<br />AHU HP SPLIT SYSTEM HEAT PUMP SCHEDULE
<br />AIR HANDLER
<br />CONDENSING
<br />UNIT
<br />MARK
<br />MANUFACTURER
<br />MODEL #
<br />REMARKS
<br />EAT
<br />TOTAL
<br />SENSIBLE
<br />SUPPLY FAN
<br />OUTDOOR
<br />POWER
<br />DB/WB
<br />COOLING (MBH)
<br />COOLING (MBH)
<br />TEMPERATURE
<br />SEER/COP
<br />SUPPLY CFM
<br />OSA CFM
<br />ESP
<br />HP
<br />VOLTS
<br />MCA
<br />MOCP
<br />VOLTS
<br />AHU-1
<br />DAIKIN
<br />FDXS09LVJU
<br />75.0/60.1
<br />4.9
<br />4.6
<br />225
<br />0
<br />0.12
<br />-
<br />208/1
<br />1
<br />15
<br />208/1
<br />1-5
<br />HP-1
<br />DAIKIN
<br />RXS09LVJU
<br />957
<br />15.1
<br />8
<br />15
<br />208/1
<br />AHU-2
<br />DAIKIN
<br />FDXS09LVJU
<br />75.0/60.1
<br />4.9
<br />4.6
<br />225
<br />0
<br />0.12
<br />-
<br />208/1
<br />1
<br />15
<br />208/1
<br />1-5
<br />HP-2
<br />DAIKIN
<br />RXS09LVJU
<br />957
<br />15.1
<br />8
<br />15
<br />208/1
<br />AHU-3
<br />DAIKIN
<br />FDXS09LVJU
<br />75.0/60.2
<br />4.4
<br />4.1
<br />225
<br />0
<br />0.12
<br />-
<br />208/1
<br />1
<br />15
<br />208/1
<br />1-5
<br />HP-3
<br />DAIKIN
<br />RXS09LVJU
<br />I
<br />957
<br />15.1
<br />8
<br />15
<br />208/1
<br />AHU-4
<br />DAIKIN
<br />FDXS09LVJU
<br />75.0/59.8
<br />6.7
<br />6.4
<br />225
<br />0
<br />0.12
<br />-
<br />208/1
<br />1
<br />15
<br />208/1
<br />1-5
<br />HP-4
<br />DAIKIN
<br />RXS09LVJU
<br />1
<br />957
<br />15.1
<br />8
<br />15
<br />208/1
<br />AHU-5
<br />DAIKIN
<br />FDXS09LVJU
<br />75.0/59.7
<br />7.4
<br />7.2
<br />225
<br />0
<br />0.12
<br />-
<br />208/1
<br />1
<br />15
<br />208/1
<br />1-5
<br />HP-5
<br />DAIKIN
<br />RXS09LVJU
<br />957
<br />15.1
<br />8
<br />15
<br />208/1
<br />AHU-6
<br />DAIKIN
<br />FDXS12LVJU
<br />75.0/59.5
<br />9.1
<br />8.8
<br />225
<br />0
<br />0.12
<br />-
<br />208/1
<br />1
<br />15
<br />208/1
<br />1-5
<br />HP-6
<br />DAIKIN
<br />RXS12LVJU
<br />1
<br />957
<br />15.1
<br />8
<br />15
<br />208/1
<br />AHU-7
<br />DAIKIN
<br />FDXS12LVJU
<br />75.0/59.8
<br />7.2
<br />6.9
<br />225
<br />0
<br />0.12
<br />-
<br />208/1
<br />1
<br />15
<br />208/1
<br />1-5
<br />HP-7
<br />DAIKIN
<br />RXS12LVJU
<br />957
<br />15.1
<br />8
<br />15
<br />208/1
<br />AHU-8
<br />DAIKIN
<br />FBQ24PVJU
<br />77.1/64.7
<br />20.2
<br />14.2
<br />660
<br />85
<br />0.4
<br />-
<br />208/1
<br />1.5
<br />15
<br />208/1
<br />1-5
<br />HP-8
<br />DAIKIN
<br />RZQ24PVJU9
<br />957
<br />16.5
<br />16.5
<br />20
<br />208/1
<br />AHU-9
<br />DAIKIN
<br />FBQ24PVJU
<br />78.1/65.5
<br />20.8
<br />13.5
<br />660
<br />100
<br />0.4
<br />-
<br />208/1
<br />1.5
<br />15
<br />208/1
<br />1-5
<br />HP-9
<br />DAIKIN
<br />RZQ24PVJU9
<br />I
<br />957
<br />16.5
<br />16.5
<br />20
<br />208/1
<br />AHU-10
<br />DAIKIN
<br />FDXS12LVJU
<br />75.0/56.8
<br />3.3
<br />3.3
<br />150
<br />0
<br />0.12
<br />-
<br />208/1
<br />0
<br />15
<br />208/1
<br />1-5
<br />HP-10
<br />DAIKIN
<br />RXS12LVJU
<br />I
<br />1
<br />957
<br />15.1
<br />8
<br />15
<br />208/1
<br />AHU-(E)
<br />DAIKIN
<br />FDXS12LVJU
<br />75.0/56.8
<br />10
<br />10
<br />300
<br />0
<br />.12
<br />-
<br />208/1
<br />1
<br />15
<br />208/1
<br />1,2,4,6
<br />95'F
<br />-
<br />* DESIGN CONDITIONS: SUMMER 957/777; WINTER LOW-177 HIGH-477 ® 657 EVAPORATOR ENTERING
<br />**MECHANICAL CONTRACTOR AND VENDOR ARE RESPONSIBLE FOR APPROPRIATE CONTROLS COMPONENTS AND INSTALLATION OF CONTROLS SYSTEM. INSTALL PER MANUFACTURER'S RECOMMENDATIONS FOR
<br />PROPER OPERATION OF SYSTEMS. CERTIFIED REPRESENTATIVE SHALL INSTALL AND STARTUP.
<br />NOTES
<br />1. PROVIDE WITH 7-DAY, 24 HOUR PROGRAMMABLE THERMOSTAT WITH THE APPROPRIATE NUMBER OF COOLING AND HEATING STAGES (SUPPLIED BY MANUFACTURER).
<br />2. PROVIDE FILTER BOX WITH FILTER, AND CONDENSATE PUMP AS REQUIRED.
<br />3. PROVIDE ALL SYSTEMS WITH EQUIPMENT REQUIRED FOR LONG LINE APPLICATIONS, AS REQUIRED BY MANUFACTURER'S RECOMMENDATIONS.
<br />4. PROVIDE ALL APPROPRIATE ACCESSORIES FOR SPECIFIED OPERATION.
<br />5. ALL DUCTABLE AHU'S SHALL BE LOW STATIC.
<br />6. EXISTING EQUIPMENT SHALL BE CLEANED INSPECTED AND REFURBISHED TO LIKE NEW CONDITION PRIOR TO INSTALLATION. CONNECT TO EXISTING VRF SYSTEM.
<br />GRILLE AND DIFFUSER SCHEDULE
<br />*MARK
<br />MANUFACTURER
<br />MODEL #
<br />DESCRIPTION
<br />FRAME
<br />FINISH
<br />MATERIAL
<br />DAMPER
<br />REMARKS
<br />CD-1
<br />PRICE
<br />620DAL
<br />DOUBLEDEFLECTION; ALUMINUM;
<br />SURFACE
<br />WHITE
<br />ALUMINUM
<br />OBD
<br />1,3,4
<br />SPACING
<br />CD-2
<br />PRICE
<br />APDSPE
<br />24X24 LAY -IN DIFFUSER FLUSH
<br />FACE; 4 WAY THROW
<br />LAY -IN
<br />WHITE
<br />ALUMINUM
<br />-
<br />1,2
<br />CG-1
<br />PRICE
<br />635DAL
<br />CEILING GRILLE; I" BLADE SPACING;
<br />SURFACE
<br />WHITE
<br />ALUMINUM
<br />OBD
<br />1,3,4
<br />ALUMINUM DAMPER
<br />CG-2
<br />PRICE
<br />635DAL
<br />24X24 LAY -IN GRILLE; J" BLADE
<br />LAY -IN
<br />WHITE
<br />ALUMINUM
<br />OBD
<br />1,2
<br />SPACING; ALUMINUM DAMPER
<br />SD-1
<br />PRICE
<br />620DAL
<br />DOUBLE DEFLECTION; ALUMINUM;
<br />SURFACE
<br />WHITE
<br />ALUMINUM
<br />OBD
<br />1,3,4
<br />SPACING
<br />SG-1
<br />PRICE
<br />630DAL
<br />HORIZONTAL BLADES; ALUMINUM;
<br />SURFACE
<br />WHITE
<br />ALUMINUM
<br />OBD
<br />1,3,4
<br />SPACING
<br />NOTES:
<br />1. PAINT PER ARCHITECT.
<br />2. NECK SIZE AS LISTED. PROVIDE FULL FACE SQUARE TO ROUND INSULATED BOOT.
<br />3. SIZE AS INDICATED ON PLANS.
<br />4. PAINT INSIDE OF DIFFUSER/GRILLE FLAT BLACK.
<br />(-) EXHAUST FAN SCHEDULE
<br />MARK
<br />MANUFACTURER
<br />MODEL
<br />TYPE
<br />CFM
<br />E.S.P.
<br />HP (WATT)
<br />VOLTS/0
<br />BACK DRAFTPER
<br />DRIVE
<br />SONES
<br />REMARKS
<br />EF-1
<br />COOK
<br />GC-120
<br />CEILING
<br />50
<br />0.125
<br />(25)
<br />115/1
<br />YES
<br />DIRECT
<br />1.1
<br />1,2
<br />EF-2
<br />COOK
<br />GC-140
<br />CEILING
<br />75
<br />0.125
<br />(70)
<br />115/1
<br />YES
<br />DIRECT
<br />1.1
<br />1,2
<br />EF-3
<br />COOK
<br />GC-160
<br />CEILING
<br />100
<br />0.125
<br />(113)
<br />115/1
<br />YES
<br />DIRECT
<br />1.1
<br />1,3
<br />EF-4
<br />COOK
<br />GC-160
<br />CEILING
<br />100
<br />0.125
<br />(113)
<br />115/1
<br />YES
<br />DIRECT
<br />1.1
<br />1,4
<br />NOTES:
<br />1. PROVIDE WITH BACK DRAFT DAMPER AND SPEED CONTROLLER.
<br />2. PROVIDE INDEPENDENT SWITCH.
<br />3. INTERLOCK WITH LIGHTS.
<br />4. CONNECT TO OPERATE CONTINUOUSLY.
<br />oAL LOUVER SCHEDULE
<br />MARK
<br />MANUFACTURER
<br />MODEL #
<br />TYPE
<br />WXH
<br />FREE ^
<br />AREA (FT 2)
<br />DRAINABLE
<br />REMARKS
<br />OAL-1
<br />RUSKIN
<br />ELF6375DXD
<br />INTAKE
<br />12X12
<br />0.31
<br />YES
<br />1,2
<br />NOTES:
<br />1. PROVIDE WITH KYNAR FINISH. COORDINATE WITH ARCHITECT ON FINAL PAINT COLOR
<br />2. PROVIDE WITH BIRD SCREEN
<br />SUPPLY FLEX RUNOUT SCHEDULE
<br />FLEX DUCT SIZE
<br />10"0
<br />250-330 CFM
<br />8"0
<br />105-245 CFM
<br />6010
<br />0 - 100 CFM
<br />MECHANICAL LEGEND
<br />®
<br />SUPPLY
<br />RETURN OR TRANSFER
<br />®
<br />EXHAUST
<br />eEQUIPMENT
<br />MARK
<br />MANUAL BALANCING DAMPER
<br />Q
<br />TEMPERATURE SENSOR (ADJ. DIGITAL)
<br />TAP W/DAMPER
<br />SINGLE LINE DUCT
<br />�/
<br />FLEX DUCT
<br />�-
<br />FIRE DAMPER
<br />ODRAWING
<br />NOTE
<br />•�
<br />PIPE DOWN
<br />c�
<br />PIPE UP
<br />-CD-
<br />CONDENSATE DRAIN
<br />(E)
<br />EXISTING
<br />EQUIPMENT TO BE REMOVED
<br />MECHANICAL NOTES:
<br />IN GENERAL, PLANS AND DIAGRAMS ARE SCHEMATIC ONLY AND SHOULD NOT BE SCALED.
<br />SUBMITTALS SHALL MEET SCHEDULED DESIGN CHARACTERISTICS. THIS INCLUDES BUT NOT LIMITED TO CFMS, EAT(DB/WB), ESP, CAPACITIES, VOLTAGES/PHASES, MCA/MOCP, SONES,
<br />ETC...
<br />ALL CONSTRUCTION WORK SHALL ALSO MEET THE FOLLOWING BUILDING CODE REQUIREMENTS:
<br />* FLORIDA BUILDING CODE (FBC) 2010
<br />* FBC ENERGY CONSERVATION 2010
<br />* FBC MECHANICAL CODE 2010
<br />* FBC PLUMBING CODE 2010
<br />ALL WALL MOUNTED THERMOSTATS AND/OR TEMPERATURE SENSORS SHALL BE INSTALLED AT AN ELEVATION OF 48" ABOVE FINISHED FLOOR TO THE TOP UNLESS OTHERWISE NOTED ON
<br />DRAWINGS. LOCATION OF THE WALL MOUNTED THERMOSTAT SHALL BE COORDINATED WITH OTHER TRADES FOR A NEAT APPEARANCE. FINAL LOCATION OF THERMOSTAT SHALL BE
<br />SUBJECT TO THE APPROVAL OF THE ENGINEER OR REPRESENTATIVE IN THE FIELD.
<br />ALL SUPPLY AIR DIFFUSERS SHALL BE 4-WAY THROW UNLESS OTHERWISE NOTED. CONTRACTOR SHALL PAINT INSIDE EACH RETURN GRILLE'S PLENUM AND DUCT CONNECTION FLAT
<br />BLACK TO CONCEAL CONNECTION. COORDINATE AIR DEVICE LOCATIONS WITH LIGHTING FIXTURES AND FIRE SPRINKLER HEADS. PRIOR TO INSTALLATION, THE CONTRACTOR IS TO REFER
<br />TO THE ARCHITECTURAL REFLECTED CEILING PLAN FOR ACTUAL FINAL LOCATIONS OF AIR DEVICES.
<br />DIFFUSERS/GRILLES SHALL NEVER BE INSTALLED ON SURFACE OF ACOUSTICAL LAY -IN TILE. ALL DIFFUSERS/GRILLES IN LAY -IN CEILINGS SHALL BE LAY -IN PANEL MOUNT. REFER TO
<br />SCHEDULE. GYPSUM BOARD SURFACE MOUNT DIFFUSERS SHALL NOT BE BEVEL MOUNT.
<br />CONTRACTOR SHALL COORDINATE DIFFUSER/GRILLE LOCATIONS WITH STRUCTURE IN EXPOSED SITUATIONS IN ORDER TO ENSURE AIR IS NOT DIRECTLY SUPPLIED OR RETURNED OVER
<br />STRUCTURE OR OTHER TRADE COMPONENTS SUCH AS FIRE SPRINKLER PIPING, PLUMBING PIPING, ETC... CAUSING DUST ACCUMULATION. DUCTWORK ALONG WITH DIFFUSER/GRILLE
<br />LOCATIONS SHALL BE INSTALLED SYMMETRICALLY WITH ANY ADJACENT DUCTWORK/GRILLES. CENTER DIFFUSERS/GRILLES BETWEEN STRUCTURAL MEMBERS WHERE DUCTWORK AND
<br />STRUCTURAL MEMBERS ARE EXPOSED. CONTRACTOR SHALL BE RESPONSIBLE FOR FINAL INSTALLATION APPEARANCE AND SHALL MAKE APPROPRIATE CHANGES WHERE DIRECTED BY
<br />ARCH./ENGINEER AT THEIR OWN EXPENSE WHERE ITEMS ARE NOT INSTALLED PER ABOVE STANDARDS.
<br />CONTRACTOR SHALL PROVIDE A COPY OF THE TEST AND BALANCE REPORT BY AN AABC OR NEBB CERTIFIED AGENCY. THIS REPORT MUST BE REVIEWED AND APPROVED BY THE
<br />ENGINEER PRIOR TO THE FINAL INSPECTION. THE CONTRACTOR MUST ALSO PROVIDE ALL REPORTS REQUIRED BY THE SPECIFICATION. OUTDOOR TEMPERATURE (DB); OUTSIDE AIR
<br />(DB/WB & CFM); SUPPLY AIR AT UNIT DISCHARGE (DB/WB & CFM); RETURN AIR €MIXEDI (DB/WB & CFM); LEAVING COIL (DB/WB); DIFFUSER/GRILLE (DB/WB); EQUIPMENT (EWT/LWT);
<br />EQUIPMENT (EAT/LAT); EQUIPMENT (GPM); EQUIPMENT (PRESSURES). OUTSIDE AIR CFM SHALL BE MEASURED DIRECTLY AND NOT CALCULATED FROM THE DIFFERENCE BETWEEN SUPPLY
<br />AIR CFM AND RETURN AIR CFM.
<br />ALL AIR -HANDLING UNITS SHALL BE MECHANICALLY ATTACHED TO OTHER AIR DISTRIBUTION SYSTEM COMPONENTS. AIR -HANDLING UNITS LOCATED OUT -SIDE THE CONDITIONED SPACE
<br />SHALL BE SEALED USING APPROVED CLOSURE SYSTEMS CONFORMING TO THE APPROVED CLOSURE AND MECHANICAL APPLICATION REQUIREMENTS OF FLORIDA BUILDING CODE.
<br />ALL DUCTWORK MUST BE INSTALLED 6" AWAY FROM ANY FIRE RATED WALL TO FACILITATE INSPECTION.
<br />THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL TRADES INSTALLATION SCHEDULES. FIXED WORK SUCH AS DUCTWORK AND PLUMBING SHALL BE INSTALLED PRIOR TO ANY TRADE
<br />WORK THAT CAN BE EASILY RELOCATED OR OFFSET SUCH AS ELECTRICAL CONDUITS, SMALL WATER LINES, ETC. IDEALLY DUCTWORK SHALL BE INSTALLED FIRST.
<br />PENETRATIONS THROUGH SMOKE OR FIRE -RATED ASSEMBLIES: PENETRATIONS FOR PIPES, CONDUITS OR OTHER PURPOSES THROUGH ASSEMBLIES (FLOORS, ROOF, WALLS, PARTITIONS,
<br />ETC.) WITH A REQUIRED FIRE RESISTANCE RATING SHALL BE SEALED TO THE PENETRATING MEMBER IN AN APPROVED MANNER WHICH MAINTAINS THE REQUIRED FIRE RESISTANCE
<br />RATING OF THE ASSEMBLY AS FOLLOWS:
<br />WHERE HOLES FOR PENETRATIONS ARE FORMED CIRCULAR OR CORE -BORED, THE PENETRATION SHALL BE PROTECTED WITH FIRE -SEAL BRAND SMOKE AND FIRE STOP FITTINGS
<br />MFG. BY 0-Z GEDLEY, LINK SEAL BRAND BY THUNDER LINE OR AN EQUAL APPROVED BY ENGINEER.
<br />WHERE HOLES FOR PENETRATIONS ARE IRREGULAR (NON -CIRCULAR) IN SHAPE, THE PENETRATION SHALL BE PROTECTED WITH DOW CORNING 3-6548, SILICONE RTV FOAM, 3M
<br />FIRE BARRIER PENETRATION SEAL SYSTEM OR AN EQUAL APPROVED BY THE ENGINEER.
<br />INTENT OF THESE NOTES AND MECHANICAL NOTES ON DRAWINGS IS TO CLARIFY THE SCOPE OF WORK AND ALERT CONTRACTOR OF EXISTING CONDITIONS. THE CONTRACTOR IS TO
<br />VISIT SITE AND VERIFY ALL CLEARANCES BEFORE FABRICATION OF DUCTWORK AND PROVIDE ADDITIONAL OFFSET AND/OR CHANGES IN DUCT SIZES TO MEET FIELD CONDITIONS AND
<br />COORDINATE WITH ELECTRICAL, PLUMBING AND FIRE PROTECTION SUBCONTRACTORS BEFORE ANY CONSTRUCTION WORK.
<br />FLEXIBLE AND RIGID ROUND DUCT TAKE -OFFS FOR DIFFUSERS SHALL BE THE SAME SIZE AS DIFFUSER NECK. MAXIMUM FLEXIBLE DUCT LENGTH SHALL BE 10'-0".
<br />UNLESS OTHERWISE NOTED, INSTALL DUCTWORK AS HIGH AS POSSIBLE, TIGHT TO BOTTOM OF STRUCTURE. COORDINATE DUCT ELEVATION WITH RAIN LEADERS, WATER PIPING, SANITARY
<br />DRAINS AND MAJOR ELECTRICAL CONDUITS.
<br />CONTRACTOR SHALL PROVIDE ALL SUPPLEMENTARY STEEL REQUIRED TO SUSPEND/SUPPORT MECHANICAL EQUIPMENT AND MATERIALS.
<br />CONTRACTOR SHALL INSTALL MOTORIZED OUTSIDE AIR DAMPERS FOR ALL AIR HANDLING EQUIPMENT. AIR HANDLING UNITS SHALL HAVE AN EQUIVALENT OR BETTER OF RUSKIN "CD504"
<br />DAMPER, WHICH SHALL MODULATED PER 24V ACTUATOR MECHANICALLY WIRED. ALL DAMPERS SHALL SHUT UPON UNIT SHUTDOWN.
<br />PROVIDE A TRAP IN ALL CONDENSATE PIPING LOCATED AT THE AIR HANDLING EQUIPMENT. INSULATE ALL CONDENSATE LINES WITH 1 /2" THICK CLOSED CELL FOAM INSULATION. ALL
<br />PIPING EXPOSED TO EXTERNAL ELEMENTS SHALL BE JACKETED WITH UV STABILIZED PVC OR ALUMINUM SHEETING.
<br />PROVIDE A 4" HIGH CONCRETE HOUSEKEEPING PAD UNDER ALL MECHANICAL EQUIPMENT, UNLESS OTHERWISE NOTED. PADS SHALL BE 4" LARGER THAN THE EQUIPMENT ON ALL SIDES.
<br />UNLESS OTHERWISE NOTED, ALL UNDERGROUND PIPING SHALL HAVE A MINIMUM OF 3'-0" OF COVER.
<br />IT IS THE RESPONSIBILITY OF THE MECHANICAL INSTALLER TO PATCH AND REPAIR ANY DUCT OPENINGS WHICH RESULT FROM THE RELOCATION OR ELIMINATION OF ANY EXISTING AIR
<br />DEVICES. THE PATCH IS TO BE OF A SIMILAR MATERIAL TO THE REPAIRED DUCT AND TO BE SEALED IN ACCORDANCE WITH SMACNA STANDARDS.
<br />AIR HANDLING EQUIPMENT WARRANTIES SHALL BE EQUAL TO OR EXCEED WARRANTY OF SCHEDULED EQUIPMENT. UNLESS OTHERWISE NOTED.
<br />PROVIDE ADDITIONAL DUCTWORK AND PIPING SUPPORTS ON BOTH SIDES AND WITHIN 18" OF FIRE RATED WALL. DUCTWORK OR PIPING SHALL NOT BE SUPPORTED FROM ANY FIRE
<br />RATED WALL.
<br />FOR DUCTWORK PENETRATING ONE HOUR FIRE RATED WALL, THE ENTIRE DUCT SYSTEM, TO BE CONSTRUCTED PER SMACNA STANDARDS WITH A MINIMUM OF 26 GA. STEEL DUCT AND
<br />SHALL CONTINUE IN THE HORIZONTAL DIRECTION WITHOUT ANY GRILLE OR OPENING FOR NOT LESS THAN 5'-0" FROM THE WALL AND DUCT SHALL NOT EXCEED SQUARE INCH
<br />REQUIREMENTS OF LOCAL CODE, OTHERWISE A FIRE DAMPER SHALL BE PROVIDED.
<br />DOUBLE WALLED TURNING VANES SHALL BE PROVIDED IN ALL RECTANGULAR SUPPLY DUCT ELBOWS WITH ANGLES FROM 45 DEGREES TO 90 DEGREES PER FIG. 2-5 OF THE SMACNA
<br />MANUAL.
<br />DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS (FREE AREA).
<br />CONTRACTOR SHALL COORDINATE ALL INTAKE/EXHAUST LOCATIONS TO INSURE AT LEAST A 10' DISTANCE BETWEEN ANY INTAKES AND VENTILATION EXHAUSTS, PLUMBING VENTS,
<br />RELIEF, ETC...
<br />ALL HVAC EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER'S RECOMMENDATIONS UNLESS INDICATED OTHERWISE.
<br />MECHANICAL CONTRACTOR SHALL SIZE AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S RECOMMENDATIONS. REFRIGERANT PIPING SHALL BE TYPE "L" COPPER WITH BRAZED
<br />JOINTS. APPLY -Y4" CLOSED CELL INSULATION ON COMPRESSOR SUCTION LINE. ALL PIPING EXPOSED TO EXTERNAL ELEMENTS SHALL BE JACKETED WITH UV STABILIZED PVC OR
<br />ALUMINUM SHEETING. PRE -CHARGED LINES AND SOLDER ON SHORT 90'S ARE NOT ACCEPTABLE. CONTRACTOR SHALL USE SWEEPING 90'S AT EVERY BEND WITH EXCEPTION OF
<br />EQUIPMENT CONNECTIONS.
<br />CONTRACTOR SHALL PROVIDE A PERMANENT/PROFESSIONAL LABEL FOR EACH PIECE OF EQUIPMENT, ASSOCIATED THERMOSTAT(S) AND/OR SENSOR(S).
<br />EQUIPMENT LOCATION IDENTIFICATIONS AT CEILINGS: WHERE VALVES, EQUIPMENT SUCH AS VAV BOXES, FANS, ETC... CIRCUIT BREAKERS OR OTHER ITEMS SUBJECT TO ROUTINE SERVICE
<br />ARE MOUNTED IN A CONCEALED AREA ABOVE A CEILING, THE CEILING MUST BE MARKED WITH A LABEL UNDER THE SERVICED DEVICE. THE LABEL SHALL CARRY APPROPRIATE
<br />IDENTIFICATION TAG.
<br />DUCTWORK, DIFFUSERS, REGISTERS, GRILLES, AND OTHER ITEMS OF THE AIR HANDLING SYSTEM SHALL NOT BE SUPPORTED BY THE CEILING OR CEILING SUSPENSION SYSTEM.
<br />METAL DUCTWORK SHALL BE CONNECTED TO AIR HANDLING EQUIPMENT WITH FLEXIBLE DUCT CONNECTORS EQUAL TO DURO DYNE "SUPER METAL-FAB" WITH EXCELON FABRIC; "GRIP
<br />LOC" SEAM; 24 GAUGE METAL TABS. INSULATION SHALL BE INSTALLED OVER METAL TABS AS TO NOT CAUSE FRICTION ON FABRIC.
<br />LOW PRESSURE SUPPLY, RETURN, AND TRANSFER DUCTWORK SHALL BE EXTERNALLY INSULATED SHEET METAL CONSTRUCTION IN ACCORDANCE WITH LATEST SMACNA STANDARDS
<br />UNLESS OTHERWISE NOTED. DUCT INSULATION TO BE 2.0" THICK FOIL BACK WRAP, K=0.25 BTUH-IN./SF. HR- 1.50#/CF AS MANUFACTURED BY JOHNS MANVILLE. JOINTS TO BE
<br />STAPLED AND TAPED WITH PRESSURE SENSITIVE TAPE (PER FMC 603) AS MANUFACTURED BY COMPAC INDUSTRIES MODEL #120 (FLAME SPREAD = 5, SMOKE DEVELOPED = 10) OTHER
<br />ACCEPTABLE MANUFACTURERS ARE OWENS CORNING AND KNAUF. IN LIEU OF SHEET METAL DUCTWORK, DUCT BOARD MAY BE USED. CONTRACTOR SHALL (BID AS DEDUCTIVE
<br />ALTERNATE). 1.5" TRICK DUCT BOARD (EQUAL TO JOHNS MANVILLE BONDED WITH THERMO SETTING RESIN ON AIR STREAM SIDE WITH AN ANTI -MICROBIAL COATING) AND CONFORM
<br />WITH UL STANDARDS FOR SAFETY AIR DUCT, NO. 181, 1967 ESTABLISHED FOR CLASS 1 AIR DUCTS. FACING SHALL BE FSK ALUMINUM FOIL. CONSTRUCTION SHALL COMPLY WITH
<br />RECOMMENDATIONS AND DETAILS IN SMACNA AND NAIMA FIBROUS GLASS DUCT CONSTRUCTION STANDARDS, LATEST REVISION AND MANUFACTURER'S RECOMMENDATIONS. ALL JOINTS
<br />SHALL BE SECURELY TAPED WITH FASSON 0810 OR APPROVED EQUAL PRESSURE SENSITIVE TAPE. METAL TO FIBERGLASS CONNECTIONS TO BE MADE USING 3" WIDE GLASS FABRIC
<br />TAPE WITH FOSTER 30/35 MASTIC OR EQUAL. SUPPORT DUCTS WITH 1X2X1 22 GAUGE MINIMUM CHANNELS AND STRAP OR 12-GAUGE WIRE FROM BUILDING CONSTRUCTION.
<br />SUSPEND FROM JOISTS WITH BEAM CLAMPS. PROVIDE HOT DIPPED STEEL FASTENERS, ANCHORS, RODS, STRAPS, TRIM AND ANGLES FOR SUPPORT OF DUCTWORK. DUCT SIZES ON
<br />CONSTRUCTION DOCUMENTS ARE INTERNAL FREE -AREA DIMENSIONS.
<br />ALL EXHAUST DUCT WORK SHALL BE NON -INSULATED SHEET METAL UNLESS OTHER WISE NOTED.
<br />FLEXIBLE DUCT SHALL HAVE CONTINUOUS TEAR RESISTANT LINER ENCASED BY INSULATING MATERIAL WITH AN OUTER VAPOR JACKET CONFORMING TO UL181 UNLESS THE FLEX DUCT
<br />MEETS THE CRITERIA STATED IN 2010 FLORIDA BUILDING CODE -BUILDING SECTION 419.3.6.4.
<br />COORDINATE AIR DEVICE LOCATIONS WITH LIGHTING FIXTURES AND FIRE SPRINKLER HEADS.
<br />CONTRACTOR SHALL SUPPLY PIPE SUPPORTS 4'-0" ON CENTERS FOR REFRIGERANT LINES AND CONDENSATE LINES. SUPPORTS SHALL BE PER DETAILS.
<br />CONTRACTOR SHALL REFER TO ALL DETAILS FOR PROPER GUIDANCE.
<br />MES,112.90.4700
<br />PareFL 33609
<br />Mark E. Awmiller, PE 111111
<br />COA # 6304
<br />Project # 2013577
<br />THE COMMONS
<br />ON PRETTY POND
<br />38130 Pretty Pond Road
<br />Zephyrhills, FL 33540
<br />- 10/15/13 PERMIT SET
<br />Mark I Date
<br />Description
<br />Issue/Revision
<br />Revision
<br />Project ID
<br />13D16
<br />CAD File Name
<br />-
<br />Drawn By
<br />DKS
<br />Reviewed By
<br />MEA
<br />Plot Date:
<br />00/00/00
<br />Record Date:
<br />00/00/00
<br />Sheet Title
<br />Drawing No.
<br />SCHEDULES
<br />SCALE: NTS
<br />M-6.0