SECOND FLOOR ELECTRICAL PLAN (ELEVATION A AND B' <br />1 /4" = 1'-0„ <br />ELECTRICAL NOTES: <br />1. GFCI'S ARE TO BE INSTALLED IN THE FOLLOWING <br />LOCATIONS AS SPECIFIED PER NFPA 70 (NEC) 2017 <br />A) BATHROOMS <br />B) GARAGES, AND ALSO ACCESSORY BUILDINGS THAT <br />HAVE A FLOOR LOCATED AT OR BELOW GRADE LEVEL <br />NOT INTENDED AS HABITABLE ROOMS AND LIMITED TO <br />STORAGE AREAS, WORK AREAS, AND AREAS OF <br />SIMILAR USE. <br />C) CRAWL SPACES AT OR BELOW GRADE. <br />D) KITCHENS - WHERE THE RECEPTACLES ARE <br />INSTALLED TO SERVE THE COUNTERTOP SURFACES. <br />E) LAUNDRY, UTILITY, AND WET BAR SINKS - WHERE <br />THE RECEPTACLES ARE INSTALLED WITHIN 6 FEET OF <br />THE OUTSIDE EDGE OF THE SINK. <br />2. ARCH FAULT OUTLETS ARE REQUIRED PER NFPA 70 <br />(NEC) 2017, INCLUDING ARTICLES 210 AND 400. <br />3. ANY CONFLICTS BETWEEN LOCATION OF <br />MECHANICAL FIXTURES ON PLANS AND THE ABILITY TO <br />LOCATE'fHEM IN THE FIELD MUST BE REPORTED TO THE <br />ARCHITECT PRIOR TO INSTALLATION. <br />4. RECEPTACLE OUTLETS IN GARAGE MUST BE <br />SERVED BY SEPARATE BRANCH CIRCUIT THAT DOES NOT <br />SUPPLY OTHER OUTLETS. <br />5. CM MUST BE AT LEAST T FROM BATH DOOR AND AT <br />LEAST 6' FROM KITCHEN RANGE/OVEN. <br />NOTES: <br />UNLESS OTHERWISE NOTED <br />1. ELECTRICAL OUTLET HEIGHTS AS MEASURED FROM FINISHED <br />FLOOR TO CENTERED LINE OF THE BOX TO BE: 12" AFF <br />(GENERAL) <br />KITCHEN <br />44" AFF <br />BATHROOM <br />39" AFF <br />LAUNDRY ROOM <br />36" AFF <br />EXTERIOR WATERPROOF <br />12" AFF <br />GARAGE GENERAL PURPOSE <br />42" AFF <br />RANGE <br />2" AFF <br />2. ALL TRIM PLATES & DEVICES TO BE GANGED, WHERE <br />POSSIBLE. <br />3. ELECTRICAL SWITCHES TO BE AT 42" CENTERLINE ABOVE <br />FINISHED FLOOR <br />4. ELECTRICAL PLAN IS INTENDED FOR BID PURPOSES ONLY. <br />ALL WORK SHALL. BE DONE IN STRICT ACCORDANCE WITH THE <br />NATIONAL ELECTRIC CODE, LATEST EDITION, BY A LICENSED <br />ELECTRICAL CONTRACTOR WHO SHALL BE RESPONSIBLE FOR <br />THE INSTALLATION & SIZING OF ALL ELECTRICAL, WIRING & <br />ACCESSORIES. <br />5. SMOKE DETECTORS SHALL BE INSTALLED AS DIRECTED BY <br />THE 2016 NFPA 72 NATIONAL FIRE ALARM CODE. <br />6. ALL ELECTRICAL IN THE LIVING ROOMS, DINING ROOMS, <br />SUNROOMS, FAMILY ROOMS, DENS, LIBRARIES, SLEEPING ROOMS, <br />PARLORS AND SIMILAR ROOMS OR AREAS SHALL BE ON AN A.F.C.I. <br />PROTECT CIRCUIT PER NFPA 70 (NEC) 2017. <br />7. IN ALL AREA SPECIFIED IN NFPA 70 (NEC) 2017 210.52, ALL 125 <br />VOLT, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED <br />TAMPER -RESISTANT RECEPTACLES. <br />Per' � <br />F' J r <br />6aSx 'jip0 <br />�S C <br />eZ6T Q�23 <br />�� �.V C'o` k Nkr r <br />a\ e w�e �\ Pn�\e `a <br />?\ansoc�`���a0e��a <br />ELECTRICAL DETAIL: <br />INTERCOM <br />SPEAKER <br />ALIGNED W/ <br />EDGE OF <br />SWITCH <br />io <br />SWITCH <br />4 1/2" <br />DOORJAMB <br />DUPLEX <br />OUTLET in <br />TRIM <br />o <br />0 <br />BASE <br />NOTE: <br />ALL DIMENSIONS ARE FROM ROUGH FRAMING <br />SMOKE DETECTOR LOCATION: <br />WALL <br />oz <br />S �' <br />SMOKE DETECTOR <br />MIN. <br />ELECTRICAL LEGEND: <br />NOTE: ALL HEIGHTS ABOVE FINISH FLOOR <br />110V DUPLEX OUTLET AT 12" <br />110V DUPLEX OUTLET AT 39" <br />NOTE: ALL <br />RECEPTACLES <br />110V DUPLEX OUTLET AT 43" <br />ABOVE <br />COUNTERS <br />110V DUPLEX OUTLET AT 45" <br />SHALL BE <br />SPLIT 110V DUPLEX OUTLET <br />MOUNTED <br />HORIZONTAL <br />AT 12" - TOP PLUG IS HOT <br />110V QUAD OUTLET AT 12" <br />WEATHERPROOF GFCI OUTLET AT 12" <br />220V OUTLET AT 30" <br />110V DUPLEX FLOOR OUTLET <br />OUTLET - VERIFY W/MANUF. SPECS <br />® FOR LOCATION & TYPE <br />TELEPHONE OUTLET AT 12" OR AS NOTED <br />�} TELEVISION OUTLET AT 12" - WIRE FOR <br />CABLE & SATELLITE <br />® STRUCTURED WIRE OUTLET <br />6- SWITCH AT 36" <br />co <br />3 WAY SWITCH AT 36" <br />4 WAY SWITCH AT 36" <br />-0 PUSH BUTTON FOR GARAGE DOOR OPENER <br />-a DIMMER SWITCH AT 36" <br />-M] PUSH-BUTTON DOORBELL <br />{�- CLG MNT LT FIXTURE <br />-�- CLG MNT PREWIRE - FIXTURE BY OWNER <br />{} SURFACE MNT FIXTURE <br />} WALL MNT FIXTURE <br />NOTE: <br />�i 40W A 6" ROUND OPALEX - ALTERNATE <br />TUB/SHOWER CANS MAY BE <br />4� 50W PAR30 NFL 6" WHITE BAFFLE USED IF <br />APPROVED BY <br />50W MR16 4" LOW VOLTAGE OWNER <br />�8 50W PAR20 NFL 4" MINI ROUND RECESS <br />�0 50W PAR20 NFL 6" RD REGRESSED BAFFLE EYEBAL <br />} CLG FAN PREWIRE AND SWITCH <br />COMBINATION CARBON MONOIXED DETECTOR/ <br />cs SMOKE DETECTOR <br />©s SMOKE DETECTOR <br />cU-18= UNDER CABINET 18" <br />CS-182 SINGLE 18" FLUOR STRIP <br />=U-24= UNDER CABINET 24" <br />=S-24= SINGLE 24" FLUOR STRIP <br />=D-24= DOUBLE 24" FLUOR STRIP <br />— U-36 = UNDER CABINET 36" <br />S-36 — SINGLE 36" FLUOR STRIP <br />D-36 — DOUBLE 36" FLUOR STRIP <br />S-48 SINGLE 48" FLUOR STRIP <br />D-48 DOUBLE 48" FLUOR STRIP <br />24 24"CLG MNT WRAPPED FLUOR LIGHT <br />48 48"CLG MNT WRAPPED FLUOR LIGHT <br />9F24:M 24" VANITY LIGHTING <br />9RF 36 :7mR 36" VANITY LIGHTING <br />96--4848" VANITY LIGHTING <br />EXHAUST FAN/LIGHT <br />0 EXHAUST FAN <br />p DOUBLE FLOOD LIGHT W/ COVERS AND <br />ZT 15OW PAR 38 FL <br />® INTERCOM SPEAKER AT 5'-0" ABV FINISH FLOOR <br />® CEILING MNT SPEAKER <br />M CHIMES (DELETE W/ INTERCOM) <br />MKr MASTER STATION <br />_M&3 ELEC PANEL <br />VACUM OUTLET AT 12" <br />CEILING RETURN AIR <br />99 A/C REGISTER <br />[� THERMOSTAT <br />SECURITY PAD <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR LOCATION PURPOSES. <br />/N > O o <br />W <br />IV ,= so U <br />C) MN ti <br />N 7 <br />N V co M <br />to <br />� o 2 S <br />�s °gig W< <br />•N tL QN c <br />EM <br />TN L. o .9 <br />v a <br />W <br />W <br />�LLj vi w0LU H <br />f-Q w a! ~Z� <br />�°-J�03wc)LL0oU__jo <br />Q Q <br />U <br />j 0 Z� LL O Z <br />0wwW!2z WoommZZ <br />a Q <br />c, <br />L <br />00 <br />0 <br />Z <br />cn a www � Z U_w< <br />¢mow°g�a-FEL ZyoZgwp�o�¢ <br />(� <br />OQ o O oQZ�a <br />aLL <br />LL <br />O <br />Z N <br />OF- <br />DD 5 <br />0 F— cM O <br />Q U) tM Lo <br />U) LL^ <br />z <br />F- W cM <br />00 <br />< <br />Z V F- <br />W <br />W <br />J� <br />co <br />t <br />t <br />t <br />t <br />t <br />t <br />t <br />t <br />t <br />t <br />� <br />O <br />O <br />•- <br />O <br />N <br />O <br />N <br />O <br />O <br />N <br />N <br />O <br />100 <br />o <br />� <br />O <br />o <br />NC) <br />o <br />t <br />t <br />t <br />' <br />z <br />O <br />NL0 <br />w <br />o <br />0 <br />0 <br />0 <br />o <br />t <br />t <br />Loi <br />> <br />N <br />C6 <br />4 <br />6 <br />w <br />}~ <br />zz <br />W <br />aw <br />O <br />Q <br />w <br />Woo <br />V <br />VU(j) <br />F- <br />OWE <br />�_o <br />Z <br />WW2 <br />F— <br />ww< <br />M[tw <br />N <br />F_2 <br />N <br />w <br />6 <br />z0 <br />o= <br />� <br />QF-:) <br />N <br />O <br />zwo <br />Z <br />V <br />aCLZw <br />z <br />Z <br />F- <br />OU <br />_0 <br />W <br />z <br />1 <br />z <br />z <br />z <br />� <br />w <br />J <br />W <br />0 <br />O <br />LAST PLOT DATE <br />• <br />July 21, 2022 <br />z <br />0 <br />J <br />2ND FLOOR <br />ELECTRICAL PLAN <br />