Laserfiche WebLink
MEDICAL GAS PIPING AND PIPE LINE COMPONENTS <br />SECTION 15480 <br />REGULATORY REQUIREMENTS <br />A. NFPA 101: Life Safety Code (2006). <br />B. NFPA 99: Standard for Health Care Facilities (2005). <br />C. Florida Building Code - 2007 with 2008 & 2009 ammendments. <br />D. Guidelines for Design and Construction of Hospital and <br />Health Care Facilities - (2006). <br />MEDICAL GAS PIPING SYSTEM <br />FURNISH, INSTALL, AND TEST COMPLETE PIPING SYSTEM FOR 02, AIR, VAC, N20 & N2. <br />SYSTEM SHALL BE PRESSURE TESTED WITH OIL FREE NITROGEN (NF) AND ANALYZED IN <br />ACCORDANCE WITH NFPA 99. PROVIDE BRAZER PERFORMANCE QUALIFICATION TEST RECORDS <br />TO ENGINEER FOR EACH BRAZER USED ON INSTALLATION PRIOR TO INSTALLATION. BRAZERS <br />SHALL BE QUALIFIED USTC WITH 32 MINIMUM HOURS TRAINING. <br />MEDICAL GAS PIPING: SEAMLESS TYPE "L" (ASTM B819) HARD DRAWN COPPER WITH <br />WROUGHT COPPER FITTINGS FOR BRAZED CONNECTIONS IN ACCORDANCE WITH NFPA 99. <br />TYPE 'K' (ASTM B819) COPPER TUBING FOR SYSTEMS OVER 185 PSI & 3" AND LARGER. <br />ALL PIPING PRECLEANED FOR OXYGEN SERVICE (PRECLEANED FOR OXYGEN SERVICE IS NOT <br />REQUIRED FOR VACUUM PIPING). PIPING SHALL BE PRECLEANED AND PLUGGED BY SUPPLIER <br />BEFORE SHIPMENT TO JOB SITE. PIPING ON SITE CLEANING SHALL NOT BE PERMITTED. <br />SILVER BRAZING MATERIAL: STAY-SILV-15, SILVALOY-15, AIRCOSIL #15, OR PROS-SILVER-15. <br />SILVER BRAZING ALLOY COMPOSITION: 15% SILVER, 80% COPPER AND 5% PHOSPHORUS, <br />NO CADMIUM. <br />FLUX: DO NOT USE FOR COPPER -TO -COPPER JOINTS. USE FLUX FOR JOINING COPPER TO <br />BRASS OR BRONZE. EXERCISE CARE IN APPLYING THE FLUX TO AVOID LEAVING ANY EXCESS <br />FLUX INSIDE THE COMPLETED JOINTS. <br />UTILIZE UNISTRUT SUPPORTS WITH PHD MANUFACTURING MODEL #2501 - 2514 UNISTRUT <br />CUSHIONED CLAMPS OR PHD MODEL #153 PVC COATED TEAR DROP HANGERS. TAPE IS NOT <br />ACCEPTABLE. <br />EXPANSION ANCHORS: HILTI KWIK-BOLT, ZINC PLATED, METAL EXPANSION ANCHOR TO BE <br />USED ON EXISTING CONSTRUCTION. ANCHOR TO MEET U.L., ICBO-4627 AND FM LISTINGS. <br />CONTRACTOR SHALL PROVIDE MEDICAL GAS CERTIFICATION REPORT TO OWNER & ENGINEER <br />PRIOR TO FINAL AHCA INSPECTION. CONTRACTOR SHALL CERTIFY EXISTING SYSTEM <br />PRIOR TO CUTTING INTO EXISTING SYSTEM AND SHALL SUBMIT MEDICAL GAS <br />CERTIFICATION TO ENGINEER FOR REVIEW PRIOR TO ANY NEW INSTALLATION. <br />CONTRACTOR SHALL ALSO PROVIDE COPY OF TESTS FOR ALL STEPS AS OUTLINED IN <br />NFPA 99 IN ADDITION TO MEDICAL GAS CERTIFICATION. <br />LABEL PIPING WITH ADHESIVE LABELS. COLOR CODED PER NFPA 99. LABEL PIPING AT <br />INTERVALS OF NOT MORE THAN 20 FEET, AT LEAST ONCE IN EACH ROOM, AT EACH STORY <br />TRAVERSED BY THE PIPING SYSTEM, AT EACH WALL AND FLOOR SLAB PENETRATION, AT <br />EACH VALVE AND AT EACH CHANGE IN DIRECTION. PROVIDE ARROWS AT EACH LOCATION <br />WHERE LABELED INDICATING DIRECTION OF FLOW. SYSTEM SHALL BE INSTALLED PER NFPA <br />99. ALL PIPING SHALL BE PRECLEANED AND PLUGGED PRIOR TO SHIPMENT TO THE JOB SITE. <br />JOINTS TO BE MADE WITH 1000 DEGREES F MELTING POINT MINIMUM WITH 15% SILVER <br />BRAZING ALLOY. SYSTEM SHALL BE PURGED CONTINUOUSLY WITH DRY NITROGEN (NF) WHILE <br />BEING ASSEMBLED AND BRAZED. USE OF FLUX IS NOT ALLOWED EXCEPT ON DISSIMILAR <br />METALS. USE SHALL BE KEPT TO A MINIMUM. PROVIDE HANGERS ON PIPING PER NFPA 99 <br />AND IN EACH ROOM. <br />CROSS CONNECTION TESTING AND CERTIFICATION OF THE NEW AND EXISTING MEDICAL <br />GAS SYSTEM MUST BE PERFORMED BY FACTORY TRAINED TECHNICIANS FROM THE <br />MEDICAL GAS PIPELINE EQUIPMENT SUPPLIER. MEDICAL GAS VALVE BOXES, <br />VALVES, ALARMS AND OUTLETS SHALL BE BY ONE MANUFACTURER. <br />MEDICAL GAS OUTLETS SHALL BE SQUIRE COGSWELL (OHIO) COMPATIBLE QUICK CONNECT STYLE. <br />CONTRACTOR SHALL VERIFY THAT OUTLETS MATCH EXISTING HOSPITAL STANDARD PRIOR TO ORDERING. <br />MEDICAL GAS AREA ALARM PANEL SHALL BE BEACON MEDEAS TOTALALERT2 <br />EIGHT MODULE ALARM PANEL WITH GAS SPECIFIC MODULES AS REQUIRED BY <br />MED GAS SCHEDULE. PROVIDE OPTIONAL NETWORK COMMUNICATIONS BOARD CAPABLE <br />OF INTERFACING WITH FACILITY'S ETHERNET AND CAT-5 ETHERNET CABLE. <br />MEDICAL GAS ZONE VALVE BOXES SHALL BE BEACON MEDEAS. VALVE BOXES SHALL INCLUDE <br />1Y2" PRESSURE GAUGES READING 0-100 PSIG FOR 02, N20 & AIR, & 0-30" HG <br />FOR VACUUM. GAUGES SHALL BE LOCATED DOWNSTREAM OF VALVES. <br />PROVIDE PERMENANTLY ENGRAVED LABELS ON ALL MEDICAL GAS ZONE VALVES AND ALARM <br />PANELS TO INDICATE AREA SERVED PER NFPA-99. COORDINATE WITH HOSPITAL STANDARDS. <br />PLUMBING CONTRACTOR SHALL PROVIDE AND COORDINATE ALL LOW VOLTAGE WIRING WITH <br />DIVISION 16 AND PROVIDE ALL REQUIRED CONDUITS. CONTRACTOR SHALL HOLD A LOW <br />VOLTAGE WIRING LICENSE. <br />FLOOR MOUNTED PEDESTAL U.L LISTED NFPA 99 APPROVED - BY AMICO FREEDOM SERIES 9" FLOOR <br />PEDESTAL SHALL BE MADE OF 18 GAUGE 304 STAINLESS STEEL WITH A #4 SATIN FINISH. IT SHALL <br />BE CAPABLE OF HOLDING MEDICAL GAS OUTLETS AND ELECTRICAL DEVICES WITHIN THE STRUCTURE <br />OF THE UNIT. THE ELECTRICAL DEVICES (SIX DUPLEX RECEPTACLES, 20 AMP RED, DEDICATED CIRCUITS) <br />SHALL BE PROVIDED WITH ELECTRICAL BOX AND CONDUIT AND WIRE AND SHALL BE HOSPITAL ENGRAVED <br />AND ENGRAVED TO INDICATE CIRCUIT. PROVIDE WITH 1- OXYGEN, 1-MEDICAL AIR, 1-VACUUM, 1-SLIDES, <br />1-N20 & 1 WAGD SQUIRE COGSWELL (OHIO) COMPATIBLE QUICK CONNECT STYLE OUTLETS. COORDINATE <br />MEDICAL GAS OUTLET TYPE WITH OWNER PRIOR TO PURCHASING. <br />PIPELINE PRODUCTS (INCLUDING ALARM PANEL, ZONE VALVE BOX AND OUTLETS) SHALL BE BY <br />BEACON MEDAES, AMICO OR OHIO MEDICAL. ALL PIPELINE PRODUCTS SHALL BE BY THE SAME <br />MANUFACTURER. <br />INSTALLATION <br />A. Joints in the piping, except those at equipment requiring screwed <br />connections, shall be made with silver brazing <br />alloy or similar high melting point (above 1000 degrees F) brazing metal. <br />B. Contractor shall provide a copy of the installers brazing certificate <br />to the engineer or, record prior to any <br />installation. Certification and training shall be in accordance with <br />ASME Section 9 or AWS B2.2 and to assure that the <br />pipeline certification report and installation complies with all <br />Chapters of NFPA 99 Latest Edition. <br />C. During the brazing of pipe connections, the interior of the pipe <br />shall be purged continuously with 5 SCFH of oil <br />free nitrogen (NF) to prevent the formation of copper oxide inside the <br />joint. The flow of purge gas shall be maintained <br />until the joint is cool to the touch. Hold pipe full of nitrogen at night. The <br />outside of the tube and fittings shall be <br />cleaned by washing with hot water after assembly, and prior to <br />inspection of joints and pressure testing. <br />D. Threaded joints in piping systems shall be made up with <br />polytetrafluorethylene (such as Teflon) tape or other <br />thread sealants suitable for oxygen service. Apply sealants to the male <br />threads only. <br />E. Sand cloth/sand paper type abrasive cleaning material shall not be allowed. <br />Joints shall be cleaned with scotch brite pads prior to brazing. <br />F. All installation tools shall be cleaned and oil free before installation <br />of piping. Tools shall remain clean during all medical gas system <br />piping installation. <br />G. All piping/valves and components shall be inspected prior to erection if <br />found to be contaminated they shall not be installed in the medical gas piping <br />system. <br />H. All pipe ends shall be cut square, and deburred with a sharp clean <br />deburring tool. Care shall be taken to prevent chips from entering the tube <br />or pipe. <br />I. Support medical gas piping at distances listed per NFPA-99. Piping <br />shall not be supported from other piping. <br />Unistrut type trapeze hangers shall contain plastic inserts to isolate <br />medical gas piping from dissimilar metals and straps. <br />1. Isolate copper piping from dissimilar metals. Do not use duct tape <br />or electrical tape as an isolation material. <br />Where medical gas piping is in contact with construction materials. Wrap <br />the exposed medical gas piping with 20 mil <br />thick adhesive polyken brand protective wrap. Wrap shall extend 6" <br />either side of contact point. <br />J. After installation of the piping, but before installation of the outlet <br />valves, blow lines clear by means of oil free, dry nitrogen (NF). <br />K. The qualified brazer/certifier shall inspect the piping system for: <br />1. Flux or flux residue <br />2. Excessive oxidation of all joints. <br />3. Presence of unmelted filler metal <br />4. Failure of the filler metal to be clearly visible all around the joint at <br />interface between the socket and the tube. <br />5. Cracks in the tube or component. <br />6. Cracks in the braze filler metal. <br />7. Failure of the joint to hold the test pressure per NFPA 99 standing <br />pressure test. <br />L. All piping shall be delivered plugged or capped by manufacturer and <br />kept sealed until prepared for installation <br />per NFPA 99 Chapter 5.1.10.1.2. Tape will not be acceptable. <br />M. Joints shall be brazed within eight (8) hours after surfaces are cleaned <br />for brazing, per NFPA 5.1.10.5.3.13. <br />N. After the joint has cooled the purge discharge opening shall be sealed to <br />prevent contamination of the inside of <br />the piping and maintain the nitrogen atmosphere within the piping system <br />per NFPA 99 chapter 5.1.10 section 5.1.10.5.3.13. <br />0. Piping protection: <br />1. Piping shall be protected against freezing, corrosion, and physical damage. <br />2. Piping exposed to physical damage shall be adequately protected. <br />3. Medical gas piping shall be protected from contact with concrete floor slabs <br />and other building materials, acceptable <br />means shall be Polyken brand 20 mil thick adhesive wrap, extending 6" <br />either side of contact surfaces. <br />INSTALLER PERFORMANCE TESTING <br />A. AFTER INSTALLATION OF THE PIPING AND VALVES, BUT BEFORE <br />INSTALLATION OF THE SERVICE OUTLETS, ALARM ACTUATING SWITCHES AND GAUGES, <br />AND BEFORE PIPING AND VALVES ARE CONCEALED IN WALLS OR CEILING THE LINE <br />SHALL BE BLOWN CLEAR BY MEANS OF OIL -FREE, DRY NITROGEN (NF). <br />B. NEXT, WITH STATION OUTLETS WITH TEST CAPS IN PLACE EACH SECTION <br />OF THE PIPING SYSTEM SHALL BE SUBJECTED TO A TEST PRESSURE OF ONE AND <br />ONE-HALF (1-1/2) TIMES THE MAXIMUM WORKING PRESSURE, BUT NOT LESS <br />THAN 150 PSIG, WITH OIL -FREE, DRY NITROGEN. AT NO TIME SHALL ANY TWO (L3 <br />MEDICAL GAS PIPELINES BE INTERCONNECTED FOR TESTING SUCH AS A PIPING ti <br />MANIFOLD. MAINTAIN TEST PRESSURE FOR AT LEAST 24 HOURS. THEN EACH JOINT <br />SHALL BE EXAMINED FOR LEAKAGE BY MEANS OF SOAPY WATER OR OTHER EFFECTIVE <br />MEANS OF LEAK DETECTION SAFE FOR USE WITH OXYGEN. <br />C. REPAIR LEAKS AND RETEST THE SECTION. <br />Y <br />D. AFTER COMPLETING THE TESTING OF EACH INDIVIDUAL PIPING SYSTEM, ALL F� <br />OF THE MEDICAL GAS SYSTEMS SHALL BE SUBJECTED TO A PRESSURE TEST AT ONE Qi o <br />AND ONE-HALF (1-1/2) TIMES THE MAXIMUM WORKING PRESSURE, BUT NOT LESS �4 <br />THAN 150 PSIG. THE TEST GAS SHALL BE OIL -FREE, DRY NITROGEN (NF). THE , N <br />MAIN LINE SHUT-OFF VALVE SHALL BE CLOSED DURING THE TEST. o <br />E. AFTER COMPLETION OF THE ABOVE TEST PROCEDURE THE FINISHING ASSEMBLIES ,Sze <br />OF ALARMS, AND ALL COMPONENTS (E.G. PRESSURE SWITCHES, GAUGES, RELIEF v a- <br />O ' <br />VALVES, ETC.) SHALL BE INSTALLED AND ALL MEDICAL GAS PIPING SYSTEMS SHALL r � <br />a, <br />BE SUBJECTED TO A 24 HOUR STANDING PRESSURE TEST AT 20% ABOVE THE NORMAL ;� ^ <br />OPERATING LINE PRESSURE. THE MAIN LINE SHUT-OFF VALVE SHALL BE CLOSED O Cq <br />Cq <br />DURING THIS TEST. � � •� � v <br />o <br />F. LEAKS, IF ANY, SHALL BE LOCATED, REPAIRED, AND THE SYSTEM RETESTED. r-�.�r�.'�� Rf <br />G. PURGE TESTING OF EACH MEDICAL GAS OUTLET AT A MINIMUM RATE OF 225 LPMw, U� <br />SHALL BE PERFORMED WITH A WHITE CLOTH LOOSELY HELD OVER THE ADAPTOR UNTIL <br />PURGE PRODUCES NO DISCOLORATION OF THE WHITE CLOTH. v <br />Pq Vwwa <br />H. TO DETERMINE THAT NO CROSS CONNECTION TO OTHER PIPELINE SYSTEMS EXISTS, <br />REDUCE ALL SYSTEMS TO ATMOSPHERIC PRESSURE. DISCONNECT ALL SOURCES TO TEST <br />GAS FROM ALL OF THE SYSTEMS WITH THE EXCEPTION OF THE ONE SYSTEM TO BE CHECKED. <br />PRESSURE THIS SYSTEM WITH OIL -FREE, DRY NITROGEN (NF) TO A PRESSURE OF 50 PSIG. Smith <br />WITH APPROPRIATE ADAPTERS MATCHING OUTLET LABELS, CHECK EACH INDIVIDUAL Seckman <br />STATION OUTLET OF ALL SYSTEMS INSTALLED TO DETERMINE THAT TEST GAS IS BEING Reid, Inc. <br />DISPENSED FROM ONLY THE OUTLETS OF THIS SYSTEM. 600 West Hillsboro, suite 300 <br />Deerfield Beach, FL 33441 <br />(954)421-1260 <br />CERTIFICATION PROCEDURE FAX: www.ssr-inc.com66 <br />Firm certfficWon- EB-0000357 <br />A. Perform mechanical check of all medical gas outlets prior to the J� �- <br />certification inspection. An necessary repairs or rework shall be <br />done prior to system certification inspection. Check to include: MRJOB # 1137W3.0 <br />1. Outlets properly supported. <br />2. Installation complete. <br />3. Appropriate adapters fit and securely lock in place. <br />B. Medical gas system suppliers and/or certification company and <br />Plumbing Contractor sign Medical Gas Pipeline Inspection Agreement <br />describing service to be performed by the medical gas system supplier, <br />services not performed by the medical gas system supplier, price <br />quotation, and exceptions affecting quoted price. <br />C. The Contractor shall provide a qualified certifier to perform pipeline <br />certification inspection and to provide report and certification in accordance <br />with previously signed agreement. which shall be a 3rd party. <br />1. Any discrepancies discovered during the inspection shall be noted, corrected, <br />and any and all portions of the system affected by corrective action shall be <br />retested and findings recorded after retest. <br />J%t,11111111111111i <br />D. Provide representative who shall serve as customer contact person and who <br />` <br />� M <br />�O�N',;;E.OU� <br />shall witness the certification inspection and certify that all outlets have been <br />�•��G <br />checked and are in accordance with inspection procedure and findings as witnessed. <br />,ie_ <br />E. Hospital Maintenance Department to provide representative who shall witness <br />the certification and certify that all spaces and the outlets have been checked in <br />accordance with inspection procedure. F <br />P � <br />F. All air, o2 & N20 outlets shall be tested to deliver 3.5 SCFM at 50 psi with a �� �O R 10•- �S <br />....sell. <br />maximum pressure drop of 5 psi. These tests shall be performed with oil -free, dry �, Otv,At.. <br />nitrogen (NF). rt;yl�t�t� <br />G. Each medical gas outlet shall be purge tested to verify that a minimum of 35 cubic <br />feet of oil free dry nitrogen (NF) shall be filtered through a clean white 0.45 micron <br />filter at a minimum flow of 3.5 SCFM. Filter shall not accrue more than 0.1 mg of matter. <br />This test shall be performed at twenty-five percent of the zones for each gas type. <br />Samples taken within each zone shall be taken at the outlet furtherest from the zone valve. <br />H. For clinical air, o2, & N20 systems measure and record the dewpoint, total <br />hydrocarbons, and halogenated hydrocarbons. The maximum allowable variation for each <br />parameter shall be: <br />1. Dewpoint:.5 degrees C @ 50 PSI co <br />2. Total hydrocarbons: 1.0 PPM <br />3. Halogenated hydrocarbons: 2.0 PPM <br />4. Tests shall be performed on the outlet most remote from the source and compared with <br />source gas tests. The two test shall not exceed the measurements outlined above. These <br />tests shall be performed with oil -free dry nitrogen (NF). <br />I. The valves shall be tested to verify proper operation and rooms or areas of control. I I <br />Each valve shall be labeled for the rooms or area they control. <br />J. The alarm panels wiring shall be tested to ensure that all components are I I <br />functioning properly. The alarm panels shall be tested per N.F.P.A. 99C. <br />K. The certifier shall furnish copies of Medical Gas Pipeline Inspection Report and <br />Medical Gas Pipeline Certification. Transmit a copy of the report and certification <br />to each of the following parties prior to 100% AHCA Inspection. <br />1. Contractor <br />2. Owner's Construction Manager <br />3. Architect <br />4. Consulting Engineer <br />5. Hospital <br />L. The following procedure should be followed in addition to the above on extensions <br />to existing systems, prior to 100% AHCA Inspection. <br />1. Contractor shall, with adequate advance notice, request that certifier or <br />inspection team be on -site when old piping is cut -in for installation of new lines. <br />2. Contractor shall arrange to have certifier or inspection team on -site when the <br />existing piping is cut into for installation of new lines. <br />3. Main line shut-off valves shall be installed in new piping as close as possible <br />to point to cut -in to previously installed piping. <br />4. After verification of proper labeling, pressure and proper gas distribution of <br />previously installed piping and after cut -in procedure, the aforementioned valves <br />shall be considered the "service shutoff" of supply for the new piping. Contractor <br />shall lock or remove the handles from these valves and turn over to the Owner. <br />5. Before connection to the existing system and before system is put into service, <br />the system shall be pressure tested, purged, outlet flow, tested, and gases analysed <br />per NFPA 99. <br />6. After re-establishing pressure in each previously installed supply line after <br />"cut -in", the previously installed outlets immediately upstream for each gas and for <br />each cut -in point shall be opened to ensure that the proper gas is being delivered. <br />Gas should be bled to atmosphere prior to analyzation to ensure purging from point <br />of cut -in to test point. <br />7. Contractor shall provide copy of tests of medical gas system prior to medical gas <br />certification process. <br />M. The presence of the desired gas shall be confirmed with the combined use of an <br />analyzer designed to measure the specific gas dispensed, and a pressure gauge attached <br />to an appropriate adaptor with results tabulated below: <br />1. Oxygen: 99-100% Oxygen, Pressure: 50 psi, +/-5 psi <br />2. NITROUS OXIDE: 99-100% NITROUS OXIDE, PRESSUE:.50 PSI +/-5 PSI. <br />3. Vacuum: Pressure -Negative <br />4. Medical Air: 19.5%-23.5% oxygen, Pressure: 50 psi, +/- 5 psi. <br />n. CONTRACTOR SHALL PROVIDE MEDICAL GAS CERTIFICATION OF EXISTING SYSTEM PRIOR TO BREACHING WHICH SHALL <br />INCLUDE FIVE (5) OUTLETS OF EACH GAS AND VACUUM. THE GAS OUTLETS SHALL BE TESTED AT THE END OF THE SYSTEM <br />AND THE VACUUM OUTLETS SHALL BE TESTED UPSTREAM OF SYSTEM TIE-IN. CONTRACTOR SHALL PROVIDE COPY OF TEST <br />TO ARCHITECT AND ENGINEER PRIOR TO BREACHING SYSTEM. <br />3.02 CROSS CONNECTION TESTING AND CERTIFICATION <br />A. Cross connection testing and certification of the medical gas system must be <br />performed by party technically competent and experienced in the field of medical gas <br />pipeline testing. <br />B. Medical gas system shall be tested in accordance with NFPA 99, Latest Edition, <br />Section 5 . <br />C. In addition to cross connection testing, this specification shall require the <br />technical certifier to test each individual pipeline systems component for performance <br />to design specifications and make any necessary adjustments to ensure a complete and <br />working system. <br />D. The system shall be tested for cross connection in one of the following methods: <br />1. Test one pipeline system at a time at 50 psi while the others are at atmospheric <br />pressure including the vacuum system. <br />2. Reduce the pressure in all medical gas systems to atmospheric pressure. Increase the <br />test pressure to the piping to the following pressures: <br />a. Oxygen: 50 psi <br />b. Compressed Air: 60 <br />c. Any medical -surgical vacuum system shall be in operation at same time that medical <br />gases are tested. <br />D. NITROUS OXIDE: 40 PSI <br />E. Obtain and present to the Owner a complete bond report of pipeline certification <br />from the equipment manufacturer. This letter of certification shall indicate: <br />1. That the system is free of crossed connections. <br />F. A CERTIFICATION SHALL BE DONE FOR EACH PHASE <br />b <br />Z <br />O <br />Q <br />U_ <br />LL <br />U <br />LU <br />a_ <br />W <br />0 <br />Z <br />m <br />2 <br />J <br />Q_ <br />ZF <br />do <br />CLOSEOUT <br />CONTRACTOR SHALL PROVIDE AS BUILT DRAWINGS IN AUTOCAD FORMAT AT COMPLETION <br />OF PROJECT. <br />Project No. 00000.00 <br />POm5 <br />D 2011 BEI PH Architects, Inc. <br />