<br />ELECTRICAL PROJECT REQUIREMENTS
<br />THE CONTRACTOR SHALL ARRANGE AND PAY FOR ALL
<br />WIRE SHALL BE SINGLE CONDUCTOR COPPER WITH 600
<br />PERMITS AND INSPECTIONS REQUIRED IN THIS WORK.
<br />VOLT INSULATION. #10 AND SMALLER SHALL BE SOLID.
<br />#8 AND LARGER SHALL BE STRANDED. MINIMUM WIRE
<br />ALL WORK SHALL BE DONE IN ACCORDANCE WITH
<br />SIZE SHALL BE ALL WIRE AND CABLE SHALL BE NEW
<br />THESE PLANS, SPECIFICATIONS, LOCAL, STATE AND
<br />BR
<br />AND SHALL BE BROUGHT TO THE SITE IN UNBROKEN
<br />NATIONAL CODES. CERTIFICATES OF INSPECTION,
<br />PACKAGES. ALL WIRING OF ANY TYPE SHALL BE IN
<br />WHERE REQUIRED, SHALL BE OBTAINED AND PAID FOR
<br />CONDUIT. GENERAL WIRING SHALL BE THW OR THEN.
<br />BY THIS CONTRACTOR AND FURNISHED TO THE TENANT.
<br />(ALUMINUM CONDUCTORS SHALL NOT BE PERMITTED).
<br />THE ELECTRICAL CONTRACTOR SHALL FURNISH ALL
<br />MC CABLE MAY BE USED FISHED IN WALLS OR NOT TO
<br />LABOR, MATERIALS, EQUIPMENT AND TOOLS TO
<br />EXCEED T-0" IN LENGTH AS FINAL CONNECTION TO
<br />PERFORM ELECTRICAL WORK AS SHOWN, NOTED OR
<br />EQUIPMENT OR FIXTURES.
<br />SCHEDULED FOR A COMPLETE INSTALLATION.
<br />RECEPTACLES SHALL BE 20A-125V 3-WIRE GROUNDING
<br />ALL MATERIALS AND EQUIPMENT SHALL BE COMMERCIAL
<br />TYPE EQUAL TO HUBBEL 5362.
<br />GRADE AND SHALL CARRY AN UNDERWRITERS
<br />ALL MOUNTING HEIGHTS SHOWN ON THE DRAWINGS
<br />LABORATORIES (U.L.) LABEL.
<br />SHALL BE MEASURED FROM FINISHED FLOOR TO TOP
<br />THE CONTRACT DRAWINGS INDICATE THE EXTENT AND
<br />OF BOX. ELECTRICAL CONTRACTOR SHALL VERIFY
<br />GENERAL ARRANGEMENTS OF EQUIPMENT AND
<br />WITH THE ARCHITECTURAL DRAWINGS, COUNTER TOP
<br />SYSTEMS. IF ANY DEPARTURES FROM THE CONTRACT
<br />AND CABINET HEIGHTS, TO AVOID CONFLICTS WITH
<br />DRAWINGS ARE DEEMED NECESSARY BY THE
<br />BACKSPLASHES, ETC.
<br />CONTRACTOR, DETAILS OF SUCH DEPARTURES AND
<br />OUTLET BOXES SHALL BE GALVANIZED STEEL, ONE
<br />REASONS THEREFORE SHALL BE SUBMITTED TO THE
<br />PIECE, PRESSED STEEL WITH SMOOTH PLASTIC COVER
<br />OWNER FOR APPROVAL.
<br />PLATE. VERIFY COLOR OF THE DEVICE AND
<br />IT IS THE INTENT OF THE PLANS AND SPECIFICATIONS
<br />COVERPLATE..
<br />TO PROVIDE A COMPLETE AND OPERATING
<br />JUNCTION BOXES AND COVERS SHALL BE GALVANIZED
<br />INSTALLATION INCLUDING ALL OBVIOUSLY NECESSARY
<br />STEEL, CODE GAUGE SIZE.
<br />ITEMS EVEN THOUGH SOME ITEMS MAY NOT BE
<br />IT IS THE RESPONSIBILITY OF THE ELECTRICAL
<br />INDICATED ON THE DRAWING OR SPECIFICATIONS.
<br />CONTRACTOR TO PROPERLY BALANCE THE LOAD OF ALL
<br />ALL OBVIOUS ERRORS AND/OR OMISSIONS IN THE
<br />BRANCH CIRCUITS BETWEEN THE PHASES OF THE
<br />ABOVE MENTIONED DOCUMENTS SHALL BE CALLED TO
<br />SYSTEM, REGARDLESS OF THE CIRCUITING INDICATED.
<br />THE ATTENTION OF THE ARCHITECT PRIOR TO
<br />CONSTRUCTION.
<br />THE ELECTRICAL SERVICE, METERING, DISTRIBUTION,
<br />FEEDERS, TRANSFORMERS AND PANELS ARE EXISTING.
<br />THIS CONTRACTOR SHALL INSPECT THE JOB SITE
<br />MODIFY CIRCUIT BREAKERS AS INDICATED ON THE PANEL
<br />WHERE THE WORK IS TO BE PERFORMED AND SHALL
<br />SCHEDULES.
<br />AQUAINT HIMSELF WITH THE CONDITIONS UNDER WHICH
<br />IT SHALL BE EXECUTED.
<br />THIS CONTRACTOR SHALL FURNISH AND INSTALL AND
<br />CONDUIT SHALL BE STANDARD ELECTRIC METALLIC
<br />MAKE OPERATIVE ALL ELECTRICAL WORK. ALL
<br />TUBING (EMT) ACCORDING TO CODE REQUIREMENTS.
<br />INCIDENTAL ITEMS NOT FULLY DESCRIBED, BUT
<br />CONDUIT SHALL BE CONCEALED IN FINISHED AREAS,
<br />NECESSARY FOR THE COMPLETE INSTALLATION ARE
<br />EXCEPT AS OTHERWISE APPROVED. EMT
<br />TO BE FURNISHED.
<br />CONNECTIONS SHALL BE COMPRESSION TYPE. EMT
<br />ELECTRICAL CONTRACTOR SHALL GUARANTEE THAT THE
<br />SHALL BE USED FOR FEEDERS AND BRANCH CIRCUITS
<br />COMPLETE ELECTRICAL SYSTEMS INSTALLED UNDER
<br />RUN ABOVE SUSPENDED CEILINGS OR CONCEALED IN
<br />THIS CONTRACT SHALL BE FREE OF DEFECTS IN
<br />INTERIOR PARTITIONS. EMT SHALL NOT BE USED BELOW
<br />WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE
<br />GRADE OR IN POURED CONCRETE SLABS OR WALLS,
<br />(1) YEAR. IF DEFECTS OCCUR DURING THIS ONE (1) YEAR
<br />PVC CONDUIT SHALL BE USED AT THESE LOCATIONS.
<br />GUARANTEE PERIOD, EXCLUSIVE OF LAMP BURNOUT,
<br />FLEXIBLE METAL CONDUIT IS TO BE USED ONLY FOR
<br />ELECTRICAL CONTRACTOR SHALL REPAIR OF REPLACE
<br />CONNECTIONS TO DEVICES AND NOT FOR HOMERUNS.
<br />THE DEFECTIVE ITEMS AT EXPENSES THE
<br />VERIFY WITH THE LOCAL JURISDICTION FOR
<br />TENANT, AND TO THE SATISFACTION OF THE TENANT.
<br />SUITABILITY OF USE IN RETAIL STRUCTURES.
<br />FIRE SEAL ALL PENETRATIONS OF RATED WALLS,
<br />FLOORS, ETC. USING UL FIRE STOP SYSTEM. FIELD
<br />SLEEVES SHALL EXTEND AT LEAST 2" ABOVE FINISHED
<br />VERIFY ALL RATED ASSEMBLIES AFFECTED BY WORK
<br />FLOOR AND ALL SLEEVES THROUGH FIRE RATED WALLS
<br />AND PROVIDE FIRE STOP SYSTEM RATED FOR THAT USE.
<br />AND FLOORS SHALL BE SEALED AFTER CONDUIT
<br />INSTALLATION.
<br />THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE
<br />FOR VERIFYING ALL EXISTING CONDITIONS.
<br />ELECTRICAL SERVICE CALCULATION
<br />PANELS 'A'. 'B', 'C'
<br />CONNECTED
<br />DEMAND
<br />RECEPTACLE LOAD
<br />7,920
<br />7,920
<br />LIGHTING >3 HR. LOAD
<br />21,050
<br />26,312
<br />OTHER LOADS
<br />7,630
<br />7,630
<br />RTU EQUIPMENT
<br />91,146
<br />91,146
<br />SIGNAGE
<br />1,690
<br />2,112
<br />TOTAL
<br />129,436
<br />135,120
<br />375.1A DEMAND
<br />400A SERVICE @ 208V, 3-PHASE EXISTING
<br />ELECTRICAL SERVICE CALCULATION
<br />PANELS 'D', 'E'
<br />CONNECTED DEMAND
<br />RTU EQUIPMENT 48,990 48,990
<br />TOTAL 48,990 48,990
<br />135.9A DEMAND
<br />400A SERVICE @ 208V, 3-PHASE EXISTING
<br />(2) BUTTON DIGITAL SWITCH (1) BUTTON DIGITAL SWITCH
<br />BLUE BOX CHELSEA BLUE BOX CHELSEA BY ELECTRICAL BY
<br />MODEL # CH-2. MODEL # CH-1. CONTRACTOR
<br />CONTRACTOR
<br />SECURITY
<br />CO
<br />ALL SALES LIGHTING - ON. SIGN & CANOPY/PARKING- ON/OFF
<br />SIGN & CANOPY/PARKING- ON/OFF MOUNT AT MGR / LP OFFICE 48" AFF. RELAY PROVIDED
<br />MOUNT AT FRONT OF STORE, AND INSTALLED
<br />SEE PLAN AND DETAIL. BY CONTRACTOR.
<br />�� MOUNT IN J.B.
<br />I r--� I "
<br />SWITCH
<br />LABEL
<br />SALES O
<br />ON
<br />SIGN B
<br />ON/OFF O
<br />DIGITAL SWITCH
<br />BUTTONS SHALL BE
<br />FACTORY LABELED AS
<br />SHOWN.
<br />SWITCH SWITCH
<br />lull LABEL LABEL lul
<br />RJ45 RJ45 RJ45
<br />CAT 5 E
<br />CABLE
<br />I
<br />BLUE BOX
<br />D6 OPTION
<br />CAT 5E
<br />ANALOG
<br />CABLE
<br />INPUTS
<br />LC&D BLUE BOX
<br />O
<br />GR1416LTC
<br />(00
<br />RJ45
<br />MASTER
<br />� O
<br />CONTROL PANEL
<br />0-0
<br />O
<br />CAT 5 E
<br />ASTRO
<br />—
<br />CABLE
<br />CLOCK
<br />24V
<br />RJ45
<br />NCL RELAYS
<br />N.O. R DC 18 GA WIRE
<br />24V
<br />NSTALL POWER SUPPLY
<br />INSTALL 18 GA WIRE FROM DEC 7EPUffUI PITY PANEL 120V
<br />RELAY TO SECURITY PANEL. AC INPUT 12V DC OUTPUT
<br />LEAVE 5' OF WIRE COILED 12pV 200 mA
<br />AT SECURITY PANEL FOR AC
<br />CONNECTION BY SECURITY
<br />INSTALLER
<br />LC&D BLUE BOX
<br />SALES AREA
<br />GR2400 ETHERNET
<br />WORK LTG
<br />INTERFACE CABINET
<br />LTG
<br />CONTROL
<br />RJ45
<br />ZONE A
<br />STOCK LTG
<br />RJ45
<br />RJ45
<br />SALES LTG
<br />DATA OUTLET
<br />MOUNTED NEAR
<br />CONTROL
<br />LIGHTING
<br />ZONE B
<br />CONTROL PANEL.
<br />WALLWASH LTG.
<br />LED DISKS
<br />CAT 5E PATCH CORD
<br />(BY B.O.S.)
<br />SPARE
<br />RELAYS
<br />CAT 5E
<br />CABLE
<br />LC&D BLUE BOX
<br />ZONE TIME PROGRAMMING
<br />GR 1404 LTC
<br />ZONE 'A' - WORK LIGHTING
<br />RJ45 REMOTE
<br />CONTROL PANEL
<br />ON - PRESET TIME 7:30 AM
<br />ON - FRONT OF STORE DIGITAL BUTTON
<br />ON -SECURITY SYSTEM INPUT
<br />OFF - PRESET TIME 9:45 PM
<br />NCL RELAYS
<br />ZONE 'B' - SALES LIGHTING
<br />SIGN - FRONT
<br />CONTROL
<br />ON - PRESET TIME 9:00 AM
<br />ZONE C
<br />ON - FRONT OF STORE DIGITAL BUTTON
<br />ON -SECURITY SYSTEM INPUT
<br />N SPARE
<br />OFF - PRESET TIME 9:15 PM
<br />N RELAYS
<br />ZONE 'C' - SIGNAGE
<br />ON - 30 MINUTES PRIOR TO SUNSET
<br />ON -FRONT AND REAR STORE DIGITAL BUTTON
<br />LIGHTING CONTROL SYSTEM SUPPLY ! INSTALL MATRIX
<br />OFF - PRESET TIME 10:00 PM
<br />OFF - FRONT AND REAR STORE DIGITAL BUTTON
<br />LIGHTING CONTROL ITEM SUPPLIED INSTALL
<br />ZONE 'D' - FRONT CANOPY / FACADE / PARKING
<br />LTG CONTROL PANELS) B.O.S.
<br />G.C.
<br />ON -30 MINUTES PRIOR TO SUNSET
<br />DIGITAL SWITCHES B.O.S.
<br />G.C.
<br />ON -FRONT AND REAR STORE DIGITAL BUTTON
<br />GR2400 COMMUNICATIONS INTERFACE FOR ETHERNET B.O.S.
<br />G.C.
<br />OFF - PRESET TIME 10:00 PM
<br />OFF - FRONT AND REAR STORE DIGITAL BUTTON
<br />CAT 5E CABLE / RJ45 JACKS (BETWEEN SYSTEM DEVICES) G.C.
<br />G.C.
<br />ZONE'E' - REAR EXTERIOR LIGHTING
<br />RELAY FOR SECURITY INTERFACE(24V N.O./12 V CONTROL) G.C.
<br />G.C.
<br />ON -30 MINUTES PRIOR TO SUNSET
<br />OFF - SUNRISE
<br />CAT 5E CABLE FOR LIGHTING SYSTEM IS UNRELATED TO OTHER CAT 5E CABLE
<br />SUPPLIED BY B.O.S. FOR DATA SYSTEMS. COLOR OF CABLE SHALL BE PURPLE.
<br />LIGHTING CONTROL DIAGRAM
<br />NO SCALE
<br />LIGHTING CONTROL NOTES
<br />DESCRIPTION:
<br />PANEL(S) AND SWITCHES SHALL BE PROVIDED, INSTALLED, CONNECTED AND
<br />PROGRAMMED BY THE ELECTRICAL CONTRACTOR.
<br />CONTACT PERSON FOR LC&D BLUE BOX EQUIPMENT IS SCOTT LIEFFERS WITH
<br />ENVISION LIGHTING SYSTEMS, TELEPHONE 727.576.8488.
<br />LIGHTING CONTROL MASTER PANEL SHALL BE LIGHTING CONTROL AND DESIGN,
<br />INC. (LC&D) BLUE BOX MODEL GR1416-LT-INT WITH FOLLOWING OPTIONS:
<br />1. "NCL" NORMALLY CLOSED LATCHING RELAYS FOR EACH CIRCUIT
<br />CONTROLLED AND SPARES (16 TOTAL)
<br />2. "DTC" DIGITAL TIMECLOCK
<br />3. "DV" TRANSFORMER
<br />4. "D6" 6 INPUTS WITH ENABLE/DISABLE FOR ANALOG INPUT.
<br />5. NEMA 1 SURFACE MOUNT CABINET GR1416-LT-ENC.
<br />LIGHTING CONTROL PANEL SHALL HAVE 16 RELAY CAPACITY, ASTRONOMIC
<br />CLOCK, NON-VOLATILE MEMORY WITH BATTERY BACKUP (10 YEAR BATTERY).
<br />RELAYS SHALL BE NORMALLY CLOSED (BLUE BOX NCL RELAY).
<br />FILL PANEL WITH RELAYS, DO NOT LEAVE ANY SPACES.
<br />IF THERE ARE GREATER THAN 16 CONTROLLED CIRCUITS A REMOTE RELAY PANEL
<br />SHALL BE USED FOR THE ADDITIONAL CIRCUITS. PANEL SHALL BE THE SAME AS
<br />THE MASTER PANEL BUT WITHOUT TIMECLOCK AND OF 4 / 8 / 16 RELAY CAPACITY
<br />LINKED TO MASTER PANEL WITH CAT 5E CABLE.
<br />BLUEBOX INTERFACE CABINET GR2400-L2-PCETH-DV-5M-NE1 SHALL BE INSTALLED
<br />TO PROVIDE COMMUNICATIONS INTERFACE TO ETHERNET.
<br />DIGITAL SWITCHES SHALL BE LC&D CHELSEA SERIES WITH 1 BUTTON MODEL
<br /># CH-1 OR 2 BUTTONS MODEL # CH-2, LINKED TO MASTER PANEL WITH CAT 5E
<br />CABLE. LABEL BUTTONS AS INDICATED. COLOR OF SWITCHES AND BUTTONS
<br />SHALL BE WHITE.
<br />PROGRAMMING:
<br />SEE LIGHTING CONTROL SCHEDULE FOR SPECIFIC ZONE INFORMATION.
<br />1. (ZONE 'A'): WORK LIGHTING SHALL TURN ON/OFF BY PRESET TIME, DIGITAL
<br />SWITCH INPUT AND UPON INPUT FROM THE SECURITY PANEL. WORK LIGHTING IS
<br />50% OF TROFFER SALES LIGHTING, STOCK ROOM LIGHTING, RESTROOMS, AND
<br />THE RESTROOM EXHAUST FAN.
<br />2. (ZONE 'B'): SALES LIGHTING SHALL TURN ON/OFF BY PRESET TIME, DIGITAL
<br />SWITCH INPUT AND UPON INPUT FROM THE SECURITY PANEL. SALES LIGHTING IS
<br />REMAINING TROFFERS IN SALES AREA AND WALL WASH FIXTURES.
<br />3. (ZONE'C'): SIGNAGE SHALL TURN ON BY ASTRONOMIC CLOCK 30 MINUTES
<br />PRIOR TO SUNSET OR DIGITAL SWITCH INPUT AND TURN OFF AT PRESET DAILY
<br />TIMES OR DIGITAL SWITCH INPUT. (ZONES 'C' AND 'E' CONTROLLED TOGETHER)
<br />4. (ZONE'D'): FRONT EXTERIOR CANOPY / FACADE / PARKING LOT LIGHTING
<br />SHALL TURN ON BY ASTRONOMIC CLOCK 30 MINUTES PRIOR TO SUNSET OR
<br />DIGITAL SWITCH INPUT AND TURN OFF AT PRESET DAILY TIMES OR DIGITAL
<br />SWITCH INPUT. (ZONES 'C' AND'D' CONTROLLED TOGETHER)
<br />5. (ZONE'E'): REAR / SIDES EXTERIOR LIGHTING SHALL TURN ON BY ASTRONOMIC
<br />CLOCK 30 MINUTES PRIOR TO SUNSET AND TURN OFF AT SUNRISE.
<br />6. INTERIOR LIGHTING SHALL TURN OFF BY DAILY SWEEP WITH WARNING BLINKS.
<br />SWEEP SHALL OCCUR AT TIME SPECIFIED BY BEALLS REPRESENTATIVE.
<br />7. ASTRONOMIC CLOCK SHALL BE SET FOR THE LATITUDE OF THE STORE LOCATION.
<br />PANELBOARD DESIGNATION: E RENAME PANEL TO'E' FROM'A'
<br />VOLTAGE:
<br />208/120V
<br />3PH-4W
<br />MAINS RATING:
<br />200
<br />AMPS
<br />MAIN CB TRIP RATING:
<br />200
<br />AMPS
<br />■ SURFACE
<br />FLUSH
<br />■ MCB
<br />MLO
<br />INTERRUPTING RATING:
<br />22,000
<br />AIC
<br />ENCLOSURE:
<br />NEMA 1
<br />SERVES
<br />CB SIZE
<br />LOAD VA
<br />CKT#
<br />CKT#
<br />LOAD VA
<br />CB SIZE
<br />SERVES
<br />RTU
<br />2 60/ 3
<br />6244
<br />1
<br />2
<br />7 20
<br />SPARE
<br />2
<br />6244
<br />3
<br />4
<br />7 20
<br />SPARE
<br />6244
<br />5
<br />6
<br />7 20
<br />SPARE
<br />RTU
<br />35/ 3
<br />3842
<br />7
<br />8
<br />7 20
<br />1 SPARE
<br />3842
<br />9
<br />10
<br />7 20
<br />SPARE
<br />2
<br />3842
<br />11
<br />12
<br />20
<br />SPARE
<br />SPARE
<br />7 20
<br />13
<br />14
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />15
<br />16
<br />20
<br />SPARE
<br />SPARE
<br />7 20
<br />17
<br />18
<br />7 20
<br />SPARE
<br />SPARE
<br />20
<br />19
<br />20
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />21
<br />22
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />23
<br />24
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />25
<br />26
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />27
<br />28
<br />7 20/ 2
<br />SPARE
<br />29
<br />30
<br />7
<br />31
<br />32
<br />33
<br />34
<br />35
<br />1
<br />36
<br />37
<br />38
<br />39
<br />40
<br />41
<br />42
<br />A B C
<br />DEMAND: 30.3 KW 83.9A
<br />PANELBOARD DESIGNATION: D RENAME PANELTO'D'FROM'B'
<br />VOLTAGE:
<br />208/120V
<br />3PH-4W
<br />MAINS RATING:
<br />200
<br />AMPS
<br />MAIN CB TRIP RATING:
<br />200
<br />AMPS
<br />■ SURFACE
<br />FLUSH
<br />■ MCB
<br />MLO
<br />INTERRUPTING RATING:
<br />22,000
<br />AIC
<br />ENCLOSURE:
<br />NEMA 1
<br />SERVES
<br />CB SIZE
<br />LOAD VA
<br />CKT#
<br />CKT#
<br />LOAD VA
<br />CB SIZE
<br />SERVES
<br />RTU
<br />2 60/ 3
<br />6244
<br />1
<br />1
<br />2
<br />7 20
<br />SPARE
<br />2
<br />6244
<br />3
<br />4
<br />7 20
<br />SPARE
<br />2
<br />6244
<br />5
<br />6
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />7
<br />8
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />9
<br />10
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />11
<br />12
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />13
<br />14
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />15
<br />16
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />17
<br />18
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />19
<br />20
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />21
<br />22
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />23
<br />24
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />25
<br />26
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />27
<br />28
<br />29
<br />30
<br />31
<br />32
<br />33
<br />34
<br />35
<br />36
<br />37
<br />38
<br />39
<br />40
<br />41
<br />42
<br />A B C
<br />DEMAND: 18.7 KW 51.9A
<br />PANEL AND CIRCUIT BREAKER NOTED ITEMS
<br />01 EXISTING CIRCUIT BREAKER USED FOR NEW CIRCUIT.
<br />© EXISTING CIRCUIT TO REMAIN.
<br />Q3 EXISTING CIRCUIT TO REMAIN. MODIFY OR RELOCATE AS INDICATED ON THE DRAWINGS.
<br />® ROUTE NEW CIRCUIT VIA NEW LIGHTING CONTROL PANEL.
<br />Q5 ROUTE EXISTING CIRCUIT VIA NEW LIGHTING CONTROL PANEL.
<br />® NEW CIRCUIT BREAKER AT EXISTING SPACE FOR NEW CIRCUIT.
<br />O EXISTING CIRCUIT IS / WILL BECOME A SPARE. VERIFY CIRCUIT WILL NO LONGER BE
<br />USED OR NEEDED AT COMPLETION OF RENOVATION
<br />® REPLACE EXISTING CIRCUIT BREAKER WITH NEW CIRCUIT BREAKER INDICATED.
<br />09 RECONNECT EXISTING DEVICE TO NEW CIRCUIT. DEVICE WAS FED FROM REMOVED
<br />PANEL.
<br />(LOCK) INDICATES TO INSTALL HANDLE LOCK
<br />CIRCUIT USAGE NOTE:
<br />CIRCUIT USAGE IS DERIVED FROM PANEL SCHEDULES. VERIFY EXACT ACTUAL
<br />ARRANGEMENT OF CIRCUITS AT EXISTING PANELS INSTALLED AS WORK OF THE SHELL
<br />BUILDING (NOT IN THIS PERMIT).
<br />IF NEW CIRCUIT IS SHOWN AT A CIRCUIT BREAKER WHERE AN EXISTING CIRCUIT MUST
<br />REMAIN, RELOCATE NEW CIRCUIT TO A SPARE OR NEW CIRCUIT BREAKER ON THE SAME
<br />PANEL.
<br />COORDINATE PHASING OF CIRCUITS OLD AND NEW SO STORE OPERATIONS ARE NOT
<br />DISRUPTED.
<br />WEATHER
<br />HEADS
<br />EXISTING
<br />200A FEED
<br />EXISTING
<br />200A FEED
<br />PANELBOARD DESIGNATION: A
<br />VOLTAGE:
<br />208/120V
<br />3PH-4W
<br />MAINS RATING:
<br />400
<br />AMPS
<br />MAIN CB TRIP RATING:
<br />400
<br />AMPS
<br />■ SURFACE
<br />FLUSH
<br />■ MCB
<br />MLO
<br />INTERRUPTING RATING:
<br />35,000
<br />AIC
<br />ENCLOSURE:
<br />NEMA 1
<br />SERVES
<br />CB SIZE
<br />LOAD VA
<br />CKT#
<br />CKT#
<br />LOAD VA
<br />CB SIZE
<br />SERVES
<br />LTG-EMERG / NITE (LOCK)
<br />3 20
<br />1411
<br />1
<br />2
<br />7 20
<br />SPARE
<br />LTG-EMERG / NITE (LOCK)
<br />3 20
<br />1411
<br />3
<br />4
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />5
<br />6
<br />20
<br />SPARE
<br />SPARE
<br />7 20
<br />7
<br />8
<br />7 20
<br />SPARE
<br />REFRIGERATOR
<br />1 20
<br />900
<br />9
<br />10
<br />20
<br />SPARE
<br />EWC
<br />1 20
<br />400
<br />11
<br />12
<br />7 20
<br />SPARE
<br />RECEPS-LOUNGE
<br />1 20
<br />540
<br />13
<br />14
<br />20
<br />SPARE
<br />RECEPS-LOUNGE
<br />1 20
<br />360
<br />15
<br />16
<br />7 20
<br />SPARE
<br />PANEL C
<br />80/ 3
<br />2616
<br />17
<br />18
<br />1500
<br />1 20
<br />HAND DRYER
<br />2616
<br />19
<br />20
<br />2762
<br />2 30/ 3
<br />RTU
<br />!+
<br />2616
<br />21
<br />22
<br />2762
<br />SPARE
<br />7 20
<br />23
<br />24
<br />2762
<br />WATER HEATER
<br />6 20/ 2
<br />1000
<br />25
<br />26
<br />8286
<br />80/ 3
<br />RTU
<br />6
<br />1000
<br />27
<br />28
<br />8286
<br />RTU
<br />D 80/ 3
<br />8286
<br />29
<br />30
<br />8286
<br />2
<br />8286
<br />31
<br />32
<br />2762
<br />30/ 3
<br />RTU
<br />2
<br />8286
<br />33
<br />34
<br />2762
<br />2
<br />RTU
<br />80/ 3
<br />8286
<br />35
<br />36
<br />2762
<br />8286
<br />37
<br />38
<br />8465
<br />2 100/ 3
<br />PANEL B
<br />j
<br />8286
<br />39
<br />40
<br />8465
<br />2
<br />HAND DRYER
<br />1 20
<br />1500 1
<br />41
<br />42
<br />8465
<br />A B C
<br />DEMAND: 135.1 KW 375.1A
<br />NOTE:
<br />THE EXISTING CIRCUIT FOR THE TELEPHONE BACKBOARD RECEPTACLE COULD NOT BE IDENTIFIED. FIELD IDENTIFY THE
<br />CIRCUIT. THE CIRCUIT SERVING THE TELEPHONE BACKBOARD RECEPTACLE SHALL REMAIN (NOT BECOME SPARE).
<br />PANELBOARD DESIGNATION: B
<br />VOLTAGE:
<br />208/120V
<br />3PH-4W
<br />MAINS RATING:
<br />200
<br />AMPS
<br />MAIN CB TRIP RATING:
<br />N/A
<br />AMPS
<br />■ SURFACE
<br />FLUSH
<br />■ MCB
<br />MLO
<br />INTERRUPTING RATING:
<br />10,000
<br />AIC
<br />ENCLOSURE:
<br />NEMA 1
<br />SERVES
<br />CB SIZE
<br />LOAD VA
<br />CKT#
<br />CKT#
<br />LOAD VA
<br />CB SIZE
<br />SERVES
<br />LTG -WORK SALES AREA
<br />1 4 20
<br />1188
<br />1
<br />2
<br />1089
<br />1 4 20
<br />LTG -SALES 2X4
<br />LTG -WORK SALES AREA
<br />1 4 20
<br />1089
<br />3
<br />4
<br />1386
<br />1 4 20
<br />LTG -SALES 2X4
<br />LTG -WORK SALES AREA
<br />1 4 20
<br />1386
<br />5
<br />6
<br />1287
<br />1 4 20
<br />LTG -SALES 2X4
<br />LTG -WORK SALES AREA
<br />1 4 20
<br />1386
<br />7
<br />8
<br />1386
<br />1 4 20
<br />LTG -SALES 2X4
<br />LTG -WORK SALES AREA
<br />1 4 20
<br />1386
<br />9
<br />10
<br />891
<br />1 4 20
<br />LTG -SALES 2X4
<br />SPARE
<br />7 20
<br />11
<br />12
<br />1400
<br />1 4 20
<br />LTG -PERIMETER
<br />SPARE
<br />7 20
<br />13
<br />14
<br />1176
<br />1 4 20
<br />LTG -PERIMETER
<br />SPARE
<br />7 20
<br />15
<br />16
<br />1372
<br />1 4 20
<br />LTG -PERIMETER
<br />SPARE
<br />20
<br />17
<br />18
<br />20
<br />SPARE
<br />SPARE
<br />7 20
<br />19
<br />20
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />21
<br />22
<br />400
<br />3 20
<br />RECEPS-SALES DRINK COOLER
<br />SPARE
<br />7 20
<br />23
<br />24
<br />LTG -LOCAL SWITCHED
<br />6 20
<br />1088
<br />25
<br />26
<br />LIGHTING CONTROL(LOCK)
<br />6 20
<br />100
<br />27
<br />28 1
<br />1500
<br />6 4 20
<br />EXTERIOR SIGNAGE
<br />LTG -STOCK
<br />6 4 20
<br />1 718
<br />29
<br />30
<br />190
<br />6 4 20
<br />INTERIOR LED DISCS
<br />A B C
<br />DEMAND: 25.4 KW 70.5A
<br />NOTE:
<br />NEW SALES LIGHTING CIRCUITS SHOWN USE THE EXISTING SALES LIGHTING CIRCUITS, FIELD VERIFY WHICH EXISTING
<br />CIRCUITS ARE AVAILABLE (EXACT CIRCUIT NUMBERS MAY VARY FROM THOSE SHOWN) AS CONSTRUCTION PHASING
<br />OCCURS TO NOT DISRUPT STORE OPERATIONS.
<br />NEW CIRCUIT BREAKERS AT REMAINING SPACES MAY BE REQUIRED TO FACILITATE PHASING. 'SPARE' CIRCUIT
<br />BREAKERS ON THIS PANEL WERE ALSO FORMER SALES LIGHTING.
<br />PANELBOARD DESIGNATION: C
<br />VOLTAGE:
<br />208/120V
<br />3PH-4W
<br />MAINS RATING:
<br />200
<br />AMPS
<br />MAIN CB TRIP RATING:
<br />N/A
<br />AMPS
<br />. SURFACE
<br />FLUSH
<br />■ MCB
<br />MLO
<br />INTERRUPTING RATING:
<br />10,000
<br />AIC
<br />ENCLOSURE:
<br />NEMA 1
<br />SERVES
<br />CB SIZE
<br />LOAD VA
<br />CKT#
<br />CKT#
<br />LOAD VA
<br />CB SIZE
<br />SERVES
<br />SPARE
<br />7 20
<br />1
<br />2
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />3
<br />4
<br />7 20
<br />SPARE
<br />SPARE
<br />7 20
<br />5
<br />6
<br />7 20
<br />SPARE
<br />7
<br />8
<br />200
<br />3 20
<br />FIRE ALARM (LOCK)
<br />SPARE
<br />7 20
<br />9
<br />10
<br />20
<br />SPARE
<br />SPARE
<br />7 20
<br />11
<br />12
<br />7 20
<br />SPARE
<br />RECEPS-CASH WRAP (LOCK)
<br />6 20
<br />720
<br />13
<br />14
<br />40/ 2
<br />SPARE
<br />RECEPS-CASH WRAP (LOCK)
<br />6 20
<br />720
<br />15
<br />16
<br />7
<br />RECEPS-EAS (LOCK)
<br />6 20
<br />540
<br />17
<br />18
<br />900
<br />6 20
<br />PLUGMOLD-MGR DESK (LOCK)
<br />RECEPS-SALES CEILING
<br />6 20
<br />360
<br />19
<br />20
<br />900
<br />6 20
<br />PLUGMOLD-LP DESK (LOCK)
<br />RECEPS-COLUMNS
<br />6 20
<br />540
<br />21
<br />22
<br />900
<br />6 20
<br />PLUGMOLD-MGR BKBD (LOCK)
<br />RECEPS-COLUMNS
<br />6 20
<br />540
<br />23
<br />24
<br />900
<br />6 20
<br />PLUGMOLD-MGR TABLE (LOCK)
<br />AUTOMATIC DOOR
<br />6 20
<br />315
<br />25
<br />26
<br />AUTOMATIC DOOR
<br />6 20
<br />315
<br />27
<br />28
<br />29
<br />30
<br />A B C
<br />DEMAND: 7.8 KW 21.7A
<br />NOTE:
<br />THE EXISTING CIRCUIT FOR THE TELEPHONE BACKBOARD RECEPTACLE COULD NOT BE IDENTIFIED. FIELD IDENTIFY THE
<br />CIRCUIT. THE CIRCUIT SERVING THE TELEPHONE BACKBOARD RECEPTACLE SHALL REMAIN (NOT BECOME SPARE).
<br />EXISTING
<br />400A FEED
<br />EXISTING O
<br />EXISTING
<br />EXISTING
<br />EXISTING
<br />METER CAN
<br />PANEL E
<br />PANEL D
<br />PANEL C
<br />200A MCB
<br />200A MCB
<br />100A MLO
<br />208/120V
<br />208/120V
<br />208/120V
<br />EXISTING
<br />3-P, 4-W
<br />3-P, 4-W
<br />3-P, 4-W
<br />GROUNDING
<br />INSTALL ENGRAVED PLAQUE STATING
<br />"BEALLS OUTLET SERVICE 2 OF 2"
<br />RELABEL EXISTING PANELS
<br />'D' (FORMERLY 'B')
<br />'E' (FORMERLY 'A')
<br />ELECTRICAL RISER DIAGRAM
<br />WEATHER
<br />HEADS
<br />EXISTING
<br />EXISTING
<br />EXISTING
<br />400A FEED
<br />400A FEED
<br />EXISTING
<br />80A FEED
<br />100A FEED
<br />EXISTING
<br />EXISTING
<br />O EXISTING
<br />PANEL B
<br />PANEL A
<br />METER CAN
<br />100A MLO
<br />400A MCB
<br />208/120V
<br />208/120V
<br />3-P, 4-W
<br />3-P, 4-W
<br />EXISTING
<br />GROUNDING
<br />NO SCALE
<br />INSTALL ENGRAVED PLAQUE STATING I
<br />"BEALLS OUTLET SERVICE 2 OF 2"
<br />(D
<br />ELECTRICAL SCHEDULES AND DETAILS
<br />NO SCALE
<br />13
<br />14
<br />1
<br />5
<br />6
<br />7
<br />8
<br />9
<br />10
<br />1 11
<br />1 12 1
<br />13 1
<br />14 1
<br />15
<br />1 16
<br />1 17
<br />1 18
<br />1
<br />2
<br />P
<br />0
<br />N
<br />M
<br />L
<br />K
<br />J
<br />H
<br />G
<br />ME3
<br />CONSULTING ENGINEERS, LLC
<br />5300 Paylor Lane
<br />Sarasota, FL 34240
<br />Tel:941-748-1319 Fax:941-361-1221
<br />www.me3-engr.com sidney@me3-engr.com
<br />Designed: BAK ME3 Job No: B17-1166
<br />Checked: BAK Date: 09/29/2017 F
<br />Drawn: BPZ C.O.A.27552
<br />Copyright 2017 ME3 All rights reserved
<br />REV. DESCRIPTION DATE
<br />BID & PERMIT SET E
<br />09.29.17
<br />CURRENT ISSUE STATUS:
<br />"To the best of the Architect's or
<br />Engineer's knowledge, the plans
<br />D
<br />and specifications comply with the
<br />applicable minimum building codes
<br />and applicable fire safety standards
<br />as determined by local authority in
<br />accordance with Chapter 553 and
<br />663 of Florida Statutes."
<br />Bryan P. Zapf
<br />Florida License # 46141
<br />WBRCI::I
<br />ARCHITECTS ENGINEERS
<br />8130 Lakewood Main Street Phone: 941-556-0757
<br />Suite 210 Fax: 941-556-0759
<br />Lakewood Ranch, FL 34202 www.wbrcae.com
<br />Firm Lic. # AA26001395 & 27389 Douglas W.Whitney AIA
<br />BEALLS OUTLET #542
<br />ZEPHYRHILLS
<br />PROJECT: 6030 Gall Blvd, Zephyrhills, FL 33542 B
<br />ELECTRICAL SCHEDULES
<br />AND DETAILS
<br />SHEET TITLE:
<br />WBRC CAD FILE:
<br />PROJECT No. 3542XX GRAPHIC SCALE: 01.
<br />SCALE: As Indicated r I A
<br />PROJECT MANAGER:
<br />SHEET No.
<br />DRAWN BY. El 03
<br />CHECKED BY:
<br />19 20