<br />BRING RIGID PIPE SLEEVE
<br />THROUGH BUILDING TO
<br />ALLOW PHONE LINE
<br />PENETRATION. SEAL ALL
<br />PENETRATIONS.
<br />3/4" PLYWOOD 8'-9" WIDE X 5-5" HIGH, FIRE
<br />RATED, NO VOIDS, PAINTED WHITE UNLESS
<br />/'`!ll"1C (•11 /'•TA TCC 11TLJCD\A/ICC
<br />THROUGH, WALL' SEE ELECTRICAL
<br />SPECIFICATION NOTE 'E' AND 'H'.
<br />ELECTRICAL PANEL ELEVATION
<br />BUZZER
<br />PUSH BUTTON
<br />BUZZER,
<br />A/4
<br />RECEIVING AREA
<br />103
<br />5
<br />PROVIDE
<br />NEMA L14-20R
<br />RECEPTACLE
<br />PROVIDE TOGGLE
<br />20 TOE
<br />SWITCH AT WATER
<br />HEATER. A/21
<br />Scale: NTS
<br />TO RTU-1
<br />4 O
<br />GFCI,
<br />WP,A/10
<br />RTU-1 DD
<br />O O
<br />A/1,3,5
<br />VERIFY ACTUAL HVAC
<br />ELECT. REQUIREMENTS
<br />WITH CONTRACTOR. (TYP).
<br />11
<br />3 DR, LOW TEMP
<br />2#10,1 #1O(G), 3/4"C
<br />A/27,29
<br />11
<br />4 DR, LOW TEMP
<br />2#8,1#1O(G), 3/4"C
<br />A/31,33
<br />�I
<br />LOW VOLTAGE VENDOR TO PROVIDE AND INSTALL ONE (1) 24 GA., 4
<br />TWISTED -PAIR, CATEGORY -FIVE (CAT5) DATA CABLE WITH MODULAR COMBO
<br />RJ-11/ RJ-45 JACK AT MANAGERS OFFICE. CABLE TO BE RUN FROM JACK
<br />TO DATA HUB LOCATION WITH 6' LEFT COILED FOR INSTALLATION TO DATA HUB.
<br />A RJ-45 MALE FITTING SHOULD BE CRIMPED ON THIS END, DOLLAR GENERAL
<br />STORE OPENING TEAM WILL MAKE FINAL CONNECTION INTO THE DATA HUB. -�
<br />SALES AREA
<br />102
<br />9 SO CORD (WHITE). ANCHOR
<br />TO PURLINS ABOVE. REFER
<br />TO ARCHITECTURAL PLANS
<br />FOR DIMENSIONS. (TYPICAL)
<br />B/36
<br />10
<br />B/36 �
<br />DEDICATED QUAD
<br />RECEPTACLE ® 3'-0"
<br />FOR CCTV EQUIPMENT
<br />DEDICATED QUAD
<br />RECEPTACLE Q 3'-0"
<br />3
<br />OFFICE
<br />`
<br />I
<br />A/26 101
<br />A/24
<br />O
<br />A/22
<br />VS
<br />A/18
<br />A/26 A/26
<br />A/28
<br />_ sw
<br />A/20
<br />SECURITY OUTLET
<br />AT 7'-0"
<br />DEDICATED DUPLEX RECEPTACLE
<br />@48" FOR INTERFACE EQUIPMENT.
<br />DEDICATED QUAD RECEPTACLE
<br />6'-0" FOR VSAT AND
<br />D-LINK EQUIPMENT
<br />ENLARGED OFFICE POWER PLAN
<br />SCALE 1/4" = V-0"
<br />RESTROOM EXHAUST FAN. B/21
<br />CONNECT TO ROOM SENSOR
<br />LIGHT CONTROL SWITCH.
<br />0
<br />GFCI
<br />A/23
<br />RESTROOM EXHAUST FAN.
<br />CONNECT TO ROOM SENSOR
<br />LIGHT CONTROL SWITCH.
<br />A/32 B/21
<br />TO RTU-2 T
<br />A/28 sw
<br />6O
<br />� � A/30
<br />4 O A/34 VS sw
<br />GFCI, A/28
<br />A/30 A/28WP,A/10 $A/30
<br />-sw DID A/7,9,11
<br />CNJ
<br />REFER TO REGISTER
<br />POWER POLE SO44
<br />DETAIL 3/E4. B/2,4,6,8,10,12.
<br />XI
<br />A/34,r,°
<br />B/14
<br />7' 8 1/2" 10'-3" 10'-5 1/2" 12'-9 1/2" 12'-8 3/4"
<br />OFFICE
<br />rA/36 101
<br />_ t
<br />I—,
<br />AUTOMATIC
<br />DOOR A/2 -
<br />2'-3" A/38
<br />4'-5" 4'-4"
<br />F
<br />A/12
<br />J
<br />1
<br />11
<br />4 DR, LOW TEMP 5 DR, MID TEMP 4 DR, MID TEMP
<br />2#8,1#10(G), 3/4"C 2#12,1#12(G), 3/4"C 2#12,1#12(G), 3/4"C
<br />B/22,24 B/26,28 B/30,32 02
<br />POWER PLAN
<br />Scale: 1/8" = V-0"
<br />LEGEND
<br />g
<br />BUZZER - TORK MDL #TA725 W/
<br />TRANSFORMER MDL#TA592
<br />PUSH BUTTON
<br />125V NEMA 5-20R DUPLEX.
<br />A/23
<br />PANEL/CIRCUIT IN PANEL
<br />(sw
<br />125V NEMA 5-20R DUPLEX.
<br />A/28
<br />SPLIT WIRED.
<br />A/ 0
<br />PAN`EL/CIRCUIT IN PANEL
<br />0
<br />JUNCTION BOX
<br />125V NEMA 5-20R QUAD.
<br />VACANCY SENSOR:
<br />GREENGATE DUAL TECH
<br />LOW VOLTAGE #VAC-DT-0501-R
<br />OR EQUAL. PROVIDE WITH
<br />SWITCH PACK.
<br />T
<br />TEMPERATURE SENSOR:
<br />BY MECHANICAL
<br />LEI
<br />DISCONNECT
<br />O
<br />BLACK MAGIC POWER POLE
<br />PHONE JACK @ REGISTER
<br />O
<br />VOICE/DATA PORT = RJ-11,
<br />RJ-45 DATA JACK, PHONE
<br />COMBO @ OFFICE
<br />A/23
<br />PANEL/CIRCUIT IN PANEL
<br />MOTION SENSOR SWITCH.
<br />m
<br />LEVITON #EZ-FIND-ODS-10-IDW
<br />20 AMP TOGGLE SWITCH
<br />NL
<br />NIGHT LIGHT CIRCUIT
<br />GENDER
<br />NEUTRAL
<br />104
<br />j
<br />HRUVIUE I UUULE
<br />SWITCH AT RESTROOM
<br />WATER HEATER. A/19
<br />GENDER
<br />NEUTRAL
<br />105
<br />DEDICATED GFCI,WP, 20AMP
<br />OUTLET RECESSED @ 4' A.F.F
<br />FOR ICE MERCHANDISER,
<br />BREAKROOM 02
<br />100
<br />3
<br />E1
<br />NOTE: IF STORE IS
<br />LABELED "RELOCATED",
<br />PROVIDE J BOX
<br />OVER ENTRY DOORS
<br />FOR CCTV.
<br />C
<br />ELECTRICAL SPECIFICATIONS
<br />A.
<br />ALL WIRING SHALL BE CONTAINED IN CONDUIT OF PROPER SIZE.
<br />B.
<br />ALL WIRING SHALL CONFORM TO LOCAL, STATE, AND FEDERAL CODES.
<br />C.
<br />SERVICE IS TO BE MINIMUM 400 AMP, 3 PHASE (PREFERRED) 600 AMP
<br />1 PHASE OR LARGER IF REQUIRED BY CODE OR ELECTRICAL LOAD.
<br />D.
<br />REQUIRED CUSTOM BUILT POWER POLE ASSEMBLIES AVAILABLE FROM D&P CUSTOM LIGHTS &
<br />PRODUCTS INC. PHONE: (800) 251-2200 OR (615) 350-7800, 7111 COCKRILL BEND INDUSTRIAL ROAD,
<br />NASHVILLE, TN 37209. SEE SHEET E3.
<br />E.
<br />EXTERIOR EXPOSED PHONE LINES TO BE INSTALLED IN RIDGED CONDUIT. PROVIDE EMERSON 3/4" X
<br />5-FT. METALLIC CABLE U-GUARD #755, OR EQUAL.
<br />F.
<br />ELECTRICAL PANELS TO BE LABELED CORRECTLY AND WITH LEGIBLE PRINT.
<br />G.
<br />PHONE LINES - TWO RJ-11 PORTS. ONE (1) LOCATED IN OFFICE W/RJ-45 DATA JACK COMBO AND ONE (1)
<br />AT REGISTER. 24 GA. CAT 5, 4-PAIR TWISTED WIRE ONLY. USE BLUE AND BLUE & WHITE WIRES. HOOK
<br />TO LINE #1 TERMINAL IN RJ-11 JACK EACH PHONE JACK TO HAVE DEDICATED, SEPARATE HOME RUN TO
<br />DMARC. LABEL AS "PHONE" AT THE DESTINATION AND AT DMARC. PHONE COMPANY PROVIDES FINAL
<br />HOOK UP TO DMARC ONLY. PHONE JACKS ARE SUPPLIED AND WIRED BY CONTRACTOR.
<br />H.
<br />PROVIDE 1 1/2" EMT CONDUIT TO ACT AS ACCESS SLEEVE TO ALLOW PHONE COMPANY TO TERMINATE
<br />AT DMARC. CONTRACTOR TO PROVIDE & INSTALL PHONE WIRING & RJ-11 PHONE JACK FOR A
<br />COMPLETED WORKING SYSTEM PRIOR TO PHONE COMPANY FINAL HOOK-UP.
<br />L
<br />ALL 120 VOLT OUTDOOR RECEPTACLES TO HAVE "WET LOCATION - IN USE" COVERS.
<br />J.
<br />ALL CONDUCTORS TO BE COPPER, #12 AWG MINIMUM SIZE, OR SIZE AS REQUIRED BY LOAD AND OVER
<br />CURRENT PROTECTION.
<br />K.
<br />SEE EMS SHEETS EMS1 AND EMS2 FOR ENERGY MANAGEMENT SYMBOLS AND INFORMATION.
<br />L.
<br />ELECTRICIAN TO PROVIDE 1 2" CONDUIT WITH PULL STRING FOR SATELLITE LINE. REFER TO 3/A3 AND
<br />1/S1 FOR LOCATION.
<br />M.
<br />ALL POWER AND DATA TO BE ROUTED OVERHEAD. UNDER SLAB IS NOT ALLOWED.
<br />N.
<br />VERIFY WIRE SIZE REQUIREMENTS FOR ALL COOLERS AND FREEZERS.
<br />O.
<br />MOUNT ALL REFRIGERATOR OUTLETS AT 12" AFF UNLESS NOTED.
<br />P.
<br />WIRE SIZES SHALL BE BASED ON THE 60 DEGREE CELSIUS AMPACITIES FOR WIRE SIZES #14 THRU
<br />#1 AWG AND 75 DEGREES CELSIUS FOR WIRE SIZES #1/0 AND LARGER.
<br />Q.
<br />BRANCH CIRCUIT WIRE SIZES AND CONDUITS SHALL BE INCREASED FROM THOSE INDICATED ON THE
<br />PLANS AS REQUIRED TO PREVENT EXCESS VOLTAGE DROP. BRANCH CIRCUITS $HALL BE INSTALLED
<br />WITH WIRES OF SUFFICIENT SIZE SO THAT THE VOLTAGE DROP BETWEEN THE PANEL AND THE LOAD
<br />DOES NOT EXCEED 3% TO MEET FLORIDA'S BUILDING CODE, ENERGY CODE PART C405.7.
<br />IF ELECTRICAL KEYED NOTES
<br />1� TEST/RESET STATION FOR STAND ALONE DUCT DETECTOR. ONE FOR EACH DEVICE. SEE KEY
<br />NOTE 2 ON THIS SHEET. SIMPLEX #4098-9842 IS SPECIFIED WITH PIEZO AND LED INDICATOR.
<br />O LOCATION SHOWN FOR MECHANICAL UNITS ARE ONLY APPROXIMATE. CONTRACTOR SHALL
<br />CONSULT MECHANICAL AND STRUCTURAL DRAWINGS TO DETERMINE ACTUAL UNIT LOCATIONS.
<br />PROVIDE 1/2" PENETRATION THRU ROOF WITHIN FOOTPRINT OF UNIT FOR USE WITH CONTROL
<br />WIRING TO UNIT BY OTHERS. PROVIDE PROPER WATERSEAL (TYPICAL).
<br /><3> FACTORY MOUNTED POWERED CONVENIENCE OUTLET. FIELD VERIFY THAT OUTLET IS POWERED.
<br />PROVIDE WP, GFCI RECEPTACLE AT ALL UNITS AND WIRE TO BREAKER IN PANEL "A" IF THEY ARE
<br />NOT FACTORY PROVIDED.
<br />® PHOTOELECTRIC DUCT DETECTOR WITH HOUSING. TIE TO LED READOUT RECESSED IN DUCT STAND
<br />ALONE DEVICE, 120V. SIMPLEX #4098-9687 IS SPECIFIED WITH 4098-9842 CONTROL STATION. PROVIDE
<br />ONE DEVICE PER UNIT. MOUNT DEVICE IN SUPPLY AIR DUCTWORK. DEVICE SHALL BE PROVIDED AND
<br />WIRED TO THE CONTROL STATION BY THE ELECTRICAL CONTRACTOR. HIRE THE MECHANICAL
<br />CONTRACTOR FOR INSTALLATION IN DUCTWORK AND CONNNECTION TO SHUT DOWN CONTROLS.
<br />ELECTRICAL CONTRACTOR SHALL PROVIDE ALL REQUIRED RELAYS AND 120V POWER. DO NOT POWER
<br />DUCT DETECTORS FROM HVAC LOW VOLTAGE. SUBMIT SHOP DRAWINGS FOR APPROVAL. PLACE ANY
<br />REQUIRED LABELING ON CEILING TILE DIRECTLY BELOW UNIT.
<br /><�> MOUNT DISCONNECT SWITCH AT UNIT. ALL DISCONNECTS SHALL BE HEAVY DUTY.FUSES TO BE TYPE
<br />RK-5 TYPE. BUSSMAN FRN-R-(AMP) FUSES ARE SPECIFIED.
<br />© MECHANICAL THERMOSTAT AT 8'-0" AFF.
<br />VACANCY SENSOR. SENSOR SHALL CONTROL LIGHTS AND TOP HALF OF THE DUPLEX RECEPTACLES
<br />INDICATED AS SPLIT WIRED, (A/28).
<br />< SPLIT WIRED RECEPTACLES. CIRCUIT A/30 SHALL BE 'ALWAYS ON', CIRCUIT A/28 SHALL BE
<br />CONTROLLED BY THE VACANCY SENSOR. RECEPTACLE SECTIONS THAT ARE AUTOMATICALLY
<br />CONTROLLED SHALL BE PERMANENTLY MARKED PER ASHRAE STANDARDS.
<br />SO WHITE ELECTRICAL CORD IS REQUIRED. SEE SHEET Al, NOTE 25 AND 25A.
<br />CONFIRM THE FINAL NUMBER AND LOCATION OF OUTLETS IN THE SALES AREA WITH THE FINAL
<br />DOLLAR GENERAL FIXTURE PLAN.
<br />PROVIDE JUNCTION BOX MOUNTED AT 90" AFF. COORDINATE WITH COOLER/FREEZER VENDOR
<br />FOR MANUFACTURER'S REQUIREMENTS.
<br />CONSULTANT:
<br />SEAL: SEAN PATRICK PIC-KELL, PE 83946
<br />QP.�FtICK p�0 ,,i
<br />�,� �\� 83946 `�
<br />zap. No
<br />�A STATE OF
<br />THIS DRAWING SHALL NOT BE USED FOR
<br />CONSTRUCTION PURPOSES UNTIL THE SEAL AND
<br />SIGNATURE OF THE RESPONSIBLE REGISTRANT
<br />APPEARS ON THE DRAWING, AND PROPER PERMIT
<br />FORMS AND RELATED FEES ARE TRANSMITTED BY
<br />THE OWNER, OWNER'S AGENT OR CONTRACTOR
<br />TO THE AUTHORITY HAVING JURISDICTION.
<br />DATE
<br />ISSUED FOR
<br />REV
<br />09/27/201 8
<br />PEMB COORDINATION
<br />12/18/2018
<br />PERMIT SUBMITTAL
<br />01 /1 1 /201 9
<br />OWNER REVIEW
<br />02/07/2019
<br />BID SET
<br />03/04/2019
<br />ADDENDUM 01
<br />06/07/2019
<br />BULLETIN 01
<br />02
<br />Project Manager
<br />Drawn
<br />L. LONG
<br />G. COLLINS
<br />Project Leader
<br />Checked
<br />L. LONG
<br />M. GOOD
<br />Date
<br />Dept Mgr Approval
<br />08/07/2018
<br />M. GOOD
<br />Client
<br />PALMETTO ZEPHYRHILLS-20th St, LLC
<br />P.O. BOX 1615
<br />THOMASVILLE, GA 31 792
<br />Office: (229) 226-0682
<br />Contact: John Tate
<br />Project
<br />DOLLAR GENERAL
<br />38965 CR 54
<br />Zephyrhills, FL 33542
<br />(City of Zephyrhills)
<br />Store #: 20360
<br />Drawing Title
<br />POWER PLAN
<br />DO NOT SCALE DRAWING
<br />Project No.
<br />Drawing No.
<br />.JCDT.18.0233
<br />E1