HVAC GENERAL NOTES <br />AHU OPERATION DURING CONSTRUCTION <br />DRAWING INDEX <br />1. HVAC DRAWINGS ARE DIAGRAMMATICAL IN NATURE AND REPRESENT <br />EXISTING CONDITIONS BASED ON DRAWINGS AND SITE OBSERVATIONS. <br />CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL ACTUAL <br />CONDITIONS INCLUDING, DUCTWORK AND PIPING LOCATIONS AND SIZES. <br />2. DUE TO DRAWINGS BEING DIAGRAMMATICAL IN NATURE RISERS AND <br />DROPS ARE NOT SHOWN - CONTRACTOR SHALL INCLUDE THESE IN THE <br />BID - WHERE POSSIBLE ALL RISERS AND DROPS SHALL BE CONSTRUCTED <br />USING 45 DEGREE OR LONG RADIUS ELBOWS. <br />3. PROVIDE AND INSTALL NECESSARY DUCTWORK TRANSITIONS AND PIPING <br />INCREASERS/REDUCERS AS REQUIRED FOR EQUIPMENT CONNECTIONS. <br />CONSULT MANUFACTURER'S DATA FOR ACTUAL DUCTWORK AND PIPING <br />CONNECTIONS SIZES, INCLUDING, BUT NOT LIMITED TO THOSE SHOWN. <br />4. PROVIDE MANUAL VOLUME DAMPERS AT ALL LOW PRESSURE BRANCH <br />DUCTS TO INDIVIDUAL DIFFUSERS AND GRILLES AND TO ALL LOW <br />PRESSURE BRANCH DUCTS TO REHEAT COILS. PROVIDE DAMPERS AS <br />CLOSE AS POSSIBLE TO MAIN IN BRANCH CONNECTION. SEE DIFFUSER <br />AND GRILLE SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL <br />INFORMATION. <br />5. SCHEDULE NEW CONSTRUCTION WORK WITH THE OWNER WELL IN <br />ADVANCE. <br />6. ALL FINISHES AND SURFACES TO REMAIN WHICH ARE DAMAGED DURING <br />CONSTRUCTION WORK SHALL BE REPAIRED OR REPLACED TO THE <br />SATISFACTION OF THE OWNER AT NO ADDITIONAL COST TO THE OWNER. <br />7. DO NOT BLOCK TUBE PULL OR SERVICE SPACE ON EQUIPMENT WITH <br />PIPING, DUCTWORK, ETC.. (FLANGED OR REMOVABLE SECTIONS MAY BE <br />USED IN SOME INSTANCES WHERE TIGHT CLEARANCES EXISTS). <br />8. NO PIPING, DUCTWORK, OR CONDUIT SHALL BE INSTALLED UNTIL IT IS <br />COORDINATED WITH ALL OTHER TRADES AFFECTED. PROVIDE ALL <br />OFFSETS REQUIRED TO AVOID INTERFERENCE WITH OTHER TRADES; <br />EXISTING CONDITIONS AND WITH THE STRUCTURE, INCLUDING, BUT NOT <br />LIMITED TO, THOSE SHOWN. <br />9. IF NO SIZE IS SHOWN FOR DUCT SERVING DIFFUSER OR GRILLES, USE <br />SIZE SHOWN ON DIFFUSER AND GRILLE SCHEDULE. <br />10.DUCTWORK ROUTED PARALLEL TO A WALL, RATED OR CORRIDOR SHALL <br />BE INSTALLED WITH MINIMUM 6' CLEARANCE TO ALLOW FOR INSPECTION <br />OF WALL PENETRATIONS. CONTRACTOR SHALL PROVIDE 12' CLEARANCE <br />WHERE POSSIBLE, COORDINATE. <br />PIPING <br />HWS HOT WATER SUPPLY <br />HWR HOT WATER RETURN <br />REDUCER <br />SHUT-OFF VALVE <br />�''v CONTROL VALVE <br />STRAINER <br />-�bF- PLUG COCK <br />III H COMPANION FLANGE <br />UNION <br />CHECK VALVE <br />GUIDE <br />i <br />GAUGE &GAUGE COCK <br />THERMOMETER <br />X_ ANCHOR <br />LL REFRIGERANT LIQUID LINE <br />RS REFRIGERANT SUCTION LINE <br />HG REFRIGERANT HOT GAS LINE <br />11. REFER TO DETAIL SHEETS AND SPECIFICATIONS FOR ADDITIONAL <br />INSTALLATION REQUIREMENTS. <br />12. CONTRACTOR SHALL SUBMIT A COMPLETE LIST OF EQUIPMENT AND <br />ITEMS TO BE REMOVED TO THE OWNER. ALL ITEMS THAT THE OWNER <br />WISHES TO RETAIN SHALL BE TURNED OVER TO OWNER AND THE <br />REMAINDER SHALL BE REMOVED FROM THE SITE AND DISPOSED OF IN A <br />PROPER MANNER BY CONTRACTOR. <br />13. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PERFORM ALL WORK <br />NECESSARY TO PREPARE THE STRUCTURE FOR THE INSTALLATION <br />AND/OR DEMOLITION WORK OF THE MECHANICAL SYSTEMS. ALL HOLES, <br />OPENINGS AND ANY DAMAGED MATERIALS OR SURFACES SHALL BE <br />REPAIRED AND FINISHED TO MATCH EXISTING. <br />14. ALL DEMOLITION WORK SHALL COMPLY WITH NFPA 241 AND THE <br />REQUIREMENTS OF THE OWNER. <br />15. PROVIDE TEMPORARY FILTERS ON ALL RETURN AIR GRILLES AND <br />TRANSFER OPENINGS IN THE WORK AREA. <br />16. EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE BASED ON <br />AVAILABLE RECORD DRAWINGS. THIS INFORMATION IS ONLY PARTIALLY <br />VERIFIED. THE CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY AND <br />INVESTIGATE ALL CONDITIONS THAT AFFECTS THE WORK PRIOR TO <br />SUBMITTING THE BID. <br />17• INSTALL AHU CONTROL PANELS TO PROVIDE FOR 3'-0' MIN. CLEARANCE IN <br />FRONT OF PANEL. <br />18. UNLESS OTHERWISE NOTED ON PLANS, LOW RETURN AIR GRILLES AND <br />LOW EXHAUST GRILLES SHALL BE 6' TO 8' AFF TO BOTTOM OF GRILLE. <br />19. ALL DIFFUSERS IN SAME SPACE SHALL HAVE THE SAME FULL FACE SIZE <br />USING LARGEST SIZE REQUIRED FROM DIFFUSER AND GRILLE SCHEDULE. <br />20. PROVIDE CLEAR ACCESS TO FIRE DAMPERS, SMOKE DAMPERS, AND <br />VALVES. <br />21. PROVIDE MANUFACTURERS CERTIFIED DATA (NOA) OR CALCULATIONS ON <br />ALL EXTERIOR MOUNTED EQUIPMENT DURING SUBMITTAL PHASE, WHICH <br />INDICATES THAT THE EQUIPMENT CAN WITHSTAND A WIND LOAD <br />REQUIRED BY THE FSBC. <br />22. ALL DUCTWORK AND PIPING MATERIALS SHALL BE PROTECTED WHILE BEING <br />SHIPPED TO THE SITE, STORED ON SITE AND AS INSTALLATION PROGRESSES. <br />DUCTWORK AND PIPING STORED ON SITE PRIOR TO INSTALLATION SHALL BE <br />OFF THE FLOOR. PIPING SHALL BE END CAPPED. COVER ALL DIFFUSERS AND <br />GRILLES AFTER INSTALLATION PRIOR TO EQUIPMENT START UP AND TEST <br />AND BALANCE. <br />23. INSTALL INTAKE AND EXHAUST PROTECTIVE SCREENS PER FMC <br />TABLE 401.6 FOR EQUIPMENT. <br />HVAC LEGEND <br />DUCTWORK <br />® SUPPLY DUCTWORK <br />RETURN OR EXHAUST <br />DUCTWORK <br />® FD FIRE DAMPER <br />® SD SMOKE DAMPER <br />® FSD COMBINATION FIRE & <br />SMOKE DAMPER <br />t� 340 SUPPLY DIFFUSER & <br />AIR QUANTITY <br />120 R. RETURN GRILLE & AIR <br />QUANTITY <br />160 E. EXHAUST GRILLE & AIR <br />QUANTITY <br />(D THERMOSTAT (ADJUST.) <br />THERMOSTAT (CON- <br />T C CEALED / KEY OPER.) <br />HO HUMIDISTAT <br />10000 �- REHEAT BOX & SYMBOL <br />010f__ REHEAT COIL <br />FID DUCT SMOKE DETECTOR <br />R• �- RISE IN DUCTWORK <br />D. I DROP IN DUCTWORK <br />- CONICAL TEE CONN. <br />(-- - BELLMOUTH CONN. <br />450 THROAT TAP <br />ED <br />BRANCH CONNECTION <br />W <br />RADIUS ELBOW R/W=1.5 <br />R <br />E:Q <br />TURNING VANES IN <br />ELBOW <br />DIVIDED FLOW <br />FITTINGS <br />I.V.D. MANUAL VOL. DAMPER <br />V.F.D. VARIABLE FREQUENCY DRIVE <br />NOTE: NOT ALL SYMBOLS MAY APPLY. <br />THE USE OF NEW OR EXISTING AIR HANDLING UNITS DURING CONSTRUCTION IS PROHIBITED <br />UNLESS APPROVED BY THE OWNER AND THE PROCEDURES OUTLINED IN THIS PARAGRAPH <br />ARE FOLLOWED RIGIDLY. <br />1. THE CONTRACTOR SHALL PROTECT THE INTERIOR OF ALL DUCTWORK AND AIR <br />HANDLING UNITS FROM THE ACCUMULATION OF DIRT AND DUST USUALLY <br />ASSOCIATED WITH THE FINISHING STAGES OF THE CONSTRUCTION WORK. <br />2. DUCTWORK STORED ON SITE AWAITING INSTALLATION SHALL BE CAREFULLY <br />EXAMINED AND THOROUGHLY CLEANED BEFORE PLACEMENT IN ITS FINAL LOCATION. <br />THE ENDS OF DUCTWORK SHALL BE CLOSED DURING CONSTRUCTION. <br />3. THE AIR HANDLING UNITS WILL BE ALLOWED TO OPERATE DURING THE FINISHING <br />STAGES OF THE GENERAL WORK PROVIDED THE PRE -FILTERS ARE IN PLACE AND <br />THE ENDS OF ALL RETURN AIR INLETS ARE COVERED WITH ROLL -UP FILTER MATERIAL. <br />4. WHEN THE SPACE IS TURNED OVER TO THE OWNER, THE CONTRACTOR SHALL REMOVE <br />ALL FILTERS USED DURING CONSTRUCTION AND REPLACE THEM WITH NEW FILTERS. <br />5. USE OF NEW AHU'S DURING CONSTRUCTION IS NOT ALLOWED. <br />MECHANICAL AS-BUILTS NOTE <br />MECHANICAL CONTRACTOR IS REQUIRED TO SUMBIT MECHANICAL AS BUILT PLANS <br />UPON COMPLETION OF THE PROJECT. COMPLETION IS DEFINED AS THE OWNER <br />RECIEVING A 'CO' AND MECHANICAL INSPECTOR HAS FINALIZED AND APPROVED THE <br />INSTALLATION. <br />AS BUILTS SHALL BE SUBMITTED IN ELECTRONIC FASHION IN EITHER AUTOCAD FORMAT <br />OR SCANNED FILES IN PDF FORMAT. <br />AS BUILTS SHALL BE LEGIBALE AND NEAT. AS BUILTS WILL BE RETAINED BY <br />ARCHITECT AND ENGINEER FOR RECORDS OF CHANGES TO THE SYSTEM. AS BUILTS WILL <br />BE SUBMITTED TO OWNER THROUGH ARCHITECT AND ENGINEER. <br />EARANCE BELOW RAISED ROOF <br />UNTED MECHANICAL EQUIPMENT <br />F <br />WIDTH OF MECHANICAL UNIT <br />MINIMUM CLEARANCE ABOVE ROOF SURFACES <br />(INCHES) <br />(INCHES) <br />< 24 <br />14 <br />24< 36 <br />18 <br />36< 48 <br />24 <br />48< 60 <br />30 <br />z 60 <br />48 <br />SHEET SHEET TITLE <br />NUMBER <br />MO.1 I MECHANICAL LEGENDS, NOTES, AND INDEX <br />MO.2 MECHANICAL SCHEDULES <br />MO.3 MECHANICAL SPECIFICATIONS <br />M1.0 CONSTRUCTION ZONE VENTILATION PLAN <br />M1 J FIRST FLOOR PLAN - DEMOLITION - MECHANICAL <br />M2.1 FIRST AND SECOND FLOOR PLANS - NEW CONSTRUCTION - MECHANICAL <br />M2.2 PARTIAL ROOF PLAN - MECHANICAL <br />M3.1 MECHANICAL DETAILS <br />M3.2 MECHANICAL DETAILS <br />M4.1 MECHANICAL CONTROLS <br />MECHANICAL DEMOLITION NOTES <br />1. FOR EQUIPMENT AND SYSTEMS TO REMAIN IT SHALL BE THE CONTRACTOR'S <br />RESPONSIBILITY TO VERIFY THE CONDITION OF, EXACT SIZES AND LOCATION OF <br />EXISTING DUCT AND PIPING ETC. BEFORE DEMOLITION WORK IS BEGUN. REPORT <br />ANY DISCREPANCIES BETWEEN PLANS AND ACTUAL FIELD CONDITIONS TO THE <br />OWNER AND ENGINEER PRIOR TO THE COMMENCEMENT OF DEMOLITION WORK. <br />2. REMOVE THE INDICATED HVAC ITEMS AS SHOWN ON PLANS, THIS INCLUDES ALL <br />HANGERS, STRAPS AND RELATED MATERIAL. AS DIRECTED THIS MATERIAL <br />SHALL BE REMOVED FROM THE SITE OR TURNED OVER TO THE OWNER (AS <br />DIRECTED BY THE OWNER). <br />3. CAP AND SEAL AIR TIGHT ALL POINTS AT WHICH DUCTWORK IS REMOVED FROM <br />DUCTWORK THAT WILL REMAIN. <br />4. PATCH AND MATCH OPENINGS IN WALLS TO MAINTAIN THE INTEGRITY OF THE <br />WALL WHERE AIR DEVICES, DUCTS, PIPING, ETC. HAVE BEEN REMOVED. <br />(MAINTAIN THE EXISTING RATINGS). <br />5. CONTRACTOR SHALL VERIFY CLEARANCE REQUIREMENTS AND INDICATE <br />ROUTING OF NEW DUCTWORK BEFORE FABRIC4TION BEGINS AS RISES AND <br />DROPS MAY BE NECESSARY DUE TO EXISTING FIELD CONDITIONS. <br />6. ALL DEMOLITION WORK SHALL COMPLY WITH NFPA 241 AND THE REQUIREMENTS <br />OF THE OWNER. <br />TEST & BALANCE NOTES <br />1. PRECONSTRUCTION: <br />PRIOR TO COMMENCEMENT OF ANY HVAC WORK AN INDEPENDENT AABC OR NEBB <br />CERTIFIED T&B CONTRACTOR SHALL MEASURE AND DOCUMENT, IN A TYPED REPORT <br />THE AIRFLOW QUANTITIES PROVIDED OR EXHAUSTED BY ALL EXISTING <br />EQUIPMENT AND DUCTS TO REMAIN THAT SERVE OR ARE SERVED FROM THE <br />RENOVATED AREA. SUBMIT TYPE WRITTEN DATA TO ENGINEER FOR REVIEW. <br />THE FOLLOWING INFORMATION IS REQUIRED: <br />- AIR FLOW OF ALL AIR DEVICES IN RENOVATED AREA(S). <br />- AIR FLOW (TRAVERSE) AT MAINS AND BRANCH DUCTS SERVING THE RENOVATED <br />AREA(S). <br />- AIR FLOW AT UNITS (TRAVERSE) AT MAINS AND BRANCH DUCTS SERVING THE <br />RENOVATED AREA(S). <br />- SUCTION AND DISCHARGE STATIC AT UNITS SERVING THE RENOVATED AREA(S). <br />- MEASURED FAN RPM, MOTOR AMPERAGE FOR ALL UNITS SERVING THE RENOVATED <br />AREA(S). <br />- PROVIDE EXISTING UNIT AND MOTOR NAME PLATE DATE. <br />2. FINAL CONSTRUCTION: <br />UPON COMPLETION OF THE HVAC RENOVATION WORK, THE SAME CONTRACTOR SHALL <br />REBALANCE THE NEW AND EXISTING EQUIPMENT AND DUCTS TO PROVIDE INDICATED <br />AIR QUANTITIES TO THE RENOVATED SPACE. ANY ADDITION OF DAMPERS, <br />ADJUSTMENTS, (FAN SPEED, CHANGE OUT OF PULLEYS, ETC.) REQUIRED FOR THIS SHALL <br />BE INCLUDED IN THIS CONTRACTORS PROPOSAL. <br />3. FINAL REPORT: <br />SUBMIT FINAL TEST AND BALANCE REPORT TO ENGINEER FOR REVIEW AND ACCEPTANCE <br />ONE WEEK PRIOR TO FINAL AHCA INSPECTION FOR EACH PHASE. <br />4. NOTE: <br />IF PRE -TAB IS NOT COMPLETE IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR <br />TO COORDINATE WITH THE OWNER TO RESOLVE ANY TEST AND BALANCE ISSUES AT <br />THE END OF THE PROJECT. <br />HAZARDOUS MATERIAL NOTES <br />1. PORTIONS OF THE EXISTING SYSTEM MAY CONTAIN HAZARDOUS MATERIAL <br />(ASBESTOS). COORDINATE WITH THE OWNER TO DETERMINE THE LOCATION <br />AND TYPES OF HAZARDOUS MATERIALS. <br />2. THE OWNER IS RESPONSIBLE FOR THE IDENTIFICATION, REMOVAL AND <br />DISPOSAL OF HAZARDOUS MATERIAL AND IS NOT TO BE INCLUDED AS <br />PART OF THE WORK OF THIS CONTRACT UNLESS SPECIFICALLY IDENTIFIED <br />AS SUCH. <br />3. IF ANY MATERIAL APPEARS TO CONTAIN HAZARDOUS MATERIAL AND WAS <br />NOT PREVIOUSLY IDENTIFIED. THE CONTRACTOR IS TO INFORM THE OWNER <br />TO RECEIVE INSTRUCTIONS ON HOW TO PROCEED. <br />SCOPE OF WORK <br />ANGIO SUITE UPGRADES: <br />EXISTING AHU SERVING AREA TO BE REBALANCE TO ALLOW FOR EXTERIOR EXHAUST <br />FOR ICRA REQUIREMENTS. <br />ADDITION OF NEW DX AHU/CU ON ROOF. SYSTEM IS A SEPARATED AHU AND <br />CONDENSER UNITS. <br />ADDITION OF A NEW EXHAUST FAN TO SERVER ANGIO PROCEDURE ROOM. <br />ADDITION OF NEW DX CRAC UNIT FOR ANGIO CONTROL ROOM. <br />NEW S/A, R/A, AND E/A DUCTWORK. <br />NEW CONTROLS TO BE TIED INTO EXISTING CONTROL SYSTEM. <br />NJ, 08 !�Iwl <br />c� <br />COD <br />v <br />o <br />o � <br />rn <br />OC-4� <br />SS'PSmith <br />%L Reid, Inc. <br />600 West Hillsboro, Suite 300 <br />Deerfield Beach, FL 33441 <br />(954) 421-1260 <br />FAX:(954) 421-1466 <br />www.ssr-inc.com <br />Firm Certificebm - EB4000867 <br />DenDavie PE - 63633 <br />John E. mmmer PE - 33200 <br />SSR JOB # 1137003.0 <br />0 <br />E OP,; <br />"®NALi,�`�'�`� <br />.o <br />x <br />b <br />t <br />O <br />c <br />A <br />COD <br />N <br />X <br />W <br />Z •� <br />CD <br />>Z <br />Cn <br />Z <br />W <br />C7 <br />LLI <br />J <br />J <br />U_ <br />Z O <br />Q O <br />2 <br />W O <br />byp <br />� •N <br />Project No. 00000.00 <br />© 2011 BHI PKArchitects, Inc. <br />