<br />PANEL "A",120/208 VOLT, 3 PHASE, 4 WIRE,
<br />600A FRAME, 600A MLO, SURFACE MOUNT, NEMA 1
<br />PANEL "R",120/208 VOLT, 3 PHASE, 4 WIRE,
<br />225 AMP, MLO, SURFACE MOUNT, NEMA 1
<br />MAIN BONDING JUMPER
<br />BARE COPPER NEUTRAL BUS
<br />TOTAL PER PHASE IN
<br />TOTAL PER PHASE IN
<br />CONDUCTION GROUND BUS
<br />(1)#6 TO PHONE BOARD
<br />WATTS
<br />WATTS
<br />MINIMUM OF 20'-0" OF 1/2"
<br />®
<br />PER NEC 800-40(D)
<br />REBAR IN BUILDING WALL
<br />e
<br />DESCRIPTION
<br />AMP
<br />POLE
<br />A
<br />B
<br />C
<br />AMP
<br />POLE
<br />DESCRIPTION
<br />LOAD
<br />CKT#
<br />CKT#
<br />LOAD
<br />DESCRIPTION
<br />AMP
<br />POLE
<br />A
<br />B
<br />C
<br />AMP
<br />POLE
<br />DESCRIPTION
<br />LOAD
<br />CKT#
<br />FOOTING, (NEC 250-50C)
<br />BARE COPPER GROUNDING
<br />3580
<br />20
<br />1
<br />AUTOMATIC DOOR
<br />C
<br />100
<br />2
<br />1
<br />1000
<br />C
<br />4900
<br />C
<br />3900
<br />2
<br />ELECTRODE CONDUCTOR
<br />A 1-A REACH -IN DAIRY CASE
<br />15
<br />2
<br />40
<br />2
<br />A2-AREACH-IN FROZEN CASE DEFROST
<br />(NEC 250-66)
<br />RTU-1
<br />30
<br />3
<br />4020
<br />20
<br />1
<br />TELEPHONE BOARD/BUZZER
<br />C
<br />540
<br />4
<br />3
<br />1000
<br />4900
<br />3900
<br />4
<br />CADWEL
<br />BONDING JUMPER TO
<br />3660
<br />20
<br />1
<br />ENERGYMANAGEMENT
<br />C
<br />180
<br />6
<br />5
<br />1000
<br />C
<br />A-1-B REACH -IN DAIRY CASE
<br />15
<br />2
<br />4200
<br />40
<br />2
<br />C
<br />A-2-B REACH -IN FROZEN CASE DEFROST
<br />3200
<br />6
<br />PANELBOARD ENCLOSURE SIZE
<br />11580
<br />20
<br />1
<br />OUTDOOR HVAC RECEP.
<br />180
<br />8
<br />7
<br />1000
<br />4200
<br />3200
<br />8
<br />VALVE,
<br />METER
<br />SUPPLY
<br />PER NEC 250-122
<br />BUILDING STRUCTURAL
<br />RTU-2
<br />100
<br />3
<br />11580
<br />20
<br />1
<br />OUTDOOR DRINKVENDING
<br />180
<br />10
<br />9
<br />1300
<br />C
<br />A 1-C REACH -IN DAIRY CASE
<br />15
<br />2
<br />4500
<br />40
<br />2
<br />C
<br />A2-C REACH -IN FROZEN CASE DEFROST
<br />3200
<br />10
<br />UNION
<br />SIDE
<br />STEEL 250-52 A 2
<br />(NEC( ( )( )
<br />11580
<br />20
<br />1
<br />OUTDOOR CONV RECEPT.
<br />180
<br />12
<br />11
<br />1300
<br />4500
<br />3200
<br />12
<br />PIPE CLAMP
<br />COLD WATER SERVICE (TYP.)
<br />CADWELD
<br />11500
<br />20
<br />1
<br />EXHAUST FAN
<br />100
<br />14
<br />13
<br />1300
<br />C
<br />Al-D REACH -IN DAIRY CASE
<br />15
<br />2
<br />39Q0
<br />25
<br />2
<br />C
<br />A-3 REACH -IN FROZEN CASE DEFROST
<br />26Q0
<br />14
<br />ENTRANCE (PROVIDE SIMILAR
<br />CONNECTION TO FIRE JUMPER
<br />RTU-3
<br />100
<br />3
<br />11500
<br />20
<br />1
<br />EXHAUST FAN
<br />100
<br />16
<br />15
<br />1300
<br />3900
<br />2600
<br />16
<br />PROTECTION WATER SERVICE
<br />11900
<br />20
<br />1
<br />INTERFACE EQUIP.
<br />500
<br />18
<br />17
<br />1150
<br />C
<br />72" COOLER
<br />20
<br />1
<br />2070
<br />C
<br />920
<br />18
<br />ENTRANCE), (NEC 250-50A)
<br />20
<br />2
<br />72" FREEZER
<br />500
<br />20
<br />1
<br />VSAT, DATAHUB EQUIP.
<br />500
<br />20
<br />19
<br />1150
<br />C
<br />PRODUCE COOLER
<br />20
<br />1
<br />2070
<br />920
<br />20
<br />NOTE: ALL GROUNDING SHALL BE INSTALLED IN
<br />SPACE
<br />3
<br />960
<br />20
<br />1
<br />CCTV EQUIP.
<br />960
<br />22
<br />21
<br />1300
<br />C
<br />COOLER
<br />15
<br />2
<br />2964
<br />20
<br />2
<br />PRODUCE COOLER C
<br />1664
<br />22
<br />ACCORDANCE WITH ARTICLE 250-50 OF THE
<br />180
<br />20
<br />1
<br />SECURITYREC
<br />C
<br />180
<br />24
<br />23
<br />1300
<br />2964
<br />1664
<br />24
<br />NATIONAL ELECTRICAL CODE.
<br />WATER HEATER
<br />20
<br />1
<br />2370
<br />20
<br />1
<br />OFFICE REC
<br />G
<br />720
<br />26
<br />25
<br />SPARE
<br />20
<br />1
<br />360
<br />20
<br />1
<br />SERVICE RECEPS ON ROOF
<br />360
<br />26
<br />GROUNDING DETAIL
<br />0
<br />SODACOOLERS
<br />20
<br />1
<br />1680
<br />20
<br />1
<br />OFFICE REC
<br />C
<br />720
<br />28
<br />27
<br />SPARE
<br />20
<br />1
<br />20
<br />1
<br />SPARE
<br />28
<br />DRINKING FOUNTAINS
<br />20
<br />1
<br />1424
<br />20
<br />1
<br />CLICK & COLLECT FREEZER/COOLER
<br />C
<br />924
<br />30
<br />29
<br />SPARE
<br />20
<br />1
<br />0
<br />20
<br />1
<br />SPARE
<br />30
<br />Scale: NTS
<br />OUTDOOR ICE MERCHANDISER
<br />20
<br />1
<br />16630
<br />15430
<br />32
<br />NEW (X), EXISTING O
<br />TOTAL
<br />15430
<br />16264
<br />13734
<br />TOTAL CONNECTED =
<br />45428
<br />WATTS
<br />HIGI KIOSK
<br />20
<br />1
<br />17464
<br />150
<br />3
<br />PANEL "R"
<br />16264
<br />34
<br />*HANDLE
<br />LOCK -ON DEVICE
<br />LOCATED AT:
<br />126.2
<br />AMPS
<br />OFFICE REC
<br />20
<br />1
<br />14742
<br />13734
<br />36
<br />DRINK COOLERS
<br />20
<br />1
<br />8395
<br />6795
<br />38
<br />SOAD COOLERS
<br />20
<br />1
<br />7909
<br />150
<br />3
<br />PANEL "B"
<br />6309
<br />40
<br />SPARE
<br />20
<br />1
<br />8208
<br />8208
<br />42
<br />NEW
<br />TOTAL
<br />54555
<br />55113
<br />51694
<br />TOTAL CONNECTED =
<br />161362.0 WATTS
<br />* HANDLE LOCK -ON DEVICE
<br />LOCATED AT:
<br />448.2
<br />AMPS
<br />120/208
<br />3-PHASE,4W
<br />PANEL LOAD CAPACITY: 600A
<br />TOTAL LOAD
<br />LOAD TYPE
<br />CONNECTED
<br />DEMAND
<br />DEMAND FORMULA
<br />CONNECTED
<br />DEMAND
<br />LIGHTING
<br />6.9 KVA
<br />8.685 KVA
<br />LOAD X 125% NEC 210.19 CONTINUOUS
<br />161.4
<br />1 KVA
<br />143.10
<br />KVA
<br />RECEPTACLE
<br />18.5 KVA
<br />14.2 KVA
<br />10KVA+50%REMAINDER NEC 220.44
<br />448.23
<br />AMP
<br />397.49
<br />AMP
<br />HVAC
<br />78.8 KVA
<br />63.07 KVA
<br />LOAD X80% (USED MCA IN CALCULATION)
<br />DOLLAR GENERAL ZEPHYRHILLS
<br />MISC
<br />57.1 KVA
<br />57.1 KVA
<br />LOAD X 100% NEC 210.19 NON-CONT.
<br />NP
<br />0 KVA
<br />0 KVA
<br />0 NONCOINCIDENTAL LOADS NEC 220.60
<br />CONNECTIVE LOAD SUMMATION
<br />INTERIOR LIGHTING =
<br />3380.0 WATTS
<br />SITE AND SIGN LIGHTING =
<br />3568.0 WATTS
<br />RECEPTACLE LOAD =
<br />18472.0 WATTS
<br />HVAC LOAD =
<br />78840.0 WATTS
<br />EQUIPMENT LOAD =
<br />57102.0 WATTS
<br />TOTAL LOAD =
<br />161362.0 WATTS
<br />448.2 AMPS
<br />VERIFY ALL WIRE SIZES SHOWN TO MEET LOCAL CODES. ADJUST, AS
<br />REQUIRED, PER LOCAL CODES.
<br />PROVIDE EXTERIOR NEMA 3R/600V/600AS/600AF
<br />MAIN SERVICE DISCONNECT CLASS J FUSES AS
<br />REQUIRED BY LOCAL CODE, COORDINATE LOCATION
<br />WITH UTILITY COMPANY AND DOLLAR GENERAL.
<br />PANEL "A" TO BE AN MLO IF DISCONNECT IS
<br />PROVIDED.
<br />AVAILABLE SHORT
<br />CIRCUIT (TYPICAL)
<br />CT'S/ METER CABINET 18.64
<br />PER UTILITY COMPANY
<br />REQUIREMENTS r�
<br />3 SETS OF (4)#500, AL, 4"C UNDERGROUND
<br />SERVICE ENTRANCE PER UTILITY AND SITE
<br />SPECIFIC CONDITIONS. REFER TO SHEET ES1
<br />FOR LOCAL UTILITY CO. TRANSFORMER
<br />LOCATION. G.C. SHALL COORDINATE WITH
<br />CIVIL FOR THE EXACT LOCATION OF THE
<br />TRANSFORMER AND MAKE ANY CHANGES TO
<br />THE SERVICE ENTRANCE WIRING
<br />SIZE IF THE CONNECTION POINT IS DIFFERENT
<br />THAN WHAT IS SHOWN.
<br />T
<br />2 SETS OF
<br />(4)#350KCMIL, 3"C,
<br />COPPER
<br />CLASS J FUSE
<br />LET -THROUGH
<br />(10kA)
<br />19.02 2 SETS OF
<br />(4)#350KCMIL,
<br />3"C, COPPER
<br />1/0 SYSTEM
<br />GROUND,
<br />SEE 2/E5
<br />EXTERIOR
<br />NOTES:
<br />B = BREAKERS FOR HVAC UNIT SHALL BE SIZED PER
<br />MANUFACTUREE REQUIREMENTS & BE HACR TYPE.
<br />C = BREAKER LOCK
<br />D = ISOLATED GROUND BUS.
<br />R = ROUTING TO EMS PANEL
<br />PANEL "B", 1201208 VOLT, 3 PHASE, 4 WIRE, 225 AMP, MLO, SURFACE MOUNT, NEMA 1
<br />TOTAL PER PHASE IN
<br />WATTS
<br />CKT#
<br />LOAD
<br />DESCRIPTION
<br />AMP
<br />POLE
<br />A
<br />B
<br />C
<br />AMP
<br />POLE
<br />DESCRIPTION
<br />LOAD
<br />CKT#
<br />1
<br />180
<br />R,G
<br />NIGHT LIGHTS
<br />20
<br />1
<br />720
<br />20
<br />1
<br />BREAK RM. RECEPS.
<br />C
<br />540
<br />2
<br />3
<br />135
<br />R,C
<br />RECEIVING LIGHTS
<br />20
<br />1
<br />135
<br />20
<br />1
<br />SPARE
<br />4
<br />5
<br />675
<br />R
<br />70% SALES LIGHTS - ROWS 2 & 3
<br />20
<br />1
<br />675
<br />20
<br />1
<br />SPARE
<br />6
<br />7
<br />585
<br />R
<br />70% SALES LIGHTS - ROWS 5 & 6
<br />20
<br />1
<br />1305
<br />20
<br />1
<br />BREAK RM. RECEPS. & SERVICE CLOSET C
<br />720
<br />8
<br />9
<br />675
<br />R
<br />30% SALES LIGHTS - ROWS 1 & 4
<br />20
<br />1
<br />1455
<br />20
<br />1
<br />REC EPT KEY ME
<br />C
<br />780
<br />10
<br />11
<br />585
<br />R
<br />70% SALES LIGHTS - ROWS 8 & 9
<br />20
<br />1
<br />1185
<br />20
<br />1
<br />RECEPT ATM
<br />G
<br />600
<br />12
<br />13
<br />90
<br />R
<br />BREAK RM./OFF./R.R. LIGHTS
<br />20
<br />1
<br />1170
<br />20
<br />1
<br />BULKHEAD RECEPS.
<br />1080
<br />14
<br />15
<br />405
<br />R
<br />30% SALES LIGHTS - ROWS 7 & 10
<br />20
<br />1
<br />455
<br />20
<br />1
<br />EMERGENCY/EXIT LIGHTS
<br />R
<br />50
<br />16
<br />17
<br />SPARE
<br />20
<br />1
<br />1200
<br />20
<br />1
<br />POWER TERMINAL BROWN
<br />C
<br />1200
<br />18
<br />19
<br />SPARE
<br />20
<br />1
<br />1200
<br />25
<br />1
<br />POWER TERMINAL BROWN
<br />C
<br />1200
<br />20
<br />21
<br />900
<br />R
<br />BUILDING SIGN
<br />20
<br />1
<br />2100
<br />25
<br />1
<br />POWER TERMINAL GREEN
<br />C
<br />1200
<br />22
<br />23
<br />900
<br />R
<br />BUILDING SIGN
<br />20
<br />1
<br />2100
<br />25
<br />1
<br />POWER TERMINAL GREEN
<br />C
<br />1200
<br />24
<br />25
<br />R
<br />SPARE
<br />20
<br />1
<br />1200
<br />20
<br />1
<br />POWER TERMINAL GREEN
<br />C
<br />1200
<br />26
<br />27
<br />300
<br />R
<br />SITE LIGHTING
<br />20
<br />2
<br />1500
<br />20
<br />1
<br />POWER TERMINAL GREEN
<br />C
<br />1200
<br />28
<br />29
<br />300
<br />R
<br />1500
<br />20
<br />1
<br />POWER TERMINAL BROWN
<br />C
<br />1200
<br />30
<br />31
<br />SPARE
<br />20
<br />1
<br />1200
<br />20
<br />1
<br />POWER TERMINAL BROWN
<br />C
<br />1200
<br />32
<br />33
<br />484
<br />R
<br />LEFT SIDE EXT. WALL LTS
<br />20
<br />1
<br />664
<br />20
<br />1
<br />ICE CREAM FREEZER
<br />C
<br />180
<br />34
<br />35
<br />584
<br />FRONT EXT. WALL/CANOPY LTS
<br />20
<br />1
<br />1448
<br />20
<br />1
<br />GATORADE
<br />C
<br />864
<br />36
<br />37
<br />SPARE
<br />20
<br />1
<br />0
<br />20
<br />1
<br />SPARE
<br />38
<br />39
<br />SPARE
<br />20
<br />1
<br />0
<br />20
<br />1
<br />SPARE
<br />40
<br />41
<br />100
<br />R
<br />EXTERIOR DUSK/DAWN
<br />20
<br />1
<br />100
<br />20
<br />1
<br />SPARE
<br />42
<br />NEW(), EXISTING O
<br />TOTAL
<br />6795
<br />6309
<br />8208
<br />TOTAL CONNECTED =
<br />21312
<br />WATTS
<br />* HANDLE LOCK -ON DEVICE
<br />LOCATED AT:
<br />59.2
<br />AMPS
<br />600A, 3PH, 4W, 120/208V,
<br />600A MLO - 42 CIRCUIT
<br />225A, 3PH, 4W, 120/208V,
<br />MLO - 42 CIRCUIT
<br />225A, 3PH, 4W, 120/208V,
<br />MLO - 54 CIRCUIT
<br />PANEL PANEL PANE[
<br />A R B
<br />�-- N N N
<br />G G G
<br />to IG
<br />17.94 —/ I 1 1 16.55
<br />INTERIOR
<br />ELECTRICAL PANEL SCHEMATIC
<br />Scale: NTS
<br />16.55 (4)#1/0, (1)#6G, (1)#61G, 2"C
<br />(4)#1/0, (1)#6G, (1)#61G, 2"C
<br />SHORT CIRCUIT RATING
<br />LET THROUGH CURRENT OF 600A CLASS J
<br />FUSE WILL BE LIMITED TO 10KA WHEN SCA
<br />IS LESS THAN 25KA. PANEL A, B & R
<br />BREAKERS MAY BE RATED 10kAIC.
<br />3 SHORT CIRCUIT ESTIMATE
<br />Scale: NTS
<br />Voltage Drop Estimate
<br />Prepared by NORR LLC
<br />Job No__%JCCT20_0451
<br />Job Name.- .'Dollar General Zephyrhills Florida 23227
<br />_- . r . .. ,.... ,. ..
<br />igner: Engineer/Desi& Pic -Kell / N. Nguyen
<br />Line Side 208 Phase to Phase Voltage
<br />120
<br />Phase to Neutral Voltage
<br />Feeders (3PH) Amps Size Type Z/1kft*
<br />#/Ph
<br />Len(ft)
<br />Vdrops
<br />VD%o
<br />LoadV
<br />Utility Ser ce
<br />397.49 500kcm AL/NM
<br />0.057
<br />3
<br />267
<br />3.49
<br />1.7%
<br />204.5
<br />600A Maier Disconnect
<br />397,49 350kcm C U/FE
<br />0.060
<br />2
<br />5
<br />0.10
<br />0.0°`a
<br />207.9
<br />600A Panel A
<br />397-49 350kcm , CU/FE
<br />0-060
<br />2
<br />10
<br />0.21
<br />0.1 %
<br />207.8
<br />150A Panel B & R
<br />150.00 #1/0 GU/FE
<br />0.130
<br />1
<br />5
<br />0.17
<br />0.1%
<br />207-8._..
<br />Total Feeder I I I i 1.9%
<br />* Effective Z at 0.85 PF taken from Table 9 of the NEC
<br />Wire Codes: CU -Copper, AL -Aluminum _
<br />Conduit Codes: FE - Ferris (Steel), N M - Non-Maanetic (PVC. Aluminum)
<br />4 VOLTAGE DROP ESTIMATE
<br />Scale: NTS
<br />HVAC UNIT WIRING TABLE
<br />UNIT WIRE COND DISC FUSE ENCL PH VOLT GND I BRKR LOAD I CFM TONS
<br />RTU-1 #10 3/4" 30A/3P 30 NEMA 3R 3$ 208 #10 30A/3P 10440 900 3
<br />RTU-2 #2 1 1/4" 100A/3P 100 NEMA 3R 3� 208 #6 10OA13P 34200 3600 12.5
<br />RTU-3 #2 1 1/4" 100A/3P 100 NEMA 3R 3� 208 #6 100A/3P 34200 3760 12.5
<br />EF-1 #12 3/4" MOTOR RATED SWITCH NEMA 1 10 120 #12 W/ LIGHTS 17 77 --
<br />EF-2 #12 3/4" MOTOR RATED SWITCH NEMA 1 1c 120 #12 20A/1P 17 77 --
<br />TABLE NOTES:
<br />1. THE ELECTRICAL CONTRACTOR SHALL FIELD COORDINATE WITH THE MECHANICAL CONTRACTOR CONCERNING THE ELECTRICAL INFO OF ALL
<br />MECHANICAL DEVICES REQUIRING AN ELECTRICAL CONNECTION PRIOR TO DOING ANY WORK. ANY DISCREPANCIES BETWEEN THE FIELD
<br />OBTAINED INFORMATION AND THE INFORMATION SHOWN ON THE ELECTRICAL PLANS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER
<br />PRIOR TO DOING ANY WORK.
<br />2. PROVIDE NEUTRALS ON AS REQUIRED BASIS, FIELD VERIFY r
<br />3. I ALL DISCONNECTS TO BE HEAVY DUTY. FUSES TO BE RK-5 TYPE, SUBMIT SHOP DRAWINGS. BUSSMAN FRN-R-(AMP) IS SPECIFIED.
<br />CONSULTANT:
<br />SEAL: SEAN PATRICK PIC-KELL, PE 83946
<br />\\\�Q�?,IGK P/c,�.,.
<br />co No. 83946
<br />%.p °•• STATE OF �e
<br />THIS DRAWING SHALL NOT BE USED FOR
<br />CONSTRUCTION PURPOSES 'UNTIL THE SEAL AND
<br />SIGNATURE OF THE RESPONSIBLE REGISTRANT
<br />APPEARS ON THE DRAWING, AND PROPER PERMIT
<br />FORMS AND RELATED FEES ARE TRANSMITTED BY
<br />THE OWNER, OWNER'S AGENT OR CONTRACTOR
<br />TO THE AUTHORITY HAVING JURISDICTION.
<br />DATE
<br />ISSUED FOR
<br />REV
<br />03/29/2021
<br />PEMB COORDINATION
<br />05/20/2021
<br />CIVIL SUBMISSION
<br />05/20/2021
<br />DUKE COORDINATION
<br />06/07/2021
<br />PEMB COORDINATION 02
<br />08/09/2021
<br />CIVIL RESUBMISSION 1
<br />08/25/2021
<br />OWNER REVIEW
<br />1 1 /08/2021
<br />REVISED ELEVATIONS
<br />1 1 /29/2021
<br />PERMIT SUBMITTAL
<br />Project Manager
<br />Drawn
<br />L. LONG
<br />N. NGUYEN
<br />Project Leader
<br />Checked
<br />L. LONG
<br />M. GOOD
<br />Date
<br />Dept Mgr Approval
<br />02/23/2021
<br />M. GOOD
<br />Client
<br />PALMETTO ZEPHYRHI'LLS - GALL BLVD., LLC
<br />P.O. Box 1615,
<br />Thomasville, GA 31 799
<br />Office: (229) 226-1 1 77
<br />Contact: Daniel Tubb
<br />Project
<br />DOLLAR GENERAL
<br />Corner of Gall Boulevard and C
<br />Avenue,
<br />Zephyrhills, FL 33542
<br />(City of Zephyrhills)
<br />Store #: 23227
<br />Drawing Title
<br />THREE PHASE
<br />ELECTRICAL PANELS
<br />DO NOT SCALE DRAWING
<br />Project No.
<br />Drawing No.
<br />,JCDT.20.0451
<br />E5
<br />- —
<br />s _ i, IJ
<br />
|