<br />F-Rating = 2 Hour
<br />T-Rating = 0 Hour
<br />0,
<br />3735 Green Rd.
<br />Beachwood, 011, 44122
<br />Drawing not to scale
<br />Pre -Rated Concrete Floor or Wall Assembly Min. 4-1/2" thickness
<br />Metallic Pipe: Steel Pipe - 12" diam. (or smaller) Sch. 10 (or heavier) steel pipe.
<br />(D Pipe Covering - Nom. 3" thick Cellular Glass Insulation.
<br />The annular space shall be min. 0" to max. 1- 1 /4" within the firestop system.
<br />Metal Jacket - Min. 12" long jacket formed of min. 26 gauge steel cut to wrap tightly
<br />around the pipe insulation with a min. 2" lap. Secure using hose
<br />clamps located 3" from each end of thejacket. Positionjacket
<br />flush with surface of floor, or both surfaces of a wall.
<br />Q TREMstop, WBM - Min. I" thickness of sealant applied within opening, flush with
<br />top surface of floor or both surfaces of wall assembly.
<br />A min. 1/2" diam. cant bead of sealant shall be applied at the
<br />insulation/concrete interface at the point contact locations.
<br />C, ev
<br />a
<br />Ivi'l t 00
<br />CAJ 5089
<br />F-Rating = 2 Hour
<br />T-Rating = 1/2 & I Hour
<br />3735 Green Rd.
<br />Beachwood, OH, 44122
<br />Drawing not to scale
<br />Pre -Rated Concrete Floor or Wall Assembly Min. 4-1/2" thickness
<br />G) Metallic Pipe: > Steel Pipe - 8" diam. (or smaller) Sch.40 (or heavier) steel.
<br />> Iron Pipe - 8" diam. (or smaller) cast or ductile iron.
<br />> Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper.
<br />> Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing.
<br />Pipe Covering - Nom. 1 " thick (or less) fiberglass insulation.
<br />Firestop, Treatment: Pipe Type Annular Space, in. T Rating, H
<br />Steel Pipe 1/2 to 1 1
<br />Iron Pipe 1/2 to 1 1
<br />Copper Pipe 3/8 to 1-1/2 1/2
<br />Copper Tube 3/8 to 1-1/2 1/2
<br />Packing Material - Min. 4" thickness of mineral wool insulation (min. 4.0 pcfl
<br />fmnly packed into opening as a permanent form.
<br />TREMstop Acrylic - Min. 1/2" thickness of sealant applied within opening,
<br />flush with top of floor or both sides of wall.
<br />'a.s S I fi
<br />Q
<br />'Sys t 70
<br />CA-T -5067
<br />F-Rating 1-1/2 & 2 Hour
<br />T-11? a+;,n 1 /1 1 R, I - 1 /1 TJrvviv
<br />9mme
<br />3735 Green Rd.
<br />Beachwood, OH, 44122
<br />Drawing not to scale
<br />(D Pre -Rated Concrete Floor or Wall Assembly Min. 4-1/2" thickness
<br />Metallic Pipe: > Steel Pipe - 10" diam. (or smaller) Sch. 10 (or heavier) steel.
<br />> Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper.
<br />> Copper Tubing - 4" diam. (or smaller) Type M (or heavier) copper tubing.
<br />Q Pipe Covering - Fiberglass insulation, see table below for thickness and annular space.
<br />Max. Pipe P�W'ie C eri!lg Annular Space Packin Material Min. Sealant F-Ratin T-Rati
<br />c v s, Thckg 9 Mg
<br />Diam., m. L�e in. in. - ness, in. Thickness, in. Hr. Fir.
<br />3 1 1/4 to 1-3/8 3-1/2 1/2 1-1/2 1/2
<br />3 1 1/4 to 5/8 3-1/2 1/4 1-1/2 1/2
<br />4 1/2 1/4 to 5/8 4-1/4 1/4 2 1/2
<br />10 1 1/2 to 1 4-1/4 1/4 2 1
<br />10 2 1/2 to 3/4 4-1/4 1/4 1-1/2 1-1/2
<br />Packing Material - Mineral wool insulation (min. 4.0 pcf) firmly packed into opening
<br />to the minimum required thickness in the table above.
<br />FYRE-SIL and FYRE-SIL S/L - Min. thickness of sealant as specified in the table above,
<br />applied within opening flush with top surface of floor or both surfaces of wall.
<br />NOTE: Apply FYRE-SIL S/L to Floor Applications Only.
<br />v
<br />'ri-S t7o
<br />CAJ 5023
<br />F-Rating = 3 Hour
<br />T-Rating = 1- 1/2 Hour
<br />VmMme
<br />3735 Green Rd.
<br />Beachwood, OH, 44122
<br />Drawing not to scale
<br />Pre -Rated Concrete Floor or Wall Assembly Min. 4-1/2" thickness
<br />Metallic Pipe - 6" diam. (or smaller) Sch. 40 (or heavier) steel pipe.
<br />The nom. annular space of I 1/ 16" is required in the firestop system.
<br />Pipe Covering - Nom. 1 " thick (or less) fiberglass insulation.
<br />Packing Material - Min. 4" thickness of CERABLANK-ET-FS or ceramic fiber insulation
<br />(min. 6.0 pcf) firmly packed into opening as a permanent form.
<br />FYRE-SHIELD - Min. 1-1/2" thickness of sealant applied within opening, flush with
<br />top surface of floor or both surfaces of wall assembly.
<br />.3.0, S I fi
<br />ov
<br />vys t eo
<br />CAJ 5111
<br />F-Rating = 2 Hour
<br />T-Rating = I Hour
<br />9d9mme
<br />3 73 5 Green Rd.
<br />Beachwood, OH, 44122
<br />Drawing not to scale
<br />(DPre-Rated Concrete Floor or Wall Assembly Min. 4-1/2" thickness
<br />(DMetalhc Pipe: A) Steel Pipe - 2 " diam. (or smaller) Sch. 10 (or heavier) steel pipe.
<br />B) Iron Pipe - 2 " diam. "or smaller' ) cast or ductile iron pipe.
<br />C) Copper Tubing - 2" diam. (or smaller) Type K (or heavier) copper tubing.
<br />D) Copper Pipe - 2" diam. (or smaller) Regular (or heavier) copper pipe.
<br />(D Pipe Covering - Nom. 3/4" thick AB/PVC flexible foam insulation.
<br />The annular space shall be min. 1/8" to max. 1/4" within the firestop, system.
<br />TREMstop IA - Min. I" thickness of sealant applied within opening, Rush with
<br />the top surface of floor or both surfaces of wall assembly.
<br />Additional fill material to be installed such that a min. 1/4"
<br />crown is formed around the penetrating item.
<br />\,a's S I f.1-0
<br />C , V
<br />UL0
<br />&,S,yqt eo`
<br />steo
<br />CAJ 8057
<br />F-Rafing 2 Hr.
<br />T-Ra"
<br />0,
<br />(11
<br />3735 Green Rd.
<br />Beachwood, OH, 44122
<br />Drawing not to scale
<br />(D Pre -Rated Concrete Floors or Block Walls Min. 4-1/2" thickness
<br />Max. Area of Opening = 60 sq. in., with a Max. Dimension of 12".
<br />Q Metallic Pipe: A) Steel Pipe - 3" diam. (or smaller) Sch. 40 (or heavier) steel pipe.
<br />B) Conduit - 3" diam. (or smaller) EMT or steel conduit.
<br />C) Copper Tubing - 3" diam. (or smaller) Type L (or heavier) copper tubing.
<br />D) Copper Pipe - 3" diam. (or smaller) Regular (or heavier) copper pipe.
<br />E) Iron Pipe - 3 " diam. (or smaller) cast or ductile iron pipe.
<br />The annular space between pipes and openings is min. 1/4" to max. 15/16".
<br />Q Pipe Covering - Nom. 3/4" thickness of flexible foam (AB/PVC) pipe insulation.
<br />TREMstop WS - Inturnescent wrap strips wrapped around pipe covering (item 3) two times.
<br />Packing Material - Min. 4" thickness of mineral wool insulation (min. 4.0 pco firmly packed
<br />into the opening as a permanent form.
<br />FYRE-SIL - Min. 1/2" thickness of sealant applied within opening, flush with top surface
<br />of floor or both sides of wall assembly.
<br />UL DETAIL NOTES
<br />DETAILS ARE FOR REFERENCE ONLY. CONTRACTOR SHALL INSTALL ALL TRADES WITH
<br />UL APPROVED METHODS OF SEALING. CONTRACTOR SHALL REFERENCE UL FIRE RESISTANCE
<br />DIRECTORY, VOLUMES 2A-2B uPENETRATION FIRESTOPPING SCHEDULEI FOR CONSTRUCTION
<br />METHODS. CONTACT ARCHITECT AND ENGINEER FOR ANY CONFLICTS OR CLARITY.
<br />'-ON BOX
<br />.ECTRICAL
<br />CEILING
<br />FINISHED FLOOR
<br />LAVATORY
<br />NOTE:
<br />COORDINATE 110 V. ELECT. JUNCTION BOX W/TRANSFORMER LOCATION.
<br />MOUNT TRANSFORMER ABOVE CEILING.
<br />PHOTO -EYE TEMPERED WATER ROUGH -IN
<br />WIRE SUPPORT HANGER
<br />FOR DRIP TROUGH ON
<br />18" CENTERS
<br />RUN A I" DRAIN LINE FROM
<br />\'DRIP TROUGH TO BEYOND
<br />ROOM SERVED AS SHOWN
<br />ONTLANS
<br />TYPICAL PIPE HANGER
<br />WASTE LINE AS SHOWN
<br />ON PLANS
<br />18 GAUGE GALV.
<br />FABRICATED SHEET
<br />METAL DRIP TROUGH
<br />NOTE: PROVIDE END PLATES WELDED
<br />TO BOTH ENDS OF DRIP TROUGH.
<br />DRIP TROUGH SECTION
<br />LINE PRESSURE
<br />ALARM VALVE BOX r'- A C
<br />NOTES:
<br />1. LINE PRESSURE ALARM (L.P.A.) PANELS ARE NOT TO
<br />BE LOCATED OVER ZONE VALVE BOXES (Z.V.B.)
<br />2. COORDINATE MOUNTING HEIGHTS WITH ARCHITECTURAL
<br />DRAWINGS. IF DISCREPANCIES ARE FOUND, NOTIFY ARCHITECT
<br />AND ENGINEER PRIOR TO INSTALLATION.
<br />MEDICAL GAS MOUNTING HEIGHT DETAIL
<br />SCALE: NONE
<br />HANGER ROD. PROVIDE A SECTION OF HIGH
<br />COMPRESSION STRENGTH
<br />INSULATION AT EACH HANGER
<br />POINT. INSULATION MAY BE
<br />HALF ROUND OR FULL ROUND
<br />AND EXTEND 2'BEYOND
<br />GALVANIZED SHIELD EACH WAY.
<br />LULr-----U
<br />/-GALVANIZED
<br />SHIELD
<br />UNINSULATED COPPER LINES
<br />PIPE CLAMPS WITH CUSHIONS
<br />,--HANGER 'PHD' MANUFACTURING MODEL
<br />ROD 2501-2514
<br />-Ah
<br />\-METAL CHANNEL STRUT INSULATED PIPE �LINE WITH
<br />P
<br />PIPE CLAMP. PROVIDE
<br />INSULATION SHIELD ON 3"
<br />NOTESs AND LARGER.
<br />1. TRAPEZE HANGERS SHALL NOT BE USED ON STORM,
<br />OVERFLOW STORM OR SANITARY PIPING SYSTEMS.
<br />2. PROVIDE ADDITIONAL HANGERS ON EACH SIDE OF A
<br />WALL WHERE THE PIPING PENETRATES THE WALL.
<br />3. ALL INTERIOR HANGERS SHALL BE GALVANIZED
<br />INCLUDING THREADED RODS, NUTS AND BOLTS.
<br />4. ALL PLUMBING TRADE ITEMS SHALL BE INDIVIDUALLY
<br />AND RIGIDLY SUPPORTED FROM STRUCTURE ABOVE
<br />INDEPENDENT OF ALL OTHER TRADES. (DO NOT HANG
<br />PLUMBING ITEMS FROM ANOTHER TRADE.)
<br />TRAPEZE PIPE HANGER
<br />SCALE: NONE
<br />N 0 T E
<br />ELEVATE A/C UNIT SUFFICIENT DISTANCE
<br />ABOVE FLOOR OR ROOF TO ALLOW FOR
<br />INSTALLATION OF TRAP WITH ADEQUATE
<br />DIMENSIONS TO WITHSTAND SYSTEM
<br />OPERATING PRESSURE. COORDINATE
<br />WITH DETAIL FOR A\C UNIT MOUNTING.
<br />PERFORATED VENT CAP
<br />121FROM BOTTOM OF
<br />HIGHEST DRAIN PAN OR RISER
<br />SEE SPECIFIATIONS
<br />FOR PIPING MATERIAL.
<br />CLEAN -OUT -DRAIN PAN
<br />PLUG CONNECTION
<br />122 TEE F FUNION I
<br />I.- T �E
<br />� H � MINIMUM FULL
<br />2
<br />CONNECTION SIZE
<br />X
<br />I UN,I,
<br />0 0 L -ELBOW
<br />OR OR ROOF
<br />BOTTOM
<br />LAVATORY
<br />FAUCET
<br />MAXUNE L
<br />VALVE
<br />HOT
<br />WATER VALVE
<br />TANK,
<br />HEATER, TEMPERED
<br />ETC. HOT SUPPLY
<br />MAIN HOT SUPPLY
<br />VALVE
<br />COLD SUPPLY
<br />NOTES:
<br />1. INSTALL PER MANUFACTURER'S WRITTEN INSTRUCTIONS
<br />2. SET TEMPERATURE TO 1100 MAXIMUM PER FBC.
<br />MIXING VALVE PIPING AT FAUCETS
<br />PIPE HANGER RING
<br />I.T.T. GRINNELL FIG.69
<br />PIPE HANGER RING PIPE
<br />I.T.T. GRINNELL FIG.260-/ T
<br />PIPES 21/2" & SMALLER PIPES 3" & LARGER
<br />NOTE: 1. PROVIDE COPPER PLATING ON HANGER BETWEEN
<br />STEEL AND COPPER WHERE UNINSULATED COPPER
<br />PIPING IS USED.
<br />2. PROVIDE ADDITIONAL HANGERS ON EACH SIDE OF A
<br />WALL WHERE THE PIPING PENETRATES THE WALL.
<br />3. ALL INTERIOR HANGERS SHALL BE GALVANIZED
<br />INCLUDING THREADED RODS, NUTS AND BOLTS.
<br />4. ALL PLUMBING TRADE ITEMS SHALL BE INDIVIDUALLY
<br />AND RIGIDLY SUPPORTED FROM STRUCTURE ABOVE
<br />INDEPENDENT OF ALL OTHER TRADES. (DO NOT HANG
<br />PLUMBING ITEMS FROM ANOTHER TRADE.)
<br />U.L./F.M. APPROVED CONCRETE
<br />INSERT PIPING HANGER DETAIL
<br />CONDENSATE TRAP SCHEDULE
<br />C
<br />TOTAL HEIGHT OF TRAP = X+H+(11/2 x PIPE DIAMETER)
<br />FOR DRAW THRU UNITS
<br />FOR BLOW THRU UNITS
<br />HX= MIN. '�VH (PREFERRED X=H)
<br />�= I
<br />H= NEGA E STATIC PRESSURE +11
<br />X= FAN STATIC PRESSURE +1'
<br />H= MIN. 11
<br />AHU
<br />IDENTIFICATION
<br />k f1r,
<br />TONNAGE
<br />PIPE DIA.
<br />(INCHES)
<br />AHU NEGATIVE
<br />STATIC PRESS.
<br />(INCHES)
<br />FAN STATIC
<br />PRESSURE
<br />(INCHES)
<br />X (INCHES)
<br />H (INCHES)
<br />TOTAL HEIGHT
<br />(INCHES)
<br />CRAC-1
<br />9
<br />11
<br />IS
<br />N/A
<br />2.75'
<br />5.5'
<br />10.125'
<br />AHU-I
<br />7
<br />11/4'
<br />2.5'
<br />N/A
<br />1.75'
<br />3.5'
<br />7.125'
<br />0�1111
<br />rwo I
<br />ci
<br />RI
<br />4�
<br />b.0
<br />Q
<br />t 3_, cc C-4
<br />CM
<br />N
<br />gg
<br />10710, 1:2 2! .4
<br />Smith
<br />Seckman
<br />SS11 Reid, Inc.
<br />600 West Hillsboro, Suite 300
<br />Deerfield Beach, FL 33441
<br />(954) 421-1260
<br />FAX: (954) 421-1466
<br />www.ssr-inc.com
<br />Fh-m Catifliestion - ES40OW7
<br />Dennis Davis PE - 58M
<br />John 1E. MouMer PE - W=
<br />&IM JOB# 11370M.0
<br />% J%%J1111111
<br />Mo
<br />a
<br />E
<br />EOF
<br />J*If ONAL
<br />00
<br />Z.
<br />W
<br />z
<br />J�
<br />C4
<br />PIPE SUPPORT U)
<br />_J
<br />LTURN PIPE DOWN AT NEAREST CONDENSATE
<br />DRAIN, WITH MIN OF I -INCH AIR GAP UNLESS SHOWN
<br />OTHERWISE ON PLANS. SEE PLUMBING PLANS FOR CONTINUATION. IUL1
<br />0
<br />NOTE: (D
<br />1. CONDENSATE TRAPS SHALL BE MADE UP OF UNIONS IN EACH SIDE OF TRAP,AND SHALL z
<br />BE COMPLETELY REMOVABLE FOR CLEANING. CONTRACTOR SHALL DEMONSTRATE TRAP
<br />REMOVAL PRIOR TO FINAL ACCEPTAN
<br />2. INSTALL PER MANUFACTURIER'S WRITTEN INSTRUCTIONS.
<br />_J
<br />a_
<br />COOLING COIL CONDENSATE DRAIN
<br />COD
<br />to
<br />Nject No, 00000.00
<br />P5ml
<br />@ 201111.111 PK Architects, Inc.