<br />DUCT DETECTOR/SENSOR INSTALLATION GUIDE
<br />PRE -INSTALLATION ROUTINES
<br />DUCT DETECTORS/SENSORS SHOULD BE INSTALLED IN A LOCATION OF
<br />RELATIVELY NON -TURBULENT AIR FLOW AND WITHIN THE INTENDED OPERATING
<br />VELOCITY RANGE OF 300-4000 FEET -PER -MINUTE (91 TO 1220 M/MIN.)
<br />SIMPLEX RECOMMENDS MEASUREMENTS OF AIR FLOW AND EXAMINATION OF
<br />ENGINEERING SPECIFICATIONS THAT DEFINE EXPECTED DUCT AIR VELOCITIES
<br />UNDER ALL CONDITIONS. THIS IS DONE TO DETERMINE IF A LOCATION IS
<br />SUITABLE FOR DUCT DETECTOR/SENSOR OPERATION,
<br />AN ALNOR INSTRUMENT CO. (CHICAGO) MODEL 6000P VELOMETER OR
<br />EQUIVALENT (NOT SUPPLIED) MAY BE USED TO CHECK THE DUCT AIR VELOCITY.
<br />INSTALLATION GUIDELINES
<br />1. IT IS RECOMMENDED TO LOCATE DETECTORS/SENSORS A MINIMUM OF SIX
<br />DUCT WIDTHS DOWNSTREAM FROM BENDS OR INLETS. SUCH LOCATIONS ENSURE
<br />THAT AIR FLOW IS NON -TURBULENT AND THAT SMOKE IS PROPERLY MIXED
<br />WITH AIR IN THE DUCT FOR MAXIMUM DETECTOR/SENSOR EFFICIENCY.
<br />SEE FIGURES 1 AND 2.
<br />NOTE: INSTALLATION OF A DUCT DETECTOR/SENSOR TO A ROUND DUCT IS THE
<br />SAME AS SHOWN IN FIGURES 1 AND 2 AS LONG AS THE ROUND DUCT
<br />IS 18 INCHES OR LARGER (45.7 CM) IN DIAMETER.
<br />;�j BEND OR OTHER
<br />OBSTRUCTION
<br />6 DUCT WIDTIHS
<br />MINIMUKF"
<br />FIGURE 1. DUCT HOUSING PLACEMENT LOCATION OF BENDS OR INLETS
<br />RETURN A�
<br />INLET
<br />�6 DUCT WIDT�s
<br />-MINIMUM I
<br />FIGURE 2. DUCT HOUSING PLACEMENT LOCATION OF AIR RETURN INLET
<br />2. LOCATE DUCT HOUSINGS SO THAT DAMPERS DO NOT RESTRICT AIR FLOW AT
<br />THE DETECTOR/SENSOR LOCATION. SEE FIGURE 3.
<br />3. LOCATE AIR DUCT DETECTORS/SENSORS ON THE RETURN OR SUPPLY DUCT
<br />OF THE EQUIPMENT'S AIR HANDLING SYSTEM. HOWEVER, DETECTORS/SENSORS
<br />SHOULD NOT BE INSTALLED IN THE RETURN AIR DAMPER BRANCH.
<br />SEE FIGURE 3.
<br />4. LOCATE AIR DUCT DETECTORS/SENSORS ON BRANCH LINES IF CLOSE
<br />IDENTIFICATION OF THE ALARM SOURCE IS REQUIRED.
<br />5. LOCATE AIR DUCT DETECTORS/SENSORS ON THE DOWNSTREAM SIDE OF
<br />FILTERS TO SENSE FIRE IN FILTERS. HOWEVER, SHOULD THE FILTERS BLOCK,
<br />SUFFICIENT AIR FLOW MAY NOT BE AVAILABLE FOR PROPER AIR DUCT
<br />DETECTOR/SENSOR OPERATION. SEE FIGURE 3.
<br />6. WHENEVER POSSIBLE, LOCATE AIR DUCT DETECTORS/SENSORS WHERE THEY CAN
<br />BE CONVENIENTLY OBSERVED AND READILY SERVICED.
<br />DETECTOR/SENSOR
<br />EXHAUST RETURN AIR
<br />EXHAUST DAMPER DO NOT WCATE
<br />DETECTORYSENSOR HERE
<br />RETURN �IR DAMPER
<br />I
<br />FRESH AIR INTAKE-F_ 11 1 - SUPPLY AIR
<br />DO NOT LOCATE FILTER
<br />K_17
<br />DETECTOR/SENSOR HEVE BAN \-'DETECTOR/SENSOR OKAY
<br />FIGURE 3. DUCT HOUSING PLACEMENT - LOCATION OF DAMPERS
<br />7. LOCATE THE AIR DUCT DETECTORS/SENSORS IN RETURN AIR DUCTS AHEAD OF
<br />MIXING AREAS.
<br />8. DO NOT LOCATE AIR DUCT DETECTORS/SENSORS NEXT TO OUTSIDE AIR INLETS
<br />UNLESS YOU WANT TO MONITOR SMOKE ENTRY TO THE HANDLING SYSTEM FROM
<br />AN ADJACENT AREA.
<br />9. LOCATE AIR DUCT DETECTORS/SENSORS UPSTREAM OF AIR HUMIDIFIERS AND
<br />COOLING COILS.
<br />DUCT DETECTOR/SENSOR INSTALLATION
<br />1. TAPE THE TEMPLATE (SUPPLIED) ON THE DUCT SURFACE AS SHOWN IN
<br />FIGURE 4.
<br />NOTE: DO NOT POSITION THE TEMPLATE WITH EDGES ANGLED WITH RESPECT TO
<br />AIR FLOW DIRECTION (FIGURE 4).
<br />2. DRILL TWO 1 1/4 INCH (31.75 MM) HOLES (MARKED "A") AS
<br />LOCATED BY THE TEMPLATE. REMOVE TEMPLATE AFTER HOLES HAVE BEEN DRILLED.
<br />3. IF THE DUCT IS MORE THAN 3 FEET (0.9 M) WIDE, THEN PUNCH A 1-INCH
<br />(25.4 MM) HOLE IN THE DUCT WALL DIRECTLY OPPOSITE THE UPSTREAM
<br />1 1/4 INCH (31.75 MM) HOLE. SEE FIGURE 5. THIS HOLE IS USED TO
<br />SUPPORT THE INLET TUBE.
<br />FOR DUCT WIDTHS FOR DUCT WIDTHS
<br />3 FEET TO 95 INCHES 12 INCHES TO 3 FEET
<br />INSERT RUBBER PLUG
<br />THIS END OF INLET TUBE
<br />TUBE SUPPORT HOLE TOP VIEW
<br />FOR DUCTS MORE
<br />THAN 3 FEET WIDE OR CUT EXHAUST TUBE
<br />OR
<br />RE FLOW
<br />CTI
<br />ERN
<br />i TUB 0 T i
<br />INLET TUBE HOLE AIR FIL TO 1h OF DUCT
<br />DIRECTI WIDTH WHEN WIDTH
<br />FACE UPSTREAM N
<br />OF AIR FLOW INLET T , UBE HOLES IS LESS THAN 24"
<br />I"T",",
<br />FACE UPSTREAM
<br />EXHAUST TUBE OF AIR FLOW EXHAUST TUBE
<br />DO NOT INSERT RUBBER PLUG DO NOT INSERT RUBBER PLUG
<br />NOTE: AIRFLOW CAN BE IN EITHER DIRECTION. MAKE SURE THE INLET TUBE
<br />HOLES FACE UPSTREAM OF AIR FLOW.
<br />FIGURE 5. INLET TUBE ORIENTATION
<br />TAB
<br />SEE NOTE 1--_Z-o\
<br />INLET U
<br />TUBE RETAINER 0
<br />_Vy
<br />BRACKET -
<br />NOTES:
<br />1. THE TAB ON THE INLET TUBE
<br />RETAINER BRACKET INDICATES THE
<br />INLET HOLE SIDE OF THE PIPE.
<br />2. THE INLET TUBE MUST BE
<br />INSTALLED THROUGH THE HOLE IN THE
<br />HOUSING CORNER NEXT TO THE
<br />SMOKE PORT/AIR FLOW TEST HOLES.
<br />EXHAUST TUBE
<br />INLET TUBE HOLES FACE
<br />UPSTREAM OF AIR FLOW
<br />0 0 0
<br />SEE NOTE 2-`�� INLET
<br />TUBE
<br />FIGURE 6. INLET TUBE INSTALLATION
<br />TABLE 3. INLET TUBE SELECTION
<br />IR FLOW AIR FLOW
<br />R ECTION D I R ECTI O!N
<br />OVERALL DUCT WIDTH
<br />TUBE REQUIRED
<br />TUBE TYPE
<br />SUGGESTED TOTAL
<br />LENGTH
<br />12" (30 CM)
<br />2098-9796
<br />13" (33.02. CM)
<br />1h INCH (1.27 CP)
<br />LONGER THAN DUCT WIDTH
<br />HORIZONTAL DUCTS OVER 13" HIGH HORIZONTAL DUCTS UNDER 13" HIGH
<br />VERTICAL OR
<br />�NCX AIR FLOW
<br />DUCTS DIRECTION
<br />4*�14 'All.
<br />1110jN NEVER MOUNT AT AN ANGLE
<br />WITH RESPECT TO AIR FLOW
<br />13" (33.02 CM) TO
<br />23" (58 CM)
<br />2098-9804
<br />24" ('60.96 CM)
<br />1h INCH (1.27 CM)
<br />LONGER THAN DUCT WIDTH
<br />24" (60 CM) TO
<br />46" (1,16 M)
<br />2098-9797
<br />49" (125.46 CM)
<br />2" (5.8 CM)
<br />LONGER THAN DUCT WIDTH
<br />46" (1. 16 M) TO
<br />71 " (1.8 M)
<br />2098-9798
<br />73" (1.85 M)
<br />2" (5.8 CM)
<br />LONGER THAN DUCT WIDTH
<br />71 " (1.8 M) TO
<br />1 95" (2.4 M)
<br />2098-9799
<br />97" (2.45 M)
<br />2" (5.8 CM)
<br />LONGER THAN DUCT WIDTH
<br />FIGURE 4. TEMPLATE POSITIONING
<br />INLET TUBE SELECTION
<br />4. INLET TUBES SHOULD BE SELECTED AND CUT TO LENGTH AS SPECIFIED IN
<br />TABLE 3. AFTER TRIMMING THE INLET TUBE OPPOSITE THE SLOT, TAP
<br />RUBBER PLUG (SUPPLIED) INTO THE TRIMMED END. SEE FIGURE 5.
<br />REFER TO INSTALLATION INSTRUCTION DOCUMENT 574-776 FOR
<br />MORE DETAILED INFORMATION.
<br />AIR PRODUCTS PAM-SD 24VDC POLARIZED RELAY MODULE
<br />(SIMPLEX 4098-9843)
<br />SP
<br />FIC
<br />TIONS:
<br />• POWER REQUIREMENTS: 0.015 AMP @ 24VDC
<br />(17 VDC TO 32 VDC)
<br />• RELAY: U.L. RECOGNIZED SPOT
<br />• CONTACT RATING: 7 AMPS @ 120VAC & 28 VDC
<br />250 MICRO AMPS @ 5 VDC
<br />• AMBIENT TEMPERATURE: -50' F TO 85 'F (-50'C TO 85*C)
<br />• APPROVALS: UNDERWRITERS LABORATORIES LISTED
<br />• 12" 18 AWG WIRE LEADS
<br />• DIMENSIONS: 1-1/2"H X 1 7/8" W X 13/16" D
<br />(38.1mm H X 47.625mm W X 20.638mm D)
<br />FEATURES:
<br />* SINGLE SPDT RELAY
<br />* DOUBLE -SIDED ADHESIVE TAPE
<br />* MOUNTING SCREW
<br />* 5 WIRE NUTS
<br />COVER PLATE
<br />SUPPLIED BY CONTRACTO
<br />ANY SINGLE GANG BOX
<br />SUPPLIED BY CONTRACTOR
<br />10,0 AMP
<br />CONTACTS
<br />ED
<br />24VDC @ 0.015A
<br />(18 VDC TO 32 VDC)
<br />PRODUCT INFORMATION 4090-9001 IDNET SLC, SUPERVISED ADDRESSABLE INPUT MODULE (AIM)
<br />FEATURES:
<br />UL LISTED
<br />- ADDRESSABLE COMMUNICATIONS SUPPLY BOTH DATA
<br />AND POWER TO PROVIDE:
<br />- SUPERVISED STYLE B MONITORING OF NORMALLY OPEN DRY CONTACTS.
<br />- COMMUNICATIONS WIRING USING ONE TWISTED, SHIELDED WIRE PAIR.
<br />- COMPATIBLE WITH SIMPLEX ADDRESSABLE FIRE ALARM CONTROL PANELS.
<br />. COMPACT, SEALED CONSTRUCTION:
<br />- ALLOWS MOUNTING IN A SINGLE GANG BOX
<br />- REDUCES DUST INFILTRATION
<br />- PROVIDES CURRENT LIMITED MONITORING
<br />- TO MONITOR TAMPER SWITCH (SUPERVISORY) AND 4090-9810 BRACKET
<br />WATER FLOW SWITCH (ALARM) ON SAME CIRCUIT REQUIRED WHEN USI�
<br />- REQUIRES ONLY ONE ADDRESSABLE POINT THE SIMPLEX TRIM F 1� >G
<br />TES
<br />�TES
<br />SELECTABLE LATCHING OPERATION OPTIONAL WHEN USING
<br />MONITORS MOMENTARY CONTACT CLOSURES SUCH AS A CONTRACTOR SUPPLIED
<br />BACK BOX COVER OPTIONS; SINGLE GANG COVER
<br />RATE -OF RISE HEAT DETECTORS
<br />SEMI -FLUSH TRIM PLATE 4090-9806 (SHOWN)
<br />SPECIFICATIONS: WITH LIGHT PIPE FOR LED VIEWING
<br />- WIRE CONNECTIONS: SCREW TERMINALS FOR IN/OUT WIRING SURFACE TRIM PLATE 4090-9807
<br />FOR WIRE FROM #18 TO #14 AWG, WITH LIGHT PIPE FOR LED VIEWING��
<br />SINGLE GANG COVER W1 2 6/32
<br />- DIMENSIONS: 1 9/16" X 1 3/4" X 1 1/4"
<br />FLATHEAD SCREWS
<br />- TEMPERATURE RANGE: 32' F TO 158' F (0' C TO 70' C)
<br />(SUPPLIED BY CONTRACTOR) F
<br />- HUMIDITY: UP TO 93% RH AT 100* F
<br />* SUPERVISION RESISTOR: 6.8kn 1/2W, (SUPPLIED)
<br />SIMPLEX PART NO. 733-886
<br />- RESISTOR FOR CURRENT LIMITED OPERATION: 4.7kn 1/2W,
<br />WITH A 1.8kn 1/2W
<br />- INPUT REQUIREMENTS: N
<br />ORMALLY OPEN, DRY CONTACTS
<br />- HOUSING MATERIAL: BLACK THERMOPLASTIC
<br />DESCRIPTION:
<br />THE 4090-9001 IS AN ADDRESSABLE INPUT MODULE (AIM)
<br />WITH POWER AND COMMUNICATIONS SUPPLIED BY A TWO WIRE ADDRESSABLE
<br />CIRCUIT. IT PROVIDES LOCATION SPECIFIC ADDRESSABILITY
<br />TO A SINGLE INITIATING DEVICE (SUCH AS SINGLE STATION SMOKE
<br />TECTOR ALARM CONTACTS OR HEAT DETECTOR CONTACTS) OR
<br />DE
<br />MULTIPLE DEVICES AT THE SAME LOCATION BY MONITORING
<br />NORMALLY OPEN, DRY CONTACTS AND THE WIRING TO AN END -OF -LINE RESISTOR.
<br />CLOSURE OF THE MONITORED CONTACTS INITIATES AN ALARM OR
<br />OTHER RESPONSE AS PROGRAMMED AT THE FIRE ALARM
<br />CONTROL PANEL. AN OPEN IN THE MONITORED CIRCUIT WIRING
<br />WILL CAUSE A TROUBLE TO BE REPORTED.
<br />IF THE INITIATING DEVICE CONTACTS ARE MOMENTARY, SUCH AS
<br />FROM A RATE -OF -RISE HEAT DETECTOR, ENABLING THE LATCH
<br />FEATURE WILL MAINTAIN THE ALARM CONDITION UNTIL THE SYSTEM
<br />IS RESET. FOR APPLICATIONS WHERE THE CONTACT CLOSURE LATCHES,
<br />OR IF ITS CONDITION NEEDS TO BE TRACKED AT THE CONTROL PANEL T-
<br />NON-LATCHING OPERATION MAY BE ENABLED.
<br />WIRING NOTES:
<br />1 . ALL WIRING TO COMPLY WITH LOCAL CODE.
<br />2. CONDUCTORS MUST TEST FREE OF ALL GROUNDS.
<br />3. ONLY N.C. DRY CONTACTS ARE ALLOWED.
<br />4. MAXIMUM WIRE LENGTH (NO, 18 AWG) IS 400 FT. W/2081-9044
<br />OVER VOLTAGE PROTECTORS OR 400 FT. W/O PROTECTORS.
<br />5. A MAXIMUM QUANTITY OF DEVICES PER CIRCUIT: CONTROL PANEL
<br />MODULE DEPENDENT
<br />6. IF SHIELD IS PRESENT, CONNECT TO THE OUTGOING IDNet SHIELD
<br />TO PROVIDE A CONTINUOUS SHIELD OVER THE LENGTH OF THE
<br />FERMINED BY AHJ.
<br />IDNet CHANNEL. METHOD OF SPLICE DE
<br />7. REFER TO INSTALLATION INSTRUCTIONS 574-331.
<br />8. MAXIMUM ALLOWABLE LINE RUN FROM THE F.A.C.P. TO THE
<br />FARTHEST DEVICE, NOT TO EXCEED 2500 FEET.
<br />9. MAXIMUM TOTAL WIRE �INCLUDING ALL T-TAPS) FROM THE
<br />FIRE ALARM CONTROL ANEL
<br />10. FOR STYLE 6 CIRCUIT WIRING IT IS RECOMMENDED
<br />THAT THE PRIMARY (D AND THE BACK-UP (Z LINES
<br />BE IN SEPARATE WIRE RUNS AND IN COMPLIANCE
<br />WITH LOCAL REQUIREMENTS.
<br />11. REFER TO FIELD WIRING DIAGRAM 842-073
<br />FROM UL-USTE
<br />SHIELD-
<br />F.A.C.P. OR
<br />PREVIOUS DNet/MAPNET + - R
<br />�,LU DEVICE DNet/MAPNET B
<br />ill
<br />P
<br />SENSING OPERATION: PRIMARY IDNet/MAPNET SLC LINES
<br />SUPERVISED INPUT: N M N
<br />- 4090-9001 AIM WITH T-SENSE CAPABILITY HAS A
<br />SUPERVISED INPUT THAT MONITORS FOR CONTINUITY
<br />TO AN END -OF -LINE RESISTOR AND CAN DIFFERENTIATE
<br />BETWEEN A SHORT CIRCUIT CONTACT CLOSURE AND A
<br />CURRENT LIMITED CONTACT CLOSURE.
<br />FOUR STATE OPERATION:
<br />- NORMAL IS WHEN ALL CONTACTS ARE OPEN AND THERE
<br />IS CONTINUITY TO THE END -OF -LINE RESISTOR.
<br />- OPEN IS WHEN CONTINUITY DOES NOT EXIST TO THE END -OF -LINE
<br />RESISTOR, CAUSING A TROUBLE CONDITION.
<br />- SHORT, INDICATES THAT A CONTACT HAS CLOSED THAT IS
<br />DIRECTLY CONNECTED TO THE INPUT CIRCUIT.
<br />- CURRENT LIMITED INDICATES THAT A CONTACT HAS
<br />CLOSED BEYOND A SERIES CONNECTED CURRENT
<br />LIMITING RESISTOR. THIS OPERATION ALLOWS
<br />DIFFERENTIATION BETWEEN TWO DIFFERENT CONTACT733-886
<br />TYPES DUE TO THEIR WIRING LOCATION, AND REPORTING
<br />AS A SINGLE IDNET ADDRESSABLE POINT TO A
<br />410OU FIRE ALARM CONTROL PANEL.
<br />733-886
<br />(6.8K 1/2W)
<br />111[
<br />4090-900,
<br />"wo
<br />'IT In R4-iN
<br />UATE coo[.
<br />il I n-affin. 71001
<br />OPTIONAL SHIELD
<br />UL LISTED SINGLE
<br />GANG ELECTRICAL BOX (2 1/8" MIN. DEPTH)
<br />(SUPPLIED BY CONTRACTOR)
<br />0
<br />ADDRESS DIP SWITCHES UNDER
<br />RE -SEALABLE LABEL
<br />SEE INSTALLATION INSTRUCTIONS
<br />(574-331) FOR SETTINGS
<br />TO ADDITIONAL
<br />S - SHIELD
<br />DEVICES OR RETURN
<br />R - + IDNet/MAPNET
<br />TO FIRE ALARM
<br />CONTROL PANELFOR
<br />B- - IDNet/MAPNET
<br />STYLE 6 SYSTEM
<br />APPLICATION
<br />(2)
<br />16
<br />_121 SECONDARY IDNet/MAPNET SLC LINES
<br />1 E E Ifl M
<br />733-886
<br />(6.8K 1/2W)
<br />4098-9756 ADDRESSABLE ANALOG 4-WIRE DUCT SENSOR MAPNET II/IDNet SLC WITH 24VDC RELAY
<br />PRODUCT INFORMATION DUCT DETECTOR SELECTION CHART
<br />A
<br />S:
<br />COMPACT AIR DUCT SENSOR HOUSING WITH CLEAR COVER
<br />TO MONITOR FOR THE PRESENCE OF SMOKE
<br />INCLUDES FACTORY INSTALL TRUEALARM PHOTOELECTRIC SMOKE
<br />DETECTOR AND FEATURES:
<br />- INDIVIDUAL SENSOR INFORMATION PROCESSED BY THE HOST
<br />CONTROL PANEL TO DETERMINE SENSOR STATUS
<br />- DIGITAL TRANSMISSION OF ANALOG SENSOR VALUES VIA
<br />M M
<br />- PROGRAMMABLE SENSITIVITY CONSISTENT ACCURACY
<br />ENVIRONMENTAL COMPENS&ION STATUS TESTING, AND
<br />MONITORING OF SENSOR DIRT ACCUMULATION
<br />MODEL:
<br />- DUCT SENSOR HOUSING WITH SUPERVISED OUTPUT FOR
<br />,I,, Tp, r mr-Tr nri � Mrn I I In 17� I rn A I All I � 1111
<br />iviu-11 - 1-viv- ni-1- - -
<br />�IRELAYS ARE UNDER PAN L CONTROL AND CAN BE
<br />CTIVATED MANUALLY OR BY A SEPARATE ALARM/INPUT)
<br />GENERAL FEATURES:
<br />UL LISTED TO STANDARD 268A
<br />CLEAR COVER ALLOWS VISUAL INSPECTION
<br />TEST PORTS PROVIDE FUNCTIONAL SMOKE TESTING ACCESS
<br />WITH COVER IN PLACE
<br />MOUNTS TO RECTANGULAR DUCTS OR ROUND DUCTS
<br />(MINIMUM SIZE 8" SQUARE OR 18" DIAMETER)
<br />MAGNETIC TEST FEATURE FOR ALARM INITIATION AT HOUSING
<br />OPTIONAL WEATHERPROOF ENCLOSURE IS AVAILABLE
<br />SEPARATELY (REFER TO DATA SHEET S4098-0032)
<br />DIAGNOSTIC LEDS (ON INTERFACE BOARD):
<br />- RED ALARM TROUBLE LED FOR SENSOR STATUS AND
<br />COMMUNICA�IONS POLLING DISPLAY
<br />- YELLOW LED FOR OPEN OR SHORTED TROUBLE INDICATION FOR DUCT WIDTHS FOR DUCT WIDTHS
<br />OF SUPERVISED RELAY CONTROL 2098-9808 2098-9806 3' TO 95" 8" TO 3'
<br />SAMPLING TUBES (ORDERED SEPARATELY):
<br />AVAILABLE IN MULTIPLE LENGTHS TO MATCH DUCT SIZE REMOTE STATUS/ALARM TEST STATION
<br />INSTALLED AND SERVICED WITH HOUSING IN PLACE INDICATOR
<br />REWE MODULE OPTIONS (ORDERED SEPARATELY):
<br />- RED STATUS/ALARM LED (2098-9808) (OPTIONAL)
<br />- TEST STATION WITH LED (2098-9806)
<br />80'
<br />2 .. TN'DICATOR
<br />- RELAYS USED (4098-9843) ALARM
<br />SPECIFICATIONS: RE�DM
<br />ALA[
<br />GENERAL SPECIFICATIONS LED
<br />(f
<br />DUCT SMOKE SENSOR HOUSING WITH PHOTOELECTRIC SENSOR
<br />MODEL
<br />DESCRIPTION
<br />___77MFA71BILI7
<br />4098-9756
<br />DUCT HOUSING WITH SUPERVISED MULTIPLE RELAY CONTRO FSOR Up
<br />TO 15, 4098-9843 RELAYSR�QRDERED SEPARATELY), RE RE
<br />SEPARATE 24 VDC FIRE ALA POWER AND RELAY ND-VFI-
<br />RESISTOR
<br />�SIMPLEX FIRE ALARM CONTROL MODELS
<br />4008, 4010, 4020, 4100, AND 4120.
<br />REMOTE LED INDICATOR AND TEST STATION, SELECT ONE IF REQUIRED
<br />M L
<br />F-2098-9808
<br />RED LED STATUS INDICATOR
<br />U,SE SINGLE GANG BOX,
<br />3 H X 2" W X 2" D
<br />(76 mm X 51 mm X 51 mm
<br />��8-9806
<br />F
<br />TEST STATION WITH KEYSWITCH AND RED LED STATUS TURNING
<br />SWITCH TO TEST INITIATES ALARM FOR SYSTEM TESTIN
<br />AIR VELOCITY RANGE (LINEAR FT/MIN)
<br />300 TO 4000 FT/min (91 TO 1220 m/min)
<br />SENSOR SENSITIVITY RANGE
<br />0.2% TO 3.7% PER FOOT OF OBSCURATION, SELECTABLE
<br />AT HOST CONTROL PANEL
<br />UL LISTED TEMPERATURE RANGE
<br />32' F TO 100' F (0' C TO 38. C
<br />OPERATING TEMPERATURE RANGE
<br />32- F TO 122- F (0' C TO 50' C)
<br />STORAGE TEMPERATURE RANGE
<br />0' F TO 140- F (-18' C TO 60- C)
<br />HUMIDITY RANGE
<br />10% TO 95% RH, NON -CONDENSING
<br />HOUSING COLOR
<br />BLACK BASE WITH CLEAR COVER
<br />WIRING CONNECTIONS
<br />TERMINAL BLOCKS, 18 TO 12 AWC
<br />REMOTE STATUS7T97M _LED AND TEST STATION WITH REMOTE STATUS/ALARM LED
<br />REMOTE ALARM LED CURRENT
<br />1.2 mA NO IMPACT -TO ALARM CURRENT (2098-9808
<br />OR 209'8-9806)
<br />TEST STATION KEYSWITCH CURRENT
<br />3.3 mA, NO IMPACT TO ALARM CURRENT (2098-9806)
<br />REMOTE ALARM LED AND TEST
<br />STATION DISTANCE
<br />250 FF. (76m) MAXIMUM
<br />ADDRESSABLE OPERATION
<br />DATA COMMUNICATIONS
<br />MAPNETII OR IDNET SLC COMMUNICATION, AUTO -SELECT
<br />I ADDRESS PER HOUSING, PROVIDES OPERATING POWER
<br />�TO MODEL 4098-9755
<br />MODEL 4098-9756 WITH SUPERVISED MULTIPLE RELAY CONTROL, REQUIRES SEPARATE FUSED
<br />24 VDC FROM FIRE ALARM POWER SUPPLY
<br />INPUT VOLTAGE
<br />17-32 VDC (24 VDC NOMINAL)
<br />STANDBY CURRENT
<br />3 mA @ 24 VDC
<br />ALARM CURRENT
<br />15 mA @ 24 VDC, ADD 15 mA ADDITIONAL FOR EACH
<br />. 40qR-qP,4� RELAY
<br />4098-9843 RELAY OUTPUT RATINGS, SINGLE FORM C
<br />COIL CURRENT
<br />15 mA 0 24-VDC UP TO 15 MAX. PER RELAY C-0NT-RTL
<br />OUTPUT
<br />RELAY CONTACTS, RESISTIVE RATINGS-
<br />7 A @ 28 VDC & 120 VAC: 250 uA @ 5 VDC
<br />LOCATION DISTANCE
<br />500 FT. (152m) MAX. TO RELAY COILS, RELAY M JSTB E
<br />WITHIN 3 FT. Cfm) OF DEVICE BEING CONTROLLED PER
<br />NFPA 72, SECTION 3-9.2.1
<br />PRODUCT INFORMATION
<br />FEATURES:
<br />- ILL LISTED
<br />* CALIFORNIA STATE FIRE MARSHAL LISTING NUMBERS:
<br />2908-9806 ALARM INDICATOR 7300-0026:150
<br />o MOUNTING: FLUSH
<br />- FINISH: CHROME OR STAINLESS STEEL
<br />SPECIFICATIONS:
<br />. ALARM CURRENT: 2.8 mA
<br />- DIMENSIONS OF BOX: 2 "W X 3"H X 2"D
<br />DESCRIPTION:
<br />SEE NOI
<br />3, 4
<br />TUBE SUPPORT HOLE SHALL BE USED
<br />FOR DUCTS MORE THAN 3 FEET WIDE
<br />INSERT RUBBER PLUG
<br />X A ST TUBE
<br />CUT TO 1/2 OF
<br />DUCT WHEN < 24
<br />DO NOT INSERT
<br />RUBBER PLUG
<br />4098-9756
<br />4-WIRE DUCT SENSOR
<br />SW2 1 o
<br />oMr=
<br />2 z
<br />3
<br />4
<br />5
<br />6
<br />7 173M
<br />8 E=lw
<br />ADDRESS
<br />SWITCH
<br />TB1F1
<br />2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
<br />1� (? ? ? 9 (� (? (? (� (� ? (P 9 � ?
<br />I 'LE
<br />q
<br />��
<br />I TEST I MAP +I MAP I +24VI 24C I 'ALM-
<br />.
<br />�-j
<br />T F
<br />(OPTIONAL)
<br />2098-9806
<br />REMOTE ALARM
<br />INDICATOR/
<br />KEYSWITCH
<br />RED
<br />ALARM
<br />LED
<br />TEST
<br />I
<br />SEE NOTES 3,4
<br />4098-9756
<br />4-WIRE DUCT SENSOR
<br />SW21
<br />2 z
<br />3 =w
<br />4 1
<br />5
<br />6
<br />7
<br />8 E=3w
<br />ADDRESS
<br />SWITCH
<br />1
<br />1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
<br />y y y y y y y y Y,?
<br />- _ +24VI
<br />TEST I MA P +,MAP,-, I -ALM-
<br />'24C
<br />_T
<br />IRED�L
<br />BILK
<br />�REI�
<br />B
<br />tt
<br />TO OTHER MAPNETII/
<br />IDNET SLC DEVICES
<br />JSTED
<br />�01_ PANEL
<br />SIMPLEX 4010, 4020
<br />4008, 4100+ OR 4120 SEE NOTE 2 OR
<br />RETURN TO FACP
<br />MAPNET I/IDNet H WHIO 1 2 W 10K EOL IELD FOR STYLE 6 SLC
<br />SHIELD BLU-c- RESISTOR SH HT
<br />(OPTIONAL) TOTE 1 4-098-9843
<br />PAM SD YEL-N..C. 4081-9008 -
<br />POWER CIRCUIT + RE- ORG-N.O. C- BLU- 4098-9843
<br />24 VDC + 1/2 W 10K EOL N.C�YEL- PAM-SD 0
<br />0 RE RESISTOR N.O�ORG- RELAY
<br />WIRING NOTES: +
<br />k_�
<br />WH T
<br />W'T'*
<br />LAY C- 3L
<br />C_YE
<br />O_ 0
<br />RE RED-* 4081-9008 7r�NR
<br />1. DUCT SENSOR WIRING IS1 2 TO 18 AWG.
<br />2. MAXIMUM QUANTITY OF DEVICES PER CIRCUIT IS 127 FOR 4020, FIRE
<br />4100+, OR 4120, AND 250 FOR THE 4010 PANEL SMOKE AIR
<br />DAMPER HANDLING
<br />IRING. LH IT
<br />3. THE 2098-9806 AND 2098-9808 ARE POLARIZED, OBSERVE COLOR -CODED W UN
<br />4. MAXIMUM WIRE LENGTH TO TEST TERMINALS AND REMOTE LED IS 250 FEET.
<br /><S> 4098-9843 PAM-SD RELAY (AIR PRODUCTS & CONTROL LIMITED) ARE RATED AT
<br />7 AMPS 28 VDC/10 AMPS @ 115 VAC. MAXIMUM WIRE LENGTH TO PAM-SD RELAYS IS FSD POWER
<br />AHU POWER
<br />500 FF. (15 PAM-SD RELAYS MAX.). WIRING FROM THE RELAY TO THE (BY OTHERS)
<br />DEVICE IT IS CONTROLLING SHOULD BE NO MORE THAN 3 FT. (PER NFPA 72), (BY OTHERS)
<br />2098-9806 REMOTE ALARM INDICATOR/KEY SWITCH
<br />2098-9806 REMOTE TEST STATION, PROVIDES A REMOTE RED
<br />ALARM LED STATUS INDICATOR AND A REMOTE TEST KEY
<br />ACTIVATED SWITCH MOUNTED ON A SINGLE GANG STAINLESS STEEL
<br />PLATE. THE LED WILL PULSE TO INDICATE NORMAL OPERATION OF
<br />THE DUCT DETECTOR AND WILL ENERGIZE CONTINUOUS WHEN IN
<br />ALARM OR IN TROUBLE. (THE EXACT STATUS OF THE SENSOR
<br />WILL BE DISPLAYED AT THE FIRE ALARM CONTROL PANEL.) TURNING
<br />THE TEST SWITCH TO "FEST" WILL INITIATE AN ALARM AND ALLOW
<br />THE RESULTING SYSTEM RESPONSES TO BE VERIFIED.
<br />WIRING:
<br />• MINIMUM 18 AWG OR TO LOC�L CODE.
<br />• CONDUCTORS MUST TEST FREE OF ALL GROUNDS.
<br />• REMOTE ALARM LED IS POLARIZED, OBSERVE
<br />COLOR CODED WIRING.
<br />• ONE INDICATOR MAY BE INSTALLED PER DETECTOR.
<br />CONNECT TO REMOTE
<br />ALARM LED OUTPUT OF
<br />APPROPRIATE INITIATING
<br />DEVICES
<br />CONNECT TO REMOTE
<br />TEST SWITCH INPUT ON
<br />APPROPRIATE INITIATING
<br />DEVICES
<br />FLUSH MOUNTING
<br />2098-9806
<br />BACK VIEW
<br />STANDARD SINGLE
<br />GANG BOX 2" X 3"
<br />MINIMUM DEPTH 2"
<br />SUPPLIED BY CONTRACTOR
<br />4090-9002 IDNet SLC, INDIVIDUAL ADDRESSABLE OUTPUT MODULE RELAY (AOM)
<br />PRODUCT INFORMATION
<br />FEATURES:
<br />- UL LISTED
<br />- A SINGLE ADDRESSABLE POINT BOTH CONTROLS A 2A FORM
<br />"C" CONTACT AND TRACKS ITS STATUS
<br />- COMPATIBLE WITH SIMPLEX MODEL 4010 AND 4100 ADDRESSABLE
<br />FIRE ALARM CONTROL PANEL
<br />- LATCHING RELAY DESIGN ALLOWS DATA AND POWER TO BE
<br />BOTH SUPPLIED BY IDNet COMMUNICATIONS
<br />- COMPACT, SEALED CONSTRUCTION:
<br />- SCREW TERMINALS FOR WIRING CONNECTIONS
<br />- REDUCES DUST INFILTRATION
<br />SPECIFICATIONS:
<br />- RELAY IAM POWER: SUPPLIED BY IDNet COMMUNICATIONS
<br />- RELAY IAM CONTACTS (FORM "C", SPDT)
<br />- POWER LIMITED RATING: 2A @ 24VDC, TRANSIENT SUPPRESSED
<br />LOADS, 1A @ 24VDC FOR INDUCTIVE LOADS
<br />- NON POWER LIMITED RATING: 1/2A @ 24VAC, TRANSIENT SUPPRESSED
<br />LOADS, 1A @ 24 VDC FOR INDUCTIVE LOADS
<br />- WIRE CONNECTIONS: SCREW TERMINALS FOR IN/OUT
<br />WIRING, #18 TO #14 AWG WIRE
<br />o COMPATIBLE WITH SIMPLEX 2081-9044 OVER VOLTAGE PROTECTORS
<br />- DIMENSIONS: 4 1/8"H x 4 1/8"W x 1 3/8"D (105mm x 105mm x 35mm)
<br />- HOUSING MATERIAL: BLACK THERMOPLASTIC
<br />- MOUNTING PLATE MATERIAL: SHEET METAL, GALVANIZED
<br />- TEMPERATURE RANGE: 32* F TO 120* F (0' C TO 49- C)
<br />INTENDED FOR INDOOR OPERATION
<br />o HUMIDITY RANGE UP TO 93% RH AT 100' F (38' C)
<br />DESCRIPTION:
<br />IDNet SLC RELAY MODULES ALLOW THE SIMPLEX FIRE ALARM
<br />CONTROL PANEL TO CONTROL A REMOTELY LOCATED FORM
<br />"C" CONTACT USING IDNet ADDRESSABLE COMMUNICATIONS
<br />FOR BOTH DATA AND POWER. TYPICAL APPLICATIONS
<br />WOULD BE FOR SWITCHING LOCAL POWER FOR CONTROL
<br />FUNCTIONS SUCH AS ELEVATOR CAPTURE, OR CONTROL OF
<br />HVAC COMPONENTS, PRESSURIZATION FANS, DAMPERS, ETC.
<br />RELAY STATUS IS ALSO COMMUNICATED REQUIRING ONLY ONE
<br />DEVICE ADDRESS.
<br />WIRING NOTES:
<br />1 . IDNet LINES ARE TO BE #18 AWG TWISTED PAIR (CONSULT
<br />SG SALES ENGINEERING FOR EXCEPTIONS).
<br />2. MAXIMUM ALLOWABLE LINE RUN, FROM THE F.A.C.P. TO THE FARTHEST
<br />DEVICE, NOT TO EXCEED 2500 FEET.
<br />3. MAXIMUM QUANTITY OF DEVICES PER CIRCUIT: CONTROL PANEL
<br />MODULE DEPENDENT
<br />4. CONTRACTOR WIRING TO RELAY CONTACTS IS UNSUPERVISED.
<br />USE #14 AWG WIRE TO LOCAL CODE.
<br />5. RELAY CONTACTS RATED 2A, 24VDC (1A FOR INDUCTIVE LOAD)
<br />RELAY CONTACTS RATED 0.5A 120VAC (NON POWER LIMITED)
<br />FOR POWER -LIMITED OPERATION, POWER MUST BE PROVIDED
<br />FROM FACP OR POWER -LIMITED POWER SUPPLY LISTED FOR FIRE
<br />PROTECTIVE SIGNALING USE.
<br />6. SEE INSTALLATION INSTRUCTIONS 574-184.
<br />7. IF SHIELD IS PRESENT, CONNECT TO THE OUTGOING IDNet SHIELD
<br />TO PROVIDE A CONTINUOUS SHIELD OVER THE LENGTH OF THE
<br />IDNet CHANNEL. METHOD OF SPLICE DETERMINED BY AHJ.
<br />8. WHEN CONNECTED TO A NON POWER -LIMITED SOURCE, THE WIRING
<br />MUST MAINTAIN A MINIMUM 1/4 INCH SEPARATION FROM IDNet WIRING.
<br />9. WHEN USED WITH NON POWER -LIMITED SOURCE, THE "POWER LIMITED
<br />WIRING" INDICATION ON THE DEVICE LABEL MUST BE OBLITERATED.
<br />10. WHEN BOTH POWER -LIMITED AND NON POWER -LIMITED SOURCES
<br />ARE PRESENT, USE TYPE FPL, FPLR OR FPLP POWER LIMITED
<br />CABLE FOR POWER -LIMITED CIRCUITS.
<br />11. MAXIMUM TOTAL WIRE (INCLUDING ALL T-TAPS) ON CIRCUIT, FROM THE
<br />F.A.C.P. NOT TO EXCEED 10,000 FEET OR .58uF. (CLASS B ONLY)
<br />12. REFER TO FIELD WIRING DIAGRAM 842-073
<br />V FCWI G
<br />2-GANG BACK BOX COVER
<br />SUPPLIED BY CONTRACTOR
<br />r -on,
<br />Q)
<br />4" SQUARE X 2 1/8" DEEP BOX
<br />SUPPLIED BY CONTRACTOR
<br />A41 Is 51 DI
<br />NORMALLY CLOSED (N.C.)
<br />COMMON
<br />- - -
<br />F_ . 11 11
<br />mo NORMALLY OPEN (N.O.) NORMALLY OPEN (N.O.)
<br />F F
<br />111111.1111L we
<br />F_ MH m:
<br />F_
<br />NOT USED NOT USED
<br />I I I 1
<br />0 0 0
<br />I L - - - - - - - - - - - - - - - - -
<br />L- - - - - - - - - - - - - - - - - -
<br />PRIMARY SECONDARY IDNet SLC LINES
<br />IDNet SLC LIN
<br />91 [21 M 0
<br />OPTIONAL SHIELD
<br />(c�� S S
<br />RI 18 R I I B
<br />+ +
<br />FROM PREVIOUS SLC DEVICE IDNet SLC
<br />OR F.A.C.P. TO F.A.C.P.
<br />341 [51 MI F91
<br />NORMALLY CLOSED (N.C.)
<br />COMMON
<br />ADDRESS SETTING UNDER
<br />RE -SEALABLE LABEL
<br />CURTIS ENGINEERING SERVICE, LLC - CA#31561
<br />JAMES M. CURTIS, P.E. - PE#37912
<br />29775 BAYHEAD ROAD
<br />DADE CITY, FLORIDA 33523
<br />DEL EGA TED ENGINEER OF RECORD
<br />Digitally signed x
<br />!; �\� 0 M: ! 4 ///,
<br />N , _!�j
<br />�A,
<br />;ot
<br />by James Curtis �000_
<br />No.
<br />Date:
<br />dop
<br />- - OF
<br />2016.07.22 wwo, N
<br />- - - of%LOR
<br />om
<br />'09:33:25 -04'00 0111111%%
<br />I
<br />04 C>
<br />CID 00
<br />4 1
<br />it C?
<br />lov
<br />c14
<br />C9 cp
<br />cl) ce)
<br />co CID
<br />a- U_
<br />a qk
<br />LU
<br />C-4
<br />LU co
<br />0 Z�
<br />c:, C6
<br />Fn - to
<br />CM4 w to, A
<br />Ei LLJ c,) -
<br />-1 co
<br />U_ 6i
<br />,:If 2
<br />c=) d- >
<br />CDMW
<br />Ln Lo Lu
<br />in cn
<br />'7"
<br />0
<br />U)
<br />I
<br />>
<br />0
<br />2-7
<br />Uj
<br />ry
<br />0
<br />Uj
<br />0
<br />06
<br />0 C/)
<br />0
<br />U)
<br />X
<br />(If
<br />LU
<br />o
<br />0
<br />I-_
<br />a_
<br />co
<br />LU
<br />LU
<br />cj
<br />0
<br />--I
<br />w Nd
<br />=) of
<br />co <
<br />ce)
<br />cy)
<br />C)
<br />0
<br />LU _j
<br />n -1
<br />(now
<br />0 fn _j
<br /><
<br />o >-
<br />o!f (=:) M:
<br />o U-) 0-
<br />_j (::) LU
<br />LL t*-- P114
<br />B. KNICKLE
<br />DRAWN BY.
<br />CHECKED BY: F. REINHART
<br />ISSUE DATE: 7119/16
<br />I I
<br />JOB #: 292415807
<br />PROJECT#.. 1 292:993523001
<br />SIMPLEXGRINNELL @ 2016
<br />SYSTEM:
<br />FIRE ALARM SYSTEM
<br />SHEET:
<br />WIRING TYPICALS
<br />FA-702