<br />DIVISION I - GENERAL
<br />SECTION 01045 - CUTTING AND PATCHING
<br />Scope: I. Cutting and patching Includes cutting Into existing construction for the Installation
<br />or performance of other work and patching required to restore the surfaces to their
<br />original condition.
<br />a. Unless otherwise specified the requirements for this section also apply to
<br />mechanical and electrical work. Refer to divisions l5 and 16 for further
<br />requirements.
<br />b. Do not cut and patch exposed work In a manner that In the Architect/Engineers
<br />opinion results In lessening the buildings aesthetic qualities. Replace any work
<br />judged by the Archltect/Engineer to be usually satisfactory.
<br />c. Do not cut and patch exposed work In a manner that would result in the
<br />reduction of load carrying capacity or load deflection ratio. When In doubt
<br />notify the Archltecl/Englneer.
<br />Products: I. Except as otherwise indicated, or as directed by Archltect/ Engineer, use
<br />material for cutting and patching that are Identical to existing materials.
<br />Execution: I. Provide temporary support and protection of existing work as required.
<br />SECTION 01300 - SUBMITTALS, PRODUCTS, AND SUBSTITUTIONS
<br />Scope: I. Format for submittals: As required for specific type and by Individual sections.
<br />2. Types of submittals and number of copies.
<br />a. Shop drawings, reviewed and annotated by the general contractor 6 copies
<br />b. Product data - 6 copies
<br />c. Samples - 2, plus extra samples as required to indicate range of color, flnlsh, and
<br />texture to be expected.
<br />d. Mock- ups - as required in Individual sections.
<br />e.Inspection and test reports - 4 copies
<br />f. Warranties - 2 copies
<br />g. Survey data - 2 copies.
<br />h. Closeout submittals - 2 copies
<br />DIVISION 5 - METALS
<br />SECTION 02200 - EARTHWORK
<br />Refer to structural drawings for Structural Steel requirements
<br />DIVISION 6 - WOOD AND PLASTICS
<br />SECTION 06100 - ROUGH CARPENTRY
<br />Scope: I. Provide rough carpentry work Including but not limited to: nollers, blocking,
<br />furring and sleepers.
<br />Products: I. Lumber, finished 4 sides,19Z maximum moisture content.
<br />a. Light framing: Construction grade Douglas fir or southern pine, appearance
<br />grade where exposed.
<br />b. Structural froming and timbers: No. I grade Douglas fIr or southern pine,
<br />appearance grade where exposed.
<br />c. Boards: Construction grade
<br />2. Wood for nollers, furring and sleepers: Construction grade, finished 4 sides,
<br />19% moisture content. Pressure preservative treat Items in contact with roofing,
<br />f lashing, waterproof Ing, mosonry, concrete or the ground.
<br />J. Plywood, APA rated for use and exposure.
<br />a. Backing: Interior A/C grade.
<br />4. Building paper: Asphalt saturated felt, non -perforated, ASTM D 226, Typ 1.30 Ibs
<br />5. Provide certification that wood products contain no urea formaldehyde.
<br />6. Wood treatment:
<br />a. Exterior wood AWPA standard UI and TI. Categories UCI, UC2, UC3A, UC3B, CU4A,
<br />CU48 Alkaline Copper Ouaternory based treatment.
<br />b. interior wood AWPA Cl Timber, AWPA C9 Plywood, AWPA C31 Lumber not In contact
<br />with ground and protected from water, AWPA 5 Waterborne Preservatives,
<br />AWPA M4 Disodlum Octoborate based treatment.
<br />7. Sealants: For setting wood bucks and nollers In exterior opening refer to Division 7.
<br />8. All wood blocking to be fire retardant treated.
<br />Execution: I. General: Set plumb, level, and square as required by job conditions.
<br />SECTION 06200 - FiNISH CARPENTRY
<br />Scope: I. Provide flnlsh carpentry for woodwork Items exposed to view
<br />a. Lumlcor panel frame and chair roll.
<br />Products: 1. Ouallty for fabrication and products shall be AWI Premium Grade
<br />2. Species for panel frame and chair roll to be red oak suitable for stain flnlsh.
<br />Execution: 1. Comply with AWI specifications.
<br />2. Set work, plumb, scribe to fit level and true as required by job conditions.
<br />DIVISION 7 - THERMAL AND MOISTURE PROTECTION
<br />SECTION 07200 - INSULATION
<br />Scope: I. Provide building Insulation as shown on the drawings.
<br />a. Unf aced fibergloss sound attenuation botts
<br />Products: I. Unf aced fiberglass sound attenuation botts.
<br />a. Unfaced mineral fiber butts complying with ASTM C665 Type I.
<br />To be full thickness of cavity It Is installed In.
<br />2. All products to be certlf led formaldehyde free.
<br />3. Auxiliary materials : Adhesives for bonding Insulation to substrates and
<br />mechanical anchors. Adhesives shall have a VOC content of 250g/L or less
<br />when calculated according to 40 CFR 59 Subpart D (EPA Method 24)
<br />Execution: I. Provide tight gaps at unit Intersections.
<br />2. Install and support units per type of substrate indicated.
<br />SECTION 07270 - FIRESTOPPING
<br />Scope: I. Provide flrestopping Insulation and caulking to prevent passage of
<br />flame and products of combustion through concealed spaces, openings
<br />between and around floors and fire rated assemblies.
<br />Products: I. Assemblies as Indicated on drawings and / or required by
<br />existing construction.
<br />SECTION 07900 - JOINT SEALERS
<br />Scope: I. Provide sealant at Intersection of building components.
<br />Products: I. Joints designed for expansion and movement conditions at site:
<br />a. Elostomerlc sealant for exterior work
<br />b. Non-elostomeric caulking compounds for interior work
<br />2. Elostomerlc joint sealants:
<br />a. Manufacturers standard one part non ocld-curing silicone sealant
<br />Type S Grade NS complying with ASTM C 920 and ASTM C 719
<br />J. Latex (non elostomeric) sealants for interior joints.
<br />a. Manufacturers standard one part, non sag acrylic sealant complying with C 834
<br />b. VOC content of Interior sealants: Sealants and sealant primers used Inside
<br />the weatherproofing system shall comply with the following limits for VOC
<br />content calculated according to 40 CFR 59, subpart D (EPA Method 24):
<br />I. Architectural sealants: 250 g/L
<br />2. Sealant primers for nonporous substrates: 250 g/L
<br />3. Sealant primers for porous substrates:775 g/L
<br />4. Joint sealant backing
<br />a. Plastic foam joint fillers of open cell polyurethane foam.
<br />b. Bond breaker tape
<br />c. Compressible joint filler backup
<br />Execution: I. Place sealants as required by job conditions and install per
<br />manufacturers recommendations.
<br />DIVISION 8 - DOORS AND WINDOWS
<br />SECTION 08110 - STEEL DOORS AND FRAMES
<br />Scope: I. Provide hollow metal door frames
<br />Products: I. Comply with the Florida Building Code.
<br />2. Frames: Welded construction with mitered corners. gage as follows:
<br />a. Interior fromes:16 gage up to 5' wide,14 gage over 5' wide.
<br />b. Exterior frames: 14 gage
<br />J. Finish
<br />a. Interior: Rust Inhibiting primer suitable for painting
<br />b. Exterior: Galvanized G60 ASTM AS2S
<br />4. Fire Roting: UL Labeled where required.
<br />Execution: I. Install per manufacturer recommendations, final shop drawings and SDI-105
<br />recommended erectors Instructions for steel frames.
<br />SECTION 08210 - WOOD DOORS
<br />Scope: I. Provide solid core flush wood doors.
<br />Products: I. Comply with the Florida Building Code
<br />2. Solid core flush wood door with particle board core.
<br />3. Faces: To match existing doors..
<br />4. Finish. To match existing flnlsh. Provide Urethane top coats.
<br />5. Products and adhesives to contain NO Urea Formaldehyde.
<br />Execution: I. Install doors plumb and true. Follow all manufacturers recommendations,
<br />final shop drawings and NFPA 80 where applicable
<br />DIVISION 8 - DOORS AND WINDOWS - CONTINUED
<br />SECTION 08710 - FINISH HARDWARE
<br />Scope: 1. Provide finish hardware for sliding, and swinging doors.
<br />Products: 1. ADA compatible hardware finish and type to match existing.
<br />Execution: I. Install per manufacturers recommendations and code requirements.
<br />Hardware Schedule: Refer to drawings.
<br />DIVISION 9 - FINISHES
<br />SECTION 09250 - GYPSUM DRYWALL
<br />Scope: 1. Gypsum drywall including screw type metal support systems.
<br />Products: 1. Gypsum wallboard: ASTM C 36, of types, edge conflguratlon and thickness Indicated:
<br />In maximum lengths available to minimize end -to -end butt joints
<br />o. Type: Standard
<br />b. Type 'X' for rated assemblies - Standard
<br />c. Edges: Tapered
<br />d. Thickness: As Indicated. or if not otherwise Indicated, as required to comply
<br />with ASTM C840 for application system and supporting spacing indicated.
<br />2. Ceiling Support Materials and Systems
<br />a. General: Size celling components to comply with ASTM C 754 unless otherwise Indicated.
<br />3. Wall/Partition Support Materials:
<br />a. Studs: ASTM C645: 20 gage unless otherwise indicated. Use /6 gage steel studs
<br />at shower seat supports and rolling counter service doors or where required by
<br />wall mounted equipment. Consult manufacturers literature limiting height/gages of all
<br />wall assemblies
<br />4. Accessories: Galvanized steel corner beads, casing beads, control joints and materials
<br />as recommended by manufacturer.
<br />5. Acoustical sealant: US Gypsum Acoustical Sealant or equal. VOC limits to comply with
<br />Section 07200.
<br />Execution: I. Comply with manufacturers recommendations and ASTM C840
<br />2. Finish: Provide smooth Level 4 flnlsh.
<br />SECTION 095/0 - ACOUSTICAL CEILINGS
<br />Scope: 1. Provide acoustical ceilings and metal suspension system.
<br />2. Fire Performance Characteristics: Provide materials that are Identical to those tested for
<br />the following fire performance characteristics, per ASTM test method Indicated below,
<br />by UL or other testing and Inspecting organizations acceptable to authorities having
<br />jurisdiction. Identify acoustical ceiling components with appropriate markings of
<br />applicable testing and Inspecting organizations.
<br />a. Flame spread 25 or less
<br />b. Smoke developed 450 or less
<br />Products: 1. Acoustical panels: Use Armstrong Cortega 1770 2 x 2 x 5/8'.
<br />Use Armstrong 3150 2 x 2 x P In MRI Scan Room.
<br />2. Exposed Grid Suspension System: Armstrong Prelude XL 15/16' 7300.
<br />Use aluminum grid and suspension system In MRI Scan Room. Armstrong
<br />AL Prelude Plus XL 7200.
<br />3. Accessories: As required for complete Installation.
<br />4. Extra Materials: 2.0 percent or minimum (I) carton of each product used.
<br />Execution: I. Comply with Manufacturers recommendations, C/SA 'Ceiling Systems Handbook' and ASTM C636.
<br />SECTION 09650 - RESILIENT FLOORING
<br />1. Provide resilient flooring.
<br />2. Fire Test Performance: Provide resilient flooring which compiles with the following
<br />fire test performance criteria as determined by an Independent testing laboratory
<br />acceptable to authorities having jurisdiction.
<br />a. Critical Radiant Flux (CRF): Not less than the following rating per ASTM E 648.
<br />0.45 watts per sq. cm.
<br />b. Flame Spread: Not more than 25 per ASTM E 84.
<br />c. Smoke Developed: Not more than 450 per ASTM E 84
<br />d. Smoke Density: Not more than 450 per ASTM E662
<br />Products: I. Resilient flooring: Vinyl plank, vinyl composition the and cove vinyl base. Refer to flnlsh drawings.
<br />2. Adhesives (Cements): Waterproof, stabilized type as recommended by flooring
<br />manufacturer to suit material and substrate conditions.
<br />J. Concrete slob primer: Non -staining type compatible with adhesive as recommended by
<br />flooring manufacturer.
<br />4. Leveling compound: Latex type compatible with adhesive as recommended by
<br />flooring manufacturer.
<br />5. Adhesives shall comply with the following limits for VOC content when calculated
<br />according to 40 CFR 59 Subpart D (EPA method 24).
<br />a. Adhesives: VOC not more than 50 g/L
<br />6. Extra materials:
<br />a. Provide additional resilient flooring in the amount of 2.0 percent, or I carton
<br />whichever Is greater, for each type specified for maintenance stock.
<br />Execution: I. Clean and prepare floor In accordance with manufacturers recommendations
<br />2. Clean all floor surfaces per manufacturers recommendations and wax
<br />vinyl composition tie (If applicable).
<br />SECTION 09900 PAINTING
<br />Scope: I. Provide painting and surface preparation for all interior surfaces,
<br />as required and scheduled.
<br />Products: 1. Provide Sherwin Williams products as specified.
<br />2. Extra Materials minimum one gallon of each type and color of paint used.
<br />Execution: I. Examine all substrates for compliance with manufacturers recommendations.
<br />2. Prepare and Install all paint per manufacturer's recommendations.
<br />DIVISION 10 - SPECIALTIES
<br />Scope: I. Provide celling mounted projector and skylight system by Dream Think Imagine
<br />28 Schenk Parkway Suite 200
<br />Astvllle NC 28803
<br />1-321-251-6826
<br />Products: I. All as required for complete Installation.
<br />Execution: I Install per manufacturers recommendations.
<br />DIVISION /3 - SPECIAL CONSTRUCTION
<br />SECTION 13/00 - MRI SHIELDING
<br />Scope: I. Provide RF and Magnetic shielding as described on vendor Installation drawings
<br />and shielding report.