY OF <br />COORDINATING WITH OTHER TRADES ON ANY CHANGES <br />REQUIRED FOR THE SUBSTITUTION, INCLUDING COSTS, <br />ASSOCIATED WITH DUCTWORK, PIPING, ELECTRICAL AND <br />STRUCTURAL TO IMPLEMENT THE SUBSTITUTED ITEM(S). <br />THE MECHANICAL CONTRACTOR SHALL VERIFY THE <br />LOCATIONS OF THE DIFFUSERS AND GRILLES AND SUBMIT <br />A REQUEST -FOR -INFORMATION IF THERE IS A CONFLICT <br />BETWEEN THE ARCHITECTURAL AND MECHANICAL <br />PORTIONS OF THE CONSTRUCTION DOCUMENTS. THE <br />MECHANICAL CONTRACTOR SHALL ALSO VERIFY THE <br />TYPES OF CEILINGS IN THE SCOPE OF WORK PRIOR TO <br />ORDERING DIFFUSERS AND GRILLES. FOR DIFFUSERS AND <br />GRILLES LOCATED IN PLASTER OR GYPSUM CEILINGS, <br />THE MECHANICAL CONTRACTOR SHALL PROVIDE TITUS <br />MODEL TRM PLASTER FRAMES. THE MECHANICAL <br />CONTRACTOR SHALL COORDINATE THE FINISH OF ALL <br />DIFFUSERS AND GRILLES, EXPOSED DUCTWORK, GRAVITY <br />VENTILATORS, LOUVERS, AND WALL CAPS WITH THE <br />-%ARCHITECT/OWNEFft. ALL VISIBLE EXTERIOR <br />COMPONENTS (SUCH AS EXPOSED DUCTWORK AND <br />LOUVERS) SHALL BE PROVIDED WITH A PAINT -GRIP <br />MECHANICAL LEGEND 4 SPECIFICATIONS <br />SCALE: NONE <br />1" IEC44ANICAL SPECIFICATIONS AND SCHEDULES <br />FINISH. <br />3. MECHANICAL EQUIPMENT INSTALLATION <br />ALL MECHANICAL EQUIPMENT SHALL BE INSTALLED AS <br />REQUIRED BY THE MANUFACTURER'S' INSTALLATION AND <br />MAINTENANCE MANUALS. THOSE MANUALS WILL <br />TYPICALLY PROVIDE MORE DETAIL THAN THE <br />CONSTRUCTION DOCUMENTS. IF THERE IS A CONFLICT <br />BETWEEN THE INSTALLATION AND MAINTENANCE MANUALS <br />AND THE CONSTRUCTION DOCUMENTS, THEN THE <br />MECHANICAL CONTRACTOR SHALL SUBMIT A <br />REQUEST -FOR -INFORMATION TO THE MECHANICAL <br />ENGINEER <br />ALL MECHANICAL EQUIPMENT SHALL BE INSTALLED SUCH <br />THAT SUFFICIENT CLEARANCES ARE PROVIDED FOR <br />MAINTENANCE. <br />THE GENERAL AND MECHANICAL CONTRACTORS SHALL <br />PROVIDE A 4" HIGI4 CONCRETE HOUSEKEEPING PAD <br />UNDER ALL MECHANICAL EQUIPMENT, UNLESS OTHERWISE <br />NOTED ON THE CONSTRUCTION DOCUMENTS. THE <br />HOUSEKEEPING PAD SHALL EXTEND 8" BEYOND THE <br />MECHANICAL EQUIPMENT ON ALL SIDES. <br />THE MECHANICAL CONTRACTOR SHALL PROVIDE <br />VIBRATION ISOLATION AS RECOMMENDED BY THE <br />MANUFACTURER(S) aND1OJaL REQUIRED BY THE <br />MECHANICAL ENGINE(* TO ENSURE QUIET OPERATION OF <br />THE MECHANICAL EQUIPMENT. NO UNDUE VIBRATION OR <br />SOUND SHALL BE TRANSMITTED TO THE STRUCTURE ,OR <br />ANY OCCUPIED SPACES WITHIN THE STRUCTURE. <br />THE MECHANICAL CONTRACTOR SHALL PROVIDE ALL <br />STARTERS, CONTACTORS, RELAYS, CONTROLS, AND <br />ACCESSORIES NECESSARY TO PROVIDE A COMPLETE <br />AND WORKING POWER AND CONTROL SYSTEM FOR THE <br />MECHANICAL EQUIPMENT WITHIN THE SCOPE OF WORK. <br />THE ELECTRICAL CONTRACTOR WILL PROVIDE ALL <br />DISCONNECT SWITCHES, CONDUIT, AND WIRING FOR THE <br />MECHANICAL EQUIPMENT WITHIN THE SCOPE OF WORK. <br />ALL ELECTRICAL WORK SHALL COMPLY WITH THE <br />REQUIREMENTS OF THE NATIONAL ELECTRIC CODE. THE <br />MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR <br />THE PROPER OPERATION OF THE COMPLETE SYSTEM AND <br />SHALL ENSURE THAT WIRING DIAGRAMS ARE PROVIDED <br />TO THE OWNER NO WIRING OF ANY KIND SHALL BE <br />EXPOSED IN FINISHED AREAS. <br />THE MECHANICAL CONTRACTOR SHALL ENSURE THAT ALL <br />MECHANICAL EQUIPMENT IS STARTED, TESTED, ADJUSTED, <br />AND PLACED IN SATISFACTORY OPERATING CONDITION <br />PRIOR TO SUBSTANTIAL COMPLETION. THE MECHANICAL <br />CONTRACTOR SHALL GUARANTEE ALL WORKMANSHIP, <br />MATERIALS, AND MECHANICAL EQUIPMENT TO BE FREE OF <br />DEFECTS FOR A PERIOD OF ONE YEAR FROM THE DATE <br />OF FINAL ACCEPTANCE BY THE OWNER AND SHALL <br />REPAIR ANY DEFECTS OCCURRING WITHIN THAT TIME <br />WITHOUT COST TO THE OWNER ALL MECHANICAL <br />EQUIPMENT IN THE SCOPE OF WORK SHALL BE COVERED <br />FOR THE DURATION OF THE MANUFACTURER'S' <br />GUARANTEE(S) OR WARRANTY(IES) AND THE <br />CONTRACTOR SHALL PROVIDE THE OWNER WITH <br />ORIGINALS OF ALL MANUFACTURER'S' GUARANTEES AND <br />WARRANTIES. ALL COMPRESSORS SHALL BE PROVIDED <br />WITH A MINIMUM FIVE (5) YEAR WARRANTY. <br />THE MECHANICAL CONTRACTOR SHALL COORDINATE ALL <br />MECHANICAL EQUIPMENT VOLTAGE REQUIREMENTS WITH <br />THE VOLTAGE AVAILABLE AT THE PROJECT SITE PRIOR <br />TO ORDERING ANY MECHANICAL EQUIPMENT. <br />4. DUCTWORK CONSTRUCTION <br />THE SHEET METAL AND AIR CONDITIONING CONTRACTORS' <br />NATIONAL ASSOCIATION'S "HVAC DUCT CONSTRUCTION <br />STANDARDS" SHALL BE CONSIDERED PART OF THE <br />SPECIFICATIONS FOR THIS PROJECT. ANY WORK THAT <br />DOES NOT COMPLY WITH THESE STANDARDS MAY BE <br />REJECTED AT ANY TIME DURING THE PROJECT. <br />ALL EXHAUST DUCTWORK SHALL BE SHEET METAL <br />ALL DUCT DIMENSIONS SHOWN ON THE CONSTRUCTION <br />DOCUMENTS ARE INSIDE CLEAR DIMENSIONS. THE <br />MECHANICAL CONTRACTOR SHALL PROVIDE FLEXIBLE <br />CONNECTIONS BETWEEN EACH ITEM OF MECHANICAL <br />EQUIPMENT AND ITS ASSOCIATED DUCT(S). ALL ITEMS OF <br />THE HEATING, VENTILATION, AND AIR CONDITIONING <br />SYSTEM INCLUDING, BUT NOT LIMITED TO, AIR HANDLERS, <br />FANS, DUCTWORC, DIFFUSERS, AND GRILLES SHALL NOT BE <br />SUPPORTED BY THE CEILING OR CEILING SUSPENSION <br />SYSTEM, BUT INSTEAD SHALL BE SUPPORTED BY THE <br />BUILDING STRUCTURE. <br />ALL FORTY-FIVE (45) AND NINETY (W) DEGREE ELBOWS <br />SHALL HAVE A ONE AND ONE-HALF (IB) CENTERLINE <br />RADIUS -TO -WIDTH OR RADIUS -TO -DEPTH RATIO OR <br />SHALL BE CONSTRUCTED WITH SINGLE BLADE TURNING <br />VANES. ANGULAR TAPERS SHALL BE LIMITED TO THIRTY <br />(30) DEGREES FOR CONTRACTING TAPERS AND TWENTY <br />(20) DEGREES FOR EXPANDING TAPERS. <br />THE MAXIMUM LENGTH OF NEW FLEXIBLE SUPPLY DUCT <br />SHALL BE 8'-0". FLEXIBLE RETURN DUCT SHALL :6 BE <br />LIMITED TO THE VERTICAL PLANEb/a. FLEXIBLE DUCT <br />SHALL BE INSTALLED AND SUPPORTED SO AS TO <br />PREVENT THE USE OF EXCESS DUCT MATERIAL, PREVENT <br />DISLOCATION OR DAMAGE, AND PREVENT CONSTRICTION <br />OF THE DUCT BELOW THE RATED DUCT DIAMETER <br />FLEXIBLE DUCT BENDS SHALL MAINTAIN A CENTERLINE <br />RADIUS OF NOT LESS THAN ONE AND ONE-HALF (1B) DUCT <br />DIAMETERS. SAGS SHALL NOT EXCEED ONE-HALF (OB) <br />INCH PER LINEAR FOOT OF FLEXIBLE DUCT. HANGERS, <br />SADDLES, AND OTHER SUPPORTS SHALL HAVE A MINIMUM <br />WIDTH OF ONE AND ONE-HALF (IB) INCHES. THE <br />MECHANICAL CONTRACTOR SHALL PROVIDE SUPPORT <br />FOR EXISTING FLEXIBLE DUCTWORK WITH A MAXIMUM <br />SPACING OF 5'-07, UNLESS OTHERWISE NOTED ON THE <br />CONSTRUCTION DOCUMENTS OR AUTHORIZED BY THE <br />MECHANICAL ENGINEER <br />SURFACES UPON WHICH CLOSURE OR SEALING PRODUCTS <br />ARE TO BE APPLIED SHALL BE CLEAN AND DRY IN <br />ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION <br />INSTRUCTIONS. ALL DUCTWORK SHALL BE SEALED WITH A <br />NON -HARDENING, NON -MIGRATING MASTIC OR LIQUID <br />ELASTIC SEALANT AS REQUIRED TO MEET THE 2001 <br />FLORIDA ENERGY CODE (INCLUDING THE 20M <br />SUPPLEMENTS). THE MECHANICAL CONTRACTOR SHALL <br />PROVIDE HOT -DIPPED GALVANIZED STEEL FASTENERS, <br />ANCHORS, RODS, STRAPS, TRIM, AND ANGLES FOR <br />INTERIOR DUCTWORK SUPPORTS. INTERIOR DUCTWORK <br />SUPPORT SPACING SHALL NOT EXCEED <br />THE MECHANICAL CONTRACTOR SHALL PROVIDE <br />INSULATION WITH A MINIMUM R-VALUE OF SIX (6) ON ALL <br />DUCTWORK. CONCEALED DUCTWORK MAY BE INSULATED <br />WITH FLEXIBLE FIBERGLASS INSULATION, BUT ALL <br />EXPOSED DUCTWORK (INCLUDING DUCTWORK LOCATED <br />IN MECHANICAL ROOMS) MUST BE INSULATED WITH <br />FIBROUS DUCTBOARD. ALL DUCTWORK INSULATION, <br />FITTINGS, COVERS, AND FINISHES SHALL HAVE A MAXIMUM <br />FLAME SPREAD RATING OF 25, A MAXIMUM SMOKE <br />DEVELOPMENT RATING OF 50, AND SHALL BE IN <br />COMPLIANCE WITH NFPA WA. PROVIDE MINIMUM OF 1/2" <br />FIBERGLASS WITH FOIL/SCRIM VAPOR BARRIER ON THE <br />BACK PAN OF ALL NEW AIR DEVICES. <br />ALL OUTSIDE AIR INTAKES SHALL BE A MINIMUM OF <br />10'-0" FROM ANY EXHAUST OUTLET OR VENT PIPE <br />(UNLESS THE VENT PIPE IS AT LEAST TWO (2) FEET <br />ABOVE THE OUTSIDE AIR INTAKE). THE MECHANICAL <br />CONTRACTOR SHALL PROVIDE SCREENS ON ALL <br />OUTSIDE AIR INTAKES AND EXHAUST OUTLETS AT NO <br />LESS THAN 1/4" BY 1/4 AND NO GREATER THAN 1/2" BY 1/2" <br />THE MECHANICAL CONTRACTOR SHALL PROVIDE AN <br />OPPOSED -BLADE VOLUME DAMPER FOR EVERY <br />RECTANGULAR BRANCH AND OUTLET AND AT EVERY <br />RECTANGULAR TAKE -OFF FOR A DIFFUSER OR GRILLE. <br />(ROUND OR OVAL BRANCHES, OUTLETS, AND TAKE -OFFS <br />FOR DIFFUSERS AND GRILLES SHALL BE PROVIDED WITH <br />STANDARD VOLUME DAMPERS.) NOT ALL DAMPERS ARE <br />SHOWN ON THE CONSTRUCTION DOCUMENTS. HOWEVER, <br />DAMPERS ARE REQUIRED FOR EVERY BRANCH, OUTLET, <br />AND TAKE -OFF. SOME DAMPERS MAY BE REQUIRED <br />AFTER TRANSITIONS. <br />THE MECHANICAL CONTRACTOR SHALL ATTACH A <br />BRIGHTLY -COLORED STRIP OF PLASTIC TAPE TO EVERY <br />VOLUME DAMPER EXCEPT THOSE AT THE HEAD OF A <br />DIFFUSER OR GRILLE. THE STRIP SHALL BE OF <br />SUFFICIENT LENGTH TO HANG A MINIMUM OF 12" BELOW THE <br />BOTTOM OF THE ASSOCIATED DUCT. <br />THE MECHANICAL CONTRACTOR SHALL CLEARLY AND <br />PERMANENTLY MARK EACH VOLUME DAMPER'S OPEN <br />AND CLOSED POSITIONS. THE MECHANICAL <br />CONTRACTOR SHALL PROVIDE A VOLUME DAMPER WITH <br />A 2" STANDOFF WITH A LOCKING QUADRANT THAT IS 24 <br />GAUGES OR 2 GAUGES HEAVIER <br />5. DUCT LEAKAGE PERFORMANCE <br />DUCT CONSTRUCTION AND SEALING SYSTEMS SHALL <br />MEET THE REQUIREMENTS OF THE 2001 FLORIDA ENERGY <br />CODE (INCLUDING THE 200E SUPPLEMENTS) AND <br />SMACNA'S "14VAC DUCT CONSTRUCTION STANDARDS': IF <br />THERE IS A CONFLICT AMONG THE STANDARDS, THEN THE <br />MORE STRINGENT STANDARD SHALL BE ENFORCED. <br />THE MECHANICAL CONTRACTOR SHALL SEAL ALL <br />TRANSVERSE JOINTS, LONGITUDINAL SEAMS, AND DUCT <br />WALL PENETRATIONS TO A MAXIMUM ALLOWABLE DUCT <br />LEAKAGE CLASS OF THREE (3) CFM PER 100 SQUARE <br />FEET OF DUCT AREA (IBA) FOR ROUND DUCT AND SIX <br />(6) CFM PER 100 SQUARE FEET OF DUCT AREA (3%) FOR <br />ALL OTHER DUCT TYPES, UNLESS OTHERWISE NOTED ON <br />THE CONSTRUCTION DOCUMENTS OR AUTHORIZED BY THE <br />MECHANICAL ENGINEER TRANSVERSE JOINTS ARE <br />CONNECTIONS OF TWO DUCT OR FITTING ELEMENTS <br />ORIENTED PERPENDICULAR TO THE DIRECTION OF THE <br />AIRFLOW. LONGITUDINAL SEAMS ARE JOINTS ORIENTED <br />IN THE DIRECTION OF THE AIRFLOW. DUCT WALL <br />PENETRATIONS ARE OPENINGS MADE BY SCREWS, <br />NON -SELF-SEALING FASTENERS, PIPES, TUBING, RODS, <br />AND WIRE. ROUND AND FLAT -OVAL SPIRAL LOCK <br />SEAMS NEED NOT BE SEALED PRIOR TO ASSEMBLY BUT <br />SHALL BE COATED AFTER ASSEMBLY TO REDUCE <br />LEAKAGE. ALL OTHER CONNECTIONS ARE CONSIDERED <br />TRANSVERSE JOINTS INCLUDING, BUT NOT LIMITED TO, <br />SPIN -INS, TAPS OR OTHER BRANCH CONNECTIONS, <br />ACCESS DOOR FRAMES, AND DUCT CONNECTIONS TO <br />EQUIPMENT. MORE INFORMATION IS AVAILABLE IN <br />CHAPTER 35 OF ASHRAE'S 'FUNDAMENTALS HANDBOOK': <br />6. ACCESS PANELS, FIRE DAMPERS, AND FIRE/SMOKE <br />DAMPERS <br />THE MECHANICAL CONTRACTORS SHALL PROVIDE <br />ACCESS PANELS TO ALLOW ACCESS TO VOLUME <br />DAMPERS ABOVE PLASTER OR GYPSUM CEILINGS, <br />TURNING VANES, FIRE DAMPERS, FIRE/SMOKE DAMPERS, <br />DUCT -MOUNTED SMOKE DETECTORS, AND WHERE <br />REQUIRED FOR THE MAINTENANCE OF ALL MECHANICAL <br />EQUIPMENT <br />THE MECHANICAL CONTRACTOR SHALL ATTACH A <br />BRIGHTLY -COLORED STRIP OF PLASTIC TAPE TO EVERY <br />DUCT -MOUNTED ACCESS PANEL. THE STRIP SHALL BE OF <br />SUFFICIENT LENGTH TO HANG A MINIMUM OF 12" BELOW THE <br />BOTTOM OF THE ASSOCIATED DUCT. <br />THE MECHANICAL CONTRACTOR SHALL PROVIDE A FIRE <br />DAMPER AT EVERY DUCT PENETRATION OF A <br />FIRE -RATED ASSEMBLY AND A FIRE/SMOKE DAMPER <br />WITH A MINIMUM FIRE/SMOKE RATING OF TWO (2) HOURS <br />AT EVERY DUCT PENETRATION OF A SMOKE ASSEMBLY <br />OR CHASE. EACH FIRE/SMOKE DAMPER SHALL CLOSE <br />AND THE ASSOCIATED AIR HANDLER SHALL SHUT DOWN <br />IF EITHER OF THE AIR HANDLER'S OR THE SPACE'S <br />SMOKE DETECTORS AR= ACTIVATED. <br />THE MECHANICAL CONTRACTOR SHALL PROVIDE <br />ADDITIONAL DUCTWORK AND PIPING SUPPORTS WITHIN <br />EIGHTEEN (18) INCHES OF BOTH SIDES OF ALL <br />FIRE -RATED ASSEMBLIES. DUCTWORK AND PIPING <br />SHALL NOT BE SUPPORTED BY FIRE -RATED WALLS, BUT <br />INSTEAD SHALL BE SUPPORTED BY THE BUILDING <br />STRUCTURE. <br />i. CONTROLS <br />THE MECHANICAL CONTRACTOR SHALL PROVIDE ALL <br />CONTROLS AND SUB -CONTRACT TO THE ELECTRICAL <br />CONTRACTOR ALL CONTROLS POWER AND <br />TRANSFORMERS NOT IDENTIFIED IN THE ELECTRICAL <br />PORTION OF THE CONSTRUCTION DOCUMENTS. <br />THE MECHANICAL CONTRACTOR SHALL PROVIDE A <br />PROGRAMMABLE THERMOSTAT FOR EACH EXISTING AIR <br />CONDITIONING SYSTEM. THE MECHANICAL CONTRACTOR <br />SHALL COORDINATE THE INITIAL OCCUPANCY <br />SCHEDULE(S) AND PROGRAMMING WITH THE OWNER AND <br />PROVIDE TRAINING AS REQUIRED. ALL PROGRAMMING <br />SHALL BE COMPLETED USING HONEYWELL'S <br />THERMOSTAT PROGRAMMING SOFTWARE. <br />EACH THERMOSTAT SHALL BE INSTALLED AT 4'-0" <br />ABOVE THE FINISHED FLOOR UNLESS OTHERWISE NOTED <br />ON THE CONSTRUCTION DOCUMENTS. THE MECHANICAL <br />CONTRACTOR SHALL COORDINATE THE EXACT <br />LOCATION OF EACH THERMOSTAT WITH THE ARCHITECT <br />AND SUBMIT THE PROPOSED LOCATION TO THE <br />MECHANICAL ENGINEER FOR APPROVAL. THE <br />MECHANICAL CONTRACTOR SHALL PROVIDE <br />COORDINATION OF ALL THERMOSTAT FINISHES WITH <br />ROOM FINISHES AT NO ADDITIONAL COST TO THE <br />OWNER <br />ALL 120-VOLT RESTROOM EXHAUST FANS WITH <br />ELECTRICAL REQUIREMENTS OF UP TO 800 WATTS <br />SHALL BE CONTROLLED BY AN OCCUPANCY SENSOR <br />WITH A TIME DELAY. THE INITIAL TIME DELAY SHALL BE <br />SET AT TWENTY (20) MINUTES. THE LASER ROOMS SHALL <br />HAVE A 24 HOUR TIMER SWITCH. <br />THE MECHANICAL CONTRACTOR SHALL PROVIDE A TIME <br />CLOCK FOR ALL EXHAUST AND OUTSIDE AIR FANS. THE <br />MECHANICAL CONTRACTOR SHALL COORDINATE THE <br />INITIAL OCCUPANCY SCHEDULE(S) AND SETTINGS WITH <br />THE OWNER AND PROVIDE TRAINING AS REQUIRED. <br />B.TESTING AND BALANCING THE HEATING, VENTILATION, <br />AND AIR CONDITIONING SYSTEM <br />THE MECHANICAL CONTRACTOR SHALL PROVIDE THE <br />SERVICES OF AN INDEPENDENT TEST AND BALANCE <br />AGENCY TO TEST, BALANCE, AND CERTIFY THE <br />PERFORMANCE OF THE COMPLETE HEATING, <br />VENTILATION, AND AIR CONDITIONING SYSTEM, TO <br />INCLUDE SUPPLY, RETURN, OUTSIDE / MAKE-UP, AND <br />EXHAUST AIR SYSTEMS. THE TEST AND BALANCE <br />CONTRACTOR SHALL PERFORM ALL TESTING, <br />ADJUSTING, BALANCING, AND DATA RECORDING <br />NECESSARY TO ESTABLISH THE CAPACITY AND <br />QUALITY OF THE SYSTEMS AND CONFIRM THE <br />SATISFACTORY COMPLETION OF ALL ASPECTS OF THE <br />SCOPE OF WORK THIS WILL INCLUDE NOT ONLY THE <br />NEW SYSTEMS, BUT ALSO ALL OF THE EXISTING SYSTEMS <br />THAT HAVE BEEN MODIFIED. <br />THE TEST AND BALANCE CONTRACTOR SHALL BE AN <br />APPROVED MEMBER OF THE AABC OR NEBB AND <br />SHALL SPECIALIZE IN THE TESTING AND BALANCING OF <br />HEATING, VENTILATION, AND AIR CONDITIONING SYSTEMS. <br />THE FOLLOWING TEST AND BALANCE CONTRACTORS <br />ARE PRE -APPROVED: THE PHOENIX AGENCY, <br />SOUTHERN INDEPENDENT TESTING AGENCY, TEST AND <br />BALANCE CORPORATION, AND SPEC TECH <br />CONSULTANTS. <br />THE TEST AND BALANCE CONTRACTOR SHALL ENSURE <br />THAT THE BUILDING IS UNDER POSITIVE PRESSURE AT <br />THE CONCLUSION OF THE TEST AND BALANCE PROCESS. <br />IF THE BUILDING IS NOT UNDER POSITIVE PRESSURE AT <br />THE CONCLUSION OF THE TEST AND BALANCE PROCESS, <br />THEN THE TEST AND BALANCE AND MECHANICAL <br />CONTRACTORS SHALL IMMEDIATELY AND WITHOUT <br />DELAY NOTIFY THE ARCHITECT AND MECHANICAL <br />ENGINEER <br />THE TEST AND BALANCE CONTRACTOR SHALL, UPON <br />COMPLETION OF ALL NECESSARY TESTING AND <br />BALANCING AND AT LEAST ONE (1) WEEK PRIOR TO <br />SUBSTANTIAL COMPLETION, SUBMIT THREE (3) BOUND <br />COPIES OF THE TEST AND BALANCE REPORT TO THE <br />MECHANICAL ENGINEER <br />THE MECHANICAL CONTRACTOR SHALL INCLUDE IN <br />HIS/HER BID THE COST OF ANY SHEAVE CHANGES <br />REQUIRED FOR REBALANCING THE SYSTEM. <br />S.SUBSTANTIAL AND FINAL COMPLETION <br />THE MECHANICAL CONTRACTOR SHALL MAINTAIN A SET <br />OF CONTINUOUSLY UPDATED, REPRODUCIBLE AS -BUILT <br />DRAWINGS DURING CONSTRUCTION AND PROVIDE A <br />COMPLETE SET OF THOSE DRAWINGS IN BOTH <br />ELECTRONIC AND HARDCOPY FORMATS TO THE OWNER <br />UPON FINAL COMPLETION. <br />THE MECHANICAL CONTRACTOR SHALL CLEAN ALL <br />COOLING AND HEATING COILS, CONDENSATE PANS, AND <br />CONDENSATE DRAIN LINES PRIOR TO SUBSTANTIAL <br />COMPLETION. THE MECHANICAL CONTRACTOR SHALL <br />ALSO REPLACE ALL FILTERS AND BELTS PRIOR TO <br />SUBSTANTIAL COMPLETION AND PROVIDE TWO (3) <br />COMPLETE REPLACEMENT SETS OF FILTERS AND (2) <br />SETS OF BELTS FOR ALL MECHANICAL EQUIPMENT TO <br />THE OWNER UPON FINAL COMPLETION. <br />THE MECHANICAL AND ELECTRICAL CONTRACTORS <br />SHALL PROVIDE FIVE (5) BOUND COPIES OF ALL <br />MECHANICAL AND ELECTRICAL CONTRACTOR <br />WARRANTIES, MANUFACTURER'S' WARRANTIES, PARTS <br />LISTS, AND INSTALLATION AND MAINTENANCE MANUALS <br />FOR ALL MECHANICAL EQUIPMENT, AS WELL AS <br />INSTRUCTIONS FOR OPERATING AND MAINTAINING ALL <br />MECHANICAL EQUIPMENT TO THE OWNER UPON FINAL <br />COMPLETION. <br />MEC 4ANICAL SHEET INDEX <br />M0 MECHANICAL LEGEND 4 SPECIFICATIONS <br />MI MECHANICAL DEMOLITION PLAN <br />M2 MECHANICAL FLOOR PLAN t SCHEDULES <br />M3 MECHANICAL DETAILS <br />MEC14AHICAL LEC-a 10 <br />SO RG EG <br />® z ® <br />NEW CEILING DFRZERAGRILLE (LAY -IN) <br />SO Firs EG <br />® z ® <br />EXISTING CEILING DIFFUSER/GRILLE (LAY -IN) <br />® <br />SUPPLY DIFFUSER BLANKING <br />0 <br />RETURN GRILLE SOLND ATTENUATION <br />NEW WW PRESSURE DUCTWORK <br />EXISTING HIGH PRESSURE DUCTWORK <br />FLEXIBLE DUCTWORK <br />EXISTING FLEXIBLE DUCT CONNECTION <br />BD BACKDRAFT DAMPER <br />FIRE DAMPER <br />I VOLUME DAMPER <br />TO TEMPERATURE SENSOR / THERMOSTAT <br />W x D RECTANGULAR DUCt WIDTH x DEPTH (IQES) <br />ROUND DUCT DIAMETER (MQES) <br />EQ <br />X>( <br />EQUIPMENT TAG <br />(E) <br />EXISTING <br />(R) <br />RELOCATED <br />(N) <br />NEW <br />NEW POINT OF CONNECtION <br />2 <br />CO <br />= SENSOR <br />BASIS OF DESIGN " <br />1. THERE ARE NO WINDOWS IN THIS SPACE. <br />2. WALL INSULATION IS R43S). <br />3. ROOF INSULATION IS R45). <br />4. DESIGN TEMPERATURE IN ALL ROOMS IS 14 DEGREES. <br />BASIS " LOAD CALCULATIONS <br />NI�NBEI <br />AND NAME <br />NUMBER OF <br />PEOPLE <br />MISC. HEAT <br />LOADCS) <br />, <br />V OF HEAT <br />LOAD(S) <br />101 WAITING <br />23 <br />-100 WATTS <br />(2) WATER COOLER <br />EXAM ROOM (TYPICAL) <br />1 <br />200 WATTS <br />1 PC <br />102 RECEPTION • <br />2 <br />1200 WATTS <br />2 PC-S, 1 PRINTER <br />IM 5REAKROOM <br />12 <br />1000 WATTS <br />FRIDGE, COFFEE MAKER <br />MICROWAVE <br />OFFICE (TYPICAL) <br />2 <br />200 WATTS <br />1 PC <br />141 MEDICAL ASSISTANTS <br />a <br />1600 WATTS <br />8 PCS <br />III INFUSION CENTER <br />IS <br />1200 WATTS <br />5 PCB, I FRIDGE <br />138 SHARED OFFICE <br />2 <br />400 WATTS <br />2 PCS <br />144 DRUG SAMPLE ROOM <br />0 <br />200 WATTS <br />FRIDGE <br />124 WORK STATION <br />1 <br />200 WATTS <br />PC <br />103 WORK AREA <br />3 <br />1200 WATTS <br />3 PC, FREEZER <br />110 ELECTRICAL <br />0 <br />500 WATTS <br />EQUIPMENT <br />NOTE: ROOM W11BERS OMITTED FROM THIS LIST INCLUDE STAIRWELLS AND SMALL <br />SPACES INCORPORATED INTO LARGER SPACES FOR SIMPLICITY. THE <br />MECHANICAL CONTRACTOR SHALL COORDINATE TIE LOCATIONS OF ALL <br />THERMOSTATS, AND OTHER CONTROLS WITH THE ARCHITECT AND OWNER AND <br />SUBMIT THOSE LOCATIONS TO THE MECHANICAL ENGINEER FOR REVIEW. <br />��•► L1CF••. B <br />•` a : • 'Vo �' .0 <br />0: <br />LN % <br />/y•'• D A•••••• •A,, <br />.,��q ,ENE, Nti���• <br />REVISIONS <br />BY <br />E <br />� <br />UU <br />N <br />u <br />�00, <br />U 4�D O <br />.0 M <br />E. <br />¢fib <br />E <br />E L� <br />R . <br />/ a � <br />�--. 1.0 <br />o tD <br />U , <br />¢ y 70 <br />¢ E °O <br />Y 3 � <br />oxco <br />—� E `j N <br />` <br />CO <br />00 <br />ti <br />N <br />ti <br />a <br />1 <br />�x <br />w <br />oUU <br />o n <br />m <br />c Z c 0 <br />0 <br />� e <br />w <br />�LL <br />E <br />Cn s <br />a <br />� Z <br />> <br />'6�� <br />2 <br />V_ <br />Z L <br />O <br />J O <br />V LL. m <br />v <br />`'- z 7 <br />� J N � •0 <br />N <br />0 V `` <br />._ V) y vi <br />m LO rn s <br />L 0 <br />0 0 -C <br />C) N <br />M <br />a` <br />0 s <br />J <br />LA. <br />Date: 02. 09. 11 <br />Scale: AS NOTED <br />Project Mgr: CWS <br />Drawn: CWS <br />Job: 10-65 <br />Sheet <br />m 1 <br />