<br />EXISTING PANELBOARD SCHEDULE
<br />PLAN
<br />MARK
<br />BRANCHES
<br />MAINS
<br />MINIMUM
<br />BREAKER
<br />AIC - SYM
<br />MOUNTING
<br />AND
<br />REMARKS
<br />NO.
<br />POLE
<br />AMP
<br />CIRCUITS
<br />SIZE
<br />POLE
<br />MAIN
<br />VOLT
<br />1AHP
<br />(NORMAL)
<br />12
<br />1
<br />20
<br />IN USE
<br />225
<br />AMP
<br />3P
<br />+
<br />SN
<br />+
<br />GRND
<br />MLO
<br />277/480
<br />35,000 AIC
<br />SURFACE MOUNTED PANEL, USE SPARE BREAKERS AVAILABLE
<br />IN PANELBOARD FOR NEW CIRCUITS. IF REQUIRED PROVIDE
<br />20A/1P BREAKERS USING SPACES. ALSO IF EXISTING CAPACITY
<br />BECOMES AVAILABLE FROM DEMOLITION WORK THE RE - USE
<br />THESE CIRCUITS AFTER LOAD READINGS.
<br />1
<br />1 3
<br />30
<br />IN USE
<br />2
<br />3
<br />20
<br />IN USE
<br />21
<br />1
<br />20
<br />SPARES & SPACES AVAILABLE
<br />1 HCB
<br />(CRITICAL)
<br />4
<br />1
<br />20
<br />IN USE
<br />225
<br />AMP
<br />3P
<br />+
<br />SN
<br />+
<br />GRND
<br />MLO
<br />277/480
<br />35,000 AIC
<br />SURFACE MOUNTED PANEL, USE SPARE BREAKERS AVAILABLE
<br />IN PANELBOARD FOR NEW CIRCUITS. IF REQUIRED PROVIDE
<br />20A/1P BREAKERS USING SPACES. ALSO IF EXISTING CAPACITY
<br />BECOMES AVAILABLE FROM DEMOLITION WORK THE RE - USE
<br />THESE CIRCUITS AFTER LOAD READINGS.
<br />38
<br />1
<br />20
<br />SPARES & SPACES AVAILABLE
<br />1 BLP
<br />(NORMAL)
<br />2-SECTION
<br />22
<br />1
<br />20
<br />IN USE
<br />225
<br />AMP
<br />3P
<br />+
<br />SN
<br />+
<br />GRND
<br />150A
<br />3P
<br />MAIN
<br />BRKR
<br />120/208
<br />10,000 AIC
<br />SURFACE MOUNTED PANEL, USE SPARE BREAKERS AVAILABLE
<br />IN PANELBOARD FOR NEW CIRCUITS. IF REQUIRED PROVIDE
<br />20A/1P BREAKERS USING SPACES. ALSO IF EXISTING CAPACITY
<br />BECOMES AVAILABLE FROM DEMOLITION WORK THE RE - USE
<br />THESE CIRCUITS AFTER LOAD READINGS.
<br />62
<br />1
<br />20
<br />SPARES & SPACES AVAILABLE
<br />1 BLCB
<br />(CRITICAL)
<br />2-SECTION
<br />27
<br />1
<br />20
<br />IN USE
<br />225
<br />AMP
<br />3P
<br />+
<br />SN
<br />+
<br />GRND
<br />150A
<br />3P
<br />MAIN
<br />BRKR
<br />120/208
<br />10,000 AIC
<br />SURFACE MOUNTED PANEL, USE SPARE BREAKERS AVAILABLE
<br />IN PANELBOARD FOR NEW CIRCUITS. IF REQUIRED PROVIDE
<br />20A/1P BREAKERS USING SPACES. ALSO IF EXISTING CAPACITY
<br />BECOMES AVAILABLE FROM DEMOLITION WORK THE RE - USE
<br />THESE CIRCUITS AFTER LOAD READINGS.
<br />57
<br />1
<br />20
<br />SPARES & SPACES AVAILABLE
<br />1 HLS
<br />(LIFE
<br />SAFETY)
<br />12
<br />1
<br />20
<br />IN USE
<br />225
<br />AMP
<br />3P
<br />+
<br />SN
<br />+
<br />GRND
<br />MLO
<br />277/480
<br />18,000 AIC
<br />SURFACE MOUNTED PANEL, USE SPARE BREAKERS AVAILABLE
<br />IN PANELBOARD FOR NEW CIRCUITS. IF REQUIRED PROVIDE
<br />20A/1P BREAKERS USING SPACES. ALSO IF EXISTING CAPACITY
<br />BECOMES AVAILABLE FROM DEMOLITION WORK THE RE - USE
<br />THESE CIRCUITS AFTER LOAD READINGS.
<br />1
<br />3
<br />45
<br />XFMR T-30 IN USE
<br />27
<br />1
<br />20
<br />SPARES &SPACES AVAILABLE
<br />1 LLS
<br />(LIFE
<br />SAFETY)
<br />11
<br />1
<br />20
<br />IN USE
<br />100
<br />AMP
<br />3P
<br />+
<br />SN
<br />+
<br />GRND
<br />100A
<br />3P
<br />MAIN
<br />BRKR
<br />120/208
<br />10,000 AIC
<br />SURFACE MOUNTED PANEL, USE SPARE BREAKERS AVAILABLE
<br />IN PANELBOARD FOR NEW CIRCUITS. IF REQUIRED PROVIDE
<br />20A/1P BREAKERS USING SPACES. ALSO IF EXISTING CAPACITY
<br />BECOMES AVAILABLE FROM DEMOLITION WORK THE RE - USE
<br />THESE CIRCUITS AFTER LOAD READINGS.
<br />31
<br />1
<br />20
<br />SPARES & SPACES AVAILABLE
<br />TO GENERATOR
<br />ELEC. CLOSET
<br />I
<br />i
<br />1BLP
<br />C
<br />T-45
<br />1BHP
<br />T-45
<br />---------------
<br />1BLCB
<br />�a
<br />a
<br />0
<br />I�
<br />�1-#2 GRND. �1-#2 GRND.
<br />I
<br />342 & 146 4-#1 & 1-#3
<br />GRND, IN 1�"C. I GRND., IN 1Y2"C.
<br />3 SETS 4-350 MCM & 142/0 GRND., IN 3-3"C.
<br />0 40OA13P 80OA13P
<br />v 40OA13P 800A13P
<br />r,
<br />120OA13P
<br />MSB I I GDP
<br />FROM UTILITY XFMR GEN. DISTRIBUTION (800/
<br />277/480 VOLT, 30
<br />7,412 SCA
<br />65,000 AIC
<br />SWBD 4000A
<br />277/480 VOLT, 30
<br />56,891 SCA
<br />65,000 AIC
<br />ATS-CB (800A
<br />480 VOLT, 30
<br />50,015 SCA
<br />65,000 AIC
<br />1LLS
<br />M
<br />1 HLS <
<br />SCHEDULES OF LIGHTING EQUIPMENT & LAMPS
<br />FIX.
<br />TYPE
<br />MANUFACTURER
<br />CATALOG
<br />NUMBER
<br />LAMPS
<br />TYPE OF FIXTURE
<br />MOUNTING
<br />NOTES
<br />INCAND.
<br />FLUOR.
<br />MISC.
<br />REC
<br />SUR
<br />SUS
<br />FA
<br />EXISTING
<br />(37) EXISTING 2x4 LIGHTS
<br />FB
<br />LIGHTOLIER
<br />SPS2GFSVI317-277-
<br />3-F17
<br />2x2 LENS TROFFER
<br />X
<br />277V.
<br />03
<br />T-8
<br />FC
<br />LIGHTOLIER
<br />11 13TCUl 102T26U
<br />(2)-26WQT
<br />6Y4" LOW PROFILE
<br />X
<br />277V.
<br />DOWNLIGHT
<br />XA
<br />LIGHTOLIER
<br />LLNURW
<br />LED
<br />SINGLE FACE W/ NO ARROW
<br />X
<br />277V.
<br />XB
<br />LIGHTOLIER
<br />LLNURW
<br />LED
<br />SINGLE FACE W/ ARROW
<br />X
<br />277V.
<br />ELEC. CLOSET #106
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />1
<br />441 & 1 44
<br />GRND., IN 1Y2"C.
<br />I
<br />— — — — — — — — — — I
<br />4-#3/0 & 1�2 3�t4 & 1�I 8
<br />GRND, IN 2"C.
<br />GRND., IN 1%"C.
<br />4-500 MCM & 142 F
<br />GRND., IN 4"C.
<br />I
<br />I
<br />ATS-LS 400A
<br />480 VOLT, 3Q1 I ^ ^ ^
<br />N N 4 SCA 1 200A/3P 70A13P 125A13P
<br />L L 65,000 AIC
<br />E E 1
<br />1HLSDP 1HCBDP
<br />I
<br />GRND HOSP.
<br />4-500 MCM & 142 1
<br />(�GRND.,IN4"C.— — — — — — — ----- --
<br />T-30
<br />(t1-#4 GRND.
<br />3 SETS 4-350 MCM & 14% GRND., IN 3-3"C. LIFE SAFETY DISTRIBUTION
<br />277/480 VOLT, 30
<br />15,963 SCA
<br />65,000 AIC
<br />EXISTING ELECTRICAL RISER DIAGRAM
<br />NO SCALE
<br />1HCBI I1AHP
<br />4-#2 & 146
<br />GRND., IN 1 Y4"C.
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />NORMAL DISTRIBUTION
<br />277/480 VOLT, 30
<br />41,874 SCA 1
<br />65,000 AIC
<br />I L^ ^�
<br />125A13P 125A13P
<br />L1-- --
<br />70A13P
<br />1HNDP
<br />-----------------I
<br />4 SETS 4-400 MCM &
<br />144/0 GRND., IN 4-3"C.
<br />CRITICAL DISTRIBUTION
<br />277/480 VOLT, 30
<br />33,800 SCA
<br />65,000 AIC
<br />design
<br />GRN
<br />Heery International Inc.
<br />4700 Millenia Boulevard,
<br />Suite 550,
<br />Orlando, Florida 32839
<br />407.992.6300
<br />EB 0005176
<br />Seal:
<br />\01►wcI l
<br />i
<br />* ; No 49493 ,
<br />700 STATE OF 1',IR7
<br />11oNa i i\\)Z- 1 Z
<br />JONATHAN R. CANDOR - PE #49493