N <br />2-31 <br />LM <br />C; <br />N <br />Go <br />N <br />te <br />ROOM NAME <br />ROOM NUMBER <br />M U =21 AI R BALAN CE TAMLE <br />REQUIRED <br />PRESSURE <br />RELATIONSHIP <br />TO ADJACENT <br />AREA <br />REQUIRED ROOM <br />PRESSURIZATION <br />FLOW <br />INDOOR AIR <br />CIRCULATION <br />OUTDOOR AIR VENTILATION <br />DESIGN AIR BALANCE <br />SUPPLY RETURN <br />EXHAUST TRANS AIR <br />[CFM] [CFM] AIR AIR AIR [CFM] [CFM] IN(+) OUT (-) <br />TRANSFER AIR DIRECTION <br />FROM TO <br />TOTAL AC/HR <br />MINIMUM AS <br />REQUIRED DESIGNED <br />O/A VALUES PER ASHRAE STD 170 <br />MINIMUM CALCULATED <br />AC/HR AS <br />REQUIRED AC/HR DESIGNED REQUIRED O/A <br />O/A VALUES PER ASHRAE STD 62.1 <br />MINIMUM PEOPLE <br />MINIMUM AREA <br />OUTDOOR AIR CALCULATED <br />RATE RATE [CFM/FT2] OUTDOOR AIR REQUIRED O/A <br />CFM/PERSON <br />R AND T NORTH <br />1-100 <br />0 <br />-100 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />860 <br />960 <br />0 <br />100 <br />R AND T SOUTH <br />1-101 <br />0 <br />-100 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />860 <br />960 <br />0 <br />100 <br />HC TOILET <br />1-102 <br />- <br />-75 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />30 <br />0 <br />105 <br />75 <br />HC DRESS EAST <br />1-105 <br />0 <br />35 <br />N/R <br />262.5 <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />35 <br />0 <br />0 <br />-35 <br />HC DRESS <br />1-106 <br />0 <br />35 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />35 <br />0 <br />0 <br />-35 <br />HC DRESS WEST <br />1-104 <br />0 <br />35 <br />N/R <br />262.5 <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />35 <br />0 <br />0 <br />-35 <br />SUB WAIT <br />1-103 <br />0 <br />-30 <br />N/R <br />1087.5 <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />145 <br />175 <br />0 <br />30 <br />R AND F <br />1-108 <br />0 <br />-100 <br />N/R <br />6450.0 <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />860 <br />960 <br />0 <br />100 <br />PASSAGE <br />1-109 <br />0 <br />25 <br />N/R <br />1687.5 <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />225 <br />200 <br />0 <br />-25 <br />STORAGE <br />1-110 <br />0 <br />0 <br />N/R <br />0.0 <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />40 <br />40 <br />0 <br />0 <br />HC TOILET <br />1-111 <br />- <br />-75 <br />N/R <br />487.5 <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />65 <br />0 <br />140 <br />75 <br />INJ ROOM <br />1-112 <br />0 <br />0 <br />N/R <br />2662.5 <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />355 <br />355 <br />0 <br />0 <br />PASSAGE <br />1-113 <br />0 <br />225 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />225 <br />0 <br />0 <br />-225 <br />PASSAGE <br />1-119 <br />0 <br />0 <br />N/R <br />1050.0 <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />140 <br />140 <br />0 <br />0 <br />NUCLEAR MEDICINE <br />1-114 <br />0 <br />-100 <br />N/R <br />9000.0 <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />1200 <br />1300 <br />0 <br />100 <br />NUCLEAR MEDICINE <br />1715 <br />0 <br />-100 <br />N/R <br />9000.0 <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />1200 <br />1300 <br />0 <br />100 <br />STORAGE <br />1-118 <br />0 <br />0 <br />N/R <br />4350.0 <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />580 <br />580 <br />0 <br />0 <br />HOT LAB <br />1-116 <br />- <br />-75 <br />N/R <br />2587.5 <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />345 <br />0 <br />420 <br />75 <br />MAIN CORRIDOR <br />1-100 <br />0 <br />300 <br />N/R <br />4875.0 <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />650 <br />0 <br />350 <br />-300 <br />HC TOILET <br />1-128 <br />- <br />-75 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />40 <br />0 <br />115 <br />75 <br />STAFF LOUNGE <br />1-122 <br />0 <br />0 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />560 <br />560 <br />0 <br />0 <br />STAFF HC TOILET <br />1-123 <br />- <br />-75 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />40 <br />0 <br />115 <br />75 <br />READING ROOM <br />1-121 <br />0 <br />0 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />425 <br />225 <br />200 <br />0 <br />STRETCHER TRANSFER ROOM <br />1-126 <br />0 <br />0 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />175 <br />175 <br />0 <br />0 <br />M RI <br />1-130 <br />0 <br />0 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />1000 <br />1000 <br />0 <br />0 <br />JANITOR <br />1-117 <br />- <br />-75 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />0 <br />0 <br />75 <br />75 <br />CLASSROOM <br />2-100 <br />0 <br />125 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />1165 <br />1040 <br />0 <br />-125 <br />STORAGE <br />2-100 B <br />0 <br />0 <br />N/R <br />1500.0 <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />200 <br />200 <br />0 <br />0 <br />COMPUTER ROOM <br />2-112 <br />0 <br />0 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />200 <br />200 <br />0 <br />0 <br />DATA PROCESSING <br />2-103 <br />0 <br />200 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />900 <br />700 <br />0 <br />-200 <br />DP TRAINING <br />2-103B <br />0 <br />0 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />750 <br />750 <br />0 <br />0 <br />OFFICE 130 <br />2-130 <br />0 <br />0 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />400 <br />400 <br />0 <br />0 <br />OFFICE 129 <br />2-129 <br />0 <br />0 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />200 <br />200 <br />0 <br />0 <br />OFFICE 128 <br />2-128 <br />0 <br />0 <br />N/R <br />N/R <br />N/R <br />N/R <br />N/R <br />0 <br />0 <br />0 <br />210 <br />210 <br />0 <br />0 <br />Total 0 0 14150 12630 1520 0 <br />NOTES <br />1 N/R = No Requirement <br />2 <br />3 <br />\\0III <br />D // N <br />0.40 3 <br />E OF PROFESSIONAL ENGINEERS <br />UEEN PALM DRIVE <br />A. FLORIDA 33619 <br />NE (813) 241-6488 <br />FAX (813- 6u�:0 v= <br />Project No. 15017.00 <br />M5,01 <br />®2015 BH/PK Architects, Inc. <br />E <br />$DATE$ $TIME$ $FILEA$ <br />