15104- PENETRATION FIRESTOPPING
<br />GENERAL
<br />1.01 RELATED DOCUMENTS
<br />A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
<br />and Division 01 Specification Sections, apply to this Section.
<br />1.02 SUMMARY
<br />1.03 Section Includes:
<br />1. Penetrations in fire -resistance -rated walls.
<br />2. Penetrations In horizontal assemblies.
<br />3. Penetrations in smoke barriers.
<br />A. Related Sections:
<br />1. Division 07 Section "Fire -Resistive Joint Systems" for joints in or between fire -resistance -rated
<br />construction, at exterior curtain-wall/floor intersections, and in smoke barriers.
<br />1.04 SUBMITTALS
<br />A. Product Data: For each type of product indicated.
<br />B. System Schedule: For each penetration firestoppIng system. Include location and design designation
<br />of qualified testing and inspecting agency and the following:
<br />I . Documentation, including illustrations, from a qualified testing and inspecting agency that Is applicable
<br />to each penetration firestopping system configuration for construction and penetrating items.
<br />2. Types of penetrating items.
<br />3. Types of constructions penetrated, Including flre-resistance ratings and, where applicable, thicknesses
<br />of construction penetrated.
<br />4. Provide single composite schedule of firestopping systems regardless of installation responsibility.
<br />Separate schedules from multiple subcontractors are not acceptable.
<br />5. Size: 8 1/2 by 11 inches in 3-ring binder.
<br />6. Number of submittals: Two copies.
<br />a. One copy to be maintained at site and provided to Owner with Operation Maintenance manuals.
<br />7. Where Pro ect conditions require modification to a qualified testing and Inspecting agency's Illustration
<br />i
<br />for a particular penetration firestopping condition, submit illustration, with modifications marked,
<br />approved by penetration firestopping manufacturers fire -protection engineer as an engineering
<br />as an engineering judgment or equivalent fire -resistance -rated assembly.
<br />C. Qualification Data: For qualified Installer.
<br />D. Installer Certificates: From Installer indicating penetration firestopping has been Installed In compliance with
<br />requirements and manufacturer's written recommendations.
<br />E. Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency,
<br />for penetration firestopping.
<br />1.05 QUALITY ASSURANCE
<br />A. Installer Qualifications: A firm that has been approved by FM Global according to FM Global 4991, "Approval
<br />of Firestop Contractors," or been evaluated by UL and found to comply with its "Qualified Firestop Contractor
<br />Program Requirements."
<br />B. Fire -Test -Response Characteristics: Penetration firestopping shall comply with the following requirements:
<br />1. Penetration firestopping tests are performed by a qualified testing agency acceptable to authorities
<br />having jurisdiction.
<br />2. Penetration firestopping is identical to those tested per testing standard referenced in "Penetration
<br />Firestopping" Article. Provide rated systems complying with the following requirements:
<br />a. Penetration firestopping products bear classification marking of qualified testing and inspecting agency.
<br />b. Classification markings on penetration firestopping correspond to designations listed by the following:
<br />3. UL in its 'Fire Resistance Directory."
<br />C. Preinstallation Conference: Conduct conference at Project site prior to start of mechanical and electrical systems.
<br />1. Discuss firestopping requirements and other preparatory work to be performed by other trades.
<br />2. Review firestopping details and installation sequence for each type of penetration firestopping.
<br />3. Review and finalize construction schedule and verify availability of materials, and personnel to make
<br />progress and avoid delays.
<br />4. Review required inspecting procedures.
<br />1.06 PROJECT CONDITIONS
<br />A. Environmental Limitations: Do not install penetration firestopping when ambient or substrate temperatures are
<br />outside limits permitted by penetration firestopping manufacturers or when substrates are wet because of rain,
<br />frost, condensation, or other causes.
<br />B. Install and cure penetration firestopping per manufacturer's written instructions using natural means of ventilations or,
<br />where this Is inadequate, forced -air circulation.
<br />1.07 COORDINATION
<br />A . Coordinate construction of openings and penetrating items to ensure that penetration firestopping Is Installed according
<br />to specified requirements.
<br />B . Coordinate sizing of sleeves, openings, core -drilled holes, or cut openings to accommodate penetration firestopping.
<br />PRODUCTS
<br />2.01 MANUFACTURERS
<br />A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
<br />1. A/D Fire Protection Systems, Inc.
<br />2. Hilti, Inc.
<br />3. 3M Fire Protection Products.
<br />2.02 PENETRATION FIRESTOPPING
<br />A. Provide penetration firestopping that is produced and installed to resist spread of fire according to requirements indicated,
<br />resist passage of smoke and other gases, and maintain original fire -resistance rating of construction penetrated. Penetration
<br />firestopping systems shall be compatible with one another, with the substrates forming openings, and with penetrating items, If any.
<br />B. Penetrations in Fire -Resistance -Rated Walls: Provide penetration firestopping with ratings determined per ASTM E 814 or UL 1479,
<br />based on testing at a positive pressure differential of 0.01 inch wg (2.49 Pa).
<br />1. Fire- resistance -rated walls Include fire walls, flre-barrler walls, smoke-banler walls and fire partitions.
<br />2. F-Rating: Not less than the fire -resistance rating of constructions penetrated.
<br />C. Penetrations in Horizontal Assemblies: Provide penetration firestopping with ratings determined per ASTM E814 or UL 1479, based on
<br />testing at a positive pressure differential of 0.01 inch wg (2.49 Pa).
<br />1. Horizontal assemblies include floors and ceiling membranes of roof/ceiling assemblies.
<br />2. F-Rating: At least 1 hour, but not less than the fire -resistance rating of constructions penetrated.
<br />3. T-Rating: At least I hour, but not less than the fire -resistance rating of constructions penetrated except for floor penetrations within the cavity of a wall.
<br />D. Penetrations in Smoke Barriers: Provide penetration firestopping with ratings determined per UL 1479.
<br />L-Rating: Not exceeding 5.0 cfm/sq.ft. (0.025 cu. m/s per sq. m) of penetration opening at 0.30 inch wg (74.7 Pa) at both ambient
<br />and elevated temperatures.
<br />E. Exposed Penetration Firestopping: Provide products with flame -spread and smoke -developed indexes of less than 25 and 450, respectively, as determined perASTM E 84.
<br />F. VOC Content: Provide penetration firestopping that complies with the following limits for VOC content when calculated according to 40 CFR 59, Subpart D (EPA Method 24):
<br />Architectural Sealants: 250 g/L.
<br />2. Sealant Primers for Nonporous Substrates: 250 g/L.
<br />3. Sealant Primers for Porous Substrates: 775 g/L.
<br />G. Accessories: Provide components for each penetration firestopping system that are needed to install fill materials and to maintain ratings required.
<br />Use only those components specified by penetration firestopping manufacturer and approved by qualified testing and Inspecting agency for firestopping Indicated.
<br />1. Permanent forming/damming/backing materials, including the following:
<br />a. Slag -wool -fiber or rock -wool -fiber insulation.
<br />b. Sealants used in combination with other forming/damming/backing materials to prevent leakage of fill materials in liquid state.
<br />c. Fire -rated form board.
<br />d. Fillers for sealants.
<br />2. Temporary forming materials.
<br />3. Substrate primers.
<br />4. Collars.
<br />5. Steel sleeves.
<br />2.03 MIXING
<br />A. For those products requiring mixing before application, comply with penetration firestopping manufacturer's written instructions for accurate proportioning of
<br />materials, water (if required)r type of mixing equipment, selection of mixer speeds, mixing containers, mixing time, and other items or procedures needed to
<br />produce products of uniform quality with optimum performance characteristics for application Indicated.
<br />EXECUTION
<br />3.01 EXAMINATION
<br />A. Examine substrates and conditions, with Installer present, for compliance with requirements for opening configurations, penetrating items, substrates,
<br />and other conditions affecting performance of the Work.
<br />B. Proceed with installation only after unsatisfactory conditions have been corrected.
<br />3.02 PREPARATION
<br />A. Surface Cleaning: Clean out openings immediately before installing penetration firestopping to comply with manufacturer's written
<br />instructions and with the following requirements:
<br />1. Remove from surfaces of opening substrates and frDm penetrating items foreign materials that could interfere with adhesion of penetration firestopping.
<br />2. Clean opening substrates and penetrating items to produce clean, sound surfaces capable of developing optimum bond with penetration
<br />firestopping. Remove loose particles remaining from cleaning operation.
<br />3. Remove laitance and form -release agents from concrete.
<br />3.03 INSTALLATION
<br />A. General: Install penetration firestopping to comply with manufacturer's written installation instructions and published drawings for products and applications indicated.
<br />B. Install forming materials and other accessories of types required to support fill materials during their application and in the position
<br />needed to produce cross -sectional shapes and depths required to achieve fire ratings indicated.
<br />1. After installing fill materials and allowing them to fully cure, remove combustible forming materials and other accessories not indicated as
<br />permanent components of firestopping.
<br />C. Install fill materials for firestopping by proven techniques to produce the following results:
<br />Fill voids and cavities formed by openings, forming materials, accessories, and penetrating items as required to achieve fire -resistance ratings indicated.
<br />2. Apply materials so they contact and adhere to substrates formed by openings and penetrating items.
<br />3. For fill materials that will remain exposed after completing the Work, finish to produce smooth, uniform surfaces that are flush with adjoining finishes.
<br />3.04 IDENTIFICATION
<br />A. Identify penetration firestopping with preprinted metal or plastic labels. Attach labels permanently to surfaces adjacent to and within 6 inches (150 mm)
<br />of firestopping edge to labels will be visible to anyone seeking to remove penetrating items or firestopping. Use mechanical fasteners or self -adhering -type
<br />labels with adhesive capable of permanently bonding labels to surfaces on which labels are placed. Include the following Information on labels:
<br />1. The words 'Warning - Penetration Firestopping - Do Not Disturb. Notify Building Management of Any Damage."
<br />2. Contractor's name, address, and phone number.
<br />3. Designation of applicable testing and inspecting agency.
<br />4. Date of installation.
<br />5. Manufacturer's name.
<br />6. Installer's name.
<br />3.05 FIELD QUALITY CONTROL
<br />A. Inspection: Manufacturer's representative to inspect ten percent ofpenetration firestopping applications, in each phase, and provide written report
<br />indicating compliance with manufacturer's systems and deficiencies to be corrected.
<br />B. Where deficiencies are found or penetration firestopping is damaged or removed because of testing, repair or replace penetration
<br />firestopping to comply with requirements.
<br />C. Proceed with enclosing penetration firestopping with other construction only after Inspection reports are issues and installations comply with requirements.
<br />3.06 CLEANING AND PROTECTION
<br />A. Clean off excess fill materials adjacent to openings as the Work progresses by methods and with cleaning materials that are approved in
<br />writing by penetration firestopping manufacturers and that do not damage materials in which openings occur.
<br />B. Provide final protection and maintain conditions during and after Installation that ensure that penetration firestopping is without damage or
<br />deterioration at time of Substantial Completion. If, despite such protection, damaqe or deterioration occurs, immediately cut out and remove
<br />damaged or deteriorated penetration firestopping and install new materials to procluce systems complying with specified requirements.
<br />PLUMBING SYSTEMS INSULATION
<br />SECTION 15250
<br />PLUMBING SYSTEMS INSULATION
<br />PART 1 - GENERAL
<br />1.01 DEFINITIONS
<br />A. Exposed - Equipment, ducts and piping in areas which will be visible without removing ceilings or opening access
<br />panels.
<br />B. Concealed - Installed above ceiling, in walls or chases.
<br />C. Outdoors - Exposed to the weather or ambient conditions.
<br />D. Underground - Buried.
<br />1.02 CERTIFICATION/QUALITY ASSURANCE
<br />A. Insulation, adhesives, coatings, sealers, tapes, shall have a flame spread rating of 25 or less and smoke
<br />development of 50 or less in accordance with ASTM E-84 and UL 723
<br />B. Materials shall meet the requirements of NFPA 90-A.
<br />1.03 SUBMITTALS
<br />A. Submit manufacturer's product data and installation procedures for review.
<br />PART 2 - PRODUCTS
<br />2.01 PIPE AND EQUIPMENT INSULATION
<br />A. Materials for Pipe and Equipment: Provide factory premolded or shop or site mitered segment type insulation for
<br />pipe, pipe fittings, and valves.
<br />B . Fitting insulation: Same thickness and material as adjoining pipe insulation.
<br />C. Flexible Tubular Elastomeric:
<br />1. Provide fire -retardant closed -cell slip-on flexible type. Minimum "R" value of 2.57.
<br />2. Acceptable manufacturers: LS manufactured by K-Flex USA.
<br />3. Use on the following services:
<br />Moisture condensate drains - 1" thick, LS 3ft white seal seam.
<br />a .
<br />D. Fiberglass Pipe Insulation:
<br />1. Acceptable manufacturers: Johns -Manville "Micro-Lok 850"; CertainTeed; Knauf; Owens Coming. Foster Jacket: ASJ
<br />fiberglass reinforced kraft paper with aluminum foil and minimum R value of 3.6.
<br />2. Use on the following services:
<br />a. Domestic hot water supply piping. Domestic hot water supply piping - 1" thick for piping 2" or less and 1-1/2"
<br />thick insulation for piping 2-1/2" and greater.
<br />b. Domestic hot water recirculation piping - I" thick.
<br />C. Horizontal and vertical rain water leaders and overflow storm and roof drain bodies - 1" thick.
<br />d. Horizontal and vertical cold Condensate Piping - 1" thick.
<br />2.03 MATERIALS FOR FITTINGS, VALVES, AND SPECIAL COVERINGS
<br />A. For all services, use premolded insulation for pipe fittings, elbows, tees, butterfly valves, and couplings 2-1/2
<br />and larger. Finish shall be as specified under Products above or as specified below. PVC fitting covers may be used
<br />over the premolded insulation for:
<br />1. Rainwater and Overflow Storm Piping
<br />2. Domestic Hot Water
<br />3. Domestic Hot Water Recirc.
<br />B. PVC fitting covers with fiberglass inserts may be used on piping fittings elbows and valves 2" and less for the
<br />following services:
<br />1. Domestic Hot Water
<br />2. Domestic Hot Water Recirc.
<br />C. For pipe fittings, valves, strainers, and other irregular surfaces, when inside building or in equipment rooms, cover
<br />insulation with white colored woven glass fabric embedded in white vapor barrier coating, Foster 30-35 or equal.
<br />Provide removable section for pump, strainer, etc. service requirements.
<br />D. For flexible tubular elastomeric pipe and fitting insulation when exposed -to- view inside building or exposed to
<br />the weather, finish with two coats of fire retardant self -extinguishing vinyl lacquer type highly flexible coating
<br />equivalent to Armstrong "Armaflex Finish", custom color blended to match surrounding surfaces.
<br />PART 3 - EXECUTION
<br />3.01 INSTALLATION - GENERAL
<br />A. Deliver and store insulation materials in manufacturers containers and kept free from dirt, water, chemical and
<br />mechanical damage.
<br />B. Complete piping pressure testing prior to applying insulation.
<br />C. Apply insulation in workmanlike manner by experienced, qualified, workmen.
<br />D. Surfaces shall be clean and dry when covering is applied. Covering to be dry when installed and before and during
<br />application of any finish, unless such finish requires specifically a wetted surface for application.
<br />E. Adhesives, cements and mastics shall be compatible with materials applied and shall not attack materials in
<br />either wet or dry state.
<br />F. Stop duct coverings, including jacket and insulation, at fire penetrations of fire or smoke rated partitions,
<br />floors above grade and roofs. "Fan -out" or extend jacketed insulation at least 2" beyond angle frames of fire dampers
<br />and secure to wall. Maintain vapor barrier.
<br />3.02 INSTALLATION OF PIPE AND EQUIPMENT COVERING
<br />A. Where glass fiber or flexible tubular elastomeric Insulation is used on piping sized 2" and larger, insert a
<br />section of foamglass or calcium silicate insulation, at hanger or support points, between pipe and metal shield for
<br />full length of shield, to prevent crushing of insulation. Where insulation passes through pipe hangers and across
<br />trapeze supports, 12" long metal saddles shall be used. Insulation thickness to be same as adjoining glass fiber
<br />insulation. On cold pipe, vapor barrier should be carried through the hanger and sealed. Saddles shall be used where
<br />rigid foamglass inserts are not acceptable.
<br />B. Finish all piping below 7-0" AFF with pvc jacket.
<br />C. Apply flexible tubular elastomeric insulation to pipe and fittings with all joints tightly fitted and sealed with
<br />adhesive.
<br />PLUMBING
<br />SECTION 15400
<br />PLUMBING
<br />PART 1 - GENERAL
<br />1.01 WORK INCLUDED
<br />A. This section includes requirements for:
<br />1. Cleanouts.
<br />2. Shock arrestors.
<br />1.02 RELATED WORK
<br />A. Section 15010: Basic Mechanical Requirements
<br />B. Section 15050: Basic Materials and Methods
<br />C. Section 15060: Piping and Fittings
<br />D. Section 15100: Valves
<br />E. Section 15061: Pipe Hangers
<br />F. Section 15250: Mechanical Systems Insulation
<br />1.03 SUBMITTALS
<br />A. Submit product data for review.
<br />PART 2 - PRODUCTS
<br />2.01 ACCEPTABLE MANUFACTURERS
<br />A. Acceptable manufacturers are indicated in subsequent paragraphs.
<br />2.02 SHOCK ARRESTORS
<br />A. Acceptable manufacturers:
<br />1. Wade.
<br />2. Precision Products.
<br />3. Zurn.
<br />4. Sioux Chief
<br />2.03 CLEANOUTS
<br />A. Acceptable manufacturers:
<br />I . Wade.
<br />2. Zurn.
<br />3. Sioux Chief
<br />4. Josam
<br />5. Jay R. Smith
<br />B. Zum model numbers are used below.
<br />C. Finished concrete floor: ZB1400-NL cast iron body with round adjustable polished nickel bronze top, ABS plug and
<br />carpet marker where required.
<br />D. Ceramic tile: ZB1400-TX series, cast iron body, polished nickel bronze top, 1/2" terrazzo recess and closure plug.
<br />E. Vinyl tile floor: ZN1400-NL-X series, cast iron body, round nickel bronze top, 1/8" tile recess and closure plug.
<br />F. Carpet: ZN1400NL. Inside caulk round brass scoriated frame and cover and prDvide carpet marker.
<br />G. Wall: 1440 Cast iron caulking ferrule with stainless round access cover and screws.
<br />H. Access covers: Minimum size 12" x 12" located for access to valves, shock absorbers, trap primers, wall
<br />cleanouts, etc.
<br />I. Furnish cleanouts occurring in waterproof floors with clamping devices.
<br />PART 3 - EXECUTION
<br />3.01 INSTALLATION AND TESTING
<br />A. Shock Arrestors:
<br />1. Install shock arrestors at each quick closing valves, solenoid type valves, and flush valves, including water
<br />closets, urinals, showers, sterilizers, ice makers, hose bibbs, sinks and lavatories. Size shock arrestors in
<br />accordance with manufacturer's instructions and PDI standards.
<br />2. Install shock arrestors within five feet of valve, provide wall access panel as required.
<br />3. Test and certify shock arrestors by Plumbing and Drainage institute.
<br />B. Cleanouts
<br />1. Provide line size cleanouts up to 4"; 4" cleanout for lines larger than 4".
<br />2. Locate cleanouts at all changes in direction greater than 45 degrees and in straight runs as shown 100 feet outside
<br />the building on drawing or spaced not greater than required by applicable Plumbing Code.
<br />3. Extend inaccessible cleanouts up through floor and/or wall to provide easy accessibility.
<br />PLUMBING FIXTURES
<br />SECTION 15440
<br />PLUMBING FIXTURES
<br />PART 1 - GENERAL
<br />1.01 WORK INCLUDED
<br />A. Comply with provisions of Section 15010.
<br />B. Provide plumbing fixtures, trim and related items such as supplies, traps, drains, cleanouts, water closet
<br />flanges, boIts, seats and covers, fixture supports and other accessory items.
<br />C. Coordinate fixture requirements by reviewing architectural, structural, and equipment drawings. Install fixtures
<br />in accordance with Contract Drawings and manufacturer's rough -in drawings.
<br />1.02 RELATED WORK
<br />A. Section 15400: Plumbing
<br />B. Section 15060: Piping and Fittings
<br />C. Section 15100: Valves
<br />1.03 CODES AND STANDARDS
<br />A. Perform work in accordance with applicable codes and standards enforced by local authorities.
<br />B. All barrier free fixtures shall be installed In accordance with the Americans with Disabilities Act (ADA) Rules
<br />and Regulations.
<br />1.04 SUBMITTALS
<br />A. Submit manufacturer's product data for review.
<br />PART 2 - PRODUCTS
<br />2.01 ACCEPTABLE MANUFACTURERS
<br />A. Brass Trim: McGuire Engineered Brass Company, Brasscraft, Zurn.
<br />B. Provide fixtures and trim as a complete unit as required in the individual nP" numbers listed on plumbing fixture
<br />schedule.
<br />C. Pre -fabricated insulation on water lines and p-trap under barrier free lavatories and sinks: Trap Wrap TrueBro,
<br />Inc. Handi Lav-Guard McGuire Pro -wrap.
<br />D. Thermostatic mixing valves: Symmons.
<br />2.02 MATERIALS
<br />A. Wall hung lavatories: Furnish complete with floor mounted carriers, Zurn 1231..
<br />B. Countertop sinks: Furnished complete with mounting rings where required.
<br />C. Fixture color: White unless specified otherwise.
<br />D. Faucets and flush valves: Provide either integral or attached heavy duty supply stops with nipples.
<br />E. Plumbing and Medical Gas roughin within wall to fixtures shall be provided with HoldRite Mounting System to
<br />secure pipng In place and prevent movement.
<br />F. All plumbing fixtures including Vitreous china fixtures shall be provided with anti -microbial finish applied from
<br />the factory.
<br />G. All plumbing fixtures shall be of high efficiency type. See fixture schedule for more information.
<br />H. Caulking: General Electric silicon sanitary sealant or equal. Product shall have no voc's - volatile organic
<br />compounds
<br />I. Provide treated wood, polystyrene pipe holder or metal backing at wall fixtures and fixture trim connections so
<br />piping and connecting faucets and valves are rigid to wall.
<br />J. Wrist blade operation:
<br />1. Pull wrist blade to operator to tum on.
<br />2. Push toward splashback to turn off faucet.
<br />K. Supply stops shall be heavy duty with wheel handle, NSF/ANSI G61, lead free.
<br />PART 3 - EXECUTION
<br />3.01 FIXTURE CONNECTIONS
<br />A. Connect to plumbing fixtures and equipment provided under this and other sections of specification, architectural
<br />drawings, and manufacturer's shop drawings. Provide rough -in connections as shown on drawings.
<br />B. Use schedule and details on drawings or manufacturer's shop drawings for connection sizes to fixtures.
<br />C. Provide separate p-trap for each fixture, floor drain, and piece of equipment.
<br />D. Where required by local or state enclay codes, provide H.W. flow limiting devices to lavatories/sinks in
<br />accordance with ASHRAE 90-75.
<br />E. Install lavatories and sinks with a minimum of 4" clearance on each side, from a wall or partition.
<br />F. Coordinate dimensions required for minimum fixture clearances with other Divisions.
<br />G. Where automatic electronic flushing devices are specified, coordinate installation with Division 16.
<br />H. Caulk around joints at fixtures mounted on wall or floor, or backed up to walls.
<br />I. Mount fixtures rigid to walls as shown on drawings or details.
<br />3. Accessories: Factory installed grab bars and curtain rod.
<br />K. Gooseneck faucets intended for staff and patient, use shall not contain aerators but shall contain plain end
<br />outlet trim ring.
<br />L. Contractor shall install fixtures as per manufacturers written instructions. Contractor shall provide all
<br />required materials as needed for a complete system.
<br />M. Contractor shall provide grout or cement as required for floor mounted carriers as needed.
<br />3.02 TESTING AND CLEANING
<br />A. Inspect and test work to insure that it is installed in accordance with drawings and specification and is
<br />functioning as designed. Test procedures and pressure as required by other sections.
<br />B. Correct all deficiencies found and retest.
<br />F,
<br />OT, 0", r1d,
<br />F/M N - W,
<br />0010,
<br />1-14
<br />�3�
<br />CYD
<br />CIA
<br />zl
<br />CV5 ;__4
<br />-4
<br />vz C,0 Cq
<br />FZ C
<br />C C-q iz.)
<br />004
<br />gx� 4
<br />rk�
<br />ceb
<br />llz�
<br />co
<br />IZQ
<br />SS)Smith
<br />Seckman
<br />VI Reid, Inc.
<br />600 West Hillsboro, Suite 300
<br />Deerfield Beach, FL 33441
<br />(954) 421-1260
<br />FAX: (954) 421-1466
<br />www.ssr-inc.com
<br />Firm Certificartion - EB-00OM7
<br />Dennis D&vis PE - 5MM
<br />Jobn E. Moulder PE .332M
<br />SSR JOB# 1137003.0
<br />J%%%J1111111
<br />S. M0
<br />#. lost
<br />\0,
<br />0
<br />40
<br />&P
<br />60 1.
<br />1W . TAT OF
<br />ORX
<br />%
<br />%%%
<br />cc
<br />ct
<br />.2
<br />2
<br />;Z�
<br />U)
<br />Z
<br />0
<br />C)
<br />LL
<br />5
<br />LU
<br />M
<br />Cf)
<br />0
<br />Z
<br />D
<br />_J
<br />CL
<br />Q6>
<br />tq
<br />COD
<br />C)
<br />:3�
<br />C�
<br />C)
<br />Z,
<br />P3Z4
<br />L
<br />0
<br />to
<br />Nject No, 00000.00
<br />POA
<br />(E) 2011 BEI PK Architects, Inc.
<br />
|