'SEE DETAIL <br />k <br />----------------- <br />I <br />CONSTRUCTION ZONE VENTILATION PLAN <br />PROVIDE FSD OR FD WHERE DUCT RUNS THROUGH RATED WALLS. COORDINATE <br />IN FIELD WITH SITE CONDITIONS AND CONTRACTORS ROUTING. PROVIDE LOW <br />VOLTAGE CONTROLS POWER FOR FSD'S. FSD'S SHALL BE WIRED TO THE <br />FIRE ALARM SYSTEM AND SHALL CLOSE WHEN FIRE ALARM IS INITIATED. <br />MVD <br />MVD <br />CONSTRUCTION AREA AIRFLOW <br />TEE FITTING <br />METAL FLEX <br />DUCT (TYP.) <br />A. I PORTABLE AIR SCRUBBER <br />I per WITH HEPA FILTER <br />ADJACENT SPACE <br />TRANSFER AIR BACK TO <br />CONSTRUCTION AREA <br />12x12 LAY -IN <br />CEILING DIFFUSER <br />l <br />is <br />1 <br />i <br />i <br />I <br />I <br />: <br />-- <br />— -- -- - — - ----- - — -- <br />�i <br />------------- <br />i <br />N <br />F F_^ UNj%1"MfAVL rnvm 1 <br />NEGATIVE AIR PRESSURE <br />MACHINE <br />EQUIPMENT SPECIFICATIONS <br />1. ROOM PRESSURE MONITOR - ABATEMENT TECHNOLOGIES MODEL HCRPM-3N2 <br />(800-634-9091) OR EQUIVALENT. PROVIDE WITH THE FOLLOWING FEATURES: <br />A.) WALL MOUNT, LCD DISPLAY, 12 TO 24 VAC, 400 MILLI AMPS. FURNISH WITH 120/24VAC <br />PLUG-IN TRANSFORMER. <br />B.) ACCURACY +/- 1 % OF SCALE, ALARM ACCURACY +/- 1 % OF SETPOINT. <br />C.) LOCAL/REMOTE AUDIO/VISUAL ALARM WITH SPDT RELAY FOR REMOTE. CONTACTS <br />RATED FOR 10 AMPS AT 250 VAC. <br />D.) ADJUSTABLE ALARM DELAY SET FOR THREE MINUTES, MAXIMUM FIVE MINUTES. <br />E.) AUTO CALIBRATION WITH DATE AND TIME MEMORY OF ALARMS. <br />F.) RANGE OF MEASUREMENT +/- 0.10 INCHES OF WATER COLUMN. <br />2. PORTABLE AIR SCRUBBERS - ABATEMENT TECHNOLOGIES MODEL HEPA - AIRE PAS <br />(800-634-9091) OR EQUIVALENT. PROVIDE WITH THE FOLLOWING FEATURES: <br />A.) U.L. OR E.T.L. LISTED. <br />B.) STAINLESS STEEL CABINET WITH INTEGRAL TRANSPORT DOLLY AND EXHAUST <br />COLLAR. <br />C.) UP TO FOUR STAGES OF FILTRATION WITH ZERO BYPASS CABINET CONSTRUCTION. <br />a.) FIRST STAGE 1' PARTICULATE FILTER. <br />b.) SECOND STAGE 2' PLEATED FILTER. <br />c.) OPTION CARBON FILTER TRACK. <br />d.) 99.97% EFFICIENT DOP HEPA FILTER. <br />D.) FILTER CHANGE INDICATOR LAMPS FOR PRE -FILTER AND FINAL FILTERS. <br />E.) POWER CORD FOR 120 VAC POWER CONNECTION, OPERATING HOUR METER, TWO <br />SPEED OR VARIABLE SPEED BLOWER. <br />EQUIPMENT SCHEDULE <br />O HCRPM-3NA ROOM PRESSURE DIFFERENTIAL MONITOR WITH REMOTE ALARM. <br />OB PAS MODEL 2400 RATED AT 2100/700 CFM. FILTRATION REQUIRED Ca/Cb/Cd, <br />120VAC,12 AMPS <br />PAS MODEL 1200 RATED AT 900/150 CFM. FILTRATION REQUIRED Ca/Cb/Cd, <br />120VAC, 4 AMPS <br />OD PAS MODEL 600 RATED AT 600/50 CFM. FILTRATION REQUIRED Ca/Cb/Cd, <br />120VAC, 2 AMPS <br />NOTE: AIRFLOW REDUCTION ALLOWANCE OF 15% FOR EXHAUST DUCT COLLAR AND 25 <br />FEET OF FLEX EXHAUST DUCT. ALLOW AN ADDITIONAL 15% REDUCTION IN <br />AIRFLOW FOR EACH ADDITIONAL 25 FEET OF FLEX DUCT. PAS MODEL 1200 <br />REQUIRES A 10' ROUND CONNECTION COLLAR AND PAS MODEL 2400 REQUIRED <br />A 12' ROUND CONNECTION COLLAR. <br />CONSTRUCTION ZONE NEGATIVE PRESSURE <br />1. MINIMUM NEGATIVE PRESSURE IN CONSTRUCTION ZONE PER OWNER'S <br />ICRA REQUIREMENTS = 0.02' WG <br />2. ADJUST DISCHARGE AIR VOLUME ON HEPA NEGATIVE PRESSURE MACHINE TO <br />MAINTAIN A MINIMUM OF 0.02' WG NEGATIVE PRESSURE AS MEASURED BY ROOM <br />PRESSURE DIFFERENTIAL MONITOR(S) UP TO A MAXIMUM OF 0.04' WG NEGATIVE <br />PRESSURE <br />3. DISCHARGE AIR TO ADJACENT ZONE ACCEPTABLE PROVIDED THE AIR IS PASSED <br />THROUGH A HEPA FILTER PER OWNERS ICRA REQUIREMENTS. <br />CONSTRUCTION ZONE VENTILATION <br />ESTIMATED VOLUME = 16,200 CU. FT. <br />HEPA SCRUBBER AIR CHANGES PER OWNER'S ICRA REQUIREMENTS = 10 <br />AIR CHANGES PROVIDES: <br />2 x 1350 CFM x 60 MIN _ 10 AIR/CHG <br />16,200 CU. FT. <br />INLET PLENUM <br />I <br />2x12 LAY -IN <br />CEILING DIFFUSER <br />CONSTRUCTION WORK ZONE <br />VENTILATION NOTES <br />1. CONTRACTOR SHALL OBTAIN FROM THE OWNER A COPY OF THE INFECTION CONTROL <br />RISK ASSESSMENT (ICRA) PREPARED FOR THIS PROJECT. CONTRACTOR SHALL REVIEW <br />THE REQUIREMENTS IN THE REPORT AND PERFORM ALL WORK IN ACCORDANCE WITH <br />THOSE REQUIREMENTS. CONTRACTOR SHALL STRICTLY ADHERE TO THE LIMITS OF <br />THE CONSTRUCTION AREA, AND WHERE PHASING APPLIES SHALL ADHERE TO THE <br />PHASING PLAN. ANY WORK OUTSIDE THE CONSTRUCTION AREA SHALL BE COORDINATED <br />WITH THE OWNER AND PERFORMED IN ACCORDANCE WITH THE ICRA REPORT, UNDER <br />THE SUPERVISION OF THE OWNER'S REPRESENTATIVE OR OTHER DESIGNATED ICRA <br />COMMITTEE OFFICER. <br />2. TO THE EXTENT THAT IT IS REQUIRED BY THE ICRA, THE CONTRACTOR SHALL <br />ENDEAVOR TO MAINTAIN EXISTING LEVELS OF INDOOR AIR QUALITY IN AREAS <br />SURROUNDING AND ADJACENT TO THE CONSTRUCTION WORK ZONE, AND ELSEWHERE <br />IN THE FACILITY. IT SHOULD BE ANTICIPATED THAT THE ICRA REPORT WILL REQUIRE <br />MEASURES TO THIS EFFECT INCLUDING ERECTION OF CONSTRUCTION ZONE BARRIERS <br />AND PROVISION OF NEGATIVE AIR PRESSURE IN THE CONSTRUCTION ZONE RELATIVE <br />TO OTHER AREAS OF THE FACILITY AS SHOWN ON PLANS. <br />3. IN ADDITION TO MEETING THE REQUIREMENTS OF THE ICRA REPORT, THE <br />CONTRACTOR SHALL PROVIDE EQUIPMENT AND COMPONENTS AS SHOWN ON <br />CONSTRUCTION WORK ZONE VENTILATION PLAN TO CREATE A NEGATIVE PRESSURE IN <br />THE CONSTRUCTION WORK ZONE RELATIVE TO ADJACENT AREA. EXISTING HVAC <br />SYSTEMS AND COMPONENTS SHALL NOT BE USED FOR THIS FUNCTION, UNLESS <br />SPECIFICALLY APPROVED BY THE OWNER'S INFECTION CONTROL OFFICER AND ONLY TO <br />THE EXTENT INDICATED ON THE CONSTRUCTION WORK ZONE VENTILATION PLAN. THE <br />CONCEPT AND ALL ASPECTS OF THIS WORK SHALL BE DONE IN ACCORDANCE WITH <br />THE ICRA REQUIREMENTS AND AT A MINIMUM AS FOLLOWS: <br />VERIFY ALL EXISTING DUCTWORK WHICH PASSES THROUGH THE <br />CONSTRUCTION ZONE, AND IS TO REMAIN, IS SEALED AND PROTECTED <br />DURING THE CONSTRUCTION DURATION. COVER AND SEAL ALL DIFFUSERS, <br />REGISTERS AND GRILLES. <br />AIR REMOVED FROM THE CONSTRUCTION ZONE SHALL BE FILTERED AND/OR <br />DISCHARGED AS INDICATED ON THE CONSTRUCTION WORK ZONE VENTILATION <br />PLAN. <br />MONITOR AND VERIFY NEGATIVE PRESSURE IS BEING MAINTAINED IN <br />ACCORDANCE WITH THE ICRA REPORT, AND PROVIDE DOCUMENTATION TO THE <br />OWNER AS REQUIRED. <br />4. COORDINATE IN ADVANCE ANY REQUIRED EQUIPMENT SHUTDOWN WITH THE OWNER, <br />AND VERIFY BEFORE SHUTDOWN THAT EXISTING OR DESIRED AIR PRESSURE <br />RELATIONSHIPS WILL NOT BE ADVERSALY AFFECTED. <br />5. CONTRACTOR SHALL HAVE AIR SCRUBBER, PRESSURE MONITORS, ALARMS, DISCHARGE <br />AIR DUCTS AND ANY MODIFICATIONS TO EXISTING HVAC SYSTEMS READY PRIOR TO <br />DEMOLITION AND READY FOR TAB CONTRACTOR TO PERFORM CONSTRUCTION WORK <br />ZONE VENTILATION PLAN TESTING, ADJUSTING AND BALANCING. <br />6. DEMOLITION WORK SHALL NOT BEGIN UNTIL CONSTRUCTION WORK ZONE VENTILATION <br />PLAN TAB REPORT HAS BEEN REVIEWED AND APPROVED BY THE ARCHITECT/ENGINEER <br />AND THE OWNER'S INFECTION CONTROL COMMITTEE. <br />CONSTRUCTION WORK ZONE VENTILATION <br />PLAN TEST & BALANCE NOTES <br />1. PRE -DEMOLITION <br />PRIOR TO COMMENCEMENT OF ANY DEMOLITION WORK IN THE CONSTRUCTION AREA <br />AN INDEPENDENT AABC OR NEBB CERTIFIED TESTING, ADJUSTING AND BALANCING <br />(TAB) CONTRACTOR SHALL MEASURE AND DOCUMENT IN A TYPED REPORT THE <br />FOLLOWING INFORMATION: <br />A.) SPEED SETTING AND AIRFLOW OF ALL AIR SCRUBBER(S), RECIRCULATING AND <br />EXHAUST. <br />B.) DIFFERENTIAL PRESSURE READING OF ALL AIR SCRUBBER FILTER GAUGES. <br />C.) DIFFERENTIAL PRESSURE BETWEEN CONSTRUCTION ZONE AND ADJACENT AREAS AT <br />EACH DOORWAY ENTRANCE TO THE CONSTRUCTION ZONE. <br />D.) VERIFY ROOM PRESSURE DIFFERENTIAL MONITORS LOCATED NEAR DOORWAY <br />ENTRANCE TO CONSTRUCTION ZONE ARE READING WITHIN +/- 10% OF FIELD <br />READINGS OF ITEM 3 ABOVE. <br />E.) VERIFY THREE MINUTE ALARM DELAY IS FUNCTIONING ON ROOM PRESSURE <br />DIFFERENTIAL MONITORS AND THAT LOCAL AND REMOTE AUDIO/VISUAL ALARMS <br />FUNCTION WHEN CONSTRUCTION AREA NEGATIVE RELATIVE PRESSURE DROPS <br />BELOW MINIMUM SETPOINT. <br />F.) ANY DEFICIENCIES IN MEETING THE OWNER'S ICRA REQUIREMENTS FOR AIR. <br />CHANGES, RELATIVE NEGATIVE PRESSURE OR FAULTY EQUIPMENT SHALL BE <br />IDENTIFIED IN THE FINAL REPORT. <br />�i <br />-w <br />0 <br />7 <br />zi <br />v� <br />t -4 <br />o <br />i y O <br />AQ <br />�r�a,a <br />Smith <br />SS13L Reid, Inc. <br />600 West Hillsboro, Suite 300 <br />Deerfield Beach, FL 33441 <br />(954) 421-1260 <br />FAX:(954) 421-1466 <br />www.ssr-inc.com <br />Firm Certification - EB-0000857 <br />Dennis Davis PE - SSW <br />John E. Moulder PE - 33200 <br />SSR JOB # 1137003.0 <br />i <br />���1111111 <br />STATE OF <br />CC) ,p.0. <br />� . <br />to AL <br />QZ <br />J <br />CL <br />Z <br />O <br />Q <br />J_ <br />z <br />W <br />LLI <br />z <br />O <br />N <br />z <br />O <br />F— <br />CU <br />Z <br />O <br />0 <br />S' <br />0 <br />0 <br />0 <br />• N <br />COMBINATION NEGATIVE AIR PRESSURE <br />MACHINE AND AIR SCRUBBER DETAIL <br />NTS <br />1 <br />DISCHARGE AIR DETAIL <br />NTS <br />Project No. 00000.00 <br />M100 <br />cg) 2011 BH1 PE Architects, Inc. <br />