<br />ABBREVIATIONS
<br />AFF
<br />ABOVE FINISHED
<br />FLOOR MAX
<br />MAXIMUM
<br />CLG
<br />CEILING
<br />MIN
<br />MINIMUM
<br />DN
<br />DOWN
<br />SPK.
<br />SPRINKLER
<br />EL
<br />ELEVATION
<br />TYP
<br />TYPICAL
<br />EXIST
<br />EXISTING
<br />UON
<br />UNLESS OTHERWISE NOTED
<br />FL
<br />FLOOR
<br />VIF
<br />VERIFY IN FIELD
<br />F
<br />FIRE MAIN
<br />FIRE PROTECTION SPECIFICATIONS
<br />1.0 PIPE FITTINGS AND VALVES
<br />A. STEEL PIPE ASTM A 135, PIPE SIZE 2" AND SMALLER SHALL BE SCHEDULE 40 BLACK STEEL
<br />WITH THREADED CAST IRON BLACK FITTINGS.
<br />1.1 CAST IRON THREADED FITTINGS
<br />ASME B16.4, CLASS 125, STANDARD PATTERN, WITH THREADS ACCORDING TO ASME B1.20.1, 175
<br />PSI RATED.
<br />1.2 MALLEABLE IRON THREADED FITTINGS
<br />ASME B16.3, CLASS 150, STANDARD PATTERN, WITH THREADS ACCORDING TO ASME B1.20.1.
<br />1.3 STEEL FITTINGS
<br />ASTM A 234/ A 234M, SEAMLESS OR WELDED; ASME B16.9, BUTTWELDING; OR ASME 816.11,
<br />SOCKET WELDING TYPE FOR WELDED JOINTS
<br />1.4 GENERAL
<br />UL LISTED AND/OR FM APPROVED SERVICE VALVES WITH 175 PSIG NON -SHOCK MINIMUM
<br />WORKING PRESSURE RATING. GATE VALVES: UL 262, CAST BRONZE, THREADED ENDS, SOLID
<br />WEDGE, OUTSIDE SCREW AND YOKE, RISING STEM. PROVIDE INDICATING (BUTTERFLY OR BALL)
<br />VALVES TYPE, BRONZE BODY WITH THREADED ENDS, AND INTEGRAL INDICATING DEVICE, INDICATOR
<br />SHALL BE VISUAL AND ELECTRICAL 115 VOLTS A.C., PRE -WIRED 2 CIRCUIT, SUPERVISORY SWITCH.
<br />2.0 SPRINKLERS
<br />PROVIDE AUTOMATIC HEAT -RESPONSIVE GLASS BULB SPRINKLER HEADS, WITH 1 /2" NOMINAL
<br />ORIFICE, 5.50 "K" FACTOR 155'F TEMPERATURE RATING, INSTALL SPRINKLERS IN A UNIFORM,
<br />CONSISTENT MANNER IN ORDER TO LINE UP EACH AREA, IN THE "CENTER" OF THE CEILING TILE
<br />AS DETAILED.
<br />3.0 PIPING INSTALLATIONS
<br />DEVIATIONS FROM APPROVED "WORKING PLANS" FOR SPRINKLER PIPING REQUIRE WRITTEN
<br />APPROVAL FROM AUTHORITY WITH JURISDICTION. FILE WRITTEN APPROVAL WITH THE ENGINEER
<br />PRIOR TO DEVIATING FROM APPROVED "WORKING PLANS". INSTALL UNION OR FLANGE ADJACENT
<br />TO EACH VALVE. INSTALL HANGER AND SUPPORT SPACING AND LOCATIONS FOR STEEL PIPING
<br />JOINED WITH GROOVED MECHANICAL COUPLINGS ACCORDING TO MANUFACTURER'S WRITTEN
<br />INSTRUCTIONS FOR RIGID SYSTEMS PER NFPA 13.
<br />4.0 FIELD QUALITY CONTROL
<br />FLUSH, TEST AND INSPECT SPRINKLER PIPING SYSTEMS ACCORDING TO NFPA 13 CHAPTER
<br />"SYSTEM ACCEPTANCE". REPORT TEST RESULTS PROMPTLY AND IN WRITING TO ARCHITECT AND
<br />TO THE AUTHORITY HAVING JURISDICTION. CLEANING: CLEAN DIRT AND DEBRIS FROM
<br />SPRINKLERS. REPLACE SPRINKLERS HAVING PAINT OTHER THAN FACTORY FINISH WITH NEW
<br />SPRINKLERS. CLEAN AND REUSE OF PAINTED SPRINKLERS IS PROHIBITED.
<br />5.0 SPRINKLER SYSTEM BASIS OF DESIGN
<br />ITEM DESIGN
<br />CLASSIFICATION COORDINATE WITH ARCHITECTURAL DRAWING AND CLASSIFY
<br />AREAS PER NFPA
<br />TYPE WET PIPE SPRINKLER SYSTEM
<br />SPRINKLER HEAD (SEE SCHEDULE)
<br />MANUFACTURER/MODEL
<br />TEMPERATURE RATING (SEE SCHEDULE)
<br />NOTES
<br />1. COORDINATE CEILING MOUNTED SPRINKLER HEADS WITH OTHER DEVICES (LIGHTS, DIFFUSERS,
<br />ACCESS PANELS, ETC.) SEE ARCHITECTURAL CEILING PLANS FOR LOCATIONS OF ALL DEVICES.
<br />2. ALL MATERIALS AND EQUIPMENT SHALL UL AND/OR FACTORY MUTUAL APPROVED WHERE
<br />APPLICABLE.
<br />2-----
<br />�
<br />rt
<br />�
<br />LEGEND
<br />EXISTING FIRE SPRINKLER PIPING SHALL REMAIN (VIF)
<br />EXISTING FIRE SPRINKLER HEAD SHALL BE REMOVED (VIF)
<br />EXISTING SPRINKLER HEAD SHALL REMAIN (VIF)
<br />NEW ARMOVER FIRE SPRINKLER PIPING
<br />CONCEALED MOUNTED SPRINKLER HEAD - (SEE SCHEDULE)
<br />SIDE CONNECTION
<br />NEW CONNECTION
<br />FIRE PROTECTION GENERAL NOTES
<br />1. FIRE PROTECTION WORK SHALL BE DESIGNED, INSTALLED, AND TESTED IN ACCORDANCE WITH
<br />NFPA 13 LATEST EDITION OR AS ADOPTED BY THE AUTHORITY HAVING JURISDICTION.
<br />2. INCLUDE ANY INCIDENTAL APPARATUS, APPLIANCES, MATERIAL LABOR AND SERVICES NECESSARY
<br />TO MAKE NEW WORK COMPLETE IN ALL RESPECTS AND FULLY READY FOR OPERATION.
<br />3. MAKE SUCH OFFSETS AND DEVIATIONS FROM WORK SHOWN ON THE DRAWINGS, AS MAY BE
<br />NECESSARY TO FIT THE ACTUAL SPACE CONDITIONS.
<br />4. THE INSTALLER SHALL VISIT THE JOB SITE, INSPECT ALL EXISTING CONDITIONS AFFECTING THE
<br />WORK. SUBMISSION OF HIS PROPOSAL SHALL BE CONSTRUED AS INDICATING SUCH KNOWLEDGE.
<br />NO ADDITIONAL PAYMENT WILL BE MADE ON CLAIMS THAT ARISE FROM THE CONTRACTOR'S
<br />FAILURE TO COMPLY WITH THIS REQUIREMENT.
<br />5. THE PLANS AND DIAGRAMS OF FIRE PROTECTION PIPING ARE SCHEMATIC ONLY AND SHOULD NOT
<br />BE SCALED. INSTALLER SHALL COORDINATE AT SITE WITH ALL EXISTING PLUMBING, HVAC AND
<br />ELECTRICAL WORK SO AS NOT TO CONFLICT IN LOCATION WITH OTHER WORK UNDER THIS
<br />CONTRACT OR THAT MAY BE EXISTING. CONTRACTOR SHALL ADJUST PIPE ROUTING AS NECESSARY
<br />TO AVOID CONFLICTS WITH DUCTWORK, EQUIPMENT, LIGHTING, ETC.
<br />6. INSTALLER SHALL NOT CUT ANY EXISTING STRUCTURAL MEMBERS WITHOUT FIRST SECURING WRITTEN
<br />APPROVAL FROM THE ARCHITECT.
<br />7. PIPE SIZED, GENERAL ROUTING, AND CONFIGURATION IN SYSTEMS REQUIRED TO BE HYDRAULICALLY
<br />CALCULATED SHALL BE INSTALLED PER THIS ENGINEER'S CONSTRUCTION DOCUMENTS. ANY
<br />DEVIATION SUBMITTED BY THE CONTRACTOR SHALL BE RE -DESIGNED BY THIS ENGINEER WITH
<br />RELATED RE -DESIGN FEES BORN BY THE CONTRACTOR.
<br />8. CONTRACTOR SHALL ARRANGE FOR, OBTAIN AND BEAR THE COST OF NECESSARY PERMITS, BONDS,
<br />AND FEES.
<br />9. ALL MATERIALS SHALL BE U.L. LISTED AND BEAR THE U.L. LABEL.
<br />10. PENETRATIONS THROUGH FIRE RATED ASSEMBLIES, PENETRATIONS FOR PIPES, CONDUITS, OR OTHER
<br />PURPOSES THROUGH ASSEMBLIES (FLOORS, WALLS, PARTITIONS, ETC.) WITH A REQUIRED
<br />FIRE RESISTANCE RATING FIRE STOP MATERIAL SHALL BE UL LISTED AND INSTALLED IN STRICT
<br />ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS TO MEET OR EXCEED THE FIRE RATING OF
<br />THE PENETRATED ASSEMBLY.
<br />11. BEFORE SHUTTING OFF ANY SECTION OF THE FIRE PROTECTION SYSTEM TO MAKE ADJUSTMENTS
<br />OR ADDITIONAL CONNECTIONS, COORDINATE WITH THE OWNER AND NOTIFY THE AUTHORITY
<br />HAVING JURISDICTION. PLAN THE WORK CAREFULLY AND ASSEMBLE ALL MATERIALS TO ENABLE
<br />COMPLETION IN THE SHORTEST POSSIBLE TIME. WORK SHALL BE USED TO COMPLETION WITHOUT
<br />INTERRUPTION, AND PROTECTION SHALL BE RESTORED AS PROMPTLY AS POSSIBLE.
<br />12. PROVIDE FLUSHING CONNECTION AT END OF SPRINKLER SYSTEM WHERE LAY -IN CEILING OCCURS.
<br />ALL SPRINKLER PIPING THAT REQUIRES CHANGE IN ELEVATION DUE TO COORDINATION ROUTING OF
<br />PIPING SHALL HAVE FLUSH CONNECTION AT ALL LOWER ELEVATION. THE SPRINKLER SYSTEM SHALL
<br />BE INSTALLED WITH COMPLETE DRAINABLE SYSTEM.
<br />13. ALL SPRINKLER HEADS SHALL BE U.L. LISTED AND INSTALLED IN ACCORDANCE WITH THEIR
<br />LISTING REQUIREMENTS. ALL ESCUTCHEONS AND ACCESSORIES SHALL BE METAL.
<br />14. YEAR FROM DATE OF FINAL ACCEPTANCE. ALL DEFECTS WHICH DEVELOP OR ARE DISCOVERED
<br />WITHIN THIS PERIOD SHALL BE REPAIRED BY THE CONTRACTOR TO THE SATISFACTION OF THE
<br />OWNER AT NO ADDITIONAL COST TO THE OWNER.
<br />15. UPON COMPLETION OF THE WORK UNDER THIS CONTRACT, THE CONTRACTOR SHALL REMOVE ALL
<br />TOOLS, APPLIANCES, SURPLUS MATERIALS, AND SCRAP. ALL IDENTIFIED EXISTING EQUIPMENT TO
<br />BE REMOVED SHALL BE TURNED OVER TO THE OWNER.
<br />16. ALL WORK IS TO BE FREE OF DEFECTS IN WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE (1)
<br />WHEN CONFLICTS OCCUR IN SPECIFICATIONS OR IN THE DRAWINGS, OR BETWEEN EITHER, THE ITEMS
<br />OF GREATER QUANTITY OR HIGHER COST SHALL BE PROVIDED.
<br />17. THE CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES IN ORDER TO AVOID CONFLICTS.
<br />18. COORDINATE EXACT LOCATION OF SPRINKLERS AND PIPING WITH CEILING, ELECTRICAL,
<br />MECHANICAL, AND STRUCTURAL ELEMENTS OF BUILDING. MAKE MODIFICATIONS WITHOUT
<br />ADDITIONAL COST TO THE OWNER.
<br />19. PROVIDE ALL HANGERS AS REQUIRED TO COMPLY WITH NFPA 13.
<br />20. PROVIDE ALL DRAINS AS REQUIRED BY NFPA 13.
<br />21. ALL SPRINKLER HEADS SHALL BE QUICK RESPONSE TYPE.
<br />22. PENDENT MOUNTED SPRINKLER HEADS SHALL BE ALIGNED WITHIN NORMAL FABRICATION AND
<br />INSTALLATION TOLERANCES AND WILL BE CENTERED IN CEILING TILES.
<br />23. THE EXISTING FIRE PROTECTION SYSTEM IN BUILDING WAS HYDRAULICALLY CALCAULATED EXISTING
<br />EXISTING SPRINKLERS INDICATED HAVE BEEN REMOVED AND NO SPRINKLER HEADS HAVE BEEN
<br />ADDED WHICH DOES NOT EFFECT THE REMOTE ZONE. THE CHANGES MADE ON THIS PROJECT
<br />DO NOT EFFECT THE HYDRAULIC CHARACTERISTICS OF THE EXISTING SYSTEM. THEREFORE HYDRAULIC
<br />CALCULATIONS ARE NOT REQUIRED FOR THIS PROJECT.
<br />FIRE PROTECTION
<br />FP1.0 ABBREVIATIONS, LEGENDS, GENERAL NOTES AND DETAILS
<br />FP2.0 FIRE PROTECTION DEMOLITION AND NEW CONSTRUCTION PARTIAL PLANS
<br />FIRE SPRWLER HEAD SCHEDULE
<br />SYMBOL
<br />NAME
<br />METAL FINISH
<br />TEMPERATURE
<br />K-FACTOR
<br />SIN
<br />N.P.T.
<br />ESCHUTCHEON
<br />MANUFACTURER
<br />MODEL
<br />0
<br />CONCEA
<br />ELED
<br />WHITE
<br />155' F
<br />5.6
<br />VK462
<br />1/2"
<br />FLUSH
<br />VIKING
<br />M QR
<br />INTERIOR SIDE OF
<br />WALL
<br />GYPSUM WALL
<br />MIN. 5/8" THICKNESS OF FILL METAL STUDS
<br />MATERIAL APPLIED WITHIN
<br />ANNULUS FLUSH BOTH SURFACES
<br />OF WALL
<br />r
<br />PIPE CENTERED
<br />IN SLEEVE
<br />NOTES: v
<br />1. UL SYSTEM NO. W-L-1054, F RATING 1 OR 2 HR
<br />1 OR 2 HOUR P_P_ESLEEVE
<br />WALL PENETRATION DETAIL
<br />EXISTING BRANCH PIPING
<br />1XISTING SECOND ELOOB
<br />Z i
<br />J
<br />EXISTING CEILING TO BE
<br />REMOVED REFER TO ARCH.
<br />DRAWINGS
<br />1 ARMOVER
<br />) CONNECT
<br />IU LX1511N6 BRANCH
<br />PIPING (VIF)
<br />EXISTING PENDANT SPRINKLER HEAD
<br />AND NIPPLE SHALL BE REMOVED
<br />(TYPICAL)
<br />NOT TO SCALE
<br />CONTINUOUS ALL THREADED ROD
<br />ADJUSTABLE HANGER
<br />(FM/UL APPROVED)
<br />1" SCH. 40 NIPPLE
<br />REDUCER
<br />12" MAX.
<br />NEW CONCEALED
<br />MOUNTED SPRINKLER
<br />NEW CEILING HEAD
<br />NEW CONCEALED MOUNTED SPRINKLER HEAD
<br />WITH NEW ARMOVER DETAIL NOT TO ICU