<br />Notes:
<br />Branch Panel: C
<br />Location:
<br />Supply From:
<br />Mounting: Recessed
<br />Enclosure: Type 1
<br />Volts: 120/240 Single
<br />Phases: 1
<br />Wires: 3
<br />A.I.C. Rating: 10,000
<br />Mains Type: MLO
<br />Mains Rating: 150 A
<br />MCB Rating: 150 A
<br />CKT
<br />Circuit Description
<br />Trip
<br />Poles
<br />A
<br />B
<br />Poles
<br />Trip
<br />Circuit Description
<br />CKT
<br />1
<br />EX CKT
<br />20 A
<br />1
<br />0 VA
<br />0 VA
<br />1
<br />20 A
<br />EX CKT
<br />2
<br />3
<br />EX CKT
<br />20 A
<br />1
<br />0 VA
<br />0 VA
<br />1
<br />20 A
<br />EX CKT
<br />4
<br />5
<br />EX CKT
<br />20 A
<br />1
<br />0 VA '
<br />0 VA
<br />1
<br />20 A
<br />EX CKT
<br />6
<br />7
<br />EXISTING RECEPTACLES
<br />20 A
<br />1
<br />1080 VA
<br />' 0 VA
<br />1
<br />20 A
<br />EX CKT
<br />8
<br />9
<br />EX CKT
<br />20 A
<br />1
<br />0 VA
<br />0 VA
<br />1
<br />20 A
<br />EX CKT
<br />10
<br />11
<br />EXIST HVAC CKT
<br />45 A
<br />2
<br />0 VA
<br />0 VA
<br />2
<br />30 A
<br />EXIST WH
<br />12
<br />13
<br />--
<br />--
<br />--
<br />0 VA
<br />0 VA
<br />--
<br />--
<br />--
<br />14
<br />15
<br />EX CKT
<br />20 A
<br />1
<br />0 VA
<br />800 VA
<br />1
<br />20 A
<br />REFRIGERATOR
<br />16
<br />17
<br />EXIST CONF ROOM LTG CKT
<br />20 A
<br />1
<br />800 VA
<br />600 VA
<br />1
<br />20 A
<br />PHARMACY UC REF
<br />18
<br />19
<br />PHARMACY RECEP
<br />20 A
<br />1
<br />360 VA
<br />540 VA
<br />1
<br />20 A
<br />PHARMACY RECEP
<br />20
<br />21
<br />PHARMACY RECEP
<br />20 A
<br />1
<br />720 VA
<br />900 VA
<br />1
<br />1
<br />20 A I
<br />PHARMACY RECEP
<br />22
<br />23
<br />PHARMACY RECEP
<br />20 A
<br />1
<br />1
<br />1720 VA
<br />0 VA
<br />--
<br />--
<br />Space
<br />24
<br />Total Load:
<br />Total Amps:
<br />2990 VA
<br />25 A
<br />3500 VA
<br />29 A
<br />Legend:
<br />Load Classification
<br />Connected Load
<br />Demand Factor
<br />Estimated Demand
<br />Panel Totals
<br />Receptacle
<br />4320 VA
<br />100.00%
<br />4320 VA
<br />Power
<br />1400 VA
<br />100.00%
<br />1400 VA
<br />Total Conn. Load:
<br />6485 VA
<br />Lighting
<br />800 VA
<br />125.00%
<br />1000 VA
<br />Total Est. Demand:
<br />6677 VA
<br />Total Conn.:
<br />27 A
<br />Total Est. Demand:
<br />28 A
<br />Notes: PROVIDE ADDITIONAL BRANCH CIRCUIT BREAKERS TO MATCH EXISTING FOR CIRCUITS 16, 18, 19, 20, 21, 22 AND 23.
<br />YWAP f
<br />ELECTRICAL PLAN
<br />1 /4" = 1 '-0"
<br />C-23
<br />LC
<br />�m � `
<br />C-22(D
<br />PULI MIDC no I n\A/ Wnl TA(-C
<br />CAB
<br />REC
<br />TYPICAL FOR FLOOR PLAN DESIGNATION
<br />LOW VOLTAGE BACKBOX AND RACEWAY DETAIL
<br />1211 = 1'-0"
<br />rl rP1Tr11/'1 A 1 IZr\/A 1/1Tre1
<br />- C L_ C V I rl I V t_% L_ r\ IE= T I V lJ I C J
<br />OEXISTING PANEL. PROVIDE ADDITIONAL 20A/1 P CIRCUIT BREAKERS TO MATCH EXISTING.
<br />OEXISTING RECEPTACLE TO REMAIN.
<br />OMAINTAIN AND RELOCATE EXISTING LIGHTING CONTROLS.
<br />- r vvv L__n
<br />SINGLE RECEPTACLE
<br />DUPLEX RECEPTACLE
<br />n
<br />DUPLEX RECEPTACLE -GFCI
<br />DUPLEX RECEPTACLE - GFCI W/ WEATHERPROOF IN USE COVER
<br />0
<br />D�
<br />DUPLEX RECEPTACLE - ABOVE SHOW WINDOW
<br />DOUBLE DUPLEX RECEPTACLE
<br />n
<br />DOUBLE DUPLEX RECEPTACLE - GFCI
<br />DOUBLE DUPLEX RECEPTACLE FLOOR BOX
<br />DUPLEX RECEPTACLE FLOOR BOX
<br />C
<br />DUPLEX RECEPTACLE CEILING MOUNTED
<br />aDATA
<br />OUTLET
<br />FZ)]
<br />DATA OUTLET- FLOOR BOX
<br />$ LV
<br />LOW VOLTAGE DIGITAL DIMMING SWITCH
<br />$ OS
<br />WALL BOX LINE VOLTAGE OCC SENSOR DIMMING SWITCH
<br />$ M(P)
<br />FRACTIONAL HORSEPOWER MANUAL MOTOR STARTER WITH
<br />OVERLOADS FOR MOTOR ("P" INDICATES PILOT LIGHT)
<br />OS
<br />CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR
<br />OS
<br />WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR
<br />DISCONNECT SWITCH - NONFUSED
<br />DISCONNECT SWITCH - FUSED
<br />MOTOR STARTER - COMBINATION TYPE C/B WITH CIRCUIT
<br />SIZE AND
<br />BREAKER, F = FUSED SWITCH, NF = NONFUSED
<br />No. OF
<br />DISCONNECT SWITCH
<br />POLES
<br />B
<br />ENCLOSED CIRCUIT BREAKER TYPE DISCONNECT SWITCH
<br />INDICATED
<br />ON PLANS
<br />Z (P)
<br />MANUAL MOTOR STARTER (1 HP AND ABOVE)
<br />("P" INDICATES PILOT LIGHT)
<br />MAGNETIC CONTACTOR OR MOTOR STARTER
<br />WAPaWIRELESS
<br />ACCESS POINT DATA OUTLET
<br />aDATA
<br />OUTLET WITH TWO CABLING DROPS
<br />TV
<br />TELEVISION OUTLET (CATV, MATV, SATV) AS INDICATED
<br />PUSH-BUTTON STATION SINGLE
<br />WM
<br />SURFACE MOUNTED RACEWAY -WI REMOLD OR EQUAL
<br />CONDUIT HOMERUN ARROW INDICATES CONDUIT AND WIRE TO BE RUN
<br />TO PANEL AS INDICATED (AMOUNT OF ARROWHEADS = AMOUNT
<br />OF CIRCUITS)
<br />PE
<br />PHOTO ELECTRIC CELL
<br />SPECIAL RECEPTACLE- TYPE AS NOTED
<br />JUNCTION BOX - SIZE AS REQUIRED
<br />T❑
<br />TRANSFORMER - SIZE AS INDICATED ON PLAN
<br />TC
<br />TIME CLOCK
<br />MOUNTING HEIGHTS
<br />1. ALL MOUNTING HEIGHTS LIST ARE TO CENTER OF DEVICE UNLESS
<br />OTHERWISE NOTED AND MUST CONFORM TO ADA, NFPA, ANSI 117.1
<br />REQUIREMENTS UNLESS OTHERWISE NOTED.
<br />2. CONTRACTOR TO VERIFY FINAL LOCATION OF ALL DEVICES WITH
<br />ARCHITECT AND/OR INTERIOR DESIGNER.
<br />3. WHERE DEVICES FALL ON TWO SURFACE FINISHES, RAISE THE
<br />DEVICE TO BE ON A SINGLE FINISH. COORDINATE WITH ARCHITECT.
<br />FIRE ALARM GONG AND BELL
<br />6-8" MAX. HT. OR 6" BELOW CLG. WHICHEVER
<br />(WALL MOUNTED)
<br />IS LOWER
<br />FIRE ALARM STROBE LIGHT & SIGNALING
<br />ENTIRE LENS IS NOT LESS THAN 80" AND
<br />DEVICES
<br />NOT GREATER 96" AFF. WHERE LOW
<br />(WALL MOUNTED)
<br />CEILINGS DO NOT PERMIT MOUNTING AT
<br />MIN. 80", DEVICE SHALL BE MOUNTED
<br />WITHIN 6" OF THE CEILING.
<br />TOP OF LIGHTING AND/OR POWER PANELS
<br />IN COMMON BUILDING SPACES TOP OF
<br />6'- 2" AFF
<br />TELEPHONE CABIN ET(MAXIMLIM)
<br />TOP OF LIGHTING AND/OR POWER PANELS
<br />4'- 6" AFF TO HIGHEST OPERABLE DEVICE
<br />IN LIVING UNITS
<br />LIGHTING SWITCH
<br />46" AFF TO CENTERLINE
<br />TOP OF BACK MOUNTED EXIT FIXTURE
<br />12" BELOW FINISHED CEILING TO CENTERLINE
<br />(NOT LOCATED ABOVE DOORS)
<br />TOP OF SAFETY DISCONNECT SWITCH,
<br />6'- 0" MAXIMUM AFF
<br />CONTACTORS, MAGNETIC MOTOR STARTERS
<br />++'
<br />6" BELOW FINISHED CEILING
<br />+'
<br />4'- 0" AFF OR 6" ABOVE COUNTER
<br />BELOW COUNTER
<br />MANUAL CONTROL DEVICES,
<br />T- 6" AFF
<br />FIRE ALARM PULL STATION, FIRE PHONE
<br />JACKS
<br />RECEPTACLES, TELEPHONE OUTLETS (DESK)
<br />1'- 6" AFF
<br />COMPUTER OUTLETS
<br />TELEVISION OUTLETS
<br />REFER TO ARCHITECTURAL DRAWINGS
<br />FINISHED FLOOR ELEV. (BASE) -
<br />0' - 0"
<br />- ELECTRICAL GENERAL NOTES
<br />1. DO NOT SCALE FROM THESE DRAWINGS.
<br />2. ALL WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH THE LOCAL AHJ,
<br />2017 NATIONAL ELECTRICAL CODE (NEC), 2020 FLORIDA BUILDING CODE (FBC)
<br />7TH EDITION, AND ALL OTHER APPLICABLE BUILDING CODES.
<br />3. ELECTRICAL CONTRACTOR SHALL COORDINATE WORK WITH ALL OTHER TRADES
<br />TO ASSURE PROPER CLEARANCES FOR EQUIPMENT AND TO KEEP THE JOB
<br />PROGRESSING.
<br />4. REFER TO MECHANICAL DRAWINGS FOR INTERLOCKING REQUIREMENTS OF
<br />MECHANICAL EQUIPMENT (MOTORS, FANS, PUMPS, ETC...). INSTALL ANY
<br />ELECTRICAL EQUIPMENT (STARTERS, RELAYS, VFD'S, ETC..) FURNISHED BY DIV.
<br />15 OR OWNER.
<br />5. ALL CEILING MOUNTED ITEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE
<br />ARCHITECTURAL REFLECTIVE CEILING PLANS. IF LOCATION FOR AN ITEM IS NOT
<br />SHOWN ON THE ARCHITECTURAL REFLECTIVE CEILING PLANS, VERIFY THE
<br />EXACT LOCATION OF THE ITEM WITH THE ARCHITECT PRIOR TO INSTALLATION.
<br />THESE REQUIREMENTS APPLY TO ALL CEILING TYPES IN ALL AREAS.
<br />6. WHERE NON -FUSED DISCONNECT IS NOT PROVIDED "WITHIN SIGHT" OF MOTOR
<br />(OR HEATER UNIT). FEEDER (AND/OR BRANCH CIRCUIT) OVER -CURRENT DEVICE
<br />SERVING SUCH MOTOR (OR HEATER) SHALL HAVE APPROVED "LOCKED -OFF"
<br />PROVISION.
<br />7. PROVIDE WALL SWITCHES AND/OR MOTION SENSORS IN EACH OFFICE/AREA TO
<br />CONTROL THE LIGHT FIXTURE(S) IN EACH OFFICE/AREA.
<br />8. REFERENCE MECHANICAL DRAWINGS FOR ALL MECHANICAL EQUIPMENT
<br />NEEDING ELECTRICAL CONNECTIONS. MAKE ALL CONNECTIONS AND PROVIDE
<br />APPROPRIATE WIRE CONDUIT AND OVERCURRENT PROTECTION FOR ALL
<br />EQUIPMENT. COORDINATE EXACT REQUIREMENTS WITH MECHANICAL
<br />CONTRACTOR.
<br />9. PROVIDE EXIT SIGNAGE AT ALL EXITS AND EGRESS PATHS AS REQUIRED OR AS
<br />SHOWN ON LIFE SAFETY PLANS.
<br />10. ALL EXTERIOR WIRING DEVICES TO BE WEATHERPROOF AND GROUND
<br />FAULT INTERRUPTING TYPE RECEPTACLES.
<br />11. REFER TO ARCHITECTURAL FLOOR PLANS FOR DIMENSIONAL LOCATIONS OF ALL
<br />FLOOR MOUNTED ELECTRICAL DEVICES.
<br />12. CONDUIT RUNS SHOWN ARE DIAGRAMMATIC IN NATURE. CONTRACTOR IS
<br />RESPONSIBLE FOR SIZING AND LOCATING PULL BOXES PER NEC AND FOR
<br />COORDINATION WITH OTHER DISCIPLINES.
<br />13. COORDINATE EXACT LOCATIONS OF ALL ITEMS INSTALLED ON SITE WITH CIVIL
<br />ENGINEER.
<br />14. COORDINATE ALL LOCATIONS OF RECEPTACLES AND SYSTEMS OUTLETS WITH IN
<br />ALL CASEWORK. WIRE TYPE THHN/THWN, MINIMUM SIZE #12.
<br />15. USE No. 10 AWG CU. CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH CIRCUITS
<br />LONGER THAN 200 FEET. (MAXIMUM 3 % VOLTAGE DROP)
<br />16. USE CONDUCTOR NOT SMALLER THAN NO. 10 AWG TO HOME RUN JUNCTION
<br />BOXES FOR LINE POWER RECEPTACLES. (MAXIMUM 3 % VOLTAGE DROP)
<br />17. USE NO. 10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS
<br />LONGER THAN 75 FEET, OR LARGER IF NOTED. (MAXIMUM 3 % VOLTAGE
<br />DROP)
<br />18. ALL SITE LIGHTING POLES AND POLE BASES SHALL BE CAPABLE OF SUPPORTING
<br />THE ENTIRE WEIGHT AND WIND LOADS OF THE ENTIRE LIGHTING SYSTEM. SHOP
<br />DRAWINGS MUST INCLUDE DRAWINGS OF THE ENTIRE ASSEMBLY FOR EACH OF
<br />THE MOUNTING CONFIGURATIONS USED. DRAWINGS MUST BE SIGNED AND
<br />SEALED BY FLORIDA REGISTERED STRUCTURAL ENGINEER AND SUBMITTED TO
<br />THE LOCAL AHJ FOR REVIEW AND APPROVAL PRIOR TO INSTALLATION AS A
<br />REVISION TO THE PERMIT.
<br />19. EXIT AND EMERGENCY LIGHTS SHALL BE WIRED ON LINE SIDE OF CONTACTORS,
<br />MOTION SENSORS AND ANY LOCAL SWITCHES.
<br />20. ALL CONDUITS SHALL BE ROUTED SURFACE ON STRUCTURE WITH FS OUTLET
<br />BOXES / CONCEALED IN WALL FUR OUT, ABOVE DROPPED CEILING OR
<br />UNDERGROUND (PREFERRED UNDERGROUND FOR NEW CONSTRUCTION) IN
<br />FINISHED AREAS.
<br />21. TOGGLE SWITCHES SHALL BE MOUNTED CENTERLINE 46" A.F.F. AND 6" FROM
<br />DOOR OPENING OR CORNER, UNLESS OTHERWISE NOTED.
<br />22. NO MORE THAN THREE CURRENT CARRYING CONDUCTORS SHALL BE COMBINED
<br />IN ANY RACEWAY LION.
<br />23. REFER TO THE SPECIFICATIONS AND NOTES OF THIS PROJECT FOR MORE
<br />DETAILED INSTRUCTIONS.
<br />24. LIGHTING SCHEDULE IS FOR REFERENCE ONLY. THE CONTRACTOR SHALL
<br />SUBMIT THE TYPES AND MODEL NUMBERS TO THE ARCHITECT FOR APPROVAL
<br />BEFORE PURCHASING.
<br />25. ALL PATTERNED DOWNLIGHT TRIMS TO BE COORDINATED TO ENSURE
<br />CONSISTENT PATTERN DIRECTION BY CONTRACTOR.
<br />26. ALL RECESSED ADJUSTABLE DOWNLIGHTS MUST BE AIMED BY CONTRACTOR
<br />AND CLOSELY COORDINATED WITH THE DEALER FOR VEHICLE ACCENT,
<br />CUSTOMER GRAPHICS, AND DISPLAYS.
<br />27. PROVIDE EMERGENCY BATTERY PACK FOR LUMINAIRES DESIGNATED AS
<br />EMERGENCY. CONNECT ON LINE SIDE OF ALL SWITCHES AND CONTACTORS.
<br />28. PROVIDE GROUND FAULT INTERRUPTER FOR ALL 125 VOLT, 15 & 20 AMP
<br />RECEPTACLES WITHIN T-0" OF A SINK, AND IN THE SERVICE GARAGE AREAS PER
<br />NEC 511.
<br />29. ALL RECESSED LIGHTS IN INSULATED AREAS SHALL BE I.C. RATED.
<br />30. ALL CONDUCTORS SHALL BE COPPER TYPE THHN/THWN UNLESS OTHERWISE
<br />NOTED.
<br />31. ALL LIGHTING SHALL BE LED, 0-10V DIMMABLE, UON. ALL LIGHTING SHALL BE
<br />DIMMABLE.
<br />32. FRONT OF HOUSE WIRING DEVICES SHALL BE LEVITON DECORA, WHITE OR
<br />BLACK TO MATCH ADJACENT WALL, WITH WHITE OR BLACK SCREWLESS
<br />FACEPLATES TO MATCH ADJACENT WALL, OR PRE -APPROVED EQUAL.
<br />33. BACK OF HOUSE WIRING DEVICES SHALL BE LEVITON, SPECIFICATION GRADE.
<br />34. GFCI TYPE RECEPTACLES SHALL BE INSTALLED IN A READILY ACCESSIBLE
<br />LOCATION PER NEC 210.8. PROVIDE GFCI TYPE CIRCUIT BREAKERS WHERE GFCI
<br />TYPE RECEPTACLES ARE NOT READILY ACCESSIBLE.
<br />35. EMERGENCY LIGHTING SHALL BE PROVIDED BY U.L. LISTED BATTERY BACKUP
<br />EMERGENCY BALLASTS THAT PROVIDE A MINIMUM OF 90 MINUTES BACKUP
<br />POWER IN ACCORDANCE WITH FFPC 101:36.2.9.
<br />- NEC ARTICLE 517 COMPLIANCE
<br />1. TYPE HCF MC CABLE SHALL BE USED IN ALL PATIENT CARE AREAS.
<br />2. PROVIDE HOSPITAL GRADE TAMPER PROOF RECEPTACLES IN ALL PATIENT
<br />CARE AREAS.
<br />3. ALL BRANCH CIRCUITS SERVING PATIENT CARE AREAS SHALL BE PROVIDED
<br />WITH AN EFFECTIVE GROUND FAULT CURRENT PATH PER NEC 517.13(A)(B).
<br />COMPLETION REQUIREMENTS
<br />CONTRACTOR SHALL SUBMIT TO THE BUILDING OWNER RECORD DRAWINGS OF THE
<br />ACTUAL INSTALLATION WITHIN 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE.
<br />RECORD DRAWINGS SHALL INCLUDE: 1). A SINGLE LINE DIAGRAM OF THE BUILDING
<br />ELECTRICAL DISTRIBUTION SYSTEM AND 2). FLOOR PLANS INDICATING LOCATION AND
<br />AREA SERVED FOR ALL DISTRIBUTION.
<br />CONTRACTOR SHALL SUBMIT AN OPERATION AND MAINTENANCE MANUAL TO THE
<br />BUILDING OWNER. THE MANUALS SHALL INCLUDE, AT A MINIMUM, THE FOLLOWING:
<br />1). SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH
<br />PIECE OF EQUIIPMENT REQUIRING MAINTENNANCE; 2). OPERATION MANUALS AND
<br />MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE.
<br />REQUIRED ROUTINE MAINTENANCE ACTIONS CLEARLY IDENTIFIED; 3). NAMES AND
<br />ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY.
<br />CONTRACTOR SHALL SUBMIT TO THE BUILDING OWNER DOCUMENTS CERTIFYING
<br />THAT THE INSTALLED LIGHTING CONTROLS HAVE BEEN INSTALLED IN ACCORDANCE
<br />WITH THESE DRAWINGS AND MEET DOCUMENTED PERFORMANCE CRITERIA OF 2020
<br />FBC ENERGY CONSERVATION CODE, SECTION C405, WITHIN 90 DAYS FROM THE DATE
<br />OF RECEIPT OF THE CERTIFICATE OF OCCUPANCY.
<br />PRIOR TO PASSING FINAL INSPECTION, THE REGISTERED DESIGN PROFESSIONAL
<br />SHALL PROVIDE EVIDENCE THAT THE LIGHTING CONTROLS HAVE BEEN TESTED TO
<br />ENSURE THAT CONTROL HARDWARE AND SOFTWARE ARE CALIBRATED, ADJUSTED,
<br />PROGRAMMED AND IN PROPER WORKING CONDITION IN ACCORDANCE WITH THE
<br />CONSTRUCTION DOCUMENTS AND MANUFACTURER'S INSTRUCTIONS. FUNCTIONAL
<br />TESTING SHALL BE IN ACCORDANCE WITH SECTION C408.3.1.1 AND C408.1.2 FOR THE
<br />APPLICABLE CONTROL TYPE.
<br />THIS DRAWING AND THE DESIGN SHOWN ARE THE PROPERTY OF
<br />SPRING ENGINEERING, INC. AND ARE NOT TO BE REPRODUCED,
<br />COPIED, PUBLISHED, OR USED IN WHOLE OR PART WITHOUT
<br />WRITTEN CONSENT. THEY ARE TO BE USED ONLY FOR THE SITE AND
<br />PROJECT IDENTIFIED AND SHALL BE RETURNED UPON REQUEST.
<br />FOR
<br />CONSTRUCTION
<br />ISSUE DATE: 06.24.2022
<br />z
<br />O
<br />a-
<br />U
<br />W
<br />w
<br />0
<br />w
<br />0
<br />w
<br />M
<br />� � • � �CEN
<br />No.60205 =
<br />itally signed by Carlos ail s
<br />J&c=US, e0kiwimiral Pq'
<br />d 'sxislnc'4ORIVP.
<br />r-A'0141 8 E
<br />7E8os M
<br />Orama
<br />Date: 2022.10.05 10:22:48 -04'0('
<br />W
<br />�aJ
<br />w
<br />LU0
<br />F_
<br />U)�
<br />Q W Cc
<br />W
<br />_ U co
<br />LU Q LU _
<br />It _
<br />Q COI
<br />am Oa
<br />V
<br />LU
<br />CONTRACT DATE:
<br />t
<br />W
<br />q
<br />E
<br />z
<br />ZZ
<br />l
<br />Rz
<br />z
<br />Lil
<br />LL,w
<br />Z
<br />a�
<br />-A
<br />s�
<br />0
<br />0
<br />z
<br />(D
<br />(D
<br />_j
<br />�z
<br />0
<br />ELECTRICAL
<br />PLANS
<br />DESIGNED BY: Designer
<br />DRAWN BY: Author
<br />CHECKED BY: Checker
<br />JOB NO.
<br />2022-16
<br />SHEET NO.
<br />E001