Laserfiche WebLink
AI <br />( <br />FIRE ALARM SPECIFICATIONS & GENERAL NOTES <br />HVAC WIRING GENERAL NOTES <br />1. DUCT DETECTOR RELAY WIRING SHALL BREAK 24VOLT <br />ELECTRICAL MOUNTING BOX <br />I. GENERAL SCOPE: <br />COIL <br />SECONDARY CONTROL SYSTEM POWER AT THE AIR <br />FOR THE CEILING MOUNTED <br />HANDLER UNIT. <br />NOTIFICATION DEVICES. <br />A. THIS PROJECT WILL REQUIRE THE INSTALLATION OF A NEW FIRE ALARM SYSTEM FOR A RETAIL OUTLET STORE. THE EXISTING SYSTEM WILL BE REMOVED. AS INDICATED ON THESE <br />2. IF ADDRESSABLE DUCT DETECTORS ARE USED, THE <br />PLANS, BEALLS/BURKES REQUIRES THE INSTALLATION OF A DIGITAL MONITORING PRODUCTS (DMP) XR150DNFC-R SYSTEM. THE PANEL/SYSTEM SPECIFIED IS REQUIRED BY THE OWNER <br />RELAY WILL BE NORMALLY CLOSED DURING <br />IN ORDER TO MAINTAIN CONSISTENCY THROUGHOUT THEIR STORES. DEVIATIONS WILL NOT BE ACCEPTED UNLESS APPROVED, IN WRITING, BY BEALLS/BURKES CONSTRUCTION MANAGER. <br />NON -ALARM CONDITIONS AND OPEN UPON ALARM <br />TO CAUSE A POWER LOSS D THE HVAC CONTROL <br />/ <br />BLOWER RELAY <br />CIRCUIT, RESULTING IN FAN AND COMPRESSOR <br />PROVIDE BATTERIES AS REQUIRED BY THE FIRE ALARM BATTERY CALCULATIONS. <br />SHUTDOWN. <br />c <br />PROVIDE BATTERIES AS REQUIRED BY THE POWER SUPPLY EXPANDER CALCULATIONS. <br />0 <br />3. IF CONVENTIONAL RELAYS (NON -ADDRESSABLE) ARE <br />c <br />000 <br />THE RELAY SHALL BE NORMALLY OPEN <br />o <br />II. REQUIREMENTS: <br />cu <br />(SED, <br />UNPOWERED) AND SHALL BE HELD CLOSED BY THE <br />vt� FROM THERMOSTAT <br />FIRE ALARM PANEL UNTIL THE DUCT SMOKE <br />�o <br />DETECTOR IS IN AN ALARM CONDITION. <br />A. THE INSTALLATION SHALL CONFORM TO THE INTENT OF NFPA 72 (2010 ED.), THESE PLANS, AND APPLICABLE REFERENCED DOCUMENTS. <br /><w <br />FUSE z� <br />4. IN SYSTEMS PROVIDED WITH A FAN SHUTDOWN DELAY <br />B. SECONDARY POWER SHALL CONSIST OF RECHARGEABLE BATTERIES HAVING A CAPACITY TO POWER THE ALARM SYSTEM FOR A PERIOD OF 24 HOURS IN A STANDBY MODE AND OPERATE <br />oQ <br />CIRCUIT, A PROGRAMMABLE RELAY SHALL BE <br />PROVIDED IN SERIES WITH THIS EQUIPMENT TO <br />ALL NOTIFICATION APPLIANCES FOR 5 MINUTES AT THE END OF THE 24 HOUR PERIOD. <br />raw <br />BREAK THE CIRCUIT ON ADDRESSABLE SYSTEMS OR <br />"CADDY" T-GRID BOX <br />HANGER o <br />W]L <br />PROVIDED WITH A NORMALLY OPEN RELAY THAT IS <br />SUPPORT, OR EQUAL. <br />"CADDY" <br />C. ALL CIRCUITS SHALL BE "POWER LIMITED". THE CIRCUIT TYPES SHALL BE INSTALLED AS INDICATED BELOW: <br />AHU STEP DOWN 00 <br />TRANSFORMER �ai <br />HELD CLOSED DURING NORMALLY SYSTEM OPERATION <br />ON CONVENTION SYSTEMS. <br />REFERENCE NO. CEC 30-302( 3) <br />INITIATION DEVICE CIRCUITS (IDC'S): CLASS "B" <br />U <br />ACOUSTICAL TILE CEILING <br />NOTIFICATION ALARM CIRCUITS (NAC'S): CLASS "B" <br />JQ <br />GRID SUPPORT FRAMING. <br />D. WALL -MOUNTED NOTIFICATION HORN/STROBES ARE TO BE MOUNTED SO THAT THE ENTIRE LENS OF THE DEVICE IS NO LESS THAT 80" AFF AND NO GREATER THAN 96" AFF. <br />ff <br />oW <br />CEILING -MOUNTED NOTIFICATION DEVICES ARE TO BE MOUNTED AT A MAXIMUM HEIGHT OF 30 FT. (AS INDICATED ON THE PLANS) <br />zL_ <br />E. ALL NEW PULL STATIONS SHALL BE INSTALLED AT 48 INCHES ABOVE THE FINISH FLOOR. <br />F.NG CONNECTIONS ARE TO BE IN SINGLE, DOUBLE, TRIPLE OR 4 INCH ELECTRICAL BOXES, AS NEEDED. WIRING CONNECTIONS OUTSIDE OF ELECTRICAL BOXES WILL NOT BE <br />A <br />B <br />ALLOWED. <br />FIRE ALARM DUCT DETECTOR <br />SHUTDOWN WIRING <br />CEILING <br />GRID ELECTRICAL BACK -BOX ATTACHMENT <br />G. ALL WIRING ON THE INITIATION AND NOTIFICATION CIRCUITS ARE SUPERVISED POWER LIMITED. <br />FA 1 0 1 .NOT TO SCALE <br />FA 1 0 1 NOT TO SCALE <br />H. SURGE SUPPRESSION DEVICES SHALL BE INSTALLED ON ALL CIRCUITS THAT ENTER OR EXIT THE BUILDING. TYPICAL DEVICES ARE LISTED BELOW: <br />PANEL POWER: DITEK MODEL DTK-120SRD, (OR EQUAL) <br />INITIATING CKTS: DITEK MODEL DTK-2MHLP-WB, (OR EQUAL) <br />PHONE LINES: DITEK MODEL DTK-MRJ31 XSCPWP, (OR EQUAL) <br />PANEL POWER SURGE SUPPRESSION MODULE TO BE CONNECTED TO FIRE ALARM CONTROL PANEL; SO THAT WHEN THE MODULE TRIPS, THE FIRE ALARM CONTROL PANEL SHALL REPORT <br />A SUPERVISORY CONDITION. <br />FIRE ALARM <br />CIRCUIT TO <br />JUNCTION BOX NEXT DEVICE <br />I. STROBE CIRCUITS SHALL BE SYNCHRONIZED EITHER THROUGH THE MAIN FACP OR SEPARATE SYNCHRONIZATION MODULES (AS NECESSARY). <br />(OR EQ) <br />III. CONDUIT AND WIRE <br />FIRE ALARM DEVICE MOUNTING <br />GUIDE <br />A. CONDUIT <br />L <br />I LDETECTOR <br />CEIUNG MOUNTED <br />SMOKE/HEAT <br />�3' (MIN) NOT TO SCALE <br />1. CONDUIT INSTALLATION SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC), LOCAL AND STATE REQUIREMENTS. <br />-1 <br />PER NFPA 72 CEILING 4" <br />2. CONDUIT FILL WILL NOT EXCEED 40 PERCENT OF INTERIOR CROSS SECTIONAL AREA WHERE THREE OR MORE CABLES ARE CONTAINED WITHIN A SINGLE CONDUIT. <br />24 MIN HANDICAP <br />UNISTRUT SUPPORT <br />BEDROOM STROBE <br />A/C SUPPLY DIFFUSER ACCEPTABLE HER <br />4" <br />3. CABLE MUST BE SEPARATED FROM ANY OPEN CONDUCTORS OF POWER, OR CLASS 1 CIRCUITS, AND SHALL NOT BE PLACED IN ANY CONDUIT, JUNCTION BOX OR RACEWAY <br />MEMBER OR DIRECT <br />AUDIOVISUAL DO NOT INSTA <br />.. <br />CONTAINING THESE CONDUCTORS. <br />ATTACHMENT TO <br />VISUAL -ONLY IN THIS AREA <br />N <br />STRUCTURAL STEEL. <br />DEVICES CEILING MOUNTED NOTIFICA <br />B. WIRE: <br />MOU <br />DEVICE (TO BE WHO :�j. WALL MOUNTED <br />SEE PLAN FOR LOCATION. HEAT DETECTO <br />1. ALL FIRE ALARM WIRING SHALL BE A MINIMUM OF 'FPLP' TYPE CABLE. <br />CONDUIT DROP TO <br />TO THE BOTTOM. <br />NOTIFICATION DEVICE <br />MINIMUM 3/8" A.T.R. <br />WALL MOUNTED <br />2. WIRING WILL BE IN ACCORDANCE WITH LOCAL, STATE AND NATIONAL CODESNEC ARTICLE 760). THE NUMBER AND SIZE OF CONDUCTORS SHALL BE AS INDICATED ON THESE <br />(E.G.,( ) <br />DROP TO DEVICE <br />BACKBOX <br />__A <br />5�_0 SMOKE DETECTOR <br />TO THE TOP. <br />PLANS, BUT SHALL NOT BE LESS THAN #18 AWG FOR INITIATING DEVICE CIRCUITS (INCLUDING SIGNALING LINE CIRCUITS) AND #14 AWG FOR NOTIFICATION DEVICE CIRCUITS. <br />MORE THAN TWO APPLL4NCES <br />IN THE SAME ROOM OR ADJACENT <br />TYP MAX FROM <br />EXIT DOOR <br />SPACE WITHIN THE FIELD OF VIEW <br />3. ALL FIELD WIRING OF INITIATION AND NOTIFICATION CIRCUITS ARE TO BE COMPLETELY SUPERVISED BY END OF LINE DEVICES, PER THE MANUFACTURER'S LITERATURE. <br />SHALL FLASH IN SYNCHRONIZATION. <br />MANUAL <br />4. HORIZONTAL WIRE RUNS ABOVE CEILINGS: HORIZONTAL WIRE RUNS IN AREAS CONTAINING DROP CEILINGS MAY BE 'FREE -WIRED' IF SUPPORTED BY TO THE BUILDING STRUCTURE. <br />srnULLL <br />LAYING WIRE ON THE CEILING OR INADEQUATE SUPPORT OF WIRING FROM THE STRUCTURE WILL NOT BE ALLOWED. <br />THIS DETAIL APPLIES TO <br />REMOTE <br />MOUNT AT HEIGHT <br />HORN/STROBE DEVICES <br />80" MIN <br />96" MAX <br />ANNUNCIATOR <br />5. VERTICAL AND HORIZONTAL WIRE RUNS IN OPEN STRUCTURE AREAS: ALL WIRING IN "OPEN TO STRUCTURE AREAS" ON THIS PROJECT SHALL BE INSTALLED IN CONDUIT. <br />INSTALLED IN THE SALES TO <br />MATCH LIGHT FIXTURE ELEVATION <br />NFPA 72 <br />�® <br />AREA. DEVICES IN THE <br />6. VERTICAL WIRE RUNS: VERTICAL WIRE RUNS TO DEVICES, PANELS, ANNUNCIATORS, ETC. SHALL BE INSTALLED IN CONDUIT PER THE NATIONAL ELECTRICAL CODE. <br />SHIPPING/RECEIVING AREA <br />CAN BE MOUNTED ON <br />FIREAARM <br />C. TERMINAL BOXES, JUNCTION BOXES AND CABINETS: ALL BOXES AND CABINETS SHALL BE UL LISTED FOR THEIR USE AND PURPOSE. <br />BOTTOM OF STRUCTURE. <br />HORNSTROBE SEE <br />" (��G) <br />80 ABOVE HIGHEST FLOOR <br />PLAN) <br />LEVEL OR 6" BELOW CEILING <br />; <br />D. THE FIRE ALARM CONTROL PANEL IS TO BE CONNECTED TO A SEPARATE DEDICATED BRANCH CIRCUIT, MAXIMUM 20 AMPERES. THIS CIRCUIT SHALL BE LABELED AT THE MAIN POWER <br />TO THE BOTTOM OF THE <br />x <br />DISTRIBUTION PANEL AS FIRE ALARM. FIRE ALARM CONTROL PANEL PRIMARY POWER WIRING SHALL BE 12 AWG. THE CONTROL PANEL CABINET SHALL BE GROUNDED SECURELY TO EITHER <br />STROBE. WHICHEVER IS LOWER. <br />48" (ADA) <br />0 " <br />A COLD WATER PIPE OR GROUNDING ROD. A 120 VOLT SURGE SUPPRESSER SHALL BE INSTALLED ON THE AC POWER AND GROUNDED PRIOR TO ENTERING THE FIRE ALARM CONTROL <br />TO THE WORKING MECHANISM <br />48" ALSO MEETS THE <br />a 0 <br />as <br />PANEL. THE BREAKER FOR THE ALARM CIRCUIT SHALL BE RED IN COLOR, OR PAINTED RED, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, AND SHALL BE IDENTIFIED WITH A <br />REQUIREMENTS OF NFPA 72 <br />PERMANENTLABEL AS "FIRE ALARM CIRCUIT". THE LOCATION OF THE DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT VIA A LABEL INSIDE <br />C <br />FINISHED <br />THE <br />PENDENT NOTIFICATION <br />DEVICE MOUNTING <br />FLOOR <br />IV. EXECUTION <br />FA 101 NOT TO SCALE <br />A. INSTALLATION: <br />1. INSTALLATION SHALL BE IN ACCORDANCE WITH THE NEC, NFPA 72, LOCAL AND STATE CODES, AS SHOWN ON THE DRAWINGS, AND AS RECOMMENDED BY THE MAJOR EQUIPMENT <br />MANUFACTURER. <br />2. DURING CONSTRUCTION MEASURES SHALL BE TAKEN TO PROTECT SMOKE DETECTORS FROM CONTAMINATION AND PHYSICAL DAMAGE UNTIL CONSTRUCTION ACTIVITIES ARE COMPLETE. <br />V. PROGRAMMING <br />1. A BASELINE PROGRAMMING MATRIX HAS BEEN INCLUDED ON THESE PLANS. <br />2. ALL SMOKE DETECTORS SHALL BE PROGRAMMED FOR ALARM VERIFICATION. <br />VI. FINAL INSPECTION <br />1. AT THE FINAL INSPECTION A FACTORY TRAINED REPRESENTATIVE OF THE INSTALLER SHALL DEMONSTRATE THAT THE SYSTEMS FUNCTION PROPERLY IN EVERY RESPECT. ALL TESTING <br />REQUIRED BY THE AHJ SHALL BE COMPLETED IN THE PRESENCE OF THE LOCAL FIRE AUTHORITY, AS REQUIRED. <br />2. DUCT SMOKE DETECTORS AND THEIR ASSOCIATED RELAY CONTROL INTERFACE WITH THE ASSOCIATED AIR HANDLER UNIT SHALL BE TESTED PRIOR TO THE FINAL INSPECTION WITH THE <br />LOCAL AHJ. THE PURPOSE OF THE PRE -TEST IS TO ENSURE THE DETECTORS AND SHUTDOWN INTERFACE WITH THE ASSOCIATED AIR HANDLER UNITS ARE FUNCTIONING CORRECTLY <br />PRIOR TO LOCAL JURISDICTION INSPECTION. <br />VII. SYSTEM MONITORING <br />1. ALARM, SUPERVISORY, AND TROUBLE SHALL BE MONITORED VIA A REMOTE SUPERVISING STATION, AS INDICATED ON THESE PLANS. <br />VIII. GENERAL <br />1. THE VOLTAGE DROP CALCULATIONS SHOWN ON THE PLANS ARE BASED ON THE CIRCUIT ROUTING SHOWN. MAJOR CHANGES TO THE CIRCUIT ROUTING SHOWN MAY NEED TO BE <br />JUSTIFIED BY THE FIRE ALARM CONTRACTOR WITH ADDITIONAL CALCULATIONS. <br />2. THE ALARM CONTRACTOR WILL BE REQUIRED TO SUBMIT A "RECORD OF COMPLETION", PER NFPA 72, TO THE OWNER PRIOR TO FINAL PAYMENT. <br />3. THE FIRE ALARM CONTRACTOR IS REQUIRED TO MAINTAIN A COMPLETE AND ACCURATE AS -BUILT DRAWING SET. UPON FINAL COMPLETION OF THE PROJECT, THE FIRE ALARM <br />CONTRACTOR SHALL SUPPLY THE OWNER & HATCHER ENGINEERING WITH AN AS -BUILT SET PRIOR TO FINAL PAYMENT. AS-BUILTS SHALL INDICATE ALL CHANGES TO THE ORIGINAL <br />LAYOUT INCLUDING, BUT NOT NECESSARY LIMITED TO, AS -BUILT DEVICE LOCATIONS, PANEL LOCATIONS, CIRCUIT ROUTING, CONDUIT ROUTING, JUNCTION BOX LOCATIONS, PANEL <br />CIRCUIT BREAKER LOCATIONS, ETC. <br />4. ALL CONDUIT AND WIRING PENETRATIONS THROUGH FIRE RATED BARRIERS (INCLUDING WALLS AND FLOORS), AND SMOKE BARRIERS THAT EXTEND FROM FLOOR TO CEILING, SHALL BE <br />SEALED WITH A UL LISTED FIRESTOPPING PENETRATION SYSTEM. THE MINIMUM PENETRATION RATING FOR FIRE RATED BARRIERS SHALL MATCH THE RATING OF THE WALL \ FLOOR \ <br />BARRIER. SMOKE BARRIERS SIMPLY NEED TO BE SEALED TO PREVENT THE PASSAGE OF SMOKE THROUGH THE ASSEMBLY. <br />BEALLS <br />BURKES OUTLET FIRE ALARM SYSTEM INSTALLATION OVERVIEW <br />SCARSDALE SECURITY SYSTEMS <br />INC. <br />OWNER & FIRE ALARM INSTALLER'S RESPONSIBILITIES: <br />STEP TWO: <br />OVERVIEW <br />PROGRAM THE PANEL WITH THE CORRECT LAN SETTINGS (FOR MONITORING BY SCARSDALE <br />SCARSDALE SECURITY SYSTEMS IS THE MONITORING COMPANY FOR ALL BEALL'S & <br />SECURITY): <br />OWNER WILL PURCHASE AND DELIVER (TO THE JOBSITE) THE FIRE ALARM EQUIPMENT FOR <br />BURKES STORES. THE FIRE ALARM SYSTEM MUST BE PROGRAMMED TO REPORT TO <br />EACH PROJECT. SCARSDALE SECURITY WILL BE THE FIRE ALARM EQUIPMENT DEALER. THE <br />THE SCARSDALE CENTRAL STATION AND ALL SIGNALS MUST BE TESTED BEFORE THE <br />THE FOLLOWING IS THE BASIC SETUP <br />INFORMATION REQUIRED PROGRAMMED INTO THE <br />FOLLOWING IS A BASIC RESPONSIBILITY LIST: <br />SYSTEM CAN BE PUT ON LINE. THE <br />PREFERRED TRANSFER PROTOCOL IS CONTACT ID. COMMUNICATOR: <br />OWNER WILL SUPPLY (VIA SCARESDALE SECURITY) THE FOLLOWING: <br />IP COMMUNICATOR LOCAL ADDRESS: <br />ACQUIRE FROM PROJECT MANAGER <br />REQUIRED STEPS: <br />SUBNET MASK: <br />255.255.255.0 <br />• L <br />GATEWAY: <br />ACQUIRE FROM PROJECT MANAGER <br />• DMP/ALTRONICS 6.5 AMP POWER SUPPLY <br />1. PROVIDE THE CENTRAL STATION WITH ZONE LIST WITH PANEL MAKE & MODEL. <br />• DMP NOTIFICATION MODULE <br />2. TEST ALL SIGNALS INTO THE CENTRAL STATION AND CALL TO CONFIRM PROPER <br />STEP THREE: <br />• DMP REMOTE ANNUNCIATOR <br />RECEPTION. <br />• FIRE ALARM DEVICES (PULL STATIONS, SMOKE DETECTORS, DUCT SMOKE DETECTORS, <br />3. MAKE THE SYSTEM ACTIVE WITH THE CENTRAL STATION. <br />TRIP ALL ZONES INTO THE CENTRAL STATION INCLUDING LOW BATTERY AC FAIL. CALL THE <br />NOTIFICATION DEVICES, MODULES, ETC.) <br />CENTRAL STATION AT 914-722-2222, <br />MAKE THE SYSTEM ACTIVE WITH THE CENTRAL STATION AND <br />• OWNER WILL PREPARE A DEVICE TAKE -OFF LIST FROM THE SHOP DRAWINGS ON EACH <br />TO IDENTIFY THE CORRECT SYSTEM TO THE CENTRAL STATION YOU MUST PROVIDE <br />TELL THEM TO PUT THE FIRE SYSTEM <br />ON LINE. TEST THE CENTRAL STATION REPORTING FOR <br />SYSTEM AND ORDER/DELIEVER DEVICES SPECIFIC TO THIS PROJECT TO THE JOBSITE. <br />THEM WITH THE FOLLOWING INFORMATION: <br />BOTH THE PHONE LINE CONNECTION AND THE ETHERNET CONNECTION. <br />THE FIRE ALARM CONTRACTOR WILL BE RESPONSIBLE FOR THE FOLLOWING: <br />- STORE NAME & NUMBER, CITY & <br />STATE <br />FIRE INSPECTIONS: <br />• PROVIDE ALL LABOR, WIRING, ELECTRICAL BOXES, CONDUIT, WIRE HANGAR SUPPORTS, <br />AND MISCELLANEOUS ELECTRICAL MATERIAL, IN ORDER TO COMPLETE THE INSTALL OF <br />STEP ONE: <br />SPECIAL INSTRUCTIONS FOR SUCCESSFULLY <br />PASSING A FIRE INSPECTION WITH THE FIRE MARSHAL. <br />THE DMP SYSTEM EQUIPMENT PROVIDED BY BEALLS/BURKES. <br />• INSTALLATION PERMIT FROM THE LOCAL MUNICIPALITY. <br />PROVIDE THE CENTRAL STATION WITH <br />A ZONE LIST. IF IT IS SMALL IT CAN BE CALLED <br />THE SYSTEM MUST BE ACTIVE WITH <br />THE CENTRAL STATION THIS MEANS YOU MUST HAVE SENT <br />• PROVIDE FULL SYSTEM INSTALLATION &TESTING IN ACCORDANCE WITH NFPA 72 AND <br />INTO THE CS AT 914-722-2222. IF <br />IT IS LARGE, FAX IT TO 914-722-2299. BE <br />THE CENTRAL STATION A <br />THE LOCAL AHJ. <br />SURE THE ACCOUNT NUMBER IS WRITTEN ON THE FAX. EXAMPLE: 51-5555. <br />ZONE LIST AND TESTED SIGNALS. <br />• PROVIDE ALL PROGRAMMING AND CLOSE OUT DOCUMENTATION. <br />• TEST AND VERIFY FINAL CONNECTION TO THE REMOTE MONITORING STATION <br />YOU MUST ALSO TELL THE CENTRAL <br />STATION THE MANUFACTURER & MODEL NUMBER <br />CALL THE CENTRAL STATION BEFORE <br />THE FIRE INSPECTIONS START AND TELL THEM YOU ARE <br />(SCARSDALE SECURITY). <br />OF THE FIRE ALARM CONTROL PANEL. EXAMPLE: DMP-XR10ONFC <br />TESTING THE SYSTEM WITH <br />THE FIRE MARSHAL TODAY AND CONFIRM <br />THE SYSTEM IS ACTIVE. <br />RECORD YOUR CELL PHONE NUMBER <br />AND COMPANY NAME ON THE ZONE LIST SO THE <br />CS CAN CONTACT YOU IF THEY HAVE <br />A QUESTION ABOUT THE ZONE LIST. <br />MAKE SURE THE CS HAS THE PROPER <br />FIRE DEPARTMENT DISPATCH NUMBER <br />PROPOSED FIRE ALARM <br />I <br />z <br />Z <br />CONTROL MATRIX <br />Z <br />W <br />� <br />> <br />u' <br />I- <br />H <br />Vl <br />� <br />� �+ <br />W <br />1- <br />J <br />''^^ <br />z <br />c.� <br />H <br />a <br />Z iZ <br />w o � <br />f- <br />a <br />� <br />vi <br />O <br />H <br />Z <br />Z <br />!- <br />r¢-( <br />� <br />N <br />Z <br />E Q ' Q <br />¢ <br />U <br />LeJ <br />� <br />Q <br />2 <br />Z <br />� V~1 W <br />Val <br />z <br />""e <br />Z <br />Z <br />O <br />'O <br />Q <br />J <br />z <br />>- <br />o <br />a <br />= <br />O l7 <br />~� �w <br />z' <br />I <br />I¢ <br />INPUTS O <br />� <br />¢ <br />W� <br />y <br />� <br />(-+ <br />a <br />Z W <br />�N �= <br />H <br />N <br />A <br />i <br />BI <br />SMOKE DETECTOR <br />C <br />X <br />X <br />DUCT SMOKE DETECTOR <br />D <br />X <br />X <br />X <br />E <br />X <br />X <br />_..._.........----._. <br />F..._._ <br />X <br />i X_ <br />MANUAL PULL STATION <br />G <br />X <br />X <br />'X <br />H <br />SYSTEM TROUBLE CONDITION <br />I <br />I <br />J <br />PANEL POWER SURGE SUPPRESSION MODULE TRIP <br />K <br />1 2 3 4 5 6 7' 8 <br />PROJECT SPECIFIC NOTES: I <br />1. ALL SMOKE DETECTORS ARE TO BE PROGRAMMED WITH ALARM VERIFICATION. <br />2. THIS CHART IS TO BE USED AS A BASIC PROGRAMMING GUIDE ONLY. ALL OTHER PANEL <br />PROGRAMMING FEATURES SHALL COMPLY WITH NFPA 72 AND THE MANUFACTURERS <br />INSTRUCTIONS. <br />FIRE ALARM DEVICE LEGEND <br />SYMBOL <br />DEVICE TYPE <br />DEVICE MODEL <br />ADDITIONAL NOTES <br />SYMBOL <br />DEVICE TYPE <br />DEVICE MODEL <br />ADDITIONAL NOTES <br />® <br />FIRE ALARM CONTROL PANEL <br />DMP XR150NFC-R <br />© <br />MAN1',�.I_ PULL STATION <br />DMP 850S WITH 711 ADDRESSABLE <br />MODULE <br />INSTALL AT48^AFF <br />® <br />REMOTE ANNUNCIATOR PANEL <br />DMP 630E-R <br />INSTALL AT 60" AFF <br />� <br />SYSTEM SENSOR D4120 WITH 711 <br />COORDINATE WITH HVAC CONTRACTOR. <br />INSTALL DETECTOR IN <br />® <br />SURGE SUPPRESSION MODULE <br />`' D <br />DUCT SMOKE DETECTOR <br />ADDRESSABLE MODULE <br />SUPPLY SIDE DUCT <br />(DOWNSTREAM OF HVAC FAN UNIT) <br />® <br />FIRE ALARM POWER SUPPLY <br />DMP AX-AL602ULADA (ALTRONICS) <br />� <br />PHOTOELECTRIC SMOKE DETECTOR <br />DMP 521 B <br />CEILING MOUNTED DEVICES TO BE WHITE <br />FLOW SWITCH <br />HORN /STROBE (CEILING MOUNTED) <br />SYSTEM SENSOR BK-PC2W <br />DEVICE TO BE 'WHITE' <br />Q3xp <br />STROBE (CEILING MOUNTED) <br />SYSTEM SENSOR BK-SCW <br />DevlcE To BE'wHIrE� <br />TAMPER SWITCH <br />�/1N� <br />END -OF -LINE RESISTOR (EOL) <br />VENDOR INSTALLED <br />AT END OF CIRCUIT <br />WEATHERPROOF <br />HORN STROBE WALL MOUNTED <br />SYSTEM SENSOR BK-P2RK <br />DEVICE TO BE'RED' <br />a <br />REMOTE TEST/RESET SWITCH <br />SYSTEM SENSOR BK-RTS151 KEY <br />MOUNT ON CEILING BELOW DUCT <br />DETECTOR. LABEL PER RTU #. <br />1 `J LU <br />NATHANIEL J. HATCHER, P.E. <br />2108 W. RISK STREET <br />PLANT CITY, FLORIDA <br />FAX: (813) 752 6901� <br />Via° 'y�i <br />® N0 59350 <br />, e a <br />STATE Ovx\\� <br />®S®® as � <br />�1f 611 I �e� <br />10\08\1 7 <br />NATHANIEL J. HATCHER. FL PE #59350 <br />IN <br />I <br />IL <br />Iv <br />I <br />I <br />I <br />IF <br />REV. DESCRIPTION DATE ll <br />............. .......... E <br />BID & PERMIT SET <br />09.29.17 <br />CURRENT ISSUE STATUS: <br />PROJECT NORTH <br />ID <br />®® <br />WBRCM ■C <br />ARCHITECTS ENGINEERS <br />8130 Lakewood Main Street Phone: 941-556-0757 <br />Suite 210 Fax: 941-556-0759 <br />Lakewood Ranch, FL 34202 www.wbrcae.com <br />_.._........_Firm Lic_AA26001395 & 27389 __Oou�s W.Whitney _1IA__... <br />BEALLS OUTLET #542 <br />ZE P HYRH I LLS <br />PROJECT: 6030 Gall Blvd, Zephyrhills, FL 33542 B <br />FIRE ALARM NOTES & <br />SPECIFICATIONS <br />SHEET TITLE: <br />........._._.......-- ------ ..............._-.................... _......._...... - ---- -- .............---............ <br />WBRCCAD FILE : T:\03Projets-Florida\3501-3600\3542M5BeallsOutletZephyrhillsFL\2Deslgn\Dwgs\Bldg\3542M5 <br />BEALLS OUTLET ZEPHYRHILLS It <br />PROJECT No 3542XX� GRAPHIC SCALE: <br />-t{.._.._._.- ........ _ pl' <br />PROJECT MANAGER: Approver I SHEET No. <br />__....--- .......................__------ <br />DRAWN BY: AJC FA 101 <br />CHECKED BY: NJH <br />' a n <br />